Rockwell Automation 1606-XLE480 DC User Manual [en, de, fr, it]

Page 1
1 EN 1606-XLE480 Instruction Manual DC Power Supply 2 DE 1606-XLE480 Bedienungsanleitung DC Stromversorgung 3 FR 1606-XLE480 Manual d'instructions DC Alimentation d'Énergie 4 ES 1606-XLE480 Manual de instrucciones DC Fuente De Alimentación 5 IT 1606-XLE480 Manuale di Istruzione DC Gruppo di alimentazione 6 PT 1606-XLE480 Manual de Instruções DC Fonte De Alimentação
1606-XLE480
Read this first! English 1
Before operating this unit please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur during operation, immediately turn power off and send unit to the factory for inspection. The unit does not contain serviceable parts. The tripping of an internal fuse (if included) is caused by an internal defect. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications the English translation will be used.
Intended Use: This power supply is designed for installation in an enclosure and is intended for general use such as in industrial control, office, communication, and instrumentation equipment. Do not use this device in equipment, where malfunction may cause severe personal injury or threaten human life.
WARNING
Risk of electrical shock, fire, personal injury or death.
1) Do not use the power supply without proper grounding (Protective Earth).
2) Turn power off before working on the device. Protect against inadvertent re-powering.
3) Make sure that the wiring is correct by following all local and national codes.
4) Do not modify or repair the unit.
5) Do not open the unit as high voltages are present inside.
6) Use caution to prevent any foreign objects from entering the housing.
7) Do not use in wet locations or in areas where moisture or condensation can be expected.
8) Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
CAUTION
Reduction of output current may be necessary when:
1) Minimum installation clearance can not be met.
2) Altitude is higher than 2000m.
3) Device is used above +60°C ambient.
4) Mounting orientation is other than output and input terminal located at the bottom of the unit.
5) Airflow for convection cooling is obstructed.
Vor Inbetriebnahme lesen! Deutsch 2
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das Gerät in Betrieb nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das Gerät darf nur durch fachkundiges und qualifiziertes Personal installiert werden. Bei Funktionsstörungen oder Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk. Das Gerät beinhaltet keine Servicebauteile. Interne Sicherungen (falls vorhanden) lösen nur bei Gerätedefekt aus. Die angegebenen Daten dienen allein der Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text.
Bestimmungsgemäßer Gebrauch: Diese Stromversorgung ist für den Einbau in ein Gehäuse konzipiert und zur Verwendung für allgemeine elektronische Geräte, wie z.B. Industriesteuerungen, Bürogeräte, Kommunikationsgeräte oder Messgeräte geeignet. Benutzen Sie dieses Gerät nicht in Steuerungsanlagen, in denen eine Funktionsstörung zu schweren Verletzungen führen oder Lebensgefahr bedeuten kann.
WARNUNG
Missachtung nachfolgender Punkte kann einen elektrischen Schlag, Brände, schwere Unfälle oder Tod zur Folge haben.
1) Betreiben Sie die Stromversorgung nie ohne Schutzleiter.
2) Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder Änderungsarbeiten ab und sichern Sie diese gegen unbeabsichtigtes Wiedereinschalten.
3) Sorgen Sie für eine ordnungsgemäße und fachgerechte Verdrahtung .
4) Führen Sie keine Änderungen oder Reparaturversuche am Gerät durch.
5) Gerät niemals öffnen. Im Inneren befinden sich gefährliche Spannungen.
6) Verhindern Sie das Eindringen von Fremdkörpern, wie z.B. Büroklammern und Metallteilen.
7) Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei der mit Betauung oder Kondensation zu rechnen ist.
8) Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühre n. Heiße Oberflächen können Verletzungen verursachen.
VORSICHT
Rücknahme der Ausgangsleistung kann erforderlich sein:
1) wenn die minimalen Einbauabstände nicht eingehalten werden kön nen.
2) bei Aufstellhöhen über 2000m.
3) Betrieb bei Umgebungstemperaturen über +60°C.
4) bei Einbaulagen abweichend von der Standardeinbaulage (Eingang und Ausgang an der Unterseite des Gerätes).
5) bei behinderter Luftzirkulation.
siaçnarF !noisnet suos esim tnava eril A 3
Merci de lire ces instructions de montage et d'entretien avant de mettre l'alimentation sous tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation doit être installée par du personnel qualifié et compétent. Le déclenchement du fusible i nterne traduit très probablement un défaut au niveau de l'appareil. Si un défaut quelconque apparaît en cours de fonctionnement, débrancher au plus vite l'alimentation. Dans ce deux cas de figure, il convient de faire contrôler l'alimentation en usine! Les données indiquées dans ce document servent uniquement à donner une description du produit et n'ont aucune valeur juridique. En cas de divergences, le texte anglais fait foi.
Utilisation: Cet appareil est conçu pour être installé dans une armoire et pour tous les équipements électroniques, tel que l'équipement industriel de commande, l'équipement de bureau, le matériel de communication et les instruments de mesures. N'utilisez pas cet appareil sur des installations dans lesquels un problème de fonctionnement de l'alimentation pourrait causer des blessures gr av es ou menacer la vie humaine.
AVERTISSEMENT
Prendre en compte les points suivants, afin d'éviter toute détérioration électrique, incendie, dommage aux personnes ou mort.
1) ne jamais faire fonctionner l'alimentation sans raccordement à la terre !
2) débrancher l'installation avant toute intervention sur l'alimentation (ou démontage) et s'assurer qu'il n'y a pas risque de redémarrage.
3) s'assurer que le câblage a été fait selon les prescriptions
4) ne pas effectuer de réparations ou modifications sur l'alimentation
5) ne pas ouvrir l'appareil. Des tensions importantes passent à l'intérieur.
6) veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation (trombones, pièces métalliques)
7) ne pas faire fonctionner l'appareil dans un environnement humide ou à l'extérieur, non protégé. Ne pas utiliser l'appareil dans un environnement où il peut y avoir de la condensation.
8) ne pas toucher le carter pendant le fonctionnement ou après la mise sous tension. Surface chaude risquant d’entraîner des blessures.
(1)
ATTENTION
Des limitations de puissance de sortie peuvent apparaître si :
1) les distances d'installation mini. ne peuvent être observées
2) installation à une altitude > 2000 m
3) pour des fonctionnements en charge et avec une température ambiante > 60°C
4) pour des positions de montage différentes de la préconisation standard (entrée en sortie dessous)
5) lorsque la circulation d'air est gênée
Page 2
1606-XLE480: Power Supply Instruction Manual 1606-XLE480: Bedienungsanleitung für Stromversorgung
Lea primero! Español 4
Conserve este manual como referencia para futuras consultas. La fuente de alimentación solo puede ser instalada y puesta en funcionamiento por personal cualificado. Por favor lea detenidamente este manual antes de conectar la fuente de alimentación. Cuando se funde un fusible interno, existe gran probabilidad de un fallo interno en el equipo.Si se produce un fallo o mal funcionamiento durante la operación, desconecte inmediatamente la tensión de alimentación. En ambos casos, el equipo debe ser inspeccionado en fábrica. La información presentada en este documento es exacta y fiable en cuanto a la descripción del producto y puede cambiar sin aviso. En casa de duda, prevalece el texto inglés.
Uso apropiado: Este equipo ha sido diseñado para su instalación en un ambiente cerrado y ha sido concebido para uso general en instalaciones de control industrial, oficinas, comunicaciones y equipos de instrumentación. No emplee esta unidad en equipos, donde un mal funcionamiento puede ocasionar lesiones graves o riesgo mortal.
ADVERTENCIA
Riesgo de descarga eléctrica, incendio, accidente grave o muerte.
1) No conectar nunca la unidad sin conexión de puesta a tierra.
2) Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite una posible reconexión involuntaria.
3) Asegurarse de que el cableado es correcto de acuerdo a los códigos locales y nacionales.
4) No realizar ninguna modificación o reparación de la unidad.
5) No abrir nunca la unidad. En el interior existe riesgo de altas tensiones.
6) Evitar la introducción en la carcasa de objetos extraños.
7) No usar el equipo en ambientes húmedos. No operar el equipo en ambientes donde se espere la formación de rocío o condensación.
8) No tocar durante el funcionamiento ni inmediatamente después del apagado. El calor de la superficie puede causar quemaduras graves
ATENCIÓN
La deriva en la tensión de salida se produce:
1) cuando no pueden mantenerse las distancias mínimas de montaje.
2) en caso de que el montaje se realice en altitudes superiores a los 2000 m.
3) en caso de funcionamiento a plena carga y temperaturas ambientales superiores a +60ºC.
4) En caso de posiciones de montaje diferentes a la posición de montaje estándar (terminales abajo).
5) en caso de que la circulación de aire para la refrigeración por conducción esté obstruida.
Leggere prima questa parte! Italiano 5
Prima di collegare il sistema di alimentazione elettrica si prega di leggere attentamente le seguenti avvertenze. Conservare le istruzioni per la consultazione futura. Il sistema di alimentazione elettrica deve essere installato solo da personale competente e qualificato. In caso di intervento del fusibile interno, molto probabilmente l'apparecchio è guasto. Se durante il funzionamento si verificano anomalie o guasti, scollegare immediatamente la tensione di alimentazione. In entrambi i casi è necessario far controllare l'apparecchio dal produttore! I dati sono indicati solo a scopo descrittivo del prodotto e non vanno considerati come caratteristiche garantite dell'apparecchio.In caso di differenze o problemi è valido il testo inglese
Uso previsto: Questo apparecchio è previsto per il montaggio in un rack per moduli elettronici, ad esempio per controllori industriali, apparecchiature per ufficio, unità di comunicazione o apparecchi di misura. Non utilizzare questo apparecchio in apparati o impianti dove il malfunzionamento può causare danni alla persona o pericolo di vita.
AVVERTENZA
Il mancato rispetto delle seguenti norme può provocare folgorazione elettrica, incendi, gravi incidenti e perfino la morte.
1) Non far funzionare in nessun caso il sistema di alimentazione elettrica senza conduttore di protezione!
2) Prima di eseguire interventi di installazione, di manutenzione o di modifica scollegare la tensione di rete ed adottare tutti i provvedimenti necessari per impedirne il ricollegamento non intenzionale.
3) Assicurare un cablaggio regolare e corretto.
4) Non tentare di modificare o di riparare da soli l'apparecchio.
5) Non aprire l'apparecchio. Al suo interno sono applicate tensioni elettriche pericolose.
6) Impedire la penetrazione di corpi estranei nell'apparecc hio, ad esempio fermagli o altri oggetti metallici.
7) Non far funzionare l'apparecchio in un ambiente umido. Non far funzionare l'apparecchio in un ambiente soggetto alla formazione di condensa o di rugiada.
8) Non toccare quando acceso e subito dopo lo spegnimento. La superficie calda può causare scottature.
ATTENZIONE
È necessario ridurre la potenza di uscita se:
1) non è possibile rispettare le distanze minime di montaggio;
2) l'apparecchio viene installato in un luogo di altitudine maggiore di 2000 m;
3) il funzionamento è a pieno carico a temperatura ambiente maggiore di +60°C;
4) la posizione di montaggio differisce da quella standard (ingresso, uscita in basso)
5) è ostacolata la libera circolazione dell'aria.
Leia primeiro! Portuguès 6
Recomendamos a leitura cuidadosa das seguintes advertências e observações, antes de colocar em funcionamento a fonte de alimentação. Guarde as Instruções para futura consulta, em casos de dúvida. A fonte de alimentação deverá ser instalada apenas por profissionais da área, tecnicamente qualificados. Se o fusível interno se fundir, é grande a possibilidade de existir um defeito no aparelho. Se por acaso, durante a utilização ocorrer algum defeito de funcionamento ou dano, desligue imediatamente a tensão de alimentação. Em ambos os casos, será necessária uma verificação na Fábrica! Os dados mencionados têm como finalidade somente a descrição do produto, e não devem ser interpretados como propriedades garantidas no sentido jurídico. Em caso de duvidas aplica-se o texto em inglês. Utilize: Este aparelho foi concebido para ser montado dentro de invólucros, caixas ou armários para aparelhos eletrônicos em geral, como, por exemplo, comandos de instalações industriais, aparelhos para escritórios, aparelhos de comunicação ou instrumentos de medida e quadros eléctricos. Não utilize este aparelho em instalações, nos quais um defeito de funcionamento poderá causar danos graves ou significar risco de morte.
ATENÇÃO
A não observância ou o incumprimento dos pontos a seguir mencionados, poderá causar uma descarga elétrica, incêndios, acidentes graves ou morte.
1) Não use a fonte de alimentação sem o condutor de proteção terra!
2) Antes de trabalhos de instalação, manutenção ou modificação, desligue a tensão de alimentação, protegendo-a contra uma nova ligação involuntária.
3) As ligações devem ser efectuadas apenas por profissionais competentes.
4) Não efectue nenhuma modificação ou tentativa de reparação no aparelho. Quando necessário contacte o seu distribuidor.
5) Não abra o aparelho mesmo quando desligado. No seu interior existem condensadores que podem estar carregados electricamente.
6) Proteger a fonte de alimentação contra a introdução inadvertida de corpos met álicos, como por ex., clipes ou outras peças de metal.
7) Não usar o aparelho em ambientes húmidos. Não usar o aparelho em ambientes propensos a condensações.
8) Não tocar enquanto estiver em funcionamento, nem após a desligar. A superficie poderá estar quente e provocar lesões.
CUIDADO
Será necessário reduzir a potência de saída nos seguintes casos:
1) Quando não forem observadas as distâncias mínimas de montagem.
2) Quando instaladas a altitudes superiores a 2000m.
3) Existencia de temperatura ambiente superior a +60ºC, em plena carga do aparelho.
4) Montagem invertida do aparelho (Entrada, saída em baixo).
5) Montagem em ambiente sem ventilação.
Rockwell Automation CH-5001 Aarau, Switzerland Fax +41 62 837 2202
Allen-Bradley Company, LCC
Industrial Components
1201 South Second Street
Milwaukee, WI 53204-2496
© 2013 by
Phone 440 646 5800
www.ab.com
Business
USA
Page 3
1606-XLE480: Power Supply Instruction Manual 1606-XLE480: Bedienungsanleitung für Stromversorgung
Technical Data 1) Technische Daten
1)
1606-XLE480EP
1606-XLE480FP
Factory Setting at Full Load Werkseinstellung bei Nennlast V0.84 V1.42.pyt ,”esU-elgniS“
gnunnapssgnagsuA egatloV tuptuO V65-84 CDV82-42 CD.mon
Output Current continuous Ausgangsstrom dauernd nom. 20A at 24V, 17.1A at 28V 10A at 48V, 8.6A at 56V Output Current PowerBoost
13)
Ausgangsstrom PowerBoost
13)
nom. 24A at 24V, 20.6A at 28V 12A at 48V, 10.3A at 56V short-term (15ms) A04A08 )sm51( gitiezzruk Output Power continuous Ausgangsleistung dauernd W084W084.mon Output Power PowerBoost Output Ripple & Noise Voltage Output Overload Behavior Überlastverhalten am Ausgang pucciH- AC Input Voltage AC Eingangsspannung nom. AC 100-240V
Input Frequency Eingangsfrequenz nom. AC Input Current 2) AC Eingangsstrom Power Factor
2)
13)
Ausgangsleistung PowerBoost
12)
Ausgangswelligkeit
12)
ppVm05ppVm05.xam
2)
typ. 4.36A / 2.33A 4.36A / 2.33A
2)
rotkafsgnutsieL
59.0 / 99.059.0 / 99.0.pyt
13)
W675W675.mon
-15%/+10%
50-60Hz
PLUS9)
±6%
PLUS 9)
14)
Hiccup
AC 100-240V
-15%/+10%
50-60Hz
±6%
Allowed Voltage L or N to Earth Erlaubte Spannung L oder N zu Erde caV003caV003.xam PFC Norm EN 61000-3-2 Class A PFC Norm EN 61000-3-2 Klasse A aJ / seYaJ / seY- Input Inrush Current Hold-up Time Efficiency Power Losses
2) 3)
Einschaltspitzenstrom
2)
2)
2)
2)
tiezreffuP
sm62 / sm62sm62 / sm62.pyt
2) 3)
kaep A7 / A9kaep A7 / A9.pyt
2)
dargsgnukriW
typ. 92.7% / 94.0% 92.6% / 93.9%
2)
gnutsieltsulreV
typ. 37.8W / 30.6W 38.4W / 31.2W
Operational Temperature Range Betriebstemperaturbereich nom. -25°C - +70°C -25°C - +70°C
eL gnitareD tuptuO istungsrücknahme C°/W21C°/W21C°07+ ot C°06+
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C Humidity
4)
4)
ethcueF
.H.r %59 - 5.H.r %59 - 503-2-86006 CEI
negniwhcS noitarbiV g26-2-86006 CEI 2g
Degree of Pollution Verschmutzungsgrad 230126 CEI
nekcohcS kcohS IEC 60068-2-27 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms
Degree of Protection Schutzart 02PI02PI92506 NE Class of Protection Schutzklasse I04116 CEI
4)
5)
2 4)
I 5)
Over-temperature Protection Übertemperaturschutz aJ / seYaJ / seYPTO Output Over-voltage Protection Überspannungsschutz am Ausgang cdV06cdV23.xam ,PVO Return Voltage Resistance 7) Rückspeisefestigkeit Leakage Current
IT-mains Parallel Use Serial Use
6)
TN/TT-mains
10)
11)
PE- Ableitstrom IT-Netze
Dimensions 8) (WxHxD) Abmessungen
7)
cdV36cdV53.xam
6)
TN/TT-Netze
10)
rabtlahcslellaraP
aJ / seYaJ / seY-
11)
rabtlahcsneireS
aJ / seYaJ / seY-
8)
(BxHxT) nom. 65x124x127mm 65x124x127mm
max. max.
0.26mA / 0.46mA
0.67mA / 1.08mA
0.26mA / 0.46mA
0.67mA / 1.08mA
thciweG thgieW bl2.2 ,g0001bl2.2 ,g0001.xam
1) All parameters are specified at 230Vac input voltage, nominal output current, “Single Use”
setting, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2) At 120Vac / 230Vac
3) Input inrush current is electronically limited, temperature independent and is valid for mains
interruptions > 500ms
4) Do not energize while condensation is present.
5) PE connection required (Ground).
6) Leakage current at 132Vac, 60Hz / 264Vac, 50Hz
7) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
8) Depth without DIN-rail.
PLUS
9) Hiccup
10) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more
11) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
12) 50-Ohm measurement, bandwidth 20MHz
13) The PowerBoost is continuously allowed up to an ambient temperature of 45°C. Above 45°C,
14) An output current derating might be necessary at input voltages <100Vac, see figure 5.
is an overload behavior with a balanced power management. In normal mode it provides generous power reserves but effectively protects connected equipment and cables against damage in the event of failure. More details on the next pages.
than three units are paralleled.
do not use the PowerBoost longer than a duty cycle of 10% and/ or not longer than max. 1 minute every 10 minutes.
1) Alle Werte gelten bei 230Va c E i ngangsspannung, Nennausgangsstrom, „Single-Use“ Mo dus, 25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, falls nichts anderes angegeben.
2) bei 120Vac / 230Vac
3) Der Einschaltstromstoß ist elektronisch begrenzt, temperaturunabhängig und gilt für Netzunterbrechungen > 500ms
4) Nicht betreiben, solange das Gerät Kondensation aufweist.
5) PE Verbindung erforderlich.
6) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz
7) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
8) Tiefe ohne DIN-Schiene
PLUS
9) Hiccup
10) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten
11) Nur für gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
12) 50-Ohm Messung, Bandbreite 20MHz
13) Der PowerBoost ist bis zu einer Umgebungstemperatur von +45°C dauerhaft erlaubt. Darüber
14) Unterhalb 100Vac kann eine Leistungsrücknahme erforderlich sein. Siehe Bilder 5
ist ein Überlastverhalten mit einem ausgewogenem Leistungsmanagement, welches im Normalbetrieb kurzzeitig großzügige Leistungsreserven zur Verfügung stellt, aber im Fehlerfall angeschlossene Verbraucher und Kabel effektiv vor Schäden schützt. Mehr Informationen auf den nächsten Seiten.
wird eine Sicherung oder eine Diode zur Entkopplung benötigt.
soll sie nicht länger als 10% (<1 Minute alle 10 Minuten) entnommen werden.
Installation
Use DIN-rails according to EN 60715 with a height of 7.5 or 15mm. Mounting orientation must be output and input terminals on the bottom. For other orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation grid must be kept free of any obstructions. The following installation clearances must be kept when power supplies are permanently fully loaded:
Left / right: 5mm (15mm in case the adjacent device is a heat source) 40mm on top, 20mm on the bottom of the unit.
Input Fuses
Internal input fuse included, not user accessible. The unit is tested and approved for branch circuits up to 32A. An external protection is only required if the supplying branch has an ampacity greater than this, however, in some countries local regulations might apply. Check local codes and requirements. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. Use a minimum value of 10A B- or C­Characteristic breaker.
CE Marking
CE mark is in conformance with EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC and the RoHS directive 2011/65/EU.
EMC Immunity: EN 61000-6-1, EN 61000-6-2 EMC Emission EN 61000-6-3, EN 61000-6-4, FCC Part 15 Class B
Installation
Geeignet für DIN-Schienen entsprechend EN 60715 mit einer Höhe von 7,5 oder 15 mm . Der Einbau hat so zu erfolgen, dass sich die Eingangs- und Ausgangsklemmen unten befinden. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Das Gerät ist für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende Einbauabstände sind bei dauerhafter Volllast einzuhalten:
Links / rechts: 5mm (15mm bei benachbarten Wärmequellen) Oben: 40mm, unten 20mm vom Gerät.
Sicherungen am Eingang
Das Gerät besitzt eine eingebaute Eingangssicherung, die nicht anwenderzugänglich ist. Das Gerät ist geprüft und zugelassen zum Anschluss an Stromkreisen bis max. 32A. Ein zusätzlicher externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert abgesichert ist oder nationale Richtlinien es vorschreiben. Um ein fehlerhaftes Auslösen externer Schutzelemente zu vermeiden sollen diese den Minimalwert von 10A B- oder C-Charakteristik nicht unterschreiten:
CE Kennzeichnung
Das CE Zeichen ist angebracht und erklärt die Erfüllung der EMV Richtlinie 2004/108/EG, der Niederspannungsrichtlinie 2006/95/EG und der RoHS Richtlinie 2011/65/EU.
Störfestigkeit: EN 61000-6-1, EN 61000-6-2 Störaussendung: EN 61000-6-3, EN 61000-6-4, FCC Part 15 Klasse B
14)
Page 4
1606-XLE480: Power Supply Instruction Manual
A
1606-XLE480: Bedienungsanleitung für Stromversorgung
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperature of: 60°C for ambient temperatures up to 45°C, 75°C for ambient temperatures up to 60°C and 90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal connection! Ferrules are allowed.
Input / Output Signals
American wire gauge AWG 20-10 AWG 26-14 Max. wire diameter (including ferrules) 2.8mm 1.5mm Wire stripping length 7mm / 0.28inch 7mm / 0.28inch
Isolation and Dielectric Strength (see Fig. 2)
The output voltage is floating and separated from the input according to SELV (IEC/EN 60950-1) and PELV (EN 60204-1, EN 50178; IEC 62103, IEC 60364-4-41) requirements. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before the test is conducted. When testing, set the cut-off current settings to the value in th e table below.
A B C D Type Test (60s) 2500Vac 3000Vac 1500Vac 500Vac Factory Test (5s) 2500Vac 2500Vac 1000Vac 500Vac Field Test (5s) 2000Vac 2000Vac 1000Vac 500Vac Cut-off current setting >15mA >15mA >20mA >1mA
PLUS
Hiccup
The output current is electronically controlled. During an overcurrent situation, the output voltage will be reduced after a defined time. If the voltage falls below 13V for the 24V unit or 25V for the 48V units, the unit switches to the Hiccup by a restart attempt after 18s for 2s. This cycle is repeated as long as the overload or short circuit exists. If the overload or short circuit has been cleared, the device will operate normally.
Overload Characteristic (see figures 3 and 4)
PLUS
Single Use / Parallel Use Selector
This selector on the front of the unit enables a load sharing when power supplies are connected in parallel. The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load. If no jumper is plugged in, the unit is also in “Single Use”. Factory setting is “Single Use”.
Instructions for parallel use: The output voltage shall be adjusted to the same value (±100mV) in “Single Use” at the same load
condition on all units, or shall be left with the factory settings. Afterwards, the jumper on the front of the unit shall be moved from “Single Use” to “Parallel Use”
DC-OK Relay Contact
This feature monitors the output voltage, which is produced by the power supply, and is independent of a return voltage from a unit which is connected in parallel.
Contact closes when the output voltage is above 90% of the adjusted value. Contact opens when the output voltage is typ. below 90% of the adjusted value. Short dips will
be extended to a length of 250ms. Dips shorter than 1ms will be ignored. Contact ratings: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load, min. current 1mA
Functional Diagram / Funktionsschaltbild
L
N
Input Fuse Input Filter Input Rectifier Active Inrush Limiter
Temper-
ature Shut­down
Manager
PLUS
Hiccup
Overload and Short-Circuit Behavior /
PLUS
Hiccup
Überlast- und Kurzschlussverhalten, typ.
PFC
Converter
Output Power
Protection
Fig. 4/ Bild 4
Fig. 1 / Bild 1
Output
Over-
Voltage
2
mm6-5.0 eriw diloS
2
mm4-5.0 eriw dednartS
0.15-1.5mm2
0.15-1.5mm2n
mode. In this mode, the output switches off followed
Power
Converter
Output Voltage Monitor
Output
Filter
Output
Voltage
Regulator
DC-ok Relay
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für: 60°C bei einer Umgebungstemperatur bis zu 45°C, 75°C bei einer Umgebungstemperatur bis zu 60°C und 90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.
Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
Eingang / Ausgang Signale
Max. Drahtdurchmesser (inklusive Aderendhülsen) 2,8mm 1,5mm
lanimret pmalc-gnirpS hcni.bl9 / mN1 euqrot gninethgiT
Galvanische Trennung und Isolationsfestigkeit (siehe Bild 2)
Die Ausgangsspannung hat keinen Bezug zur Erde oder Schutzleiter und ist zum Eingang nach den SELV (IEC/EN 60950-1) und PELV (EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41) Standards getrennt. Typ- und Stückprüfungen werden beim Hersteller durchgeführt. Wieder­holungsprüfungen dürfen mittels geeigneten Prüfgenerators mit langsam (2s) ansteigenden und abfallenden Spannungsrampen in der Anwendung erfolgen. Vor den Tests sind alle Phasen wie auch alle Ausgangspole miteinander zu verbinden. Während der Tests darf die Strom-
bschaltschwelle nicht kleiner als der in der Liste angegebene Wert sein. A B C D Typprüfung (60s) 2500Vac 3000Vac 1500Vac 500Vac Stückprüfung (5s) 2500Vac 2500Vac 1000Vac 500Vac Wiederholungsprüfung (5s) 2000Vac 2000Vac 1000Vac 500Vac Strom- Abschaltschwelle >15mA >15mA >20mA >1mA
Hiccup
Der Ausgangsstrom ist elektronisch überwacht. Während einer Überstromsituation wird nach einer bestimmten Zeit die Ausgangsspannung reduziert. Fällt die Spannung unter 13V beim 24V Gerät oder 25V beim 48V Gerät schaltet das Gerät in den Hiccup das Gerät ab und macht nach 18s einen Startversuch mit einer Dauer von 2s. Der Vorgang wiederholt sich solange, bis die Überlast oder der Kurzschluss entfernt ist. Nach entfernen der Überlast oder des Kurzschlusses schaltet das Gerät wieder in den Normalbetrieb.
„Single Use“ / „Parallel Use“ Steckbrücke
Diese Steckbrücke an der Frontseite des Geräts ermöglicht eine Lastaufteilung, wenn mehrere Geräte parallel geschaltet sind. In „Parallel Use“ Modus ist die Ausgangsspannung so geregelt, dass diese im Leerlauf um etwa 4% höher ist als bei Nennlast. Ein nicht eingesteckter Jumper bedeutet auch „Single Use“. Werkseinstellung ist „Single Use“.
Anleitung für Parallelbetrieb: Die Ausgangsspannung aller Geräte bei gleicher Belastung in „Single Use“ auf ±100mV genau
einstellen oder in Werkseinstellung belassen. Danach die Steckbrücke an der Front des Gerätes von „Single Use“ auf „Parallel Use“ umstecken.
DC-OK Relais Kontakt
Diese Funktion überwacht die vom Gerät erzeugte Ausgangsspannung und lässt sich von einer rückwärts eingespeisten Spannung nicht beeinflussen (z.B.: bei Parallelschaltung)
Kontakt schließt, wenn die Ausgangsspannung typ. höher als 90% des eingestellten Wertes ist. Kontakt öffnet, wenn die Ausgangsspannung typ. kleiner als 90% des eingestellten Wertes ist.
Kurze Einbrüche werden auf 250ms verlängert. Einbrüche kürzer 1ms werden ignoriert. Kontakt Belastbarkeit: max.: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, (R-Last), min. Strom 1mA
+ +
-
-
Single / Parallel
V
OUT
DC-ok LED
DC-ok Contact
Leistungsrücknahme
Input
(+)
L
N
Earth, PE
Fig. 5 / Bild 5
Output derating /
PLUS
Überlastverhalten (siehe Bilder 3 und 4)
Fig. 2 / Bild 2
Insulation / Isolation
DC-ok
(-)
B
B
DA
Output
C
+/-
DC-ok
2
mm6-5,0 thardrratS
2
mm4-5,0 eztiL
PLUS
Modus. In diesen Modus schaltet
Output Characteristic /Ausgangskennlinie, typ.
Output Voltage
28V
56V
24V
48V
20V
40V
16V
32V
12V
24V
8V
16V
4V
8V
48V Unit
0V
0V
24V Unit
Dimensions / Abmessungen
Fig. 3/ Bild 3
0 40% 80%
Fig. 6 / Bild 6
0,15-1,5mm2 0,15-1,5mm2
120% 160% 200%
41-62 GWA 01-02 GWA GWA
Adjustment range
PLUS
Hiccup
mode
Output Current
hcni82,0 / mm7 hcni82,0 / mm7 egnälreilosibA
emmelktfarkredeF hcni.bl9 / mN1 tnemomherdsguznA
Output Current
Normal
operation
I
SC
0
ISC:
24V units: 42A 48V units: 20A
10000314393 (Version 00)
2s
18s
Short -circuit
2s
2s
18s 18s
Normal
operation
Allowed Output Power
576W
480W 384W 288W 192W
t
96W
0
A...100 to 264Vac or
100 to 375Vdc, continuous B... 85Vac or 88Vdc, continuous C... Short-term
-25 0 20 40
Ambient Temperature
B A
60
C
70°C
(4)
Loading...