Installation Instructions
(Cat 1609-B)
Bulletin 1609 Industrial Uninterruptible Power Supply
ATTENTION: Please read and save these instructions. This manual contains important instructions for the Bulletin 1609 Uninterrupt-
ible Power Supply. Follow these instructions during the unpacking, installation and maintenance of the UPS. If you have a problem
with the UPS, please refer to this manual and the User Manual trouble shooting section before calling Technical Services.
Contents for UPS Include:
• Installation Instruction
•1609-B
•USB Cable
•CD
•1 Battery Jumper Wire (inside the battery compartment)
•Battery Harness (inside the battery compartment)
Additional Resources
1. Go to http://www.rockwellautomation.com/literature
2. Go to Search, select Publication Number.
3. Type the Publication Number in the search box and press enter.
1609-IN014 (1609-SPD Installation Instructions)
1609-UM007 (1609 UPS Management Software User Manual)
1609-UM009 (1609 UPS User Manual)
Install the 1609 UPS in the Appropriate Environment
Do not operate the UPS where there is excessive dust or the temperature or humidity is outside the
specied limits. The maximum ambient temperature is 40 degree Celsius using the 1609-SBAT or 50 degree
Celsius using the 1609-HBAT. The maximum humidity specification is 95% RH (Non-condensing).
Note: Batteries are not included with the UPS.
Bulletin 1609 Industrial Uninterruptible Power Supply
1. To access the battery compartment
remove the three screws and the
battery door.
3. Fold the battery container and seal it with tape.
4. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white
connector retainer and connect the two cables together as shown in the photo below.
2. Remove the battery container, jumper and wire harness
from the battery compartment. Place the battery
container and batteries onto a flat surface. Use the
provided jumper wire to connect the batteries in series.
Connect the positive terminal (red) of the battery to the
negative terminal (black) of another battery. Connect
the red wire of the harness to the positive terminal (top
red) and the black wire of the harness to the negative
terminal (bottom black). See photo below for details.
Batteries Wiring and Installation Instruction for the UPS
Only use battery wires that have been provided with the UPS.
Warning: Do not service the 1609-SPD without disconnecting the power sources due to electric shock harzard for risk of
severe injury or death.
2
Publication 1609-IN013B-EN-P - August 2012 DIR 10000234490 (Version 01)
Black
Black
Notch
End
Red
Red
Mount the UPS
The 1609-B products are designed to mount to heavy duty DIN-rail (see Diagram 1 below). The 1609-B
products are also designed with an option bracket assembly (1609-BRK) that allows it to mount to either
the panel or floor (see Diagram 2 below).
Diagram 1 - Standard DIN-Rail Mount
Diagram 2 - Optional Panel or Floor Mount
Batteries Wiring and Installation Instruction for the UPS (Cont’d)
5. To complete the battery installation, close the white connector retainer and reattach the battery door with
the three screws (torque of 8.7+/-1.7 lb-in).
Bulletin 1609 Industrial Uninterruptible Power Supply
3
Publication 1609-IN013B-EN-P - August 2012 DIR 10000234490 (Version 01)