This unit is designed to mount on the back panel of an enclosure. An optional Din rail mounting kit, 1609SDK1, is also available.
When mounting on the back panel of an enclosure, select screws that are appropriate for the weight of this unit
and the mounting surface material.
Six screws must be used when mounting this unit in an enclosure. Three screws in the top of the bracket and
three screws in the bottom of the bracket. Failure to follow these instructions may result in damage to the unit.
Top Bracket
Bottom Bracket
3
Page 3
Installation
Connecting the Battery
Remove the Battery Door, Connect the Battery, and Reinstall the Battery Door
Hardwiring
Wiring of the UPS should be performed by a qualified electrican using appropriate wire gauges.
Connecting Power and Equipment to the UPS
Front Panel (120 V model shown):
Test
PUSH
TO
RESET
INPUT
208/220-240V~ 50/60Hz, 7A MAX
GROUND
4
OUTPUT
23
0V~ 50/ 60H z, 500 VA
325W, 2.7A MAX
GROUND
LINENEUTRAL
N
L
LINENEUTRAL
N
L
Page 4
Start-Up
1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the front panel.
The TVSS screw is used for connecting the ground lead on surge suppression devices such as telephone
and network line protectors.
Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery
power.
2. Connect the battery (see Connecting the Battery).
3. Hardwire the UPS.
Note: Hardwiring should be performed by a qualified electrician. Use appropriate size wires.
•In 230 V applications, the UPS must be protected with a circuit breaker that complies with
European standards for branch rated protection per the country of installation.
•In 208 V applications, the 1609-S350ES must be protected by a dual pole, 10 A branch rated
circuit breaker with UL489 rating.
•The 120 V 1609-S350NS has supplementary circuit breaker protection. The unit should be
protected by a single-pole, 15 A branch rated circuit breaker with a UL489 rating. Allen-Bradley
part number 1492-MCAA115 is suggested. Ensure that the branch circuit breaker is off prior to wiring the unit.
120 V models
INPUT
OUTPUT
208/230 V models
INPUT
OUTPUT
Installation
N
L
LN
L2/N
L1
4. Connect equipment to the UPS.
5. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected
equipment is switched on.
6. Press the button on the front panel to start the UPS.
•The battery charges to 90% capacity during the first four hours of normal operation.
•Do not expect full battery run capability during this initial charge period.
7. For optimal computer system security, install PowerChute
monitoring software included with the UPS.
Communications/Serial Port
A standard serial interface cable is incompatible with the UPS. Use the cable supplied with the unit.
L1L2/N
5
Page 5
Operation
Operation
Display Panel
120 V models
Test
INPUT
208/220-240V~ 50/60Hz, 7A MAX
GROUND
Display Panel Indicators and Function Buttons
LINENEUTRAL
N
L
GROUND
23
OUTPUT
0V~ 50/60Hz, 500VA
325W, 2.7A MAX
N
LINENEUTRAL
L
208/230 V models
INPUT
208/220-240V~ 50/60Hz, 7A MAX
L2/N
L1
IndicatorTitleDescription
On-LineThe UPS is supplying utility power to the connected equipment.*
AVR TrimThe UPS is compensating for a high utility voltage.*
AVR BoostThe UPS is compensating for a low utility voltage.*
On BatteryThe UPS is supplying battery power to the connected equipment.
Test
OUTPUT
23
0V~ 50/60Hz, 500VA
325W, 2.7A MAX
L2/N
L1
OverloadThe connected equipment is drawing more than the UPS power rating allows.*
Replace Battery/Battery
Disconnected
*See Troubleshooting.
6
The battery is disconnected or must be replaced.*
Page 6
FeatureFunctionDescription
Power OnPress this button to turn on the UPS. Read on for additional
capabilities.
Power OffPress this button to turn off the UPS.
Self-TestAutomatic: The UPS performs a self-test automatically when turned on,
and every two weeks thereafter (by default). During the self-test, the
UPS briefly operates the connected equipment on battery.
Operation
Battery
Charge
Manual: Press and hold the
buttonfor a few seconds to initiate the
self-test.
Cold Start When there is no utility power and the UPS is off, the cold start feature
will switch the UPS and connected equipment onto battery power
(see Troubleshooting).
Diagnostic Utility
Vo l t a g e
The UPS has a diagnostic feature that indicates the utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not
affect the voltage display.
Press and hold the button to view the utility voltage bar graph
indicator. After a few seconds, this five-LED Battery Charge
indicator on the right of the display panel will show the utility input
voltage.
Refer to the figure on the left for the voltage reading (values are not
listed on the UPS).
The indicator on the UPS shows the voltage is between the displayed
value on the list and the next higher value (see Troubleshooting).
7
Page 7
User Configurable Items
User Configurable Items
Settings are adjusted through PowerChute software or optional network management card.
Voltage SensitivityHigh sensitivityHigh sensitivity
Alarm Delay
Control
Every 14 days
(336 hours)
Manufacture
Date
0 percent• 0%
Enable• Enable
• Every 7 days
(168 hours)
• On start-up only
• No self-test
(alphanumeric)
mm/dd/yyReset this date when you replace the battery
• 15%
• 30%
• 45%
Medium sensitivity
Low sensitivity
• Mute
• Disable
• 60%
• 75%
• 90%
Set the interval at which the UPS will execute a
self-test.
Uniquely identify the UPS (i.e. server name or
location) for network management purposes.
module.
Specify the percentage to which battery
module(s) will be charged following a low
battery shutdown before powering connected
equipment.
The UPS detects and reacts to line voltage
distortions by transferring to battery operation
to protect the connected equipment.
In situations of poor power quality, the UPS
may frequently transfer to battery operation. If
the connected equipment can operate normally
under such conditions, reduce the sensitivity
setting to conserve battery capacity and service
life.
Mute ongoing alarms or disable all alarms
permanently.
Shutdown Delay90 seconds• 0 s
Low Battery
War nin g
8
2 minutes2, 5, 8, 11, 14,
• 360 s
• 90 s
• 180 s
• 270 s
17, 20, 23 minutes
• 450 s
• 540 s
• 630 s
Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.
PowerChute software interface provides
automatic, unattended shutdown when
approximately two minutes of battery operated
run time remains.
The low-battery warning beeps are continuous
when two minutes of run time remain.
Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.
Specify the time the UPS will wait after the
return of utility power before start-up (to avoid
branch circuit overload).
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
The 1609-S350ES ships ready for 230 V
sources. When operating the UPS in 208 V
applications, the UPS low transfer voltage
settings are adjusted through PowerChute
software. The proper setting for low transfer
voltage is 196 V.
Refer to the PowerChute user guide for setting
adjustment details.
Sets the output voltage of the UPS while
operating on battery.
9
Page 9
Storage, Maintenance, Transport
Storage, Maintenance, Transport
Storage
Store the UPS covered in a cool, dry location with the battery module(s) fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery module every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery module every three months.
Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated
from electrical hazards. You may leave the UPS and connected equipment on during the replacement
procedure.
For instruction, see applicable steps in Connecting the Battery.
Ensure battery replacement every 2-4 years.
Standard (40C) battery; Allen-Bradley catalog number: 1609-500SBAT.
Once the battery module(s) are disconnected the connected equipment is not protected from power
outages.
Refer to the appropriate replacement battery installation guide for battery module installation instructions. See
your dealer or contact Rockwell Automation at 440-646-5800 for information on replacement battery modules.
Be sure to deliver the spent battery module(s) to a recycling facility or ship it to the address
specified in the replacement battery literature.
10
Page 10
Troubleshooting
Troubleshooting
Use this chart to solve minor installation and operation problems. Refer to Rockwell Automation Tech Support
at 440-646-5800 for further support.
Problem and/or Possible CauseSolution
UPS will not turn on
The battery is not connected properly.Check that the battery module connector is fully engaged.
button not pushed.
The UPS is not connected to utility
power supply.
UPS will not turn off
The UPS is experiencing an internal
fault.
UPS beeps occasionally
Normal UPS operation when running
on battery.
UPS is not providing expected backup time
The UPS battery module(s) are weak
due to a recent power outage or battery
module(s) are near the end of their
service life.
Left half, right half, or center section of front panel is flashing
The UPS is experiencing an internal
fault.
Press the
equipment.
Check that the UPS is properly connected to utility power.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
The UPS is protecting the connected equipment. Press the button to
silence this alarm.
Charge the battery module(s). Battery modules require recharging after
extended outages. Battery modules can wear faster when put into service
often or when operated at elevated temperatures. If the battery module(s) are
near the end of their service life, consider replacing the battery module(s)
even if the replace battery LED is not yet illuminated.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
button once to apply power to the UPS and connected
All LEDs are illuminated and the UPS emits a constant beeping
The UPS is experiencing an internal
fault.
Front panel LEDs flash sequentially
The UPS has been shut down remotely
through software or an optional
accessory card.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
None. The UPS will restart automatically when utility power returns.
11
Page 11
Troubleshooting
Problem and/or Possible CauseSolution
All LEDs are off and the UPS is wired to input utility power
The UPS is shut down or the battery
module is discharged from an extended
None. The UPS will restart automatically when utility power is restored and
the battery module has a sufficient charge.
outage.
The overload LED is illuminated and the UPS emits a sustained alarm tone
The UPS is overloaded.The connected equipment exceeds the specified “maximum load” as defined
in Specifications listed on the rating label located on the UPS.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
The UPS continues to supply power as long as it is online and the circuit
breaker does not trip. The UPS will not provide power from battery
module(s) in the event of a utility voltage interruption.
The replace battery/battery disconnected LED is illuminated
The replace Battery/battery
Check that the battery module connectors are fully engaged.
disconnected LED flashes and a short
beep is emitted every two seconds to
indicate the battery is disconnected.
Weak battery module.Allow the battery module to recharge for 24 hours and perform a self-test. If
the problem persists after recharging, replace the battery module.
Failure of a battery module self-test.
Replace battery/battery disconnected
LED
illuminates and the UPS emits short
beeps for one minute. The UPS repeats
the alarm every five hours.
Allow the battery module to recharge for 24 hours. Perform the self-test
procedure to confirm the replace battery condition. The alarm stops and the
LED clears if the battery module passes the self-test.
If the battery module fails again, it must be replaced. The connected
equipment is unaffected.
The input circuit breaker trips
The connected equipment exceeds the
specified “maximum load” as defined
in Specifications listed on the rating
Unplug all nonessential equipment from the UPS.
Reset the circuit breaker.
label located on the UPS.
The AVR boost or AVR trim LEDs are illuminated
The system is experiencing very high or
low utility voltage.
12
Have a qualified service person check your facility for electrical problems. If
the problem persists, contact the utility company for further assistance.
Page 12
Problem and/or Possible CauseSolution
There is no utility power
Troubleshooting
There is no utility power and the UPS is
off.
Use the cold start feature to supply power to the connected equipment from
the UPS battery module(s).
Press and hold the button. The unit will emit two beeps, one short beep
and one long beep. Release the button during the second beep.
UPS operates on battery although line voltage exists
The UPS input circuit breaker trips.Unplug all nonessential equipment from the UPS.
Reset the circuit breaker.
Your system is experiencing very high,
low or distorted line voltage.
Move the UPS to a different outlet on a different circuit. Inexpensive fuel
powered generators may distort the voltage. Test the input voltage with the
utility voltage display (see Operation). If acceptable to the connected
equipment, reduce the UPS sensitivity.
Battery charge and load LEDs flash simultaneously
The UPS has shut down
The internal temperature of the UPS has
exceeded the allowable threshold for
safe operation.
Check that the room temperature is within the specified limits for operation.
Check that the UPS is properly installed, allowing for adequate ventilation.
Allow the UPS to cool down. Restart the UPS. If the problem persists,
contact Rockwell Automation at 440-646-5800.
Diagnostic utility voltage
All five LEDs are illuminated.The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination.If the UPS is plugged into a properly functioning utility power outlet, the line
voltage is extremely low and should be checked by an electrician.
On-line LED
There is no LED illumination.The UPS is running on battery, or it must be turned on.
The LED is blinking.The UPS is running an internal self-test.
Software/network integration problems
Communication problems between the
UPS and PowerChute software.
Ensure the correct communication cable (940-0024D) is being used.
Refer to the PowerChute user manual on the CD shipped with the software.
13
Page 13
Service and Contact Information
Service and Contact Information
Service
If the UPS requires service do not return it to the dealer. Follow these steps:
1. Review the problems discussed in Troubleshooting to eliminate common problems.
2. If the problem persists, contact Rockwell Automation Customer Support.
•If the product is determined to be defective, contact the distributor for typical return procedures.
•Retain the battery module.
3. Pack the UPS in its original packaging.
•Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging.
Damage sustained in transit is not covered under warranty.
•Always DISCONNECT THE BATTERY MODULE before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery module may
remain in the UPS.
.
Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800
www.ab.com
41063-287-01 (1)
14
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.