1336 PLUS
Adjustable
Frequency AC
Drive for the
Fiber Industry
1.5- 22 kW (2- 30 HP)
User
Manual
Important User Information
Solid state equipment has operational characteristics differing from
those of electromechanical equipment. “Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls”
(Publication SGI-1.1) describes some important differences between
solid state equipment and hard–wired electromechanical devices.
Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended
application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable
for indirect or consequential damages resulting from the use or
application of this equipment.
The examples and diagrams in this manual are included solely for
illustrative purposes. Because of the many variables and
requirements associated with any particular installation, the
Allen-Bradley Company cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with
respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part,
without written permission of the Allen-Bradley Company is
prohibited.
Throughout this manual we use notes to make you aware of safety
considerations.
ATTENTION: Identifies information about practices
!
Attentions help you:
or circumstances that can lead to personal injury or
death, property damage, or economic loss.
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is especially important for
successful application and understanding of the product.
SCANport is a trademark of Allen-Bradley Company, Inc.
PLC is a registered trademark of Allen-Bradley Company, Inc.
Taptite is a registered trademark of Research Engineering and Manufacturing, Inc.
Chapter 1 provides general information on the 1336 PLUS
Adjustable Frequency AC Drive for use in the Fiber Industry.
Manual Objectives
Software Compatibility
Conventions Used in this
Manual
This publication provides planning, installation, wiring and
diagnostic information. To assure successful installation and
operation, the material presented must be thoroughly read and
understood before proceeding. Particular attention must be directed
to the Attention and Important statements contained within.
Three-Phase Drive Rating
200-240V380-480V
1.5 kW
2 HP
3.7 kW
5 HP
–7.5 kW
11 kW
15 HP
1
kW and HP are constant torque.
–
3.7 kW
5 HP
10 HP
7.5-22 kW
10-30 HP
1
Compatible withFrame
Version . . .
2.03, & 2.04
2.03, & 2.04
2.03, & 2.04
2.03, & 2.04
Reference
A2
A3
A4
B1/B2
To help differentiate parameter names and display text from other
text in this manual, the following conventions will be used:
General Precautions
• Parameter Names will appear in [brackets]
• Display Text will appear in “quotes”
ATTENTION: This drive contains ESD
!
(Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required
when installing, testing, servicing or repairing this
assembly. Component damage may result if ESD
control procedures are not followed. If you are not
familiar with static control procedures, reference A-B
publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD
protection handbook.
1–2Information and Precautions
ATTENTION: An incorrectly applied or installed
!
drive can result in component damage or a reduction in
product life. Wiring or application errors, such as,
undersizing the motor, incorrect or inadequate AC
supply, or excessive ambient temperatures may result
in malfunction of the system.
ATTENTION: Only personnel familiar with the
!
1336 PLUS Adjustable Frequency AC Drive and
associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the
system. Failure to comply may result in personal
injury and/or equipment damage.
ATTENTION: To avoid a hazard of electric shock,
!
verify that the voltage on the bus capacitors has
discharged before performing any work on the drive.
Measure the DC bus voltage at the + & – terminals of
TB1. The voltage must be zero.
Catalog Number Explanation
1336S
First Position
Bulletin Number
BR
Second Position
Voltage
LetterVoltages
AQ200-240V AC or
310V DC
BR380-480VAC or
513-620V DC
A200-240V AC
B380-480V AC
The diagram on the following page describes the 1336 PLUS catalog
numbering scheme.
F50
Third Position
Nominal HP Rating
Code kW (HP)
F20 1.5 (2)
F50 3.7 (5)
F50 3.7 (5)
F100 7.5 (10)
015 11 (15
010 7.5 (10)
030 22 (30)
Code Description
Human Interface Module, IP 20 (Type 1)
HAB Blank – No Functionality
HAP Programmer Only
HA1 Programmer/Controller w/Analog Pot
HA2 Programmer/Controller w/Digital Pot
Human Interface Module, IP 65/54 (Type 4/12)
HJP Programmer Only
HJ2 Programmer/Controller w/Digital Pot
Refer to page 1-1 for frame reference classifications.
A Frame Drives1
Nameplate Located on
Mounting Plate of
Main Control Board
ESC SEL
B Frame Drives
JOG
1
1–4Information and Precautions
End of Chapter
Chapter 2
Installation/Wiring
Chapter 2 provides the information you need to properly mount and
wire the 1336 PLUS Drive. Since most start-up difficulties are the
result of incorrect wiring, every precaution must be taken to assure
that the wiring is done as instructed. All items must be read and
understood before the actual installation begins.
ATTENTION: The following information is merely
!
a guide for proper installation. The Allen-Bradley
Company cannot assume responsibility for the
compliance or the noncompliance to any code,
national, local or otherwise for the proper installation
of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if
codes are ignored during installation.
Mounting
Minimum Mounting Requirements for Proper Heat Dissipation
(Dimensions shown are between drives or other devices)
152.4 mm
(6.0 in.)
101.6 mm
(4.0 in.)
ESC SEL
JOG
UP
152.4 mm
(6.0 in.)
152.4 mm
(6.0 in.)
ESC SEL
JOG
152.4 mm
(6.0 in.)
NOTE: F Frame drives require 152.4 mm (6.0 in.) on the sides and/or back for proper air flow.
2–2Installation/Wiring
Installation Guidelines
GND
PE
R
GND
(L1)S(L2)T(L3)
AC Supply Source
CAT. NO.
FREQUENCY
POWER RATING
PRIMARY VOLTAGE
SECONDARY VOLTAGE
INSULATION CLASS
NO. OF PHASES
VENDOR PART NO.
ALLEN-BRADLEY
Input Power Conditioning
Input Fusing
Input Devices
Input Filters
Electrical Interference
Page 2–3
Page 2–4
Page 2–4
Page 2–5
Page 2–6
Page 2–6
PE
GND
(T1)
U
ESC SEL
JOG
(T2)V(T3)
W
Grounding
Power Cabling
Control & Signal Cabling
Output Devices
Cable Termination
Motor
Page 2–7
Page 2–10
Page 2–15
Page 2–29
Page 2–29
2–3Installation/Wiring
AC Supply Source
1336 PLUS drives are suitable for use on a circuit capable of
delivering up to a maximum of 200,000 rms symmetrical amperes,
600 volts maximum when used with the AC input line fuses
specified in Table 2.A.
A TTENTION: To guard against personal injury and/or
!
equipment damage caused by improper fusing, use only
the recommended line fuses specified in Table 2.A.
Unbalanced Distribution Systems
This drive is designed to operate on three-phase supply systems
whose line voltages are symmetrical. Surge suppression devices are
included to protect the drive from lightning induced overvoltages
between line and ground. Where the potential exists for abnormally
high phase-to-ground voltages (in excess of 125% of nominal), or
where the supply ground is tied to another system or equipment that
could cause the ground potential to vary with operation, suitable
isolation is required for the drive. Where this potential exists, an
isolation transformer is strongly recommended.
Ungrounded Distribution Systems
All 1336 PLUS drives are equipped with an MOV (Metal Oxide
Varistor) that provides voltage surge protection and phase-to-phase
plus phase-to-ground protection which is designed to meet IEEE
587. The MOV circuit is designed for surge suppression only
(transient line protection), not continuous operation.
With ungrounded distribution systems, the phase-to-ground MOV
connection could become a continuous current path to ground.
Energy ratings are listed below. Exceeding the published line-to-line
and line-to-ground voltage ratings may cause physical damage to the
MOV. Refer to page A–1.
Joules = (A)
Joules = (A)
1234
Line-to-Line MOV Rating
Energy Rating = 2 x Line-Line Rating (A)
Line-to-Ground MOV Rating
Energy Rating = Line-Line (A) + Line-Ground (B)
Three-Phase
AC Input
Ground
R
S
T
Joules = (A)
Joules = (B)
Frame Reference
Device Rating (V)
Line-Line (A)
Line-Ground (B)
A
240 480 600
160 140 NA
220 220 NA
B
240 480 600
160 160 160
220 220 220
2–4Installation/Wiring
Input Power Conditioning
In general, the 1336 PLUS is suitable for direct connection to a
correct voltage AC line that has a minimum impedance of 1% (3%
for 0.37-22 kW/0.5-30 HP drives) relative to the rated drive input
kVA. If the line has a lower impedance, a line reactor or isolation
transformer must be added before the drive to increase line
impedance. If the line impedance is too low, transient voltage spikes
or interruptions can create excessive current spikes that will cause
nuisance input fuse blowing, overvoltage faults and may cause
damage to the drive power structure.
The basic rules for determining if a line reactor or isolation
transformer is required are as follows:
1. If the AC source experiences frequent power outages or
significant voltage transients, users should calculate the kVA
max
(see formula below). If the source transformer kVA exceeds the
calculated kVA
and the drive is installed close to the source, it
max
is an indication that there may be enough energy behind these
voltage transients to cause nuisance input fuse blowing,
overvoltage faults or drive power structure damage. In these
cases, a line reactor or isolation transformer should be considered.
V
Z
kVA
drive
(Ω/Φ) =
=
max
(V
line–line
line–line
√3 x Input Amps
)2 x % Source Leakage (5-6% typical)
x 0.01
Z
drive
Input Fusing
2. If the AC source does not have a neutral or one phase referenced
to ground (see Unbalanced Distribution Systems on page 2–3),
an isolation transformer with the neutral of the secondary
grounded is highly recommended.
If the line-to-ground voltages
on any phase can exceed 125% of the nominal line-to-line
voltage, an isolation transformer with the neutral of the secondary
grounded, is highly recommended.
3. If the AC line supplying the drive has power factor correction
capacitors that are switched in and out, an isolation transformer or
5% line reactor is recommended between the drive and
capacitors. If the capacitors are permanently connected and not
switched, the general rules above apply.
Refer to Unbalanced Distribution Systems on page 2–3.
ATTENTION: The 1336 PLUS does not provide
!
input power short circuit fusing. Specifications for the
recommended fuse size and type to provide drive input
power protection against short circuits are provided.
Branch circuit breakers or disconnect switches cannot
provide this level of protection for drive components.
Table 2.A
gg
y
must be used for all drives in
ty e gG or equivalent should be used for these drives. Fuses that
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
2–5Installation/Wiring
European InstallationsNorth American Installations
Recommended fuse is Class gG, general industrial applications
and motor circuit protection.
BS88 (British Standard) Parts 1 & 2*, EN60269-1, Parts 1 & 2,
type gG or equivalent should be used for these drives. Fuses that
meet BS88 Parts 1 & 2 are acceptable for Frames A - F.
*Typical designations include, but may not be limited to the following:
GG, GH.
1
Both fast acting and slow blow are acceptable.
Input Devices
*
2
Dual element-time delay fuses are required.
Starting and Stopping the Motor
UL requirements specify that
UL Class CC, T or J1 fuses
must be used for all drives in
this section*.
* Typical designations include:
Type CC: KTK, FNQ-R
T
,
pe J:JKS, LPJ
Type T:JJS, JJN
ATTENTION: The drive start/stop control circuitry
!
includes solid-state components. If hazards due to
accidental contact with moving machinery or
unintentional flow of liquid, gas or solids exist, an
additional hardwired stop circuit may be required to
remove AC line power to the drive. When AC power is
removed, there will be a loss of inherent regenerative
braking effect & the motor will coast to a stop. An
auxiliary braking method may be required.
by control input signals that will start and stop the
motor. A device that routinely disconnects then
reapplies line power to the drive for the purpose of
starting and stopping the motor is not recommended.
Bypass Contactors
ATTENTION: An incorrectly applied or installed by-
!
pass system can result in component damage or reduction in product life. The most common causes are:
• Wiring AC line to drive output or control terminals.
• Improper bypass or output circuits not approved by
Allen-Bradley.
• Output circuits which do not connect directly to the
motor.
Contact Allen-Bradley for assistance with application
or wiring.
2–6Installation/Wiring
Electrical Interference –
EMI/RFI
Immunity
The immunity of 1336 PLUS drives to externally generated
interference is good. Usually, no special precautions are required
beyond the installation practices provided in this publication.
It is recommended that the coils of DC energized contactors
associated with drives be suppressed with a diode or similar device,
since they can generate severe electrical transients.
Emission
Careful attention must be given to the arrangement of power and
ground connections to the drive to avoid interference with nearby
sensitive equipment. The cable to the motor carries switched
voltages and should be routed well away from sensitive equipment.
The ground conductor of the motor cable should be connected to the
drive ground (PE) terminal directly. Connecting this ground
conductor to a cabinet ground point or ground bus bar may cause
high frequency current to circulate in the ground system of the
enclosure. The motor end of this ground conductor must be solidly
connected to the motor case ground.
Shielded or armored cable may be used to guard against radiated
emissions from the motor cable. The shield or armor should be
connected to the drive ground (PE) terminal and the motor ground as
outlined above.
Common mode chokes at the drive output can help reduce common
mode noise on installations that do not use shielded cable. Common
mode chokes can also be used on analog or communication cables.
Refer to page 2–29 for further information.
An RFI filter can be used and in most situations provides an effective
reduction of RFI emissions that may be conducted into the main
supply lines.
If the installation combines a drive with sensitive devices or circuits,
it is recommended that the lowest possible drive PWM carrier
frequency be programmed.
2–7Installation/Wiring
RFI Filtering
CE Conformity
Grounding
1336 PLUS drives can be installed with an RFI filter, which controls
radio-frequency conducted emissions into the main supply lines and
ground wiring.
If the cabling and installation recommendation precautions described
in this manual are adhered to, it is unlikely that interference
problems will occur when the drive is used with conventional
industrial electronic circuits and systems. However, a filter may be
required if there is a likelihood of sensitive devices or circuits being
installed on the same AC supply.
Where it is essential that very low emission levels must be achieved
or if conformity with standards is required the optional RFI filter
must be used. Refer to Appendix C and instructions included with the
filter for installation and grounding information.
Refer to Appendix C.
Refer to the grounding diagram on page 2–9. The drive must be
connected to system ground at the power ground (PE) terminal
provided on the power terminal block (TB1). Ground impedance
must conform to the requirements of national and local industrial
safety regulations (NEC, VDE 0160, BSI, etc.) and should be
inspected and tested at appropriate and regular intervals.
In any cabinet, a single, low-impedance ground point or ground bus
bar should be used. All circuits should be grounded independently
and directly. The AC supply ground conductor should also be
connected directly to this ground point or bus bar.
Sensitive Circuits
It is essential to define the paths through which the high frequency
ground currents flow. This will assure that sensitive circuits do not
share a path with such current. Control and signal conductors should
not be run near or parallel to power conductors.
Motor Cable
The ground conductor of the motor cable (drive end) must be
connected directly to the drive ground (PE) terminal, not to the
enclosure bus bar. Grounding directly to the drive (and filter, if
installed) can provide a direct route for high frequency current
returning from the motor frame and ground conductor. At the motor
end, the ground conductor should also be connected to the motor
case ground.
If shielded or armored cables are used, the shield/armor should also
be grounded at both ends as described above.
2–8Installation/Wiring
Encoder & Communications Cabling
If encoder connections or communications cables are used, the wiring must be separated from power cabling. This can be accomplished
with carefully routed, shielded cable (ground cable shield at the drive
end only) or a separate steel conduit (grounded at both ends). Belden
9730, 8777 (or equivalent) is recommended for encoder cable runs
less than 30 meters (100 feet). Belden 9773 (or equivalent) is recommended for encoder cable runs greater than 30 meters (100 feet).
Discrete Control and Signal Wiring
The control and signal wiring must be grounded at a single point in
the system, remote from the drive. This means the 0V or ground
terminal should be grounded at the equipment end, not the drive end.
If shielded control and signal wires are used, the shield must also be
grounded at this point.
If the control and signal wires are short, and contained within a
cabinet which has no sensitive circuits, the use of shielded control
and signal wiring is not necessary. The recommended control signal
wire is:
• Belden 8760 (or equiv.)–0.750 mm
• Belden 8770 (or equiv.)–0.750 mm
• Belden 9460 (or equiv.)–0.750 mm
2
(18 AWG), twisted pair, shielded.
2
(18 AWG), 3 conductor, shielded.
2
(18 AWG), twisted pair, shielded.
Shield Termination – TE (True Earth)
The TE terminal block (not available on 0.37-7.5 kW (0.5-10 HP) A
Frame drives) is used for all control signal shields internal to the
drive. It must be connected to an earth ground by a separate
continuous lead. Refer to Figure 2.1/2.3 for location.
The maximum and minimum wire size accepted by this block is 2.1
and 0.30 mm
2
(14 and 22 AWG). Maximum torque is 1.36 N-m
(12 lb.-in.). Use Copper wire Only.
Safety Ground – PE
This is the safety ground required by code. This point must be
connected to adjacent building steel (girder, joist) or a floor ground
rod, provided grounding points comply with NEC regulations. If a
cabinet ground bus is used, refer to Grounding on page 2–7.
RFI Filter
Important:Using an optional RFI filter may result in relatively
high ground leakage currents. Surge suppression
devices are also incorporated in the filter. Therefore, the
filter must be permanently installed and solidly
grounded to the supply neutral. Grounding must not
rely on flexible cables and should not include any form
of plug or socket that would permit inadvertent
disconnection. The integrity of this connection should
be periodically checked.
Conduit/4-Wire Cable
Nearest
Building Structure Steel
General Grounding
Common
R (L1)
U (T1)
S (L2)
T (L3)
ESC SEL
V (T2)
JOG
W (T3)
PE/Gnd.
PE
RIO/DH+
or Analog
Common
Mode Core*
To Computer/Position Controller
(for TE shield ground, see "Control Connections")
Single-Point Grounding/Panel Layout
R (L1)
Mode
Core*
Shield*
Shield
Motor Frame
Motor
Terminator*
* Options that can be
installed as needed.
2–9Installation/Wiring
PE
Ground per
Local Codes
Nearest
Building Structure Steel
S (L2)
T (L3)
TE – Zero Volt Potential Bus
(Isolated from Panel)
PE Ground Bus
(Grounded to Panel)
For Programmable Controller
grounding recommendations,
refer to publication 1770-4.1
1336 FORCE1336 PLUS
ESC SEL
Logic
PE TE
Logic
PE
To Nearest Building
Structure Steel
JOG
Nearest Building
Structure Steel
Important: Grounding requirements will vary with the drives being used. Drives with True Earth (TE) terminals must have a zero potential bus, separate from potential
earth (PE) ground bus. Note that buses can be tied together at one point in the control cabinet or
brought back separately to the building ground grid (tied within 3
meters (10 feet)).
2–10Installation/Wiring
Power Cabling
Input and output power connections are performed through terminal
block, TB1 (see Figure 2.1 for location).
Important:For maintenance and setup procedures, the drive may
be operated without a motor connected.
Table 2.B
TB1 Signals
Terminal
PEPotential Earth Ground
R (L1), S (L2), T (L3)AC Line Input Terminals
+DC, –DCDC Bus Terminals
U (T1), V (T2), W (T3)Motor Connection
Table 2.C
TB1 Specifications – Use 75° C Copper wire Only
Wire sizes given are maximum/minimum sizes that TB1 will accept – these are not recommendations.
Description
Max./Min. Wire Size
mm2 (AWG)
1
Maximum Torque
N-m (lb.-in.)
ATTENTION: The National Codes and standards
!
(NEC, VDE, BSI etc.) and local codes outline
provisions for safely installing electrical equipment.
Installation must comply with specifications regarding
wire types, conductor sizes, branch circuit protection
and disconnect devices. Failure to do so may result in
personal injury and/or equipment damage.
Figure 2.1
Terminal Block Locations
TB1
TB2
TB3
TB4
TB6
Frames A2-A4
1
Refer to page 1–1 for frame reference classifications and Figure 2.2 for TB1 details.
Power Terminal Block
Control & Signal Wiring
Control Interface Option
24V DC Auxiliary Input
High Voltage DC Auxiliary Input
TB3
Option
Control Interface
TB1
TB2
TB1
1
Control Interface
Option
TB1
Frames B1/B2
TB4
TB6
TB3
TB2
TB1
1
2–11Installation/Wiring
Motor Cables
A variety of cable types are acceptable for drive installations. For
many installations, unshielded cable is adequate, provided it can be
separated from sensitive circuits. As an approximate guide, allow a
spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of
length. In all cases, long parallel runs must be avoided. Do not use
cable with an insulation thickness less than or equal to 15 mils.
The cable should be 4-conductor with the ground lead being
connected directly to the drive ground terminal (PE) and the motor
frame ground terminal.
Shielded Cable
Shielded cable is recommended if sensitive circuits or devices are
connected or mounted to the machinery driven by the motor. The
shield must be connected to both the drive ground (drive end) and
motor frame ground (motor end). The connection must be made at
both ends to minimize interference.
If cable trays or large conduits are to be used to distribute the motor
leads for multiple drives, shielded cable is recommended to reduce
or capture the noise from the motor leads and minimize “cross
coupling” of noise between the leads of different drives. The shield
should be connected to the ground connections at both the motor and
drive end.
Armored cable also provides effective shielding. Ideally it should be
grounded only at the drive (PE) and motor frame. Some armored
cable has a PVC coating over the armor to prevent incidental contact
with grounded structure. If, due to the type of connector, the armor is
grounded at the cabinet entrance, shielded cable should be used
within the cabinet if power leads will be run close to control signals.
In some hazardous environments it is not permissible to ground both
ends of the cable armor because of the possibility of high current
circulating at the input frequency if the ground loop is cut by a
strong magnetic field. This only applies in the proximity of powerful
electrical machines. In such cases, consult factory for specific
guidelines.
2–12Installation/Wiring
Conduit
If metal conduit is preferred for cable distribution, the following
guidelines must be followed.
• Drives are normally mounted in cabinets and ground connections
are made at a common ground point in the cabinet. Normal
installation of conduit provides grounded connections to both the
motor frame ground (junction box) and drive cabinet ground.
These ground connections help minimize interference. This is a
noise reduction recommendation only, and does not affect the
requirements for safety grounding (refer to pages 2–7 and
2–8).
• No more than three sets of motor leads can be routed through a
single conduit. This will minimize “cross talk” that could reduce
the effectiveness of the noise reduction methods described. If
more than three drive/motor connections per conduit are required,
shielded cable as described above must be used. If practical, each
conduit should contain only one set of motor leads.
ATTENTION: To avoid a possible shock hazard
!
Motor Lead Lengths
Installations with long cables to the motor may require the addition
of output reactors or cable terminators to limit voltage reflections at
the motor. Refer to Table 2.D for the maximum length cable allowed
for various installation techniques.
For installations that exceed the recommended maximum lengths
listed, contact the factory.
caused by induced voltages, unused wires in the
conduit must be grounded at both ends. For the same
reason, if a drive sharing a conduit is being serviced or
installed, all drives using this conduit should be
disabled. This will eliminate the possible shock hazard
from “cross coupled” drive motor leads.
2–13Installation/Wiring
y
y
y
Drive
Drive kW
Motor kW
Any
Any
Any
Any
Any
Any
Any
Any
Appli
g
tions using
andnew
For retrofit
checkwith
Table 2.D
Maximum Motor Cable Length Restrictions in meters (feet) – 380V-480V Drives
1
No External Devicesw/1204-TFB2 Term.w/1204-TFA1 TerminatorReactor at Drive
MotorMotorMotorMotor
DriveDrive kWMotor kW
Frame
(HP)
(HP)
A21.5 (2)1.5 (2)7.6
1.2 (1.5)7.6
0.75 (1)7.6
0.37 (0.5)7.6
2.2 (3)2.2 (3)7.6
1.5 (2)7.6
0.75 (1)7.6
0.37 (0.5)7.6
A33.7 (5)3.7 (5)7.6
2.2 (3)7.6
1.5 (2)7.6
0.75 (1)7.6
0.37 (0.5)7.6
A45.5-7.5
(7.5-10)
B5.5-22
(7.5-30)
5.5-7.5
(7.5-10)
5.5-22
(7.5-30)
AB13291329R, LA or B1329AB1329AB or 1329
AnyAnyAnyAn
Cable
Cable
Cable
Cable
12.2
91.4
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
(25)
7.6
(25)
7.6
(25)
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
12.2
(40)
(300)
114.3
(375)
114.3
(375)
114.3
(375)
91.4
(300)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
114.3
(375)
91.4
(300)
182.9
(600)
182.9
(600)
182.9
(600)
91.4
(300)
182.9
(600)
182.9
(600)
182.9
(600)
Unlimitedpp182.9
new installa-
tions usin
new motors
and new
drives.
For retrofit
situations,
check with
the motor
manufactur-
er for insula-
tion rating.
es to
Cable Type
Shld.3Unshld.
91.4
91.4
(300)
(300)
91.4
182.9
(300)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
182.9
182.9
(600)
(600)
Cable TypeCable Type
An
Shld.3Unshld. Shld.3Unshld.
Cable
91.4
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
30.5
(100)
(300)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
91.4
(300)
91.4
(300)
91.4
(300)
91.4
(300)
Use 1204-TFB2
61.0
(200)
61.0
(200)
61.0
(200)
61.0
(200)
AnyAnyAn
Cable
Cable
91.4
22.9
(300)
(75)
182.9
22.9
(600)
(75)
182.9
22.9
(600)
(75)
182.9
22.9
(600)
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
22.9
(75)
24.4
(80)
24.4
(80)
Cable
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
Type A Motor Characteristics: No phase paper or misplaced phase paper, lower quality insulation systems, corona inception voltages between 850 and 1000 volts.
Type B Motor Characteristics: Properly placed phase paper, medium quality insulation systems, corona inception voltages between 1000 and 1200 volts.
1329R Motors:These AC Variable Speed motors are “Power Matched” for use with Allen-Bradley Drives. Each motor is energy efficient and
designed to meet or exceed the requirements of the Federal Energy Act of 1992. All 1329R motors are optimized for variable speed
operation and include premium inverter grade insulation systems which meet or exceed NEMA MG1. Part 31.40.4.2.
NR = Not Recommended
1
Values shown are for 480V nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz.
Multiply values by 0.85 for high line conditions. For input voltages of 380, 400 or 415V AC, multiply the table values by 1.25, 1.20 or 1.15, respectively.
2
A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn–turn insulation rating of 2100
volts or higher.
TB2 is located at the bottom of the Main Control Board. 0.37-7.5
kW (0.5-10 HP) A Frame drives have 18 positions. Remaining frame
sizes from 5.5 kW (7.5 HP) and up have 22 positions. The maximum
and minimum wire size accepted by TB2 is 2.1 and 0.30 mm
2
(14
and 22 AWG). Maximum torque for all terminals is 1.36 N-m (12
lb.-in.). Use Copper wire only. See Figures 2.1 and 2.3.
The recommended control signal wire is:
• Belden 8760 (or equiv.)–0.750 mm
• Belden 8770 (or equiv.)–0.750 mm
• Belden 9460 (or equiv.)–0.750 mm
2
(18 AWG), twisted pair, shielded.
2
(18 AWG), 3 conductor, shielded.
2
(18 AWG), twisted pair, shielded.
Control Connections
If the drive control connections are to be linked to an electronic
circuit or device, the common or 0V line should, if possible, be
grounded at the device (source) end only.
Important:Signal Common – User speed reference signals are termi-
nated to logic common at TB2, terminal 3 or 4. This puts
the negative (or common) side of these signals at earth
ground potential. Control schemes must be examined for
possible conflicts with this type of grounding scheme.
Shield Termination – TE (True Earth)
The TE terminal block (not available on 0.37-7.5 kW (0.5-10 HP) A
Frame drives) provides a terminating point for signal wiring shields.
Refer to Figures 2.1 and 2.3 for location.
The maximum and minimum wire size accepted by this block is 2.1
and 0.30 mm
2
(14 and 22 AWG). Maximum torque is 1.36 N-m (12
lb.-in.). Use Copper wire Only and always separate control and
power cabling.
Cable Routing
If unshielded cable is used, control signal circuits should not run
parallel to motor cables or unfiltered supply cables with a spacing
less than 0.3 meters (1 foot). Cable tray metal dividers or separate
conduit should be used.
Important:When user installed control and signal wiring with an
insulation rating of less than 600V is used, this wiring
must be routed inside the drive enclosure such that it is
separated from any other wiring and uninsulated live parts.
2–16Installation/Wiring
9
Analog Out ut
Jum er JP1 to select 0-10V DC out ut
13, 14
CR3 Fault
ResistiveRating115VAC/30VDC,5.0A
g5C/30C,0
16, 17
CR4 Alarm
Figure 2.3
TB2 Connections
10 Bit
A/D
Only Present
on B Frame
& Up Drives
TETE
to
TE
10 Bit
A/D
75k
+5V
1µf
Logic
3.42k
Common
100
1
23456
10k Ohm
10 Bit
A/D
47.5k
1µf
150
1µf
100
1.4k
Typical
12 Bit
D/A
CR1
215
10052.3k
215
10
9
–+–+++
0-10V
Pulse
4-20mA
Source
Analog Out
User Supplied
Analog Device
Table 2.E
Terminal Block TB2 Specifications
CR2
1112131415161718A1A287
Contacts Shown
in Unpowered State
CR3
CR3CR4CR4
Only Present
on B Frame
& Up Drives
Reserved for
Future Use
Terminal
Signal
TETrue Earth – Shield Termination
1, 2, 3External Speed Pot. or Analog Trim Pot. (10k ohm pot. required)
4Signal Common
50-10V DC Input
64-20mA Input
7, 8Pulse Input
9Analog Output
A Frame Drives
Analog Output
B Frame Drives and Up
2
2
4
1
1
Input Impedance = 100k ohms
Input Impedance = 250 ohms
Refer to Pulse Input on the following page
Jumper JP1 to select 0-10V DC output
Jumper JP2 to select 0-20mA output
Jumper J5 selects output
pins 1-2 = 0-20mA
pins 3-4 = 0-10V DC
6
5
10, 11CR1 Programmable Contact
11, 12CR2 Run Contact
Refer to the Output Config group parameters
for analog scaling.
2
Refer to the [Maximum Speed] parameter on
page 5–43.
3
Refer to Chapter 6 for contact description.
4
Not available if Encoder Feedback option is
used.
5
Minimum Load Impedance:
A Frame drives = 3.5k ohms
B Frame drives & Up = 1.5k ohms.
Recommended load for all frames = 10k ohms.
6
Maximum Load Impedance:
A Frame drives = 260 ohms
B Frame drives & Up = 315 ohms
Pulse Input
ATTENTION: If reverse polarity or voltage levels
!
Frequency Reference
The pulse input signal must be an externally powered square-wave
pulse at a 5V TTL logic level. Circuits in the high state must
generate a voltage between 4.0 and 5.5VDC at 16 mA. Circuits in
the low state must generate a voltage between 0.0 and 0.4VDC.
Maximum input frequency is 125kHz. Scale factor [Pulse/Enc Scale]
must be set.
are maintained above +12V DC, signals may be
degraded and component damage may result.
Control Interface Option –
TB3
Ride Thru Monitor
The pulse input terminals can also be used as an input from devices
used to monitor input line conditions. Input voltage must be between
4.0 and 5.5VDC at 16 mA for high state. Low state must be between
0.0 and 0.4VDC. Refer to [Ride Thru Mode] for further details.
Important:Pulse inputs (TB2-7, 8) cannot be used if encoder inputs
(TB3, terminals 31-36) are being used.
The Control Interface Option provides a means of interfacing various
signals and commands to the 1336 PLUS by using contact closures.
Six different versions of the option are available:
L4Contact Closure Interface
1
L4EContact Closure Interface1 with Encoder Feedback Inputs
L5+24V AC/DC Interface
L5E+24V AC/DC Interface with Encoder Feedback Inputs
L6115V AC Interface
L6E115V AC Interface with Encoder Feedback Inputs
1
Uses internal +5V DC supply.
2–18Installation/Wiring
The user inputs are connected to the option board through TB3 (see
Figure 2.1 for location). The L4, L5 and L6 options each have nine
control inputs. The function of each input must be selected through
programming as explained later in this section. The L4E, L5E and
L6E options are similar to L4, L5 and L6 with the addition of
encoder feedback inputs. Refer to Figure 2.6 (a, b & c) for input
impedance values.
2–19Installation/Wiring
Available Inputs
A variety of combinations made up of the following inputs are
available.
InputDescription
1st/2nd Accel/DecelThese inputs allow selection of the accel or decel time used by
AuxiliaryRequired for Operation – this input is intended to fault the drive
Digital Pot Up/DownThese inputs increase (up) or decrease (down) the drive
EnableRequired for Operation – opening this input shuts the drive
Local ControlClosing this input gives exclusive control of drive logic to the
ReverseAvailable Only with three-wire control – In single source
Run Forward/ReverseAvailable Only with two-wire control – Closing these inputs
Speed Select 1, 2, 3These inputs choose the frequency command source for the
StartIssues a Start command for the drive to begin acceleration to
Stop TypeClosing this input selects the stop mode in [Stop Select 2] as the
Stop/Fault ResetIssues a Stop command for the drive to cease output per the
SyncThis function has one On/Off input that can come from the
TraverseThe Traverse function has one On/Off input that can come from
the drive.
via external devices (i.e. motor thermoswitch, O.L. relays, etc.).
Opening this contact will fault (F02 – Aux Fault) the drive and
shut the output off, ignoring the programmed stop mode.
commanded frequency when MOP (Motor Operated
Potentiometer) is chosen as the frequency command source.
The rate of increase/decrease is programmable.
output off, ignoring the programmed stop mode.
inputs at terminal block TB3. No other devices may issue logic
commands (excluding Stop) to the drive.
reversing modes, closing this input commands reverse direction
and opening this input commands forward direction.
issues both a start command and a direction command to the
drive. Opening these contacts issues a stop command to the
drive.
drive. See following pages for details.
commanded frequency.
method of stopping when a stop command is issued. Opening
this input selects the stop mode in [Stop Select 1] as the method
of stopping.
programmed stop mode. If the drive has faulted, opening this
input resets the fault if [Fault Clear Mode] is enabled.
Control Interface option (TB3) or from a local bus type 2
command. The parameter [Sync Time] is associated with the
function.
When the Sync input is low (0), the drive operates normally.
However, when the input is high (1), the speed of the drive will be
held constant and the speed command will have no effect.
During this period the speed input of the drive will normally be
changed to a different source and/or value.
the Control Interface option (TB3) or from a local bus type 2
command.
Traverse is disabled by setting either the [Traverse Inc] or
[Traverse Dec] parameter to zero or setting [Speed Control] to
something other than “P Jump.“
2–20Installation/Wiring
The available combinations are shown in Figure 2.5. Programming
the [Input Mode] parameter to one of the Input Mode numbers listed,
will select that combination of input functions.
Important:If a Control Interface Option is not installed, the [Input
Mode] parameter must be set to 1 (default) and jumpers
must be installed as shown in Figure 2.7. If the drive
was shipped from the factory without the option, these
jumpers will have been installed.
Important:The [Input Mode] parameter can be changed at any
time, but the change will not affect drive operation until
power to the drive has been removed and bus voltage
has decayed completely. When changing the [Input
Mode] parameter, it is important to note that the
functions of the TB3 inputs will change when power is
reapplied to the drive.
The programming options of the Control Interface Option allow the
user to select an input combination to meet the needs of a specific
installation. Appropriate selection of a combination may be done by
using Figure 2.5. First determine the type of start/stop/direction
control desired. Then select the remaining control functions
available. Record the selected mode number below.
Selected Mode Number:
Figure 2.4 provides the terminal designations for TB3. The
maximum and minimum wire size accepted by TB3 is 2.1 and 0.30
2
mm
(14 and 22 AWG). Recommended torque for all terminals is
0.90-1.13 N-m (8-10 lb.-in.). See Figure 2.6 for TB3 interconnection
information. Use Copper wire only.
Figure 2.4
TB3 Terminal Designations
Included on L4E, L5E & L6E Only
192021222324252627282930
Input 1
Input 2 (Stop)
Input 3
Common
Input 4
Input 5
Input 6
Common
Input 7
Input 8
Common
313233343536
Enable
Encoder B
Encoder NOT A
Encoder A
Encoder NOT B
(200mA max.)
+12V
Encoder Common
2–21Installation/Wiring
Speed Select/Frequency Reference
The drive speed command can be obtained from a number of
different sources. The source is determined by drive programming
and the condition of the Speed Select Inputs on TB3 (or reference
select bits of command word if PLC controlled – see Appendix A).
The default source for a command reference (all speed select inputs
open) is the selection programmed in [Freq Select 1]. If any of the
speed select inputs are closed, the drive will use other parameters as
the speed command source. Refer to Table 2.F and the examples that
follow.
Table 2.F
Speed Select Input State vs. Frequency Source
Important:The final speed command may be affected by the type
of modulation selected with [Speed Control], parameter
77. Refer to [Speed Control] in Chapter 5 for further
information.
Example 1
Input Mode 2 – Application calls for a local Human Interface
Module (HIM) speed command or remote 4-20mA from a PLC. The
drive is programmed as follows:
With Speed Select inputs 2 & 3 open and the selector switch set to
“Remote” (Speed Select 1 closed), the drive will follow [Freq Select
2] or 4-20mA. With the switch set to “Local” (Speed Select 1 open)
all speed select inputs are open and the drive will follow the local
HIM (Adapter 1) as selected with [Freq Select 1].
Speed Select 3 (Open)
Speed Select 2 (Open)
Speed Select 1
Remote
Local
26
27
28
2–22Installation/Wiring
Switch
Parameter Used
Programmed
g
Example 2
Input Mode 7 – Application is to follow a local HIM unless a preset
speed is selected. The drive is programmed as follows:
Contact operation for the speed select switch is described in the table
below. Since Input Mode 7 does not offer a Speed Select 3 input,
[Preset Freq 4-7] are not available.
1
Local
See Table
Speed Select Input
Position
LocalOpenOpen[Freq Select 1]Adapter 1
1ClosedOpen[Freq Select 2]Preset Freq 1
2OpenClosed[Preset Freq 2]20 Hz.
3ClosedClosed[Preset Freq 3]30 Hz.
1 (#28)
2 (#27)
for Speed Ref.
26
2
3
27
28
Settin
Speed Select 2
Speed Select 1
Loading...
+ 119 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.