![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg1.png)
Reference Manual
egaP egaP
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC Input...............................................................4
4.
DC Input...............................................................5
5. Input Inrush Current ...........................................5
6. Output .................................................................6
7. Hold-up Time.......................................................7
8. Efciency and Power Losses................................8
9. Functional Diagram.............................................9
10. Front Side and User Elements.............................9
11. Terminals and Wiring........................................10
12. Lifetime Expectancy and MTBF.........................10
13. EMC ....................................................................11
14. Environment ......................................................12
15. Protection Features ...........................................13
16. Safety Features ..................................................13
17. Dielectric Strength .............................................14
18. Certications
......................................................15
19. Physical Dimensions and Weight ..................... 16
20.
Application Notes ............................................. 17
20.1. Peak Current Capability ...........................17
20.2. Back-feeding Loads ..................................17
20.3. Charging Batteries ...............................18
20.4. External Input Protection .........................18
20.5. Parallel Use to Increase Output Power .... 18
20.6. Series Operation ....................................... 19
20.7. Inductive and Capacitive Loads ................ 19
20.8. Operation on Two Phases ........................ 20
20.9.
Use Without PE on the Input ................... 20
20.10.
Use in a Tightly Sealed Enclosure ............ 22
20.11.
Mounting Orientations ............................22
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLP15B
Index
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
• 230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
• 50Hz vs. 60Hz—As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
•shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg2.png)
Bulletin 1606 Switched Mode Power Supplies
Power Supply
100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efciency up to 83%
Compact Design, Width only 22.5mm
Full Output Power Between -10°C and +60°C
Large International Approval Package
3 Year Warranty
Description
Compact size, light weight, simple installation on the
DIN rail and the integration of only the highest quality
components are the factors that make the XLP power
supplies so easy to commission and use within minutes.
A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains provides reliable output power. This power supply
offers superior protection for equipment connected to
the public mains network or exposed to a critical
industrial environment.
The XLP family of power supplies offers output voltages
from 5 to 56Vdc and power ratings from 15 to 120W.
Specication Quick Reference
Output voltage DC 12V
Adjustment range 12 - 15V
Output current 1.3A at 12V
1.0A at 15V
Output power 15W
Output ripple < 75mVpp 20Hz to 20MHz
Input voltage AC 100-240V -15% / +10%
Mains frequency 50-60Hz ±6%
AC Input current 0.28 / 0.17A at 120 / 230Vac
Power factor 0.51 / 0.44 at 120 / 230Vac
AC Inrush current typ. 16 /31A peak value at
120/230Vac, 40°C
and cold start
DC Input 88-375Vdc
Efciency 83.0 / 82.5% at 120 / 230Vac
Losses 3.2 / 3.1W at 120 / 230Vac
Temperature range -10°C to +70°C operational
Derating 0.4W/°C +60 to +70°C
Hold-up time typ. 46 / 191ms at 120 / 230Vac
Dimensions 22.5x75x91mm WxHxD
Weight 130g / 0.29lb
Catalog Numbers
Power Supply 1606-XLP15B 12-15V Standard unit
Certication Marks
UL 508
UL 60950-1
NEC Class 2
Class I Div 2
CSA 22.2 No107.1
Marine
EMC, LVD
Marine RINA
GOST R
C-TICK
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM020A-EN-P — March 2014
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg3.png)
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
• This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
• Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or
threaten human life.
• This device is designed for use in non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
• This device may only be installed and put into operation by qualified personnel.
• This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
• If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
• Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to Mounting.
• This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid
(e.g. cable conduits) by more than 30%!
• Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the
device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat
source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless
power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.
Rockwell Automation Publication 1606-RM020A-EN-P — March 2014 3
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg4.png)
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input nom. AC 100-240V -15% / +10%, TN/TT/IT-mains
AC input range 85-264Vac continuous operation
264–300Vac < 0.5s
Allowed voltage L or N to earth max. 300Vac
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 59Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 54Vac steady-state value, see Fig. 3-1
AC 100V AC 120V AC 230V
Input current (rms) typ. 0.34A 0.28A 0.17A at 12V, 1.3A see Fig. 3-3
Power factor *) typ. 0.52 0.51 0.44 at 12V, 1.3A see Fig. 3-4
Crest factor **) typ. 3.45 3.53 3.94 at 12V, 1.3A
Start-up delay typ. 780ms 780ms 780ms see Fig. 5 2
Rise time typ. 12ms 12ms 12ms at 12V, 1.3A, see Fig. 3-2
Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
54V 300Vac264V
Shut-down
59V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 3-3 Input current vs. output load at 12V Fig. 3-4 Power factor vs. output load
1.4A
0.2
0.4
0.80
0
0.10
0.4A
Input Current, typ.
1.0
0.20
0.6
1.2
0.25
0.15
0.05
0.30
0.35
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
1.4A
0.2 0.4 0.6 1.0
0.30
0.35
0.40
0.45
0.50
0.55
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
0.8 1.2
Output Current
4 Rockwell Automation Publication 1606-RM020A-EN-P — March 2014
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg5.png)
4. DC Input
DC input nom. DC 110-300V -20%/+25%
DC input range min. 88-375Vdc continuous operation
DC input current typ. 0.16A / 0.057A 110Vdc / 300Vdc, at 12V, 1.3A
Turn-on voltage typ. 80Vdc steady state value
Shut-down voltage typ. 60Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
a) Use a battery or similar DC source.
For other sources, please contact Rockwell Automation.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
5. Input Inrush Current
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 13A
peak
16A
peak
31A
peak
40°C ambient, cold start
typ. 11A
peak
13A
peak
26A
peak
40°C ambient, cold start
Inrush energy max. 0.1A
2
s 0.1A2s 0.4A2s 40°C ambient, cold start
Fig. 5-1 Input inrush current, typical behavior
Fig. 5-2 Input inrush current, zoom into rst peak
Input: 230Vac
Output: 12V, 1.3A
Ambient: 25°C
Upper curve: Input current 5A/DIV
Lower curve: Input voltage 500V/DIV
Time basis: 10ms / DIV
Input: 230Vac
Output: 12V, 1.3A
Ambient: 25°C
Input current curve: 5A/DIV, 500μs / DIV
Ipeak 23A
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.
Rockwell Automation Publication 1606-RM020A-EN-P — March 2014 5
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg6.png)
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 12V
Adjustment range min. 12-15V guaranteed
max. 16V *) at clockwise end position of potentiometer
Factory setting 12.0V ±0.2%, at full load, cold unit
Line regulation max. 10mV 85-264Vac
Load regulation max. 100mV static value, 0A 1.3A
Ripple and noise voltage max. 75mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 1 650μF
Output current nom. 1.3A at 12V, see Fig. 6-1
nom. 1.0A at 15V, see Fig. 6-1
Output power nom. 15W
Short-circuit current min. hiccup mode, see Fig. 6-2
max. hiccup mode, see Fig. 6-2
*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee that this value can be achieved. The typical value achievable by turning the potentiometer to the clockwise end position
is 15.7V.
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Hiccup mode; output current at
shorted output, 230Vac, typ.
Output Voltage
0
0
2
4
6
16V
8
10
12
2.0
2.06.00.1 1.44.08.0 1.2141.8
Adjustment
Range
Output Current
Continuous
Hiccup Mode
Output
Current
0
1.7A
60ms
t
240ms 240ms
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specied short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and cause a voltage dip on the output. Detailed curves are provided in section 20.1.
Peak current voltage dips typ. from 12V to 7.8V at 2.6A for 50ms, resistive load
typ. from 12V to 5.2V at 6.5A for 2ms, resistive load
typ. from 12V to 2.0V at 6.5A for 5ms, resistive load
6 Rockwell Automation Publication 1606-RM020A-EN-P — March 2014
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg7.png)
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 100V AC 120V AC 230V
Hold-up Time typ. 62ms 96ms 365ms at 12V, 0.65A, see Fig. 7-1
typ. 30ms 46ms 191ms at 12V, 1.3A, see Fig. 7-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
0
25
50
125
150ms
85 120 155 190 230Vac
Input Voltage
Hold-up Time
75
100
a) 12V 0.65A typ.
b) 12V 0.65Amin.
c) 12V 1.3A typ.
d) 12V 1.3A min.
a b c d
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.
Rockwell Automation Publication 1606-RM020A-EN-P — March 2014 7
![](/html/70/707e/707e02430c1c89a801e59427af5a3bb8c20f92f9ef01f244a7f39591b4fd8cf8/bg8.png)
Bulletin 1606 Switched Mode Power Supplies
8. Efciency and Power Losses
AC 100V AC 120V AC 230V
Efciency typ. 82.4% 83.0% 82.5% at 12V, 1.3A (full load)
Power losses typ. 0.5W 0.55W 0.75W at 0A
typ. 1.7W 1.6W 1.8W at 12V, 0.65A (half load)
typ. 3.2W 3.1W 3.2W at 12V, 1.3A (full load)
Fig. 8-1 Efciency vs. output current at 12V,
typ.
Fig. 8-2 Losses vs. output current at 12V,
typ.
Efciency
0.2
77
78
79
80
81
82
83
76
84%
1.4A0.6 0.8 1.2
Output Current
0.4 1.0
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
Power Losses
00.2 1.4
0
0.5
1.5
2.0
4W
2.5
0.4 0.6 0.8
Output Current
1.0 1.2
1.0
3.0
a) 100Vac
b) 120Vac
c) 230Vac
3.5
b
c
a
Fig. 8-3 Efciency vs. input voltage at 12V,
1.3A, typ.
Fig. 8-4 Losses vs. input voltage at 12V, 1.3A,
typ.
Efciency
85 120
155
190 225 260Vac
79
80
81
82
83
84
85%
Input Voltage
Power Losses
2.75
3.25
3.50
3.75
4W
85 120
155
190 225 260Vac
Input Voltage
3.00
8 Rockwell Automation Publication 1606-RM020A-EN-P — March 2014
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time.unless noted otherwise.