Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLE960DX-3N
Index
1. Description ...........................................................1
2. Specication Quick Reference ............................1
3. Catalog Numbers .................................................1
4. Certication Marks ..............................................1
5. AC Input
6. Input Inrush Current
7. Output .................................................................5
8. Hold-up Time.......................................................6
9. Efciency and Power Losses................................7
10. Functional Diagram.............................................8
11. Front Side and User Elements.............................8
12. Terminals and Wiring..........................................9
13. Reliability .............................................................9
14. EMC ....................................................................10
15. Environment ......................................................11
16. Protection Features ...........................................12
17. Safety Features ..................................................12
18. Dielectric Strength ............................................12
19. Certications
.............................................................3
..........................................4
.....................................................13
Terminology and Abbreviations
Environmental Compliance ........................... 13
20.
21. Physical Dimensions and Weight .................... 14
22. Installation and Operating Instructions ..........14
23. Accessories ........................................................ 15
24. Comparison between the 160
a Transformer and a Traditional Switched-
Mode Power Supply .........................................15
25. Application Notes
25.1. Periodic PeakPower Capability
25.2. Charging Batteries ..................................16
25.3. Output Circuit Breakers ................17
25.4. External Input Protection ......................... 18
25.5. Back-Feeding Loads ...................................18
25.6. Parallel Use to Increase Output Power ....18
25.7. Parallel Use for Redundancy ....................18
25.8. Series Operation .......................................19
25.9. Inductive and Capacitive Loads ................19
25.10 Loss of One Input Phase ...........................19
25.11. Use in a Tightly Sealed Enclosure ............19
25.12. Mounting Orientations ............................20
........................................... 16
Page
6-XLE960DX-3N,
.................16
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• 3AC 400V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. 3AC means three phase input. E.g.: DC 12V describes a 12V battery disregarding whether it is charged (13.7V) or discharged (10V).
If not otherwise stated, 3AC 400V parameters are valid at 50Hz and 3AC 480V parameters are valid at 60Hz mains frequency.
• 3x 400Vac—A figure with the unit (Vac) at the end is a value used during testing without any additional tolerance included. 3x 400Vac
means a three phase input.
Bulletin 1606 Switched Mode Power Supplies
Semi-Regulated Power Supply
••
Alternative or Replacement for AC Transformer
•
Three Phase Input – DC Output
•
Mountable on a Din Rail
•
Width only 96mm
•
95.5% Eciency
•
125% Peak Power Capability
•
No Input Inrush Current
•
Active Input Transient Blocker
•
Full Power Between -25°C and +60°C
•
Easy Failure Diagnostics
•
No Electrolytic Capacitors on Input Side
•
Cost Eective and Robust
•
3 Year Warranty
1. Description
2. Specication Quick Reference
Output voltage DC 24V Factory setting to
24.1V
Adjustment range none
Output current 40A continuous
50A for typ. 15s
Output power 960W continuous
1200W for typ. 15s
Output ripple < 1500mVpp 20Hz-2kHz
< 200mVpp 2kHz to 20MHz
Input voltage 3AC 480V 1606-XLE960DX-3N
Mains frequency 50-60Hz ±6%
AC Input current 1.4A / phase 3x480V
Power factor 0.93 24V, 40A
AC Inrush current typ. 2A peak
Eciency 95.5%
Losses 45.2W
Temperature range -25°C to +70°C operational
Derating 24W/°C +60 to +70°C
The power supplies in the three-phase (-3) series
feature a new and innovative concept for
generating an isolated DC voltage from a
three-phase mains system.
A semi-regulated resonant converter enables a very
compact design, maximum eciency and extremely
competitive pricing with only a small compromise in
the output voltage regulation, output ripple and
hold-up time.
Weighing just 1.4 kg, the device provides 960 watts
of continuous output power and an additional 25%
power reserve for dynamic loads. The light-weight
design along with compact dimensions facilitate
straightforward mounting on DIN rail.
Primary use are applications involving supplies to
motors, valves and other load circuits with a high
power consumption, where an accurate output
voltage regulation which is standard on traditional
switched-mode power supplies is not required.
Furthermore, these switched-mode power supplies
can often replace mains transformers with rectiers.
Dimensions 96x124x159mm WxHxD
3. Catalog Numbers
4. Certication Marks
Power Supply
1606-XLE960DX-3N 480V Input
IND. CONT. EQ.
18WM
LISTED
UL 508
UL 60950-1
EMC, LVD
Accessory 1606-XLSBUFFER24 24V Buffer Unit
Marine RINA
GOST R
C-Tick
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Intended Use
• This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
• Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or
threaten human life.
• This device is designed for use in non-hazardous, ordinary or unclassified locations.
Installation Requirements
• This device may only be installed and put into operation by qualified personnel.
• This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
• If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
• Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to section 25-14
in this document.
• This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid
(e.g. cable conduits) by more than 30%!
• Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the
device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat
source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless
power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014 3
Bulletin 1606 Switched Mode Power Supplies
5. AC-Input
1606-XLE960DX-3N
AC input nom. 3AC 480V
Mains arrangement
TN-, TT- or IT-Mains. Consult factory if one phase is grounded.
AC input range
min.
3x 432-528Vac fully regulated output (±2%), Pout > 48W
min. 3x 360-552Vac
*)
permanently allowed,
see Fig. 5-1 for output voltage regulation
max. 3x 565Vac Absolute maximum input voltage with no
damage to the power supply. Output
might be o at this level.
Input frequency
nom. 50 – 60Hz ±6%
Turn-on voltage typ. 3x 390Vac see
Fig. 5-2
Shut-down voltage typ.
3x 355Vac see Fig. 5-2
Input current
nom. 1.4A at 40A, symmetrical input, see Fig. 5-4
Power factor **) typ. 0.93 at 40A, symmetrical input, see Fig. 5-5
Turn-on overshoot typ. 480mV see
Fig. 5-3
Start-up delay ***) typ. 350ms over the entire load range, see Fig. 5-3
Rise time typ. 40ms 0mF, 40A, see
Fig. 5-3
typ. 70ms 40mF, 40A, see
Fig. 5-3
*) A minimum voltage of 3x408Vac is required to turn the power supply on.
**) The power factor is the ratio of the true (or real ) power to the apparent power in an AC circuit.
***) The start-up delay for mains voltage interruptions up to 350ms is close to zero. In such cases, the power supply will
immediately generate the output voltage once the mains voltage interruption is over. Do not use the 1606-XLSBUFFER24
buer module as an accessory when longer mains interruptions need to be bridged (see section 23).
Input Voltage Range
Fig. 5-1
Output voltage vs. input voltage and input current
Changes of the input voltage will be fully
regulated within certain limits. The
output voltage will only start to change
proportionally to the input voltage with
extreme under or over-voltages. The
yellow LED reports an input voltage
problem if exceeded by a window of
±15%. The maximum increase of the
output voltage is limited to the 29.9V
OVP level. This level will be kept
regulated for 2s before the power supply
will shut down and re ports “Shut-down”
by the red LED.
24V
20V
26V
22V
504456 576Vac384
V
OUT
V
IN
1606-XLE: 480
28V
528 552432408 360
P
OUT
> 48W (5%)
P
OUT
= 0W
4 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Fig. 5-2 Input Voltage Range Fig. 5-3 Turn-on behavior denitions
Turn-on
fully regulated
range
V
IN
P
OUT
3x 528Vac
Shut-down
3x 432Vac480V Version:
3x 440Vac3x 360Vac400V Version:
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-4 Input current vs. output load Fig. 5-5 Power factor vs. output load
50A
510 30 45
0
0.3
0.6
0.9
1.2
1.5
1.8A
Input Current per Phase, typ.
Output Current
15 20 25 35 40
50A
510 30 45
0.70
0.75
0.8
0.85
0.9
0.95
1.0
Power Factor, typ.
Output Current
15 20 25 35 40
6. Input Inrush Current
There is virtually no input inrush current surge as there are no electrolytic bulk-capacitors used on the input side of
the power supply.
The charging current into the EMI suppression capacitors is disregarded for the rst millisecond after switch-on.
1606-XLE960DX-3N
Inrush current
max. 4A
peak
-25°C to +70°C, see Fig. 6-1
Inrush energy max. 5A2s -25°C to +70°C, see
Fig. 6-1
Inrush delay
typ. 350ms see
Fig. 6-1
Fig. 6-1 Input inrush current
Input Current
Input Voltage
Output Voltage
A
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014 5
Bulletin 1606 Switched Mode Power Supplies
7. Output
Output voltage nom. 24.1V
Output voltage adjustment range
none The output voltage is xed. No adjustment possible.
Output current
nom. 40A continuous, see Fig. 7-1
50A up to 15s with full output voltage, see Fig. 7-1
Short-circuit current
typ. 180A load impedance 25mOhm, see
Fig. 7-1
Note: The short-circuit current is available for 0.1s.
Output power
nom. 960W continuous
1200W up to 15s
Line regulation
max. ±2% see Fig. 5-1
Load regulation max. 800mV static value, 0A 40A 0A
max. 200mV static value, 5A 40A 5A
Ripple and noise voltage *)
max. 1500mVpp 20Hz-2kHz, 50Ohm
max. 50mVpp 2kHz to 20MHz, 50Ohm
Output capacitance
typ. 20 000μF
*) The ripple and noise voltage mostly consist of a mains ripple with 300Hz (50Hz mains) or 360Hz (60Hz mains). The ripple and
noise voltage can be reduced by using external capacitors.
The power supply is also designed to support loads with a higher short-term current and power requirement. The
short-term duration is rmware-controlled by an output power manager. If the nominal output power is exceeded for
a certain period of time which is dened in zone A, B and C, the power supply responds with an automatic shutdown. Pressing the reset button or cycling the input power (10s o time is required) initiates a restart attempt.
If the fault has been cleared the device will operate normally.
The short term power can be used periodically . See section 25.1 for further information.
Fig. 7-1 Output voltage vs. output current, typ.
V
OUT
40A A041A0580A
0
A
15s
24V
200A60A A081A061A021A001
A02
12V
I
OUT
B
5s
C
0.1s
3x 408V
3x 480V
3x 552V
Zone A : 25% extra output power for typ. 15s
Zone B:
100% higher output current for typ. 5s
Zone C:
Quick-acting shut-down after typ. 0.1s
6 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
8. Hold-up Time
1606-XLE960DX-3N
Hold-up Time typ. 2.0ms 40A, resistive load, see
Fig. 8-2
ees ,daol rewop tnatsnoc ,A04 sm8.1 .pyt
Fig. 8-2
sm0.4 .pyt
20A, resistive load
daol rewop tnatsnoc ,A02 sm6.3 .pyt
Hold-up Time min. 1.6ms 40A, resistive load, see
Fig. 8-2
ees ,daol rewop tnatsnoc ,A04 sm54.1 .nim Fig. 8-2
sm2.3 .nim 20A, resistive load
daol rewop tnatsnoc ,A02 sm9.2 .nim
Fig. 8-1 Hold-up time, denitions
The energy is stored in the output capacitor. As
soon as the input is turned o, the output
capacitor will be discharged and the voltage will
dissipate according to the curves in Fig 8-2.
The lighter the load, the longer the hold-up time.
Half the load means twice the hold-up time.
The hold-up time depends on the load
characteristic. The curves below show the hold-up
time for a load with a resistive and a constant
power characteristic.
The hold-up time is dened as the period of time
when the input is turned o and until the output
voltage falls below 24V
–15% (20.4V). This value is
dened in the IEC61131-2 as the lower limit for the
supplying voltage.
-15%
Hold-
up
Time
Zero Transition
Output
Voltage
Intput
Voltage
Fig. 8-2 Hold-up time vs. input voltage
24V
12V
18V
14V
V
OUT
22V
16V
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
5.5 6.0 6.5 7.0 7.5 8.05.0 8.5 9.0ms
40A, constant power load, typ.
40A, resistive load, typ.
T
40A, constant power load, min.
40A, resistive load, min.
20.4V
Note: At no load, the hold-up time can be up to one minute. The green DC-ok LED is on at this time.
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014 7