The products described in this publication are designed specifically for use
on rectified power. The basic design includes Class F Insulation, 1.0 Service
Factor, 40 degree C (104 degree F) ambient, continuous duty, with
drip-proof guarded and force-ventilated enclosure, with horsepower speed
ratings, overload and voltage in accordance with NEMA Standards. A wide
variety of modifications, enclosures and accessories is available.
ATTENTION: Only qualified electrical personnel familiar with
the construction and operation of this equipment and the hazards
!
involved should install, adjust, operate, and/or service this motor.
Read and understand this manual in its entirety before
proceeding. Failure to observe this precaution could result in
personal injury or loss of life.
Thoroughly inspect this equipment before accepting shipment from the
transportation company. If any of the goods called for in the bill of lading or
express receipt are damaged or the quantity is short, do not accept them
until the freight or express agent makes an appropriate notation on your
freight bill or express receipt. If any concealed loss or damage is discovered
later, notify your freight or express agent at once and request him to make
an inspection. We are willing to assist you in collecting claims for loss or
damage in shipment; however, this willingness on our part does not remove
the transportation company's responsibility in reimbursing you for
collection of claims or replacement of material. Claims for loss or damage
in shipment must not be deducted from the invoice, nor should payment of
the invoice be withheld awaiting adjustment of such claims, as the carrier
guarantees safe delivery.
If considerable damage has been incurred and the situation is urgent,
contact the nearest Allen-Bradley Sales Office for assistance. Please keep a
written record of all such communications.
DC Motors3
Handling
ATTENTION: Eyebolt(s) or lifting lug(s) are intended for
lifting the motor only with the standard accessories such as
!
tachometer, brakes, etc., mounted by Allen-Bradley. The lifting
means on the motor must not be used to lift the unit plus
additional equipment. The lifting means on the motor cannot be
used to lift assemblies or equipment mounted on a common base.
Failure to observe this precaution could result in personal injury.
In all cases, care should be taken to assure lifting in the direction intended
in the design of the lifting means. Lift using all lugs provided. Likewise,
precautions should be taken to prevent hazardous overloads due to
deceleration, acceleration or shock forces.
Angle of lift with rope or chain must be greater than 45 degrees from
horizontal.
For unusual conditions, such as side-wall and ceiling mounting of
horizontal motors or installation of vertical motors shipped in a horizontal
position, special precautions must be taken. It is recommended that an
experienced rigger be employed.
Installation
Storage
Motors must be stored in a clean, dry area protected from extremes of
temperature, moisture, shock and vibration. Storage temperatures of 10 to
49 degrees C (50 to 120 degrees F) with a maximum relative humidity of
60% must be observed. In addition, motors subjected to extended storage
must be handled and treated per the requirements specified in publication
“Motors-5.0.” This publication is available from your Allen-Bradley Sales
Office or online at: http://www.controlmatched.com.
DC motors have characteristics which can cause serious or fatal injury
unless they are selected, installed, maintained and operated by qualified
personnel familiar with special requirements of DC machines.
Allen-Bradley DC motors are designed and built in accordance with Safety
Standard for Construction and Guide for Selection, Installation and Use Of
Electric Motors And Generators published by the National Electrical
Manufacturers Association (NEMA), publication MG-2-1983 (ANSI
C51.5). It is recommended that this publication be referred to whenever you
select or install any motor.
The application of motors and other electrical equipment in hazardous
locations is restricted by the National Electric Code. Users must observe
these regulations and consult with local code inspection and enforcement
agencies to insure compliance.
4DC Motors
Location
Locate the machine where the ambient temperature is not over 40 degrees C
(104 degrees F) and where clean air has free access to ventilating intake and
outlet openings. Except for machines with a suitable protective enclosure,
the location should be clean and dry.
Important: Sufficient clearance must be provided on all inlet and outlet
openings to provide for unrestricted flow of air. Separately
ventilated motors with exhaust to ambient (pipe-in only) must
have at least 152.4 mm (6 in.) of clearance between the opening
and adjacent walls or floor.
Air Supply
Cooling air through a self-ventilated or forced-ventilated motor must be
clean and have relative humidity between 30 and 100% with no free water
in the air. Use of damp, cool outside air with high humidity and free water
may cause the motor to flash over. Use of excessively dry air may cause
excessive brush and commutator wear. Cooling air temperature must not
exceed the maximum ambient temperature indicated on the motor
nameplate (standard 40 degrees C/104 degrees F). Cooling air temperature
must not be lower than 0 degrees C (to provide base speed and regulation
within NEMA limits). Use of outside air below 0 degrees C may cause
excessive brush and commutator wear due to the low humidity. Cooling air
absolute humidity must be at least 2 grains per cu. ft.
Important: Motors located in damp, moist environment must have space
heater or fields energized at 50% voltage to protect against
condensation when motor is not operating.
Separately ventilated motors must have the following volume of air to
adequately cool the motor unless the motor nameplate specifies a different
value.
Frame
DC180ATZ,
C180ATZ and
DC210ATZ
Base Speed
RPM
25001522.0
1750 and lower1050.95
Air Volume
CFM
Static Pressure
Inches of Water
Power Supply
Check the motor nameplate to be sure the voltage and type of power rating
is the same as that of the power source.
A code stamped on the nameplate identifies the type of power supply that
must be used to supply armature power to the motor in order to obtain the
rated nameplate output. Since the code letter has been selected in alphabetic
order of increasing magnitude of ripple current, a motor may be operated on
a power supply having a letter designation prior in the alphabet to the letter
stamped on the nameplate, with no loss in nameplate rating.
DC Motors5
For example, a motor designed for a D type of power supply may be used
on a C power supply having the same voltage rating. The types of power
supplies are defined as follows.
DescriptionCode
DC generator, battery or twelve pulse/cycle, 6 phase, full controlA
Six pulse cycle, 3 phase, full control 230 or 460 volt, 60 Hz input to rectifierC
Three pulse/cycle, 3 phase, semi-bridge, half control 230 or 460 volt, 60 Hz input to rectifier D
Three pulse/cycle, 3 phase, half-wave (single way) 460 volt, 60 Hz input to rectifierE
Two pulse/cycle, 1 phase full wave (bridge circuit with 2 controlled rectifiers and
K
2-uncontrolled rectifiers with free wheeling rectifier) 230 volt, 60 Hz input
1
When the armature power supply cannot be designated by a single letter code (A. K etc.) the power supply shall
be identified by the following code stamped on the motor nameplate: “M/N F-V-H-L.”
where M = Total pulses per cycle
N = Total controlled pulses per cycle
F = Free wheeling (if used)
V = Nominal line-to-line a-c voltage to rectifier
H = Line frequency-Hz
L = Value of series inductance (in millihenries) to be added externally to the motor armature circuit.
Examples:
A. "6/3 F-380-50-12" defines a power supply having 6 total pulses per cycle, 3 controlled pulses per cycle
(S-3), with free wheeling, 380 volts. 50 Hz AC input to bridge, and a 12 millihenry choke to be added
externally to the motor armature circuit.
B. "3/3 480" defines a power supply having three total pulses per cycle, three control pulses per cycle. 480
volts line-to-line input to the rectifier. 60 Hz power supply and no external inductance required in the
armature circuit. Note that since the power source is 60 Hz and no series inductance is required. both
quantities may be omitted from the code. If one of the quantities is indicated, both must be included to
avoid confusion.
Conduit Box
1
Conduit boxes can be rotated in 90 degree increments for lead outlet at top,
sides or bottom.
Conduit box locations can be changed from F1 to F2 or F2 to F1 by rotating
the commutator end bracket 180 degrees and reconnecting the leads. The
conduit box location cannot be changed on DC180ATZ & DC210ATZ
frames.
Connections
Important: If motor has parallel leads, all lugs with the same marking: For
example, A1, A1, must be connected together.
Figure 1 Basic DC Motor and Generator Connections
Rotation Facing Commutator End
Type
Motor
Generator
+A1
A2
S1
A1
+A2
S1
CCW
–S2
+F1
–F2
–S2
–F1
+F2
A1
+A2
S1
A1
+A2
–S1
CW
–S2
+F1
–F2
S2
+F1
–F2
If machine has no series field, disregard S1 and S2 above. For machines
with special windings, refer to motor or generator and controller diagrams.
6DC Motors
Thermostat (Thermal Protector)
Important: When motors are provided with thermal protection (typically
thermostats), it is important to properly connect and apply the
devices. This will ensure that the motor is properly protected
from being operated if thermal limits are reached and/or
exceeded. The control system must be configured to reduce the
motor load and/or shut down the motor control system to allow
the motor to cool to a level within acceptable operating ranges.
If the motor is operated with the thermal protective devices
tripped (indicating an over temperature condition), the motor
insulation could be damaged and complete failure of the motor
insulation is possible. In the event of motor failure due to an
over temperature condition, Rockwell Automation requires that
motor thermal protective devices (when supplied) be
adequately monitored and incorporated into the motor control
system to maintain warranty. Failure on the part of the
individual installing this equipment to take these steps will
result in the factory warranty being voided.
Important: Motors may have one or more thermostats (leads marked P1,
P2, etc.) designed to trip before the frame reaches the
maximum allowable temperature for specific class and group.
The normally closed contacts of the thermostat must be
connected in that motor control circuit so that power to the
motor armature and field is removed immediately when the
thermostat trips. An explosion-proof tachometer mounted on
the motor will also have an internal thermostat which must be
connected to stop the drive within 30 seconds upon tripping.
Failure to connect the thermostat leads will void the motor
warranty. the rating of the thermostat contact is:
Maximum Voltage250V, 60 Hz
Rated Current 6.3 amps
Maximum Breaking Current20 amps
Important: Motors with an overspeed switch must have the overspeed
switch terminals properly connected in the control circuit to
remove armature power when the switch reaches the set speed.
Grounding
The user is responsible for assuring that the grounding method is in
accordance with the National Electric Code and the applicable local codes.
The ground connection should be a solid and permanent metallic
connection between the ground point, the motor terminal housing and the
motor frame. On two pole units, DC180ATZ, C180ATZ & DC210ATZ, the
ground connection is a tapped hole in the end bracket adjacent to the
conduit box.
DC Motors7
Mounting
Motors must be mounted on a rigid, solid base or foundation. Poor base
construction may cause resonances in the motor/base assembly which can
result in bearing failure and other motor damage. All hold down bolts must
be the correct grade for the type of mounting and must be torqued to their
recommended value.
Table A Recommended Torque
Frame
C180ATZ 11.2 (0.44)3/8-161.81 (16)
Hole Diameter
mm (in.)
Bolt Size and
Thread
SAE Grade I Dry Components-Not Lubricated
N-m (lb.-ft.)
Belted Drive
Motor slide bases or rails, when used, must be securely anchored to the
foundation with the proper bolts.
Important: The motor shaft and load shaft must be parallel and the sheaves
aligned. Refer to
“Motor Application Data” on page 8.
Coupled Drives
Important: Flexible couplings must be used between the motor shaft and
the load shaft. Motor shaft and load shaft must be aligned to
values recommended for the specific coupling before coupling
is connected.
Important: Motors will operate successfully mounted on the floor, wall or
ceiling, and with the shaft at any angle from horizontal to
vertical. Special mountings, duty or thrust demands may,
however, require a different bearing system. Drive-end bracket
and/or outer caps can be rotated either 90 or 180 degrees to
conveniently locate grease fittings, or air outlet openings.
Handhole covers can be interchanged as necessary.
Important: Vertical mount drip covers are required to provide protection to
vertically mounted Drip-Proof motors. Stock motors and other
motors designed for horizontal mounting can be adapted for
vertical mounting by ordering vertical mount drip covers.
Self-ventilated frames cannot be mounted vertical shaft up and
retain the drip-proof feature due to louvers on the drive end
bracket.
Motor C-Face is intended for mounting auxiliary equipment such as pumps,
gears, etc. When mounted horizontally, these motors should be supported
by the feet and not by the C-Face. Installations requiring a horizontally
mounted motor without feet should use a D-Flange.
ATTENTION: Surface temperature of the motor enclosure may
reach temperatures which can cause discomfort or injury to
!
personnel coming into contact with hot surfaces. The user must
apply appropriate guards and/or shields to protect against
accidental contact with motor surface. Failure to observe this
precaution may result in personal injury.
8DC Motors
Direction of Rotation
Unless otherwise ordered, brush rigging is assembled for NEMA standard
direction of rotation, counterclockwise for motors and clockwise for
generators facing the commutator end. These motors will operate in either
direction of rotation, without changing the angle of the brush holders for
normal field weakened speed ranges. Extended field weakened speed range
motors should have the direction of rotation specified.
Drive
DC180ATZ, C180ATZ & DC210ATZ frame motors are supplied with a
shaft suitable for a belt or coupled drive.
Proper alignment is a key step for long life of bearings, shafts and belts, and
minimum downtime. Misalignment can cause excessive vibration and
damaging forces on shaft and bearings. For direct coupled drives, flexible
couplings facilitate alignment. For belt drives, the driving and driven
tension must be adjusted as required for proper operation. The belt sheaves
should be placed as close as possible to the motor bracket.
Motor Application Data
ATTENTION: To guard against personal injury and/or machine
damage caused by incorrect motor rotation, verify direction of
!
motor rotation before coupling motor to load.
ATTENTION: Ensure that all guards are properly installed, to
guard against personal injury caused by contact with rotating
!
parts,
Shipping Blocks
Motors supplied with roller bearings at the drive end are shipped with
wooden blocking to prevent axial movement of the shaft during shipment.
Remove the blocking and bolts securing it and discard. Make sure motor
shafts turn freely. If motor is to be reshipped, blocking of bearing is
required.
Maximum Safe Speed
ATTENTION: The machinery builder and/or user are
responsible for assuring that all drive train mechanisms, the
!
driven machine, and process material are capable of safe
operation at the maximum speed at which the machine will
operate. Failure to observe these precautions could result in
personal injury.
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.