Thank you for purchasing the LightSYS™ 2 hybrid security system, offering Smartphone App
control and communication flexibility as well as a choice of wired, 2-way wireless, or RISCO Bus
detectors. This simple setup procedure guide covers all common LightSYS installation and
programming steps (based on factory default settings) required in order to set up a working system.
For more comprehensive instructions, refer to the LightSYS2 Installation and Programming Manual (5IN2048).
Selecting Mounting Location
Decide where to position your LightSYS control panel. A central location is often the best place,
making wiring to expanders and accessories easier. It is advisable to prepare a plan of
expander/accessory physical locations in advance of the installation, as this will determine which
type of expander is required at each location.
The control panel location should:
• Be in a dry place near an AC power supply
• Have access to the routing of cables for the system from detection devices
• Have access to the customer’s phone lines/IP network
• (In case you installed GSM / GPRS module before mounting the system into the desired
position)
Ensure a good signal of the GSM network (Advisable to have a level of at least 4 out of 5).
Installing Hardware
Main Unit — BUS Connection
The set of four terminals on the left of the terminal block represent the expansion bus. These
terminals support the connection of keypads and expansion modules. The connections are terminalto-terminal with color-coded wires, as follows:
Connect any/all keypads and expanders/accessories necessary for the installation using the bus
connections.
LightSYS Quick Install er Guide 5
ID
DIP switches
ID
DIP switches
1 2 3 4 5 1 2 3 4 5
01
OFF
OFF
OFF
OFF
OFF 17
OFF
OFF
OFF
OFF
ON
02
ON
OFF
OFF
OFF
OFF 18
ON
OFF
OFF
OFF
ON
03
OFF
ON
OFF
OFF
OFF 19
OFF
ON
OFF
OFF
ON
04
ON
ON
OFF
OFF
OFF 20
ON
ON
OFF
OFF
ON
05
OFF
OFF
ON
OFF
OFF 21
OFF
OFF
ON
OFF
ON
06
ON
OFF
ON
OFF
OFF 22
ON
OFF
ON
OFF
ON
07
OFF
ON
ON
OFF
OFF 23
OFF
ON
ON
OFF
ON
08
ON
ON
ON
OFF
OFF 24
ON
ON
ON
OFF
ON
09
OFF
OFF
OFF
ON
OFF 25
OFF
OFF
OFF
ON
ON
10
ON
OFF
OFF
ON
OFF 26
ON
OFF
OFF
ON
ON
11
OFF
ON
OFF
ON
OFF 27
OFF
ON
OFF
ON
ON
12
ON
ON
OFF
ON
OFF 28
ON
ON
OFF
ON
ON
13
OFF
OFF
ON
ON
OFF 29
OFF
OFF
ON
ON
ON
14
ON
OFF
ON
ON
OFF 30
ON
OFF
ON
ON
ON
15
OFF
ON
ON
ON
OFF 31
OFF
ON
ON
ON
ON
16
ON
ON
ON
ON
OFF 32
ON
ON
ON
ON
ON
Notes:
1. The parallel wiring system supports parallel connections from any point along the wiring.
2. The maximum wire run permitted is 300 meters (1000 feet) for all legs of the bus.
3. In case of bus communication problems, connect two 2.2KΩ resistors, one at each end of the data
bus terminals, between the green and yellow wires.
4. If connecting remote power supplies, do NOT connect the Red wire (+12v) between the Power
Supply Unit and LightSYS.
5. For long cable runs, please use the correct cable as stated in the Installation Manual, Wiring appendix.
1. Setting Bus Accessory ID Numbers
For most devices, a DIP switch number must be set to identify its ID category number.
Devices are split into ‘Families’. Each ‘Family’ of devices has sequential identification numbers
which are set by the DIP switches. Before setting power on, define each module’s ID number by
setting the dipswitches as follows:
Notes:
• Most accessories have four DIP switches, while bus detectors have five DIP switches
• IDs 9–32 are only available for bus detectors.
• If a DIP switch is changed on any device, it is necessary to shut down the device’s power and
then re-power it.
The first module in each category is defined as ID= 1.
Families that have sequential ID numbers are:
• Keypads (LCD, LCD with proximity and wireless keypad (both 1- and 2-way)
• Zone Expanders (8 zones expander, bus zone expander)
on 4A power supply, 2 relay output expander on Wireless zone expander, X-10 Outputs,
again, both 1-and 2-way)
• Power Supplies (4A switching mode power supply)
• Bus Zones
• WL Zone Expanders
6 LightSYS Quick Install er Guide
Notes:
Total
Wired / BUS Expanders
3
BUS Zones
32
WL Zone Expanders
2
BUS Zones Expanders
4
Outputs Expanders
4
Keypads
4
1.5A or 3A Power Supply
4
BUS Sirens (ProSound / Lumin8)
4
ENDOFLINEZONE
(N.O CONTACT)
zonecom
ALARM
2.2
K
DETECTOR
NORMALLY OPEN ZONE
CONFIGURATION
ALARM
zone
com
DETECTOR
NORMALLY CLOSED
ZONE CONFIGURATION
ALARM
zone
com
DETECTOR
END OF LINE ZONE
(N.C CONTACT)
2.2
K
zonecom
ALARM
DETECTOR
DOUBLEENDOFLINE
ZONECONFIGURATION
com
2.2
K
ALARMTAMPER
zone
2.2
K
DETECTOR
1. The main unit can support a maximum load of 1.4 Amp. If more current is required install
additional power supply modules (3 Amp max.).
2. On 3 AMP supervised power supplies and on the wireless expander, there are two
programmable outputs. These programmable outputs belong to the ‘Output’ family. These
outputs have dedicated DIP switches that identify the OUTPUT ID.
Maximum number of devices possible:
2. Zone Inputs Connection
The following diagrams illustrate the various possible zone connections to the main unit or to
the 8 wired zones expander.
Notes:
1. For a zone with a tamper switch, you can use a double end-of-line resistor to save additional main
panel connections.
2. It is recommended that you use an end-of-line resistor at the far end of each hardwired zone (16 x
2.2K resistors are supplied).
3. In the LightSYS you have the ability to define separately the end-of-line resistance of the zones on
the main unit and of the wired zones for each eight-unit expander block (Quick key ).
Selection is done by the software with the following available options:
Use the Auxiliary PowerAUX (+) COM (-) terminals to power PIRs, glass-break detectors (4-wire
types), smoke detectors, audio switches, photoelectric systems and/or any device that requires a 12V
DC power supply.
4ANote:
If the auxiliary outputs are overloaded (exceed 800/1500mA) and are shut down, you must
disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any
load to the auxiliary outputs.
4. Wiring Internal Bell
The Bell/LS terminal provides power to the internal siren. When connecting an internal sounding
device, pay attention to the polarity.
It is important to position the BELL/LS Dip Switch SW1 correctly. The position varies depending on
the type of internal siren.
Note:
To avoid bell loop trouble, if no connections are made to an internal siren, use a 2.2KΩ resistor in its
place.
5. Wiring Bell Tamper
Connect the bell tamper to the BELL TMP and COM terminals on
the main panel using 2.2KΩ resistors in serial.
8 LightSYS Quick Install er Guide
Important:
DIP Switch SW1
Status
1: Bell
ON: Bell: For bell or electronic siren with a built-in siren driver.
OFF (Default): For loudspeaker without a built-in sound driver.
2: Default
ON: Resets installer, sub-installer and grand master codes to their
OFF (Default): Codes preserve their set values.
3: Extern - Back
ON: Back tamper bypass is in effect. Use this setting during
OFF (Default): No tamper bypass is in effect
4: Intern –
Bypass
ON: Front tamper bypass is in effect. Use this setting when the
OFF (Default): No tamper bypass is in effect
If you DO NOT use the terminal TMP BELL, remember to connect a 2.2KΩ
resistor (Resistor colors: Red, Red, Red) between TMP and COM.
6. Wiring Utility Output 1 to Activate Self-Power Devices
Utility output 1 can be used to activate a self-powered siren or any other self-powered device.
7. Main Unit DIP Switch settings
default factory values and bypasses main unit front tamper alarm.
Tamper Bypass
Front Tamper
programming and if no back tamper has been connected to PLUG 2.
LightSYS is installed inside the metal enclosure RP432BM1.
Connecting BUS Detectors
Up to 32 addressable bus detectors can be assigned to the LightSYS. Bus detectors can be wired to
the main bus or to a Bus Zone Expander (BZE).
For full installation instructions refer to the instructions supplied with each bus detector.
Connecting BUS Detectors to the Main LightSYS BUS:
1. Set the bus detector ID number (1-32) using the detector's DIP switches.
Note:
For WatchOUT, LuNAR, WatchIN, BWare and Seismic set the switch that defines the
LightSYS Quick Install er Guide 9
detector operation mode to bus mode.
2. Wire the bus terminals AUX(RED), COM (BLK), BUS (YEL) and BUS (GRN) to the
LightSYS Bus.
Note:
For maximum operation stability, it is best NOT to exceed a total 300 meters (1000 feet)
of wiring from the bus detector to the LightSYS panel.
Connecting Bus Detectors using a Bus Zone Expander (BZE):
1. Set the BZE ID number (1-3) using the DIP switches SW1 1-3.
2. Set the BZE SW2-3 to ON position.
3. Wire the BZE terminals marked as TO PANEL to the LightSYS Bus.
4. Set the bus detector ID number (1-32) using the detector's DIP switches.
Note:
Do not repeat the same ID twice on the same BZE.
5. Wire each detector's bus terminals to the relevant BZE's terminals marked as TO
DEVICE.(see figure below)
Note:
For maximum operation stability, it is best NOT to exceed a total of:
300 meters (1000 feet) of wiring from the BZE to the LightSYS panel.
300 meters (1000 feet) of wiring from the BZE to the last bus detector.
GSM Communication Module
The GSM Module provides voice and data communication on the LightSYS over the cellular
network
1. Power down the LightSYS.
2. Plug in the GSM module to the LightSYS main board.
3. Insert the dedicated SIM card and, if required, enter the enabling PIN code or disable the
SIM PIN Code in advance by placing it in a cell phone and disabling the code.
4. Attach the antenna plate and slide it into its right-wall housing. (See figure
5. Power up the LightSYS. The green LED should flash for thirty seconds, indicating the
network signal strength, and then steadily stay lit.
10 LightSYS Quick In staller Guide
, page 3)
6. Perform manual setting for the GSM module. From the main installer programming menu
Key
= 1,'?!"–()@/:_+&*#
= 8tuvTUV
Key
= 3defDEF
Key = 9wxyzWXYZ
select []. Select Type GSM and press to confirm.
Note:
To establish GPRS communication set up the APN (Access Point Name) and Email
according to the details instructed by the cellular provider. (Quick programming key
)
IP Communication Module
The IP module provides data communication on the LightSYS over the TCP/IP network.
1. Power down the LightSYS.
2. Plug in the IP module to the LightSYS main board.
3. Connect the incoming LAN cable in order to enable IP Communication. Make sure that the
cable is connected to the network.
4. Power up the LightSYS and refer to the Programming IP section.
5. Perform manual setting for the IP module. From the main installer programming menu
select
[]. Select Type IPC and press to confirm.
Note:
For IP communication set to dynamic IP (Quick programming key )
Programming
Keys Menu Navigation
This manual explains how to program the LightSYS from the default model 432KP keypad. The
following table describes the uses of the keypad keys during programming:
–
or
1. To enter numeric values where required.
2. For quick key programming. Press the number keys to access a
programming option.
3. To edit labels and names.
To go back (up) / quit / don’t save.
Enter / Save (to move into the displayed menu or to save the data that you
have changed).
Used to scroll through the menu listing.
Used to toggle displayed menu options from ‘N’ to ‘Y’ and vice-versa.
Used to increase or decrease selected screen digital values.
If you do not know where you are in the menu structure, press repeatedly to return to the
main menu.
Entering Text Descriptions (Labels):
Key
LightSYS Quick Install er Guide 11
= 2abcABC
Key
Key
= 4ghiGHI
Key =0
Key
Key = Move cursor left
Key = Move cursor right
Key = Save
Key
Key
= 5jklJKL
= 6mnoMNO
= 7pqrsPQRS
Programming Menu Concept
The LightSYS programming menu is a dynamic menu that adjusts itself to the system hardwired
devices. For example, in order to see menu option regarding wireless zones or keyfobs, first you
must add a wireless expander to the system.
Access Installer Programming Menu
1. First Time Power Up
1. Disconnect all power from the main panel
2. Set SW1 – 2 (Default) to ON position.
3. Set tamper switches SW1 3,4 to bypass unused tampers according to the relevant
enclosure to prevent tamper alarm
4. Connect – power to the assembled mounted unit. The LightSYS panel – keypad
initialization ensues for a period of minutes.
5. Press the
6. Select language. Scroll through the options and press
Note:
Changing the language can be done also in regular operation mode by pressing +
key.
.
simultaneously
7. Enter the Installer code (default: ) and press .
8. Correct the time and date and confirm by pressing
9. The system automatically enters the automatic accessories settings process option.
10. Move to the section "Identifying the connected devices" as described below.
2. Enter Installer Programming Mode
1. From the main display press .
2. Enter the Installer code (default: ) and press .
3. Select [1] Programming and press
12 LightSYS Quick In staller Guide
.
.
4. You are now in Installer Programming mode. Move to the section "Identifying the
connected devices" described below
Identifying the connected devices
1. Automatic Setting
Note:
By default, when entering Installer mode with the default DIP Switch 2 in ON position , the
system will take you immediately to Auto Settings. If the keypad is already showing BUS SCANNING, skip to step 2 below.
1. Enter the programming key sequence (Install, BUS Devices, Automatic).
2. Press to begin the automatic BUS SCANNING (the Auto Settings process) in which it
identifies all the devices on the bus.
3. Verify that the keypad displays all the devices you have connected. If a device does not
appear, ensure that you have given it a unique ID within its “family”.
4. Press
and to advance on to the next device found.
5. Repeat steps 3 and 4 until the presence of all devices has been confirmed and all
parameters configured.
Note:
1. When adding a zone expander you should define the zones expander resistance
compatibility, depending on the detectors you intend to connect to the expander. By
default the resistance is set to 2.2K for EOL and DEOL termination.
2. When adding a wireless expander, define the “Bypass Box Tamper” as YES if the wireless
expander is mounted inside the LightSYS housing and not in its own.
to accept what is being displayed, to progress through configuration screens
2. Bus Test
The bus test (Quick key ) sends multiple test commands to each device connected to the
system to ensure reliable connectivity.
Press to begin the automatic BUS TEST in which every device is tested to report if
connections are 99% or higher.
Note:
If a low reading is experienced, check connections with the device and repeat the bus test.
Zones Attributes
The LightSYS supports up to 32 zones. Each zone can be defined to be a wired zone, a wireless
zones or a bus zone. The attributes for each zone vary according to the zone’s type (wired, wireless
or type of bus zone).
You can define the basic parameters for a zone using the “One By One” option or you can define
all attributes using the zones category (Quick key
1. From the main Installer Programming menu select (Zones, Parameters)
2. Select [One B y One] and press .
3. Using the numeric keys, enter the desired zone number and press
LightSYS Quick Install er Guide 13
).
.
Important
The display next to the selected zone number defines the type of zone and its location in the
system in the format XY:ZZ
X: Zone physical type (E=Wired zone, W=Wireless zone, B=Bus zone, I=Input zone)
Y: The expander ID number. “0” represent the main bus, for example:
E0:04 refers to wired zone 04 on the main board.
B0:15 refers to BUS zone 15 on the main BUS.
ZZ The serial zone number in the system (01-32)
4. Set the zones parameters as follows:
•Labels: Zone description text to give it a meaningful name. Use the numeric keys as
described in section “Keys Menu Navigation” (see page 11)
•Partitions: Using the numeric keys, select or deselect the relevant partitions to which
this zone will belong to and using the
partition groups. To confirm press
, , or , keys, select the
.
• Zone Type: Using the Up/Down keys, select the required zone type and press
• Zone Sound: Select the required zone sound while the system is armed in Away,
Armed at Stay or Disarmed.
Note:
This determines if the zone will ‘be silent’, ’cause bell to activate’, ‘cause buzzer to
activate’, ‘cause bell and buzzer to activate’, ‘create keypad bleep for chime’ etc…
when the zone is opened/causes an alarm condition.
‘Buzzer’ refers to the sound emitted from the keypad(s).
•Zone Termination (Only applicable for hard-wired zones). Using the Up/Down keys,
select the required zone termination type (NO, NC, EOL, DEOL) and press
•Zone Response: Using the Up/Down keys, select the required response time and press
.
•Advanced: Includes advanced attributes for a zone such as supervision for wireless
zones, bus zone parameters, forced arming and more. .
.
.
Wireless Zones
Each of the 32 zones in the LightSYS can be defined as a wireless zone.
Step 1: Allocate a Wireless expander
1. From the Installer menu, select (Install, Bus Device, Manual,
WL Expander)
2. Set the receiver ID (1 or 2) and using , set the type to WM and press .
3. If the receiver is mounted inside the LightSYS box select Y to bypass the box tamper. Press
and move to step 2.
Step 2: Calibrate the Receiver
For successful communication, strength of the signal should be higher than the noise threshold level,
measured in a process termed calibration.
1. From the Installer menu, select (Install, WL Device, RX Calibration)
2. Select the wireless expander and press .
14 LightSYS Quick In staller Guide
3.Using the key, choose [Y] (Yes) to ‘Re-Calibrate’ the Wireless expander and press
Wireless Device
Sending Write Message
Detector/Contact/Siren
Press and hold the tamper switch for 3 seconds.
within 10 seconds.
Gas, CO detectors
Press and hold the test button for 3 seconds.
seconds.
to confirm.
Explanation:
The calibration measurement above shows the amount of background ‘noise’ that the receiver can
‘hear’ on the same frequency as the RISCO wireless devices. This ‘noise’ could be neighboring
devices of another system or other devices operating on the same frequency nearby. These are
‘unwanted’ signals that the LightSYS wireless expander must be told ‘not to listen to’.
The threshold (set above) is the absolute minimum signal strength needed to be heard from a
wireless device in order for the receiver to effectively ‘hear it’.
Step 3: Allocating Wireless Zones
Each wireless device must identify itself to the system receiver, in a process termed “enrollment”.
Enrollment can be performed by sending an RF signal from each device, or by entering the device’s
unique serial code into the system. Enrollment can be done locally using the keypad or remotely
using the configuration software. The following steps describe quick enrollment by RF signal using a
keypad.
1. From the Installer menu, select (Install, Wireless Devices, Allocate, By RF)
2. Using the numeric keys, enter the desired zone number and press
3. The WL Receiver is in learn mode. Send a write message from your wireless zone as
shown in the table below:
Smoke Detector Insert battery. Write message is sent automatically
Key fobs (see page Error!
Bookmark not defined. )
2-Way: Depress both buttons (
seconds.
and ) for at least 7
1-Way: Depress the button () for at least 7 seconds.
2-Way Slim Keypad
Press and hold both buttons (
and ) for at least 7
4. Repeat steps 2 to 3 until all required wireless zones have been enrolled.
5. Continue entering the wireless zones attributes section.(see page 13)
Bus Detectors
The following section describes the flow of adding bus detectors to the LightSYS. Bus detectors can
be programmed to the main unit or to a bus zone expander.
1. Programming bus detectors on the main bus
Step 1: Adding Bus Detector to the Main Unit
Note:
If you have already performed Auto Settings, skip to Step 2 below: Assign Bus Detectors to a
Zone ID and set basic parameters.
LightSYS Quick Install er Guide 15
1. From the main installer menu press to access the bus Zone category.
2. Press to move the cursor to the ID field.
3. Type the bus detector ID number as set by the detector's DIP switches (01-32)
Note:
The display "(x:yy) Type: None" represent the BUS detector location in the system. In the
0:yy designation, the 0 denotes that the bus detector is on the main unit and is not
assigned to a bus zone expander. The yy represents the bus detector ID number (up to
32) as set by the detector's DIP switches.
4. Using the arrow keys move to the Type field. Use the key to select the detector's
type.
5. Repeat steps 2 - 4 for other bus detectors.
Step 2: Set Bus Zone Basic Attributes
Refer to section Programming Zones Attributes to define the zone parameters. (see page 13)
Step 3: Programming the Bus Detectors Advanced Parameters
1.From the main Installer menu select [2] Zones > [1] Parameters > [ 2] By Category > [7]
Advanced > [4] BZ Parameters .
2. Select the zone number that the bus zone was assigned to and press
.
3. Configure the parameters for the relevant bus detector.
2. Programming Bus Detectors on a Bus Expander
Using bus expanders you can create a separate bus loop that is used only for the bus
detectors connected to it. The separate bus loop increases the total system security in case a
certain bus detector is sabotaged. Up to four bus expanders can be added to the LightSYS
Step 1: Adding the Bus Expander to LightSYS
Note:
If you already performed Auto Settings skip to Step 2 below: Assign Bus Detectors to a Zone ID
and set basic parameters.
1. From the main installer menu press to enter the Bus Expander menu.
2. Using the arrow and numeric keys select a bus zone expander ID.
3. Using the arrow keys move to TYPE. Use the key to select a BZE32 and press
.
Step 2: Adding Bus Detector
Refer to section Step 1: Adding Bus Detector to the Main Unit to assign a bus detector to the
system.
Note
When the bus zone is connected to a BUS expander, you should define the X in the (x:yy)
display as the BUS expander ID (1,2,3 or 4). The yy represents the bus detector ID number
(up to 32) as set by the detector's DIP switches.
16 LightSYS Quick In staller Guide
Step 3: Set Bus Zone Basic Attributes
Refer to section Programming Zones Attributes to define the zone parameters.
Note:
In the zone designation XY:ZZ the X represent the Bus Expander ID as set by its dip
switches.
Step 4: Programming the Bus Detectors Advanced Parameters
1.From the main Installer menu select [2] Zones > [1] Parameters > [2] By Category >
[7] Advanced > [4] BZ Parameters .
2. Select the zone number that the bus zone was assigned to and press
3. Configure the parameters for the relevant bus detector.
.
Communication Method
1. From the main installer programming menu: 5) Communication menu > 1) Method.
2. Select each method (PSTN, IP and/or GSM) and define its parameters.
Note:
1. LightSYS’s menus include only those communication modules installed on-board
2. To establish GPRS communication set up the APN (Access Point Name) and Email
according to the details instructed by the cellular provider.
3. For IP communication set to dynamic IP (Quick key )
Report to Monitoring Station
You can define up to three MS accounts and several associated parameters that define the nature of
communication, event reporting and confirmation between the system and the MS.
1. From the main installer programming menu select 5) Communication menu and select 2) MS.
2. Select the 1) Report type (Voice, SMS, IP/GPRS) for each MS and define its parameters.
3. Select 2) Account number and define an account number for each MS.
4. Select 3) Comm format to define the transmission format, SIA or Contact ID.
5. Go through the menus to program any other parameters for the communication with the
monitoring station.
Follow Me Destinations
Now that you have set up the methods for LightSYS to communicate with the MS and the owner,
you can define the destinations to which event notifications will be sent. Up to 16 follow me
destinations can be defined in the system.
1. From the main installer programming menu: 5) Communicati on menu > 4) Follow Me.
2. Under 1) Define FM set each destination’s:
Or
1. From your riscocloud log-in (p 21), click: SETTINGS >
2. Enter recipient Name, choose the Alert Language and then the following:
Alerts > ADD NEW
• Report Type (Voice (panel only), SMS, Email,)
• Partitions: Specify the partitions that will initiate the Follow Me report due to a certain
event that occurred in the assigned partitions
• The events that will be sent, organized by category (possibly including Alarms,
• The operations the user will be able to perform through remote connection via phone,
SMS or the Cloud
Note:
The actual destinations (telephone numbers, email addresses) are not defined within the
Programming menu.
General Settings
There are several system-wide parameters that define how the LightSYS works. All these
parameters are set with default values that apply for most installations. If you wish to modify the
default settings, go through the menus to program any other system parameter.
1. Main System Timers
1. From the main installer programming menu select 1) System 1)Timers
2. Select options 01 and 02 to define exit entry times.
3. Select option 03 to define siren duration time.
4. Scroll through the other options of the menu.
2. Set Up Users
As the installer, you must set up the system’s users. The owner (Grand Master) will be allowed to
subsequently set their code.
1. From the main installer programming menu select 4) Codes.
2. Under the 1) User option define for each user its authority level and the partitions it can
control with his code.
3. Change the default installer code under the option 3) Ins taller.
Keyfobs and 2-Way Slim Keypads
Each keyfob and keypad can be set up to perform different system functions and control different
utility outputs. Up to eight keyfobs (1-way and 2-way) and four 2-way keypads can be enrolled in
the system. The programming options vary according to whether the device is 1-way or 2-way.
Each user can be assigned with a single keyfob.
Step 1: Allocating Keyfobs and Slim Keypads
• Allocate and calibrate the devices as described in Wireless Zones section (page 14)
Step 2: Setting Keyfob Options [for both 1-way and 2-way keyfobs]
a. From the installer (Programming) menu, select 8) Devices > 2) Keyfob > 1) Select
User
b. Select the user that the keyfob belongs to. and then press
c. Use the arrow keys to scroll between menus and the
options for the 1-way and 2-way keyfobs:
.
key to select menu
Options for the 1-Way Keyfob:
For each button (1-4), define its function, from the available options (see table below for
a description of options). Use the respective “Quick key” to designate an option for each
button:
18 LightSYS Quick In staller Guide
•Button 1 options (): None, Arm. Stay, Group, UO
Description of 1-Way Keyfob Options
Quick Key
Option
Description
None
Button disabled
Arm
The button is used for away (full) arming of the assigned
partitions
Disarm
The button is used for disarming its assigned partitions
Stay
The button is used for stay (home) arming of the assigned
partitions
The button is used for Group arming (Partial arming
UO
The button is used to operate a single utility output
Panic
The button is used to send a panic alarm
Description of 2-Way Keyfob Options
Quick Key
Option
Description
Serial No
The identifying 11-digit number of the keypad (display only)
within a partition / area) of the assigned partitions
Options for the 2-Way Keyfob:
• Serial Num: displays the serial number
• Masking: enables user / keyfob authorization granularity per partition
• Controls : enables panic alarm
• Code: set the PIN Code for high security mode as per system or keyfob flag settings
• UO Key (1/2/3): normally “disabled”
Masking: Specifies the partitions that are controlled by the specified keypad.
Panic Enable: Disable/enable the issue panic alarm button
UO Key 1: The button is used to operate a single utility output
UO Key 2: The button is used to operate a single utility output
UO Key 3: The button is used to operate a single utility output
Step3: Setting Slim Keypad Options
From the installer (Programming) menu, select 8) Devices > 1) Keypad > keypad 1, 2,
or 3)
a. Select the user that the slim keypad belongs to, and then press
b. Use the arrow keys to scroll between menus and the
options:
LightSYS Quick Install er Guide 19
key to select menu
.
Available Options per Keypad Type:
Wired keypad :
• Label: provide a meaningful name (see page xx for details)
• Partition assignment: (in most cases this is left as 1)
• Masking : enables user / keypad authorization granularity per partition
• Controls: enables emergency, multi-view
Slim 2-way Wireless keypad:
• Label: provide a meaningful name (see page xx for details)
• Partition assignment: (in most cases this is left as 1)
• Masking : enables user / keypad authorization granularity per partition
• Controls: enables emergency, exit beeps
• Serial Number
• Function Key > panic , MS Listen-talk, Disable
• UO 1 – 3
1-Way Wireless keypad :
• Label: provide a meaningful name (see page xx for details)
• Partition assignment: (in most cases this is left as 1)
• Masking : enables user / keypad authorization granularity per partition
• Controls: enables emergency
• Serial Number
Exiting Programming Mode
1. Set SW1 – 2 (Default) to OFF position.
2. Close the main box in order to prevent Front Tamper Alarm.
3. Press [*] repeatedly to return to ‘Main Menu’.
4. Press > to Exit and SAVE your settings.
Note:
The system will not allow exit from the Installer mode if a ‘Tamper’ or ‘System Fault’
condition exists. Correct any tamper and/or system fault conditions before attempting to exit
the Installer mode.
20 LightSYS Quick In staller Guide
Connecting the LightSYS2 to the Cloud
Application Options and Connectivity Capabilities
System Configuration
Voice Event
Control
Configuration
Cloud
Comm.
Y
Y
–
Y
Y
Y
– Y
GPRS
GSM/GPRS + PSTN
Y Y –
Y
Y
Y –Y
GPRS
Y
Y
Y
Y
Y
Y YY
IP
GPRS + IP +PSTN
Y
Y
–
–
Y
Y YY
IP
IP +PSTN
LightSYS2 enjoys seamless Configuration Software connectivity and can be configured to be
constantly connected to a server, enabling user Smartphone applications. When connected to the
server, the server handles all communication between the system, service providers and web users,
enabling monitoring and control to be performed via the Web. The following table summarizes the
LightSYS 2 communication and cloud connection capabilities as per installed communication
modules:
Module
Connect
via
Cloud
Software vi a
SynopSYS
IP Receiver &
MS Reporting
App
Smartphone
SMS
Control
Messages
SMS Event
Messages &
To enable cloud communication:
From the Installer menu select: 1) System > 2) Controls > 3) Communication > 4) Cloud
Enable [Y]
Or
In the Configuration Software interface: Click System > Communication Control tab > Cloud enable checkbox
To establish IP network connection to the server using the IP or GSM/GPRS module:
From the Installer menu select: 5) Communication > 5) Cloud
Or
Select the Cloud Node and specify:
1) IP Address: The server IP address (riscocloud.com or that of your organization's server)
2) IP Port: The server port is set to 33000.
3)Password — The password for server access as provided by your provider (if required). This
password MUST be identical to the Password defined in the Cloudserver. If Self-Registration
is to be performed, do not change from the default.
4) Channel: Select IP Only or GSM Only depending on the communication module in the
LightSYS. If GSM selected, APN Name must be entered in the GSM/GPRS menu.
Email
Events
Note:
When in Cloud mode, the settings defined through it are applied to all reporting channels
(including MS communication and FM destination). If the cloud connection is lost/terminated
and the LightSYS reverts to Back up mode, then the direct channel communication settings
become active..
LightSYS Quick Install er Guide 21
[For Configurtion Software connection] To configure the CS settings:
In the Connection Settings node > Cloud area, specify:
1. IP Address: (as per above)
2. Port: (set to 34000)
3. CPID: System panel ID
User Definitions and System Operation
1. Instruct the user to define the actual user codes. Advise the user to change the default Grand
Master code. Help the user enroll proximity tags.
2. Instruct the user on defining and editing the Follow Me destinations.
3. For Cloud mode connections, instruct users with smartphones to download the iRISCO App
from the Apple App store or Android Play Store. Ensure that the connection between the
App and the LightSYS is established.
4. Instruct the user on the following operations, performed from the keypad, keyfobs,
smartphone or Cloud application:
• Away (Full) Arm Stay (Home) Arm Disarm
• Disarm under duress Send a panic event Check the system status
• Check the system status Operate a utility output
• Use the voice menu for remote operation Use SMS for remote operation
Testing the system
Before leaving the site, it is important to fully test the system. LightSYS has several testing tools that
help you feel confident the system will operate optimally, including relieving any concerns you may
have about the wireless communication.
From the Installer menu, go through the tests under the 2) Testing menu:
• Main Unit noise level, buzzer, speaker and battery.
• You can test each device for communication and perform a battery test.
• For zones you can perform a Walk Test – during which you should receive a “TRIP”
from each detector, (User Menu > Maintenance > Walk test).
• GSM signal strength.
• Perform a test to ensure follow me is working (User Menu > Follow Me > Test FM).
The system is now programmed and ready for use.
For more comprehensive and detailed instructions, please refer to the LightSYS 2 Installation and Programming Manual (5IN2048).
For user functions, please refer to the LightSYS 2 User Manual (5IN2052).
22 LightSYS Quick In staller Guide
Technical Specifications
Main
Technical Information
Input Power:
AC/DC Adaptor 100-240V 50/60Hz 14.4V—1.5A or 4A PS
Current Consumption:
60 mA, typical / 70 mA, maximum
Rechargeable Standby Battery:
1.5A PS: 12 Volts up to 7 Amp-Hours (AH), typical
4A PS: 12 Volts up to 17 Amp-Hours (AH), typical
Power Outputs:
Auxiliary Power:
UO2-UO4: 100 mA, opto relay
Main Box Dimensions
RP432B Polycarbonate (1.5A PS): 290 x 254 x 97 mm
RP432BM1 Metal, large (4A or 1.5A PS): 420 x 379 x 95 mm
Operating temperature
-10°C to 55°C (14°F to 131°F)
Storage temperature
-20°C to 60°C (-4°F to 140°F)
Expanders
Technical Information
LCD Keypad (RP432KP)
13.8V +/-10%, 48 mA typical/52 mA max
Proximity LCD Keypad (RP432KPP)
13.8V +/-10%, 62 mA typical/75 mA max
LCD Keypad ( RP128KP)
13.8VDC +/-10%; 100 mA maximum
Proximity Keypad (RP128KPP)
13.8VDC +/-10%; 280 mA maximum
Touchscreen Keypad (RP128KP01)
13.8VDC +/-10%; 30 mA typical / 180 mA max
Touchscreen Keypad with
Proximity (RP128KPP1)
13.8VDC +/-10%; 30 mA typical / 280 mA max
8 zone expansion module
13.8VDC +/-10%; 25 mA, typical / 30 mA, maximum
Bus Zone Expansion
Wireless Expansion module
13.8VDC +/-10%; 65mA maximum
4 Form C (SPDT) Relays.; 5 A / 24V DC
8 transistor output expansion
13.8VDC +/-10%; 25 mA typical / 40 mA maximum
Proximity Key Reader
13.8VDC +/-10%; 70 mA, typical / 180 mA max
Digital Voice Module
13.8VDC +/-10%; 30 mA typical / 70 mA maximum
Plug In GSM/GPRS Module:
During Communication - 300mA ; During Standby - 30mA
1.5A PS: Total current 800mA; Maximum Aux = 500mA;
Maximum BUS (AUX RED) = 800mA
4A PS: Total current 1500mA; Maximum Aux = 500mA;
Maximum BUS (AUX RED) = 1000mA
4 relay output expansion module 13.8VDC +/-10%; 25 mA typical / 160 mA maximum
module
LightSYS Quick Install er Guide 23
Open Collector, Active Pull-Down, 70 mA maximum
90
maximum
Notes
24 LightSYS Quick In staller Guide
Notes
LightSYS Quick Install er Guide 25
Notes
26 LightSYS Quick In staller Guide
CE Declaration of Conformity
Hereby, RISCO Group declares that this LightSYS control panel, with wired accessories (including cables)
and wireless accessories, is in compliance with the essential requirements and other relevant provisions of
Directive 1999/5/EC.
For the CE Declaration of Conformity please refer to our website: www.riscogroup.com.
RISCO Group Limited Warranty
RISCO Ltd. ,its subsidiaries and affiliates (the "Seller") warrants its products to be free from defects
in materials and workmanship under normal use for 24 months from the date of production.
Because the Seller does not install or connect the product, and because the product may be used in
conjunction with products not manufactured by the Seller, the Seller cannot guarantee the
performance of the security system which uses this product.
The Seller's obligation and liability under this warranty is expressly limited to repairing and
replacing, at the Seller's discretion, within a reasonable time after the date of delivery, any product
not meeting these specifications.
The Seller makes no other warranty, expressed or implied, and makes no warranty of merchantability
or of fitness for any particular purpose.
Under no circumstances should the Seller be liable for any consequential or incidental damages for
breach of this or any other warranty, expressed or implied, or upon any other basis of liability
whatsoever.
The Seller's obligation under this warranty shall not include any transportation charges or costs of
installation or any liability for direct, indirect, or consequential damages or delay.
The Seller does not warrant that the product may not be compromised or circumvented; that the
product will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or
that the product will in all cases provide adequate warning or protection.
The buyer/customer understands that a correctly installed and maintained alarm may only reduce
the risk of burglary, robbery or fire without warning, but is not an insurance or a guarantee that such
an event will not occur or that there will be no personal injury or property loss as a result thereof.
Consequently the Seller shall have no liability for any personal injury, property damage or loss based
on a claim that the product fails to give warning.
However, if the Seller is held liable, whether directly or indirectly, for any loss or damage arising
under this limited warranty or otherwise, regardless of cause or origin, the Seller's maximum liability
shall not exceed the purchase price of the product, which shall be a complete and exclusive remedy
for the Seller.
No employee or representative of the Seller is authorized to change this warranty in any way or grant
any other warranty.
Batteries installed in or used with the products are explicitly excluded from this or any other
warranty. Seller gives no warranty whatsoever as to batteries and buyer's only remedy (if any) shall
be in accordance with the warranty provided (if and to the extent provided) by the manufacturers of
batteries.
LightSYS Quick Install er Guide 27
United Kingdom
Tel: +44
support
USA
China (Shanghai)
Italy
Tel: +39
support
Brazil
China (Shenzhen)
Spain
Tel: +34
support
France
Israel
Poland
Tel: +48
support
Belgium
Australia
Contacting RISCO Group
RISCO Group is committed to customer service and product support. You can contact us through our
website www.riscogroup.com or as follows:
-(0)-161-655-5500
-uk@riscogroup.com
-02-66590054
-it@riscogroup.com
-91-490-2133
-es@riscogroup.com
-22-500-28-40
-pl@riscogroup.com
RISCO product was purchased from
Tel: +1-631-719-4400
support-usa@riscogroup.com
Tel: +55-11-3661-8767
support-br@riscogroup.com
Tel: +33-164-73-28-50
support-fr@riscogroup.com
Tel: +32-2522-7622
support-be@riscogroup.com
Tel: +86-21-52-39-0066
support-cn@riscogroup.com
Tel: +86-755-82789285
support-cn@riscogroup.com
Tel: +972-3-963-7777
support@riscogroup.com
Tel: +1-800-991-542
support-au@riscogroup.com
All rights reserved.
RISCO Group reserves the right to amend the software and features without prior notice.
No part of this document may be reproduced in any form without prior written permission from the
publisher.