Thank you for purchasing the LightSYS™ 2 hybrid security system, offering Smartphone App
control and communication flexibility as well as a choice of wired, 2-way wireless, or RISCO Bus
detectors. This simple setup procedure guide covers all common LightSYS installation and
programming steps (based on factory default settings) required in order to set up a working system.
For more comprehensive instructions, refer to the LightSYS2 Installation and Programming Manual (5IN2048).
Selecting Mounting Location
Decide where to position your LightSYS control panel. A central location is often the best place,
making wiring to expanders and accessories easier. It is advisable to prepare a plan of
expander/accessory physical locations in advance of the installation, as this will determine which
type of expander is required at each location.
The control panel location should:
• Be in a dry place near an AC power supply
• Have access to the routing of cables for the system from detection devices
• Have access to the customer’s phone lines/IP network
• (In case you installed GSM / GPRS module before mounting the system into the desired
position)
Ensure a good signal of the GSM network (Advisable to have a level of at least 4 out of 5).
Installing Hardware
Main Unit — BUS Connection
The set of four terminals on the left of the terminal block represent the expansion bus. These
terminals support the connection of keypads and expansion modules. The connections are terminalto-terminal with color-coded wires, as follows:
Connect any/all keypads and expanders/accessories necessary for the installation using the bus
connections.
LightSYS Quick Install er Guide 5
ID
DIP switches
ID
DIP switches
1 2 3 4 5 1 2 3 4 5
01
OFF
OFF
OFF
OFF
OFF 17
OFF
OFF
OFF
OFF
ON
02
ON
OFF
OFF
OFF
OFF 18
ON
OFF
OFF
OFF
ON
03
OFF
ON
OFF
OFF
OFF 19
OFF
ON
OFF
OFF
ON
04
ON
ON
OFF
OFF
OFF 20
ON
ON
OFF
OFF
ON
05
OFF
OFF
ON
OFF
OFF 21
OFF
OFF
ON
OFF
ON
06
ON
OFF
ON
OFF
OFF 22
ON
OFF
ON
OFF
ON
07
OFF
ON
ON
OFF
OFF 23
OFF
ON
ON
OFF
ON
08
ON
ON
ON
OFF
OFF 24
ON
ON
ON
OFF
ON
09
OFF
OFF
OFF
ON
OFF 25
OFF
OFF
OFF
ON
ON
10
ON
OFF
OFF
ON
OFF 26
ON
OFF
OFF
ON
ON
11
OFF
ON
OFF
ON
OFF 27
OFF
ON
OFF
ON
ON
12
ON
ON
OFF
ON
OFF 28
ON
ON
OFF
ON
ON
13
OFF
OFF
ON
ON
OFF 29
OFF
OFF
ON
ON
ON
14
ON
OFF
ON
ON
OFF 30
ON
OFF
ON
ON
ON
15
OFF
ON
ON
ON
OFF 31
OFF
ON
ON
ON
ON
16
ON
ON
ON
ON
OFF 32
ON
ON
ON
ON
ON
Notes:
1. The parallel wiring system supports parallel connections from any point along the wiring.
2. The maximum wire run permitted is 300 meters (1000 feet) for all legs of the bus.
3. In case of bus communication problems, connect two 2.2KΩ resistors, one at each end of the data
bus terminals, between the green and yellow wires.
4. If connecting remote power supplies, do NOT connect the Red wire (+12v) between the Power
Supply Unit and LightSYS.
5. For long cable runs, please use the correct cable as stated in the Installation Manual, Wiring appendix.
1. Setting Bus Accessory ID Numbers
For most devices, a DIP switch number must be set to identify its ID category number.
Devices are split into ‘Families’. Each ‘Family’ of devices has sequential identification numbers
which are set by the DIP switches. Before setting power on, define each module’s ID number by
setting the dipswitches as follows:
Notes:
• Most accessories have four DIP switches, while bus detectors have five DIP switches
• IDs 9–32 are only available for bus detectors.
• If a DIP switch is changed on any device, it is necessary to shut down the device’s power and
then re-power it.
The first module in each category is defined as ID= 1.
Families that have sequential ID numbers are:
• Keypads (LCD, LCD with proximity and wireless keypad (both 1- and 2-way)
• Zone Expanders (8 zones expander, bus zone expander)
on 4A power supply, 2 relay output expander on Wireless zone expander, X-10 Outputs,
again, both 1-and 2-way)
• Power Supplies (4A switching mode power supply)
• Bus Zones
• WL Zone Expanders
6 LightSYS Quick Install er Guide
Notes:
Total
Wired / BUS Expanders
3
BUS Zones
32
WL Zone Expanders
2
BUS Zones Expanders
4
Outputs Expanders
4
Keypads
4
1.5A or 3A Power Supply
4
BUS Sirens (ProSound / Lumin8)
4
ENDOFLINEZONE
(N.O CONTACT)
zonecom
ALARM
2.2
K
DETECTOR
NORMALLY OPEN ZONE
CONFIGURATION
ALARM
zone
com
DETECTOR
NORMALLY CLOSED
ZONE CONFIGURATION
ALARM
zone
com
DETECTOR
END OF LINE ZONE
(N.C CONTACT)
2.2
K
zonecom
ALARM
DETECTOR
DOUBLEENDOFLINE
ZONECONFIGURATION
com
2.2
K
ALARMTAMPER
zone
2.2
K
DETECTOR
1. The main unit can support a maximum load of 1.4 Amp. If more current is required install
additional power supply modules (3 Amp max.).
2. On 3 AMP supervised power supplies and on the wireless expander, there are two
programmable outputs. These programmable outputs belong to the ‘Output’ family. These
outputs have dedicated DIP switches that identify the OUTPUT ID.
Maximum number of devices possible:
2. Zone Inputs Connection
The following diagrams illustrate the various possible zone connections to the main unit or to
the 8 wired zones expander.
Notes:
1. For a zone with a tamper switch, you can use a double end-of-line resistor to save additional main
panel connections.
2. It is recommended that you use an end-of-line resistor at the far end of each hardwired zone (16 x
2.2K resistors are supplied).
3. In the LightSYS you have the ability to define separately the end-of-line resistance of the zones on
the main unit and of the wired zones for each eight-unit expander block (Quick key ).
Selection is done by the software with the following available options:
Use the Auxiliary PowerAUX (+) COM (-) terminals to power PIRs, glass-break detectors (4-wire
types), smoke detectors, audio switches, photoelectric systems and/or any device that requires a 12V
DC power supply.
4ANote:
If the auxiliary outputs are overloaded (exceed 800/1500mA) and are shut down, you must
disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any
load to the auxiliary outputs.
4. Wiring Internal Bell
The Bell/LS terminal provides power to the internal siren. When connecting an internal sounding
device, pay attention to the polarity.
It is important to position the BELL/LS Dip Switch SW1 correctly. The position varies depending on
the type of internal siren.
Note:
To avoid bell loop trouble, if no connections are made to an internal siren, use a 2.2KΩ resistor in its
place.
5. Wiring Bell Tamper
Connect the bell tamper to the BELL TMP and COM terminals on
the main panel using 2.2KΩ resistors in serial.
8 LightSYS Quick Install er Guide
Important:
DIP Switch SW1
Status
1: Bell
ON: Bell: For bell or electronic siren with a built-in siren driver.
OFF (Default): For loudspeaker without a built-in sound driver.
2: Default
ON: Resets installer, sub-installer and grand master codes to their
OFF (Default): Codes preserve their set values.
3: Extern - Back
ON: Back tamper bypass is in effect. Use this setting during
OFF (Default): No tamper bypass is in effect
4: Intern –
Bypass
ON: Front tamper bypass is in effect. Use this setting when the
OFF (Default): No tamper bypass is in effect
If you DO NOT use the terminal TMP BELL, remember to connect a 2.2KΩ
resistor (Resistor colors: Red, Red, Red) between TMP and COM.
6. Wiring Utility Output 1 to Activate Self-Power Devices
Utility output 1 can be used to activate a self-powered siren or any other self-powered device.
7. Main Unit DIP Switch settings
default factory values and bypasses main unit front tamper alarm.
Tamper Bypass
Front Tamper
programming and if no back tamper has been connected to PLUG 2.
LightSYS is installed inside the metal enclosure RP432BM1.
Connecting BUS Detectors
Up to 32 addressable bus detectors can be assigned to the LightSYS. Bus detectors can be wired to
the main bus or to a Bus Zone Expander (BZE).
For full installation instructions refer to the instructions supplied with each bus detector.
Connecting BUS Detectors to the Main LightSYS BUS:
1. Set the bus detector ID number (1-32) using the detector's DIP switches.
Note:
For WatchOUT, LuNAR, WatchIN, BWare and Seismic set the switch that defines the
LightSYS Quick Install er Guide 9
detector operation mode to bus mode.
2. Wire the bus terminals AUX(RED), COM (BLK), BUS (YEL) and BUS (GRN) to the
LightSYS Bus.
Note:
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.