•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
• 230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
• 50Hz vs. 60Hz—As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
•shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
Power Supply
100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efciency up to 77.2%
Compact Design, Width only 22.5mm
Full Output Power Between -10°C and +60°C
Large International Approval Package
3 Year Warranty
Description
Compact size, light weight, simple installation onto the
DIN rail and the integration of only the highest quality
components are the factors that make the XLP family of
power supplies so easy to deploy and use within seconds.
A rugged electrical and mechanical design as well as
high immunity against electrical disturbances on the
mains provide reliable output power. This power supply
offers superior protection for equipment connected to
the public mains network or exposed to a critical
industrial environment.
The XLP family of power supplies offers output voltages
from 5 to 56Vdc and power ratings from 15W to 120W.
Specication Quick Reference
Output voltage DC 5V
Adjustment range 5 – 5.5V
Output current 3A at 5V
Output power 15W
Output ripple < 50mVpp 20Hz to 20MHz
Input voltage AC 100-240V -15% / +10%
Mains frequency 50-60Hz ±6%
AC Input current 0.28 / 0.17A at 120 / 230Vac
Power factor 0.51 / 0.44 at 120 / 230Vac
AC Inrush current typ. 16 /31A peak value at
120/230Vac, 40°C
and cold start
DC Input 88-375Vdc
Efciency 76.8 / 77.2% at 120 / 230Vac
Losses 4.6 / 4.5W at 120 / 230Vac
Temperature range -10°C to +70°C operational
Derating 0.4W/°C +60 to +70°C
Hold-up time typ. 45 / 186ms at 120 / 230Vac
Dimensions 22.5x75x91mm WxHxD
Weight 130g / 0.29lb
Catalog Numbers
Power Supply 1606-XLP15A 5V Standard unit
Certications
UL 508
UL 60950-1
NEC Class 2
Class I Div 2
CSA 22.2 No107.1
Marine
EMC, LVD
Marine RINA
GOST R
C-Tick
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
2Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
• This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
• Do not use this power supply in equipment where malfunction may cause severe personal injury or threaten human life.
• This device is designed for use in non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
• This device may only be installed and put into operation by qualified personnel.
• This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
• Should damage or malfunction occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
• Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to Mounting.
• This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid
(e.g. cable conduits) by more than 30%!
• Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the
device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat
source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless
power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 20143
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input nom. AC 100-240V -15% / +10%, TN/TT/IT-mains
AC input range 85-264Vac continuous operation
264–300Vac < 0.5s
Allowed voltage L or N to earth max. 300Vac
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 59Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 54Vac steady-state value, see Fig. 3-1
AC 100V AC 120VAC 230V
Input current (rms) typ. 0.34A 0.28A 0.17A at 5V, 3A see Fig. 3-3
Power factor *) typ. 0.52 0.51 0.44 at 5V, 3A see Fig. 3-4
Crest factor **) typ. 3.45 3.53 3.94 at 5V, 3A
Start-up delay typ. 630ms 630ms 630ms see Fig. 5 2
Rise time typ. 10ms 10ms 10ms at 5V, 3A, see Fig. 3-2
Turn-on overshoot max. 100mV 100mV 100mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
54V300Vac264V
Shut-down
59V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 3-3 Input current vs. output load Fig. 3-4 Power factor vs. output load
3.0A
0.5
1.0
2.00
0
0.10
0.4A
Input Current, typ.
2.5
0.20
1.5
0.25
0.15
0.05
0.30
0.35
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
3.0A
0.51.0
1.52.5
0.30
0.35
0.40
0.45
0.50
0.55
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
2.0
Output Current
4Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
4. DC Input
DC input nom. DC 110-300V -20%/+25%
DC input range min. 88-375Vdc continuous operation
DC input current typ. 0.16A / 0.057A 110Vdc / 300Vdc, at 5V, 3A
Turn-on voltage typ. 80Vdc steady state value
Shut-down voltage typ. 60Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
a) Use a battery or similar DC source.
For other sources, please contact Rockwell Automation.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
5. Input Inrush Current
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120VAC 230V
Inrush current max. 13A
peak
16A
peak
31A
peak
40°C ambient, cold start
typ. 11A
peak
13A
peak
26A
peak
40°C ambient, cold start
Inrush energy max. 0.1A
2
s 0.1A2s 0.4A2s 40°C ambient, cold start
Fig. 5-1 Input inrush current, typical behavior
Fig. 5-2 Input inrush current, zoom into rst peak
Input: 230Vac
Output: 5V, 3A
Ambient: 25°C
Upper curve:Input current 5A/DIV
Lower curve:Input voltage 500V/DIV
Time basis: 10ms / DIV
Output: 5V, 3A
Ambient: 25°C
Input current curve: 5A/DIV, 500μs / DIV
Ipeak 23A
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 20145
Bulletin 1606 Switched Mode Power Supplies
6. Output
Output voltage nom. 5V
Adjustment range min. 5-5.5V guaranteed
max. 6V *) at clockwise end position of potentiometer
Factory setting 5.1V ±0.2%, at full load, cold unit
Line regulation max. 10mV 85-264Vac
Load regulation max. 100mV static value, 0A 3A
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 4 800μF
Output current nom. 3A at 5V, see Fig. 6-1
nom. 2.72A at 5.5V, see Fig. 6-1
Output power nom. 15W
Short-circuit current min. hiccup mode see Fig. 6-2
max. 3A rms-current short circuit impedance <10mOhm, unit makes start-up
attempts at short-circuit (hiccup mode)
*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee this value can be achieved. The typical value achievable by turning the potentiometer to the clockwise end position
is 5.8V.
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Hiccup mode; output current at
shorted output, 230Vac, typ.
Output Voltage
0
0
1
2
6V
3
4
5
3.5
A
2.51.50.52.01.03.0
Adjustment
Range
Output Current
Continuous
Hiccup Mode
Output
Current
0
3.3A
45ms
t
235ms235ms
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specied short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and causes a voltage dip on the output. Detailed curves can be found in section 20.1.
Peak current voltage dips typ. from 5V to 2.4V at 6A for 50ms, resistive load
typ. from 5V to 1.0V at 15A for 2ms, resistive load
typ. from 5V to 0.8V at 15A for 5ms, resistive load
6Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 100V AC 120VAC 230V
Hold-up Time typ. 61ms 93ms 340ms at 5V, 1.5A, see Fig. 7-1
typ. 29.5ms 45ms 186ms at 5V, 3A, see Fig. 7-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions
0
25
50
125
150ms
85120155190230Vac
Input Voltage
Hold-up Time
75
100
a) 5V 1.5A typ.
b) 5V 1.5Amin.
c) 5V 3A typ.
d) 5V 3A min.
a bcd
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 20147
Bulletin 1606 Switched Mode Power Supplies
8. Efciency and Power Losses
AC 100V AC 120VAC 230V
Efciency typ. 75.8% 76.8% 77.2% at 5V, 3A (full load)
Power losses typ. 0.2W 0.3W 0.6W at 0A
typ. 2.3W 2.3W 2.4W at 5V, 1.5A (half load)
typ. 4.9W 4.6W 4.5W at 5V, 3A (full load)
Fig. 8-1 Efciency vs. output current at 5V,
typ.
Fig. 8-2 Losses vs. output current at 5V,
typ.
Efciency
0
71
72
73
74
75
76
77
70
78%
3.0A1.0 1.52.5
Output Current
0.52.0
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
Power Losses
00.53.0A
0
2
3
5W
4
1.0 1.52.0
Output Current
2.5
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
1
c
b
a
Fig. 8-3 Efciency vs. input voltage at 5V, 3A,
typ.
Fig. 8-4 Losses vs. input voltage at 5V, 3A,
typ.
Efciency
85120
155
190225 260Vac
72
73
74
75
76
77
78%
Input Voltage
Power Losses
3.75
4.25
4.50
4.75
5W
85120
155
190225 260Vac
Input Voltage
4.00
8Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
9. Functional Diagram
Fig. 9-1 Functional diagram
Input Fuse
&
Input Filter
L
N
Output Over-
Voltage
Protection
Input
Rectier
&
Inrush
Limiter
Power
Converter
Output
Voltage
Regulator
+
-
-
Output
Filter
V
OUT
DC
on
PE
10. Front Side and User Elements
Fig. 10-1 Front side
A
Output Terminals
Screw terminals,
Dual terminals for the negative pole allows an easy grounding of the output voltage.
+ Positive output
- Negative (return) output
B
Input Terminals
Screw terminals
L Phase (Line) input
N Neutral conductor input
PE (Protective Earth) input
CDC-on LED (green)
On when the voltage on the output terminals is > 2V
D
Output voltage potentiometer
Turn to set the output voltage. Factory set: 5.1V
A
B
C
D
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 20149
Bulletin 1606 Switched Mode Power Supplies
11. Terminals and Wiring
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b) Follow national installation codes and regulations!
c) Ensure that all strands of a stranded wire are fully inserted in the terminal connection.
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed.
12. Lifetime Expectancy and MTBF
These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.
AC 100V AC 120VAC 230V
Lifetime expectancy
*)66 000h 70 000h 93 000h at 5V, 3A and 40°C
> 15 years > 15 years > 15 years at 5V, 1.5A and 40°C
> 15 years > 15 years > 15 years at 5V, 3A and 25°C
MTBF
**) SN 29500, IEC 61709 2 479 000h 2 838 000h 2 686 000h at 5V, 3A and 40°C
4 066 000h 4 654 000h 4 405 000h at 5V, 3A and 25°C
MTBF
**) MIL HDBK 217F 1 175 000h 1 251 000h 1 145 000h at 5V, 3A and 40°C; Ground Benign GB40
1 575 000h 1 676 000h 1 534 000h at 5V, 3A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours and is calculated according to the
capacitor’s manufacturer specication. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF gure is a statistical representation of the likelihood of a device to fail. A MTBF gure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the eld. However, it cannot be determined if the failed unit
has been running for 50 000h or only for 100h.
10Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
13. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available upon request.
EMC Immunity
Generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
8kV
Criterion A
Criterion A
Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5
L
N
N
PE, L PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + -
+
PE, - PE
500V
2kV
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
Criterion A
Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C
Input voltage swells Rockwell Automation internal standard 300Vac, 500ms Criterion A
Powerful transients VDE 0160 over entire load range 750V, 1.3ms Criterion A
Criteria:
A: Power supply shows normal operation behavior within the dened limits.
C: Temporary loss of function is possible. Power supply may shut down and restart by itself. The power supply will incur no damage or hazard.
EMC Emission
Generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Not applicable below 75W
input power
Voltage uctuations, icker EN 61000-3-3 fullled
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesirable operation.
Switching frequency
Constant, typ. 65kHz
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201411
Bulletin 1606 Switched Mode Power Supplies
14. Environment
Operational temperature
*)-10°C to +70°C (14°F to 158°F) Reduce output power according Fig. 14-1
Storage temperature -40 to +85°C (-40°F to 185°F) For storage and transportation
Output de-rating 0.4W/°C 60-70°C (140°F to 158°F)
Humidity
Altitude 0 to 6000m (0 to 20 000ft) Reduce output power or ambient temperature
above 2000m sea level.
Altitude de-rating 1W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 14-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is dened as the air temperature 2cm below the unit.
**) Do not energize in the presence of condensation.
Fig. 14-1 Output power vs. ambient temp. Fig. 14-2 Output power vs. altitude
0
-10 02040
70°C
2.5
5.0
7.5
10.0
12.5
15W
60
Ambient Temperature
Allowable
Output Power
0
020004000
6000m
2.5
5.0
7.5
10.0
12.5
15W
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
A
B
C
Allowable
Output Power
12Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
15. Protection Features
Output protection Electronically protected against overload, no-load and short-circuits
Output over-voltage protection typ. 8.7Vdc
max. 9.6Vdc
Output over-current protection electronically limited see Fig. 6-2
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 2.5mm in diameter e.g. screws, small parts
Over-temperature protection Not included
Input transient protection MOV Metal Oxide Varistor
Internal input fuse T3.15A H.B.C. not user replaceable
*) In case of a protection event, audible noise may occur.
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again.
*)
16. Safety Features
Input / output separation
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
Class of protection I PE (Protective Earth) connection required
II (with restrictions) for use without PE connection contact PULS
Isolation resistance > 5MOhm Input to output, 500Vdc
Touch current (leakage current) typ. 0.17mA / 0.38mA 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.24mA / 0.55mA 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.40mA / 0.86mA 230Vac, 50Hz, TN-,TT-mains / IT-mains
< 0.21mA / 0.44mA 110Vac, 50Hz, TN-,TT-mains / IT-mains
< 0.30mA / 0.66mA 132Vac, 60Hz, TN-,TT-mains / IT-mains
< 0.54mA / 1.08mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) Double or reinforced insulation
*)
SELV IEC/EN 60950-1
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201413
Bulletin 1606 Switched Mode Power Supplies
17. Dielectric Strength
The output voltage is oating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the eld using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1 Dielectric strength
A B C
Type test 60s 2500Vac 3000Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac
Cut-off current setting > 6mA > 6mA > 1mA
A
C
N
L
Input
Earth, PE
Output
-
+
B
To fulll the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or cannot be switched off in the occurrence of
unnoticed earth faults.
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
14Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
EN 60950-1, EN 61204-1
Complies with CE EMC and CE Low Voltage Directives
UL 508
LISTED E56639 for use in the U.S.A. (UL 508) and Canada
(C22.2 No. 14-95). Industrial Control Equipment
UL 60950
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and
Canada (C22.2 No. 60950)
Information Technology Equipment, Level 3
NEC Class 2
NEC
CLASS 2
Listed as Limited Power Source (LPS) in the UL 60950-1 UL report.
According to NEC (National Electrical Code) Article 725-41 (4).
CSA C22.2 No. 107.1,
60950-1
CSA Certied under File Number 240020
GL (Germanischer Lloyd) classied for marine and offshore
applications. Environmental category: C, EMC2
See below for link to Certicate.
Marine
GOST R
GOST R certication is applicable for products intended for sale
and use within Russia. See below for link to Certicate.
ISA 12.12.01, CSA
C22.2 No. 213
RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A.
(ISA 12.12.01) and Canada (C22.2 No. 213)
Hazardous Location ClassI, Div. 2, Groups A, B, C, D
Marine RINA
RINA (Registro Italiano Navale) certied. See below for link to
Certicate.
C-TICK
C-Tick compliance is for products intended for sale and use within
the Australian market. See below for link to the C-Tick Declarations
of Conformity.
Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certifications.
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201415
Bulletin 1606 Switched Mode Power Supplies
19. Physical Dimensions and Weight
Weight 130g / 0.29lb
DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN rail height must be added to the unit depth (91mm) to calculate the total required
installation depth.
Installation Clearances See section 2.
Fig. 19-1 Front view Fig. 19-2 Side view
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
16Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
20. Application Notes
20.1. Peak Current Capability
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current
demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal
output current (including the PowerBoost) The same situation applies, when starting a capacitive load.
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit,
the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe
operation of subsequent circuit breakers.
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the
power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following
two examples show typical voltage dips:
Fig. 20-1 Peak loading with 2x the nominal
current for 50ms, typ.
Fig. 20-2 Peak loading with 5x the nominal
current for 5ms, typ.
Peak load 6A (resistive load) for 50ms
Output voltage dips from 5.1V to 2.4V.
Peak load 15A (resistive load) for 5ms
Output voltage dips from 5.1V to 0.8V.
20.2. Back-feeding Loads
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
The maximum allowed feed back voltage is 6.3Vdc. The absorbing energy can be calculated according to the built-in
large sized output capacitor which is specied in section 6.
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply.
It does not matter, whether the power supply is on or off. However, please note that the output voltage can dip to
zero for approximately 200ms if the back-feed voltage is removed.
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201417
Bulletin 1606 Switched Mode Power Supplies
20.3. External Input Protection
The unit is tested and approved for branch circuits up to 20A. An external protection is only required, if the supplying
branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local
regulations might apply.
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of
the circuit breaker. A minimum value of 6A B- or 3A C-Characteristic breaker should be used.
20.4. Parallel Use to Increase Output Power
1606-XLP15A power supplies can be paralleled to increase the output power.
This power supply does not include the capacity to balance the load current
between the power supplies. Usually the power supply with the higher
adjusted output voltage draws current until it goes into current limitation. This
causes no harm to the power supply as long as the ambient temperature stays
below 45°C. The 1606-XLP15A can also be paralleled with other XLP power supplies
with 5V output voltage. The output voltages of all power supplies must be
adjusted to the same value (±100mV).
A fuse or diode on the output of each unit is required only if you connect more than three units in parallel. If you use
a fuse or circuit breaker, choose one with approximately 150% of the rated output current of one power supply.
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power
supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard
mounting orientation (input terminals on the bottom and output terminals on top of the unit). Please note that leakage
current, EMI, inrush current and harmonics will increase when using multiple power supplies.
Unit A
AC
Unit B
AC
DC
DC
+
+
Load
+
-
-
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
18Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
20.5. Parallel Use for Redundancy
Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two
power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is
automatically able to support the load current without any interruption. Redundant systems for a higher power
demand are usually built in a N+1 method. E.g. ve power supplies, each rated for 3A are paralleled to build a 12A
redundant system.
Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in
the secondary side of the power supply. In such a case, the failing unit becomes a load for the other power supplies
and the output voltage can no longer be maintained. This can only be avoided by using decoupling diodes
which are included in the decoupling module 1606-XLPRED.
Recommendations for building redundant power systems:
a)Use separate input fuses for each power supply.
b)Monitor the individual power supply units.
c)1+1 Redundancy is allowed up to an ambient temperature of 60°C
N+1 Redundancy is allowed up to an ambient temperature of 45°C
d)It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting.
20.6. Series Operation
Power supplies of the exact same type can be connected in series for higher
output voltages. It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed 150Vdc. Voltages
with a potential above 60Vdc are not SELV any more and can be dangerous.
Such voltages must be installed with a protection against touching. Grounding
the output is required when the sum of the output voltage is above 60Vdc.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals. Keep an installation clearance of 15mm (left /
right) between two power supplies and avoid installing the power supplies on
top of each other. Do not use power supplies in series in mounting
orientations other than the standard mounting orientation (input terminals on the bottom and output terminals on
top of the unit). Please note that leakage current, EMI, inrush current and harmonics will increase when using multiple
power supplies.
Unit A
AC
Unit B
AC
DC
DC
+
-
+
Load
+
-
-
Earth
20.7. Inductive and Capacitive Loads
The unit is designed to supply unlimited inductive loads.
The max. capacitive load depend on the steady state output current. At 3A output current, the output capacity should
not be larger than 10 000μF and at 0.3A output current not larger than 25 000μF. In case of larger capacitors, the unit
can show start-up attempts or start-up problems.
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201419
Bulletin 1606 Switched Mode Power Supplies
20.8. Operation on Two Phases
The power supply can also be used on two phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying
voltage is below 240V
input. The N input is not protected internally; in this case it is connected
to a hot wire. Appropriate fuses or circuit breakers are specied in section
20.3, “External Input Protection”.
+10%
. Use a fuse or a circuit breaker to protect the N
L3
L1
max.
+10%
240V
L2
Power Supply
L
Fuse
N
PE
AC
internal
fuse
DC
20.9. Use Without PE on the Input
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Contact Rockwell Automation if you do not use the PE terminal. A different marking of the front foil is then required.
Grounding of the input is benecial for a high EMI immunity: Symmetrical spikes or fast transients on the input side
can be conducted directly to earth by the built-in lter capacitors. The magnitude of such spikes or fast transients on
the output side caused by the input is much smaller compared to not connecting this terminal to the ground.
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
20Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
20.10. Use in a Tightly Sealed Enclosure
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature denes the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box; no other heat producing item is inside the box.
Enclosure: Rittal Type IP66 Box PK 9510 100, plastic, 130x130x75mm
Input: 230Vac
Case A:
Load: 5V, 3A; load is placed outside the box.
Temperature inside the box: 38.2°C (in the middle of the right side of the power supply with a distance of 1cm)
Temperature outside the box: 26.0°C
Temperature rise: 12.2K
Case B:
Load: 5V, 2.4A; (=80%) load is placed outside the box.
Temperature inside the box: 35.3°C (in the middle of the right side of the power supply with a distance of 1cm)
Temperature outside the box: 25.6°C
Temperature rise: 9.7K
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM019A-EN-P — March 201421
Bulletin 1606 Switched Mode Power Supplies
20.11. Mounting Operations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the max. allowed ambient temperature. The amount of reduction
inuences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 20-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
0
10203040
60°C
3
9
12
15W
50
A
1
6
Ambient Temperature
Fig. 20-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Power
0
10203040
60°C
3
9
12
15W
50
6
A
1
A
2
Ambient Temperature
Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)
Output Power
0
10203040
60°C
3
9
12
15W
50
6
A
1
A
2
Ambient Temperature
Fig. 20-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10203040
60°C
3
9
12
15W
50
6
A
1
A
2
Ambient Temperature
Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10203040
60°C
3
9
12
15W
50
6
A
1
A
2
Ambient Temperature
All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
22Rockwell Automation Publication 1606-RM019A-EN-P — March 2014
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support
notes, sample code and links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools. You can also visit our Knowledgebase at http://
www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums,
software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechCon ne ct
representative, or visit http://www.rockwellautomation.com/support/
SM
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in
this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or CanadaUse the Wor ldwi de Lo cato r at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these
procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain o ne) to your
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002