Rockwell Automation 1609 ENET User Manual

Installation Instructions
(Cat 1609-ENET)
Bulletin 1609 Network Management Card
ATTENTION: Please read and save these instructions. This manual contains important instructions for Bulletin 1609 Uninterruptible
Power Supply. Follow these instructions during the unpacking, installation and maintenance of the UPS. If you have a problem with the UPS, please refer to this manual before calling Technical Services.
Contents for 1609-ENET Include:
• 1609 Network Management Card
• 1609-ENET Installation Instruction
• 1609-ENET Cover
• 2 Screws
• Cable
Installation
1. Loosen the 2 screws on 1609 UPS to remove the1609-ENET cover.
2. Insert the 1609-ENET card into the slot (This 1609-ENET Card is hot Swappable).
3. Place the 1609-ENET cover (provided with the EtherNet card) and screw the two screws in place
(torque
of 8.7+/-1.7 lb-in)
.
Note: For detail of configuration, refer to the 1609 Network Management Card User Manual (1609-UM008).
DIR 10000251453 (Version 00)
Copyright © 2012 Rockwell Automation, Inc. All Rights Reserved. Printed in China.
Additional Resources
1. Go to http://www.rockwellautomation.com/literature
2. Go to Search, select Publication Number.
3. Type the Publication Number in the search box and press enter.
1609-IN012 (1609-D UPS Installation Instructions)
1609-IN013 (1609-B UPS Installation Instructions)
1609-IN014 (1609-SPD Installation Instructions)
1609-UM007 (1609 UPS Management Software User Manual)
1609-UM008 (1609 Network Management Card User Manual)
1609-UM009 (1609 UPS User Manual)
Setup Procedure
Note: The minimum requirement to operate the 1609 Network Management Card is to setup the Host
Name (default of 1609 Network). If you want to assign a static IP Address then please disable DHCP, provide the IP Address, Subnet Mask and the Gateway.
Congure by EzSetting
The easiest way to configure the 1609 Network Management Card is by running the EzSetting Software. You can find the software on the CD that shipped with the UPS.
1. Make sure both the dip-switches of 1609 Network Management Card are set to OFF position (normal mode) to enable network transmission.
2. Make sure the workstation and the 1609 Network Management Device are in the same LAN. The default device for the 1609 Network Management device is 192.168.1.100; therefore, set the workstation device to 192.168.1.xxx.
3. Put the software CD in the CD-ROM drive and run the EzSetting Software.
4. On the top right corner select the appropriate LAN and press the Discover button to search for all the
devices in the same LAN. The 1609 Network Management device should display in the device list. If the 1609 Network Management device cannot be found, check the networking port UDP 3456 in the Operating System (OP) and open it if it is blocked.
5. Select the device in the Device List to configure the network parameters then press the Modify button to provide your account and password. The default account name and password are admin and
password, respectively.
6. Click the Configuration button and setup the essential network parameters.
7. Once the 1609 Network Management Card installation and configuration is complete, you are now able
to monitor and control the 1609 Network Management Card.
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1609-IN015A-EN-P - April 2012