Rockwell Automation 1609-BD UPS User Manual

User Manual
Bulletin 1609 Uninterruptible Power Supply
Catalog Numbers 1609-D and 1609-B

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication your local Rockwell Automation® sales office or online at
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and Figures in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and Figures.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
SGI-1.1 available from
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Identifies information that is critical for successful application and understanding of the product.
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.

Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication
Product Certifications website,
Publication Number:
1609-UM007_-EN-P
Publication Number:
1609-UM008_-EN-P
Publication Number:
1609-IN012_-EN-P
Publication Number:
1609-IN013_-EN-P
Publication Number:
1609-IN014_-EN-P
Publication Number:
1609-IN015_-EN-P
1770-4.1
http://www.ab.com Provides declarations of conformity, certificates, and
Provides general guidelines for installing a Rockwell Automation industrial system.
other certification details.
Bulletin 1609 UPS Management Software User Manual
Network Management Card - Cat. No. 1609-ENET User Manual
Bulletin 1609-D Installation Instructions
Bulletin 1609-B Installation Instructions
Surge Protective Device (Cat. No. 1609-SPD) Installation Instructions
Network Management Card (Cat. No. 1609-ENET) Installation Instructions
You can view or download publications at
http:/www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 3
Preface

Notes:

4 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

Table of Contents

Bul. 1609-D Installation Instructions

Bul. 1609-B Installation Instructions

Bul. 1609-EXBAT Installation Instructions

Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mount the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hardwire UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connect Power and Equipment to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . 10
Bul. 1609-D Block Figure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Mount the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Hardwire UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Connect Power and Equipment to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . 14
1609-B Block Figure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Battery Wiring and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Mount the 1609-EXBAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connect the 1609-EXBAT to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

General Information 1609-D and 1609-B

Troubleshooting

Recommended Battery for use with the UPS . . . . . . . . . . . . . . . . . . . . . . . .19
Dry I/O Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
USB Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Manual or Remote Enable/Disable of UPS Output Selection . . . . . . . . . 20
Manual Enable/Disable/Self-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Remote Enable/Disable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Display LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
UPS LED Fault Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Output Short Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Output Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Temperature from the Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Voltage from The DC/DC Converter of Inverter . . . . . . . . . . 23
Over Voltage from The Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Under Voltage from The Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Over Voltage from the Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Under Voltage from the Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Fan Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Charger Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
TMOV Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Missing Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Replace Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 5
Table of Contents

Troubleshooting (continued)

Specifications

Dimensions

Service Instructions

UPS Management Software Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . .25
UPS Network Managemenr Card Troubleshooting . . . . . . . . . . . . . . . . . .26
Bul. 1609-D Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Bul. 1609-B Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Bul. 1609-D Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-B Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-EXBAT Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Bul. 1609-BRK Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Service Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
6 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

-Bulletin 1609-D Installation Instructions

ATTENTION: Do not service the 1609-SPD without disconnecting the power
sources due to electric shock hazard for risk of severe injury or death.

Battery Wiring and Installation

1. To access the battery compartment remove the three screws and the battery door.

2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. See photo below for details.

3. Connect the red wire of the harness to the positive terminal (top red) and the black wire of the harness to the negative terminal (bottom black). See photo below for details.

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 7
Bulletin 1609 UPS

Battery Wiring and Installation (cont.)

4. Fold the battery container and seal it with tape.

5. To connect the batteries to the UPS, insert the batteries into the battery
compartment, open the white connector retainer and connect the two cables together as shown in the photo below.

Mount the UPS

6. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws (torque of 8.7+/-1.7 lb-in).

The UPS-D is designed to mount on the back of the panel or to the floor of the enclosure. The UPS mounts to a bracket assembly (1609-BRK) that allows it to mount to either the panel or floor (see Figure 1 below).

Figure 1 - Mounting the UPS

8 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

Hardwire UPS

Selection of Cables

Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.

Table 1 - AC Main Input/Output Wiring for UPS:

Item Specification
Wire Size 14 AWG
Minimum temperature 75 °C
Wire conductor material Copper only
Tightening torque for terminals 4.4 lb-in.

Table 2 - DC Input / Output Wiring for External Battery Cabinet:

Item Specification
Wire Size 10 AWG
Minimum temperature 75 °C
Wire conductor material Copper only
Tightening torque for terminals 12 lb-in.
WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit. To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 9
Bulletin 1609 UPS

Connect Power and Equipment to the UPS

WARNING: This UPS features Surge Protection Device (SPD) is located
on the left front of the unit. Disconnect all power sources before servicing due to Electric Shock Hazard for risk of severe injury or death.

1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 2).

2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see Figure 2).

Figure 2 - System Wiring

1609-D Block Figure

3. Connect any additional optional accessories (1609-ENET card).

AC
Input
Breaker
L
E
N
Input
Filter
Backfeed
Relay
Backfeed
Relay
+
-
AC to DC DC to DC DC to AC
AVR
AC to AC
Inverter
Relay
L
E
N
AC
Output
10 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

1609-B Installation Instructions

ATTENTION: Disconnect the 1609-SPD before servicing, due to electric shock
hazard for risk of severe injury or death.
Bulletin 1609 UPS

Battery Wiring and Installation

Note: Batteries are not included with the 1609-B UPS

1. To access the battery compartment remove the three screws and the battery door.

2. Remove the battery container, jumpers, and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. Connect the red wire of the harness to the positive terminal (top red) and the black wire of the harness to the negative terminal (bottom black). See photo below for details.

3. Fold the battery container and seal it with tape.

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 11
Bulletin 1609 UPS

Battery Wiring and Installation (cont.)

4. To connect the batteries to the UPS, insert the batteries into the battery compartment, open the white connector retainer and connect the two cables together as shown in the photo below.

5. To complete the battery installation, close the white connector retainer and reattach the battery door with the three screws (torque of 8.7+/-1.7 lb-in).

12 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

Mount the UPS

The 1609-B UPS products are designed to mount to a heavy duty DIN-rail (see Figure 3 below). The 1609-B UPS products are also designed with an optional bracket assembly (Cat 1609-BRK) that allows it to mount to either the panel or floor (see Figure 4 below).

Figure 3 - Standard DIN-Rail Mount

Figure 4 - Optional Panel or Floor Mount

Hardwire UPS

Selection of Cables

Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.

Table 3 - AC Main Input / Output Wiring for UPS

Item Specification
Wire Size 14 AWG
Minimum Temperature 75 °C
Wire Conductor Material Copper only
Tightening Torque for Terminals 4.4 lb - in.
WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit. To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 13
Bulletin 1609 UPS

Connect Power and Equipment to the UPS

WARNING: This UPS features Surge Protective Device (SPD) located on the top
of the unit. Please disconnect all power sources before servicing due to Electric Shock Hazard for risk of severe injury or death.

1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see Figure 5).

2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see Figure 5).

Figure 5 - System Wiring
INPUT
OUTPUT
LLNNGG
AC Input

1609-B Block Figure

AC
Input
AC Output
Input
Filter
L
E
N
AC to DC (Charger) DC to DC DC to AC (Step Wave)
Backfeed
Relay
Backfeed
Relay
+
-
Inverter
Relay
L
E
N
AC
Output
14 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

1609-EXBAT Installation Instructions

Bulletin 1609 UPS

Battery Wiring and Installation

Only use battery wires that have been provided with the 1609-EXBAT.
WARNING: A disconnect switch shall be provided by others for DC output circuit. To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent protection for 35 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
Before connecting a battery pack to UPS, the emergent disconnecting device shall be provided between the UPS and battery pack.

1. To access the battery compartment remove the six screws and the battery door.

2. Remove the battery container, jumpers and wire harness from the battery compartment. Place the battery container and batteries onto a flat surface. Use the provided jumper wires to connect the batteries in series. Connect the positive terminal (red) of the battery to the negative terminal (black) of another battery. See photo below for details.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 15
Bulletin 1609 UPS

Battery Wiring and Installation (cont.)

3. Connect the shorter set of red and black wires of the harness to the top terminals (red - to - red and black - to - black). Connect the longer set of red and black wires of the harness to the bottom terminals (red - to - red and black - to - black) and route the wires through the cut-out hole. See photo below for details.

4. Fold the battery container and seal it with tape.

5. Insert the batteries into the battery compartment in the orientation as
shown in the photo below.

6. Open the white connector retainer and connect the two cables together as shown in the photo below.

16 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

Battery Wiring and Installation (cont.)

Mount the 1609-EXBAT

7. To complete the battery installation, insert the surplus wire harness into the free space, close the white connector retainer and reattach the battery door with the six screws (torque of 8.7+/-1.7 lb-in).

The 1609-D UPS can be used with the External Battery Unit (1609-EXBAT). The 1609-EXBAT unit is designed to mount to a heavy duty DIN-rail (see Figure 6) or the optional mounting bracket assembly (1609-BRK) which allows it to mount to either the panel or floor (see Figure 7).

Figure 6 - Heavy Duty DIN Rail Mount

Figure 7 - Panel or Floor Mount

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 17
Bulletin 1609 UPS

Selection of Cables

Connect 1609-EXBAT to the UPS

Table 4 - DC Input/Output Wiring for External Battery Cabinet

Item Specification
Wire Size 10 AWG
Minimum temperature 75 °C
Wire conductor material Copper only
Tightening torque for terminals 12 lb-in.
To install the 1609-EXBAT unit with the 1609-D UPS, connect the three 10 AWG wires from the 1609-EXBAT terminals to the 1609-D UPS terminals marked as ‘EXTERNAL BATT PACK (36V)’. (See Figure 8)
Dispose of used batteries according to the battery instructions.

Figure 8 - System Wiring

18 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

General Information 1609-D and 1609-B UPS Units

Bulletin 1609 UPS

Recommended Battery for Use with the UPS and 1609-EXBAT

Dry I/O Contacts

Rockwell Automation battery catalog numbers 1609-SBAT and 1609-HBAT consist of the battery manufacturers listed below:
Manufacturer MH Number Type Rating
B & B Battery (USA) MH19884 HRLS 5.5-12 12V DC, 2.75 Ah
BP 5-12 12V DC, 5.0 Ah
HR 5.5-12 12V DC, 2.75 Ah
SHR7-12 12V DC, 3.375 Ah
GS Yuasa International Ltd. MH12970 NPH5-12 12V DC, 5.0 Ah
Shenzhen Center Power Tech Co., Ltd. MH25860 CP1250 12V DC, 5.0 Ah
Shenzhen Ritar Power Co., Ltd. MH28539 RT1250 12V DC, 5.0 Ah
CSB Battery Co., Ltd. MH14533 HR1221W 12V DC, 5.25 Ah
Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.
Dispose of used batteries according to the battery instructions.
There is one Remote Enable/Disable Switch connection and 3 Dry I/O Contacts available on the front of the UPS. Do not apply external power to the Remote Enable/Disable Switch; however, the 3 sets of Dry Contacts require external power supplies (Contacts Rating is 1A/24V DC). Each of the dry contacts is used to provide a remote status indication of the UPS, as follows:
87654321
1 and 2 On Battery Contact (NO)
3 and 4 Low Battery Contact (NO)
5 and 6 Fault (Indicates UPS has faulted see trouble shooting section)
7 and 8 Remote On/O (Shorted (closed) for ON, Open for OFF)

USB Communication Port

The UPS supports a USB communication port for the end user to connect with a computer. The user may monitor all the UPS status through the USB port if the 1609 UPS Management Software is installed in the computer. The software is stored in the CD and can be found in the accessory bag.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 19
Bulletin 1609 UPS

Manual or Remote Enable/Disable of UPS Output Selection

Manual Enable/Disable/ Self-test

The 1609 UPS output is designed to be manually or remotely enabled or disabled. User is required to enable or disable the remote function switch on the front panel.
REMOTE FUNCTION
ENABLEDISABLE
Selected 'DISABLE' for Manual Enable/Disable the UPS's Output.
Selected 'ENABLE' for Remote Enable/Disable the UPS's Output.
The Power Button on the front of the UPS is used to manually enable or disable the output of the 1609-D UPS.
To enable the 1609-D UPS, press and hold the power button until one beep is heard.
To disable the 1609-D UPS, press and hold the power button until three beeps are heard, then release immediately (takes approximately 3 seconds).
To perform a self-test, press and hold the power button until two beeps are heard, then release immediately. (The UPS must operate for at least 4 hours before executing this function)

Remote Enable/Disable

An external switch connected to the Dry I/O terminals 7 and 8 is required to remotely Enable or Disable the UPS output.
87654321
SW
R
R
R
24 Vdc
To enable the UPS, close the switch that is connected to the Dry I/O terminals 7 and 8.
To Disable the UPS, open the switch that is connected to the Dry I/O terminals 7 and 8.
20 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

Display LED Indicators

Bulletin 1609 UPS
Indicator LED Indicator Title Description
Online The UPS is supplying utility power to the connected equipment
(see Troubleshooting).
Applies to 1609-D only
AVR Trim The UPS is compensating for a high utility voltage
(see Troubleshooting).
AVR Boost The UPS is compensating for a low utility voltage
(see Troubleshooting).
On Battery The UPS is supplying battery power to the connected equipment.
Overload The connected equipment is drawing more than the UPS power
rating allows (see Troubleshooting).
Replace Battery/Disconnect The battery is disconnected or must be replaced
(see Troubleshooting).
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 21
Bulletin 1609 UPS

Troubleshooting

Button Function Explanation
UPS Output Enable Press and hold the button until one beep is heard, then release
UPS Output Disable Press and hold the button until three beeps are heard, then release
Self-Test Press and hold the button until two beeps are heard, then release
Problem Possible Cause Solution
No LED illuminates / No alarm
No UPS output The UPS has not been enabled Manually Enable - Make sure the Remote Function
UPS Operates on battery although input utility voltage exists
Input line utility power circuit breaker trip
FAULT LED illuminates An internal fault has been detected Refer to the UPS LED Fault Indicators below to identify the
ONLINE LED illuminates, but no UPS output is available
The battery did not provide expected runtime
No communication between the UPS and your PC
UPS output is disabled or input utility power is not present
The system may experience high, low or distorted input utility voltage
The system may have experienced an overload
The UPS output connection may not be connected properly
The batteries might be weak or the lifespan is due
Wrong cable Verify cable used.
The connection cable is not firmly connected
PC Communication Port may have been used by another process or is defective
There is interference on the connection cable
immediately
immediately
immediately (The UPS must operate for at least 4 hours before executing this function)
Have qualified electrician trouble shoot the input utility power system and make the necessary corrections.
selector switch is in the Disable position, then press and hold the UPS Power button until one beep is heard and release immediately. Remotely Enable - Make sure the Remote Function selector switch is in the Enable position and verify that there is an adequate connection to the remote on/off dry I/O connection (terminals 7 & 8)
Reduce the UPS sensitivity by using the 1609 UPS Management software. If the problem persists, move or connect the UPS with a known good quality utility power source.
Verify that the circuit breaker is sized properly. Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output rating of the UPS.
specific fault that occurred and possible resolution.
Disable the UPS output and have qualified electrician troubleshoot the output connection system and make the necessary corrections.
Charge the batteries for 8 hours and retest the runtime. If the runtime is still less than expected after charging, replace the batteries even if the Replace Battery LED doesn’t illuminate.
Reconnect the communication cable firmly.
Check if there is other software or service accessing the Communication Port on your PC, or connect it to a different communication port.
Lay the cable differently or away from other cables and reconnect the cable.
22 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

UPS LED Fault Indicators

General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
No. Fault Description Solution
1 Output Short Circuit The UPS has detected a
short circuit on the Output
GRN
RED
of the UPS and disabled its output.
2 Output Overload The UPS has detected an
overload and disabled its
RED
GRN
3 Over Temperature from the
Heatsink
output.
The UPS has detected an over temperature of the heatsink and disabled its output.
RED
GRN
Have a qualified electrician troubleshoot the load connected to the output to the UPS and remove the short circuit if present.
To clear fault, follow the General Clear Fault Procedure described above. If the problem persists, contact Technical Support.
Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output rating of the UPS. If the load exceeds the rating of the UPS please remove excess load or select the appropriate size UPS. If the problem persists, contact Technical Support.
To clear fault, follow the General Clear Fault Procedure described above.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C (1609-SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
4 Over Ambient Temperature The UPS has detected an
over ambient temperature and disabled its output.
RED
GRN
5 Over Voltage from The DC/DC
Converter of Inverter
The UPS has detected an over voltage of the DC/DC Converter and disabled its output.
RED
GRN
6 Over Voltage from The Inverter The UPS has detected high
voltage on the inverter
GRN
RED
and disabled its output.
7 Under Voltage from The Inverter The UPS has detected low
voltage on the inverter
RED
GRN
and disabled its output.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C (1609SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
Have a qualified electrician verify that the quality of utility voltage is within specification. To clear the fault, follow the General Clear Fault Procedure described above. If the fault is still present after attempting to clear fault, contact Technical Support.
Have a qualified electrician verify that the quality of utility voltage is within specification. To clear fault, follow the General Clear Fault Procedure described above. If the fault is still present after attempting to clear fault, contact Technical Support.
Have a qualified electrician verify that the quality of utility voltage is within specification. To clear fault, follow the General Clear Fault Procedure described above. If the fault is still present after attempting to clear fault, contact Technical Support.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 23
Bulletin 1609 UPS
No. Fault Description Solution
8 Over Voltage from The Output
of AVR
BLINK
GRN
RED
The UPS has detected an over voltage on the output of AVR and disabled its output.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact Technical Support.
9 Under Voltage from The Output
of AVR
The UPS has detected low voltage on the output of AVR and disabled its output.
RED
BLINK
GRN
10 Fan Failure The UPS has detected that
the fan of the UPS has failed and disabled its
RED
GRN
output.
11 Charger Failure The UPS has detected that
the battery charger circuit has failed; however, the UPS will continue running.
GRN
BLINK
GRN
12 TMOV Failure The UPS has detected that
the MOV circuit has failed; however, the UPS will continue enabling the
GRN
BLINK
GRN
output.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact Technical Support.
To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists, contact Technical Support.
Clear this fault by removing the input utility voltage and batteries then plug the batteries back in place and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.
Schedule to have a qualified electrician replace the MOV board (1609-SPD). Remove the input utility power before service on this 1609-SPD due to risk of electrical shock.
13 Missing Battery The UPS has detected that
the batteries are missing; however, the UPS will continue enabling the
BLINK
GRN
RED
output.
14 Replace Batteries The UPS has detected that
the batteries are bad; however, the UPS will continue running.
GRN RED
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Missing Battery, new batteries are required.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Replace Battery, new batteries are required.
24 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

Bulletin 1609 UPS Management Software Troubleshooting

General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
Status Indications Indication Description Solution
Buzzer Alarm The UPS has detected a fault and generate a buzzer
alarm. Test In Progress The UPS is currently in a test mode. Do not interrupt the UPS testing. The UPS is doing battery test. UPS Fault The UPS has detected a fault and disabled its output. Verify the type of fault from the Status Indicators or the LEDs on the UPS for further
Battery Low The UPS has detected that the batteries are low. The batteries must be charged for 24 hours and re-verify the battery status. If the batteries still
Power Failed The UPS has detected that the input utility voltage
has failed.
Overheat The ambient temperature is greater than 60 °C, or
some internal components are over temperature.
Overload The UPS has detected that output load of UPS is
greater than 110%.
Load Warning The output load over the warning threshold. Verify the output load. If it is close to 100% load, remove the excess load or select the appropriate
Load Severity The output load over the severity threshold. Verify the output load. If it is actually at 100% load, remove some of the non-essential load or
UPS Disconnect The UPS has detected a communication loss between
the UPS and the computer.
Output Abnormal To indicate the output voltage is abnormal. Have qualified electrician verify that the quality of the output voltage and the input utility voltage
Output Off The UPS is operating in standby mode, or UPS is
faulted. UPS System Off The UPS system is in the standby state. If it is identified as the UPS fault shutdown then turn the UPS off. Turn UPS on again to reset the
Awaiting Power The battery is depleted and the UPS awaits the return
of input utility voltage. Battery Need Replace The UPS has detected that the battery is bad or
opened.
Battery Depleted The UPS has detected that the batteries are depleted. Have a qualified electrician verify the battery connection for good contact and charge the
Verify the type of fault from the Status Indicators or the LEDs on the UPS for further troubleshooting.
troubleshooting. To clear fault, follow the General Clear Fault Procedure described above and if the fault persists,
contact Technical Support.
indicate to be low, replace the batteries. Verify that the input utility voltage is within the UPS’s input specification.
If it is not, make the necessary correction to the input utility power system. Have a qualified electrician checked the ambient temperature to make sure that it does not exceed
40 °C(1609-SBAT) or 50 °C (1609-HBAT). If the temperature exceeds the UPS rating, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above and if the fault persists, contact Technical Support.
Verify that the load does not exceed the load specification. If it is, remove the excess load from the UPS’s output and clear its fault. If the problem persists, have a qualified electrician troubleshoot the UPS Load System and make the necessary corrections or select the appropriate size of UPS. If the problem persists, contact Technical Support.
size of UPS.
select the appropriate size of UPS. Please check the USB cable between computer and UPS for secure connection or replace the cable
with a known good cable. If communication is established, re-open the UPS Management software. If the problem persists,
contact Technical Support.
are within its specification. To clear fault, follow the General Clear Fault Procedure described above and if the problem
persists, contact Technical Support. If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to
reset the fault. If the fault persists, contact Technical Support.
fault. If the fault persists, contact Technical Support. Apply the input utility voltage to the UPS.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Battery Need Replace, new batteries are required.
batteries for 24 hours. To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
indicates Battery Depleted, new batteries are required.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 25
Bulletin 1609 UPS

Bulletin 1609 Network Management Card Troubleshooting

General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately to turn the UPS off then press and hold the button again until one beep is heard then release to enable the output.
Status Indications Indication Description Solution
UPS Disconnect The communication between UPS and
the 1609-ENET card has been disconnected.
Buzzer Alarm The UPS has detected a fault and
generated a buzzer alarm.
Input Out Of Range The UPS has detected that the input
utility voltage is out of range.
Battery Low The UPS has detected that the
batteries are low.
Battery Depleted The UPS has detected that the
batteries are depleted.
Battery Need Replace The UPS has detected that the battery
is bad or opened.
Test In Progress The UPS is currently in a test mode. Do not interrupt the UPS testing. Test Fail The UPS has detected that the battery
is bad.
Output Off The UPS is operating in standby mode
or fault shutdown.
UPS System Off The UPS system is in the standby state. If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the
UPS Shutdown The UPS was commanded to shut
down or fault shutdown.
Output Over Voltage The UPS has detected that the output
voltage is above the UPS’s output specification.
Output Under Voltage The UPS has detected that the output
voltage is below the UPS’s output specification.
Overload The UPS has detected that the UPS’s
output load is greater than 110%.
Over Temperature The UPS has detected that the
ambient temperature is greater than 60 °C, or some of the internal components are over temperature.
Fan Abnormal The UPS has detected that the UPS’s
fan has failed.
Inverter Abnormal The UPS has detected that the UPS
inverter circuit has failed.
Charger Abnormal The UPS has detected that the UPS
battery charger circuit has failed.
Check the 1609-ENET LEDs for the communication status and the operation of UPS. If the UPS is operating normal but the LEDs of the 1609-ENET card are not working properly, make sure the
cable is securely connected from the 1609-ENET card to the computer. If the LEDs of the 1609-ENET card is still not working properly, apply a known good 1609-ENET card to verify
whether the failure is on the UPS or the 1609-ENET. Please verify the type of fault from the Status Indicators or the LEDs on the UPS for further troubleshooting.
Verify that the input utility voltage is within the UPS’s input specification. If it is not, makes the necessary correction to the input utility power system.
The batteries must be charged for 24 hours. After charging batteries verify the battery status. If the batteries still indicate that they are low, replace the batteries.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Battery Depleted, new batteries are required.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still indicates Battery Need Replace, new batteries are required.
Verify that the battery is not disconnected or replace the batteries with a brand new set of batteries. Ensure the UPS ran for at least 4 hours before test.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the fault If the fault persists, contact Technical Support.
fault. If the fault persists, contact Technical Support. If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to reset the
fault. If the fault persists, contact Technical Support. Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within
its specification. To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact
Technical Support. Have qualified electrician verify that the quality of the output voltage and the input utility voltage are within
its specification. To clear fault, follow the General Clear Fault Procedure described above and if the problem persists, contact
Technical Support. Verify that the load does not exceed the load specification.
If it is, remove the excess load from the UPS’s output and clear the fault. If the problem persists, have a qualified electrician troubleshoot the UPS Load System and make the necessary corrections or select the appropriate size of UPS. If the problem persists, contact Technical Support.
Have a qualified electrician check the ambient temperature to make sure that it does not exceed 40°C (1609­SBAT) or 50°C (1609-HBAT). If it is over, make the necessary correction to the system. This issue may be corrected by improving the room ambient temperature (add ventilation or provide air conditioning).
Following the General Clear Fault Procedure to clear this fault. To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists, contact
Technical Support. Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above and if the Inverter Failure persists, contact Technical Support.
Clear this fault by removing the input utility voltage and batteries. Plug the batteries back in place and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.
26 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS

Bul. 1609-D Specifications

1609-D600N 1609-D1000N 1609-D1500N
Input V nom. 120V 120V 120V
Capacity 600 VA (390 W) 1000 VA (650 W) 1500 VA (980 W)
Voltage Range, default 90...145V 90...145V 90...145V
Voltage Range, widest online 90...145V 90...145V 90...145V
Current nom. 5.5 A 8.8 A 13 A
Capacity Frequency 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz
PFC None None None
Output V nom. 120V
Capacity 600 VA (390 W) 1000 VA (650 W) 1500 VA (980 W)
Online Output Voltage Range, default 108...132 V
Output Voltage Range, widest online 108...132 V
Transfer Point Accuracy ± 3 %
On Battery V nom 120V (sine wave)
Frequency 50/60 Hz ± 0.5Hz
THD ≤ 10% Full Linear Load
Short Circuit Protection Crest Factor 2.2:1
Efficiency On Battery (Typical with resistive load) 75%
Online - Typical with resistive load excluding AVR mode) 86% 94% 95%
Protection Surge 380 Joules
Overload (Shutdown after 10 s) > 110...130%
Overload (Shutdown immediately) 130%
Output Short Online/Battery Premises branch circuit over-current protection/Shutdown
Thermal Protection UPS inside temperature ≥ 60 ºC
Regulatory Safety UL1778, CSA C22.2 No. 107.3, EN/IEC62040-1
EMC FCC & CE (EN 62040-2)
Markings UL, cULus, FCC, CE, C-Tick
Battery Pack Run Time ≥5 min (at 25 °C, full R load) ≥3.5 min (25 °C, full R load) ≥2.5 min (at 25 °C, full R load)
Type Sealed Lead Acid Battery 12V/5Ah (for 0...40 °C B.B. BP5-12) 12V/5.5Ah (for 0...50 °CB.B. HRL5.5-12)
Voltage 36V
Charger Current limited, constant voltage float charger
Recharger Time Less than 8 hr to 90% capacity after discharge with full load
Lifetime 2...3 years at 25 °C ambient temperature
Environment Temperature Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Altitude Operating 0...6600 feet (0... 2000 meters)
Humidity Operating/Storage 5...95% RH (Non-condensing)
Heat Output On Line, Full load: 217 BTU/hr
Non-operating/Storage -15...+45 °C (+5...+113 °F)
On Line, Full load: 142BTU/hr On Line, Full load, Charging: 296 BTU per hour On Battery: Full Load: 1331 BTU per hour
On Line, Full load, Charging:
221 BTU per hour
On Battery: Full Load: 2218BTU
per hour
On Line, Full load: 176BTU/hr On Line, Full load, Charging: 256BTU per hour On Battery: Full Load: 3344BTU per hour
Audible Noise < 50 dBA @ Front Side 1 Meter
Mechanical Approximate Dimensions L*W*H In. (mm)
Approximate Weight lbs (kg) 29.7 (13.5) 30.1 (13.7) 31 (14.1)
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 27
8.66 x 16.14 x 10.24 (220 x 410 x 260)
Bulletin 1609 UPS

Bul. 1609-B Specifications

1609-B600N 1609-B1000N
Input V nom. 120V 120V
Capacity 600 VA (360 W) 1000 VA (600 W)
Voltage Range, default 96...138V
Voltage Range, widest online 96...138V
Current nom. 5.4 A 8.9 A
Capacity Frequency 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz
PFC None None
Output V nom. 120V
Capacity 600 VA (360 W) 1000 VA (600 W)
Online Output Voltage Range, default 96...138V
Output Voltage Range, widest online 96...138V
Transfer Point Accuracy ± 3%
On Battery V nom 120V (step wave)
Frequency 50/60 Hz ± 1 Hz
THD 47.5% (step wave) 47.6% (step wave)
Short Circuit Protection Crest Factor 2.5:1
Efficiency On Battery (Typical with resistive load) 80% Typical with resistive load
Online - Typical with resistive load excluding AVR mode) 94% Typical with resistive load
Protection Surge 380 Joules (Total performance rated with 10*1000 μ s pulse)
Overload (Shutdown after 10 s) > 110...130% - shutdown after 5 sec
Overload (Shutdown immediately) 130% shutdown immediately
Output Short: Online Premises branch circuit over-current protection
Output Short: Battery Shutdown
Thermal Protection UPS inside temperature ≥ 70 °C
Regulatory Safety UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1
EMC FCC & CE (Class A)
Markings UL, cULus, FCC, CE, C-Tick
Battery Pack Run Time ≥5 min (at 25 °C, full load = 360W, PF = 0.6...0.75) ≥2 min (at 25 °C, full load = 600W, PF = 0.6...0.75)
Type Sealed Lead Acid Battery
12V/5Ah (for 0...40 °C: B.B. BP5...12)
12V/5.5 Ah (for 0...50 °C: B.B. HRL5.5...12)
Voltage 24V
Charger Current limited, constant voltage float charger
Recharger Time Less than 12 hrs to 90% capacity after discharge with full load
Lifetime 2...3 years at 25 °C ambient temperature
Environment Temperature Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Altitude Operating 0...6600 feet (0... 2000 meters)
Humidity Operating/Storage 5...95% RH (Non-condensing)
Heat Output On Line, Full load: 107 BTU/hr
Audible Noise < 45 dBA @ Front Side 1 Meter
Mechanical Approximate Dimensions L*W*H In. (mm) 6.1 x 11 x 7.09 (155 x 300 x 180)
Approximate Weight lbs (kg) 14.5 (6.6) 14.7 (6.7)
Non-operating/Storage -15...+45 °C (+5...+113 °F)
On Line, Full load, Charging: 160 BTU per hour On Battery: Full Load: 1228 BTU per hour
On Line, Full load: 178 BTU/hr On Line, Full load, Charging: 231 BTU per hour On Battery: Full Load: 2047 BTU per hour
28 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

1609-D UPS Dimensions

Appendix A

1609 UPS Dimensions

1609-B UPS Dimensions

196
375
UNINTERRUPTIBLE
POWER SUPPLY
160 9-D
339
300
UNINTERRUPTIBLE
POWER SUPPLY
1609-B
220
200
257
187
170
160
DISABLE ENABLE
REMOTE FUNCTION 8 7 6 5 4 3 2 1
178

1609-EXBAT Unit Dimensions

196
140
339
300
140
187
170
160
178
140140
197
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 29
Appendix A 1609 UPS Dimensions

1609-BRK Dimensions (1609-D orientation)

1609-BRK Dimensions (1609-B orientation)

382 302
40
227
7
175
110
125
33
30 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
1609 UPS Dimensions Appendix A

Service Instructions

If the UPS requires service, do not return it to the distributor. Follow these steps:
1. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
2. When replacing batteries, replace with the same number of the 1609 battery packs supplied by Rockwell Automation.
WARNING: Do not dispose of battery in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolytes are harmful to the skin and eyes. It may be toxic. A battery can present a risk of electrical shock and high short circuit current.
3. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems.
4. If the problem persists, contact Rockwell Automation Customer Support at 440-646-5800.
5. Pack the UPS in its original packaging.Pack the UPS properly to avoid damage in transit. Never use Styrofoam
beads for packaging.
– Damage sustained in transit is not covered under warranty.
ATTENTION: Always disconnect the battery(s) before shipping, in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS.
The following precautions should be observed when working on batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Do not lay tools or metal parts on top of batteries.
Determine if battery is inadvertently grounded. If inadvertently grounded, remove
source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013 31
Appendix A 1609 UPS Dimensions
32 Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample
At code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at information, support chat and forums, software updates, and to sign up for product notification updates.
http://www.rockwellautomation.com/knowledgebase for FAQs, technical
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
SM
TechConnect representative, or visit
support programs. For more information, contact your local distributor or Rockwell Automation
http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the
Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication
Publication 1609-UM009A-EN-P - January 2013
RA-DU002, available at http://www.rockwellautomation.com/literature/.
Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...