REMKO PGT Series, PGT 30, PGT 100, PGT 60 Operation,technology,spare Parts

REMKO PGT
Propane gas heaters
Operation · Technology · Spare parts
Edition GB – D05
Contents
Safety notes 4
Unit description 4
Installation instructions 5
Gas connection 6
Commissioning 8
Shutdown 10
Care and maintenance 10
Troubleshooting 12
Intended use 13
Customer service and guarantee 13
Environmental protection and recycling 13
Electrical wiring diagram PGT 30/60 14
Electrical wiring diagram PGT 100 15
Exploded view of PGT 30 16
Spare parts list for PGT 30 17
Exploded view of PGT 60 18
Spare parts list for PGT 60 19
Exploded view of PGT 100 20
Spare parts list for PGT 100 21
Maintenance protocol 22
Technical data 23
Carefully read this operating manual prior to commissioning / using the unit!
This operating manual is a translation of the German original. These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO PGT
Safety notes
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations when using the units.
The units have been subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can arise from the units if they are used improperly or not as intended by untrained personnel! Please observe the following information:
The units may only be operated
by persons that have been instructed in their operation
The power plug must be pulled
out of the mains socket before maintenance and repair work
■ The units must be installed such
that they are stable on a non­combustible surface
■ It is necessary to ensure that no
flammable objects or materials can be drawn in
The units must be installed and
operated in such a way that personnel are not endangered by exhaust gases and radiant heat and no fires may occur
■ Portable liquid gas tanks must
be installed such that they are stable and upright
■ Liquid gas tanks must never
be used whilst lying horizontal during unit operation
■ All unit electrical cables must be
protected against damage, e.g. by animals
The units must then only
be operated in areas where the units can be supplied with an adequate amount of air for combustion
■ The units must only be operated
in well-ventilated spaces and away from flammable materials. Personnel must not remain in the installation area
Appropriate prohibition signs should be put up at the entrances!
A safety zone of 1.5 m must be
maintained around the units, incl. to non-combustible items
■ A minimum distance of 3 m must
be maintained from the unit outlet
■ The unit outlet must not
be restricted or fitted with hoses or pipes
■ Never insert foreign objects
in the unit
■ The air intake grille must always
be kept free of dirt and loose objects
■ The units must not be exposed
to direct jets of water e.g. pressure washers, etc.
CAUTION
The units must not be used for heating living spaces in residential buildings.
Unit description
The units are mobile fan-assisted air heaters (WLE) directly fired with liquid gas, without a heat exchanger. The units operate without an exhaust gas connection and are designed exclusively for commercial use. The units are equipped with integrated power regulation for the stepless control of the heating capacity, quiet and low-maintenance axial fans, robust gas burners with thermal flame monitoring, electric solenoid valves, electric ignition, room thermostat socket and mains cable with earthed safety plug.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations and are simple to operate.
The units are EC type-tested, DVGW-registered and approved for EU countries.
The units may be used among other things for the following:
Drying newly completed
buildings
Spot heating of outdoor
workplaces
Spot heating workplaces
in open, non-flammable manufacturing facilities and halls
Temporarily heating enclosed
spaces with a sufficient fresh air supply
De-icing machines, vehicles and
non-combustible warehoused goods
Maintaining the temperature
of frost-sensitive parts
4
Installation instructions
Operating sequence
Moving the operating switch to the “I” position puts the supply air fan into operation and the program sequence for the automatic burner is started.
After a few seconds, the electric solenoid valve opens the gas supply to the burner. The liquid gas is transported through a nozzle under pressure into the mixing tube. Here, the gas is enriched with a quantity of oxygen aligned with the unit output.
The gas/air mixture is ignited at the burner head by an electric ignition spark. Ignition is automatically ended as soon as a flawless flame burns, and the automatic burner has taken over the flame monitoring.
Regulation of the min/max heating capacity can be implemented on a stepless basis during unit operation on the integrated “power regulation”.
Monitoring the units
It is possible to safely monitor all functions with the safety devices of the units. In the event of irregularities or if the flame is extinguished, the units are switched off and interlocked.
Safety temperature limiter (STB)
The units are equipped with a safety temperature limiter (STB), which interrupts the gas supply in case of overheating and electrically interlocks the unit.
A manual reset of the STB can only be implemented after the units have cooled down.
CAUTION
If the safety temperature limiter has been tripped then the cause of the malfunction should be identified and rectified before resetting it.
The STB is reset by actuating the reset key 2.
1. Unscrew the protective cap 1.
2
1
2. Push in key 2.
3. Screw the protective cap 1 back on again.
Automatic burner
In the event of irregularities or if the flame is extinguished, the automatic burner switches off and interlocks the units.
The unit's fault lamp will light up in this case.
The automatic burner is unlocked by pressing the malfunction button.
The automatic burner can be unlocked after a waiting time of approx. 60 sec.
NOTE
Before resetting safety equipment, the cause of the malfunction must be identified and rectified.
The safety regulations of the accident prevention and insurance associations, the respective regional building regulations and the combustion appliances regulations apply to operation of the unit. For example, for Germany:
■ Combustion plant order (FeuVo)
for the individual federal states
■ Accident prevention regulations
(UVV) "Heating, flaming and melting devices for construction and installation work" (VBG 43)
■ Accident prevention regulations
(UVV) “Use of liquid gas” (BGV D34)
■ Workplace directives ASR 5
■ Workplace regulations §§ 5 and 14
Outdoor installation
The operation of the units
must not present a hazard or unreasonable loading
The unit operator must
ensure that it is not possible for unauthorised persons to manipulate either the unit or the power supply
To prevent damage due
to inclement weather, units installed outdoors must be adequately protected
Installation in enclosed, well­ventilated rooms
The units are designed without
an exhaust gas connection according to type, and can only be used in enclosed rooms on a conditional basis
Reliable extraction
of the combustion gases must be guaranteed in all cases in order to exclude impermissible contamination of the room air with hazardous substances
s
s
s
5
REMKO PGT
s
s
s
Gas connection
The fresh air supply required
for trouble-free combustion must be ensured. It is practical to have the fresh air supply provided by windows and doors or through appropriately dimensioned openings in the outside wall
The units must not operate
continuously whilst unattended
The units may only be operated in rooms if:
■ a sufficient quantity
ofair is supplied to the units for the combustion
■ these are well ventilated and
aerated
■ the proportion of substances
harmful to health in the breathing air is at a harmless level
The gas connection / unit operation must take place exclusively on the basis of the accident prevention regulation BGV D34, as well as the respective local construction and fire prevention regulations.
The units are operated with liquid gas in accordance with DIN 51622. They require a constant connection pressure of 1.5 bar. It is prohibited to exceed or undershoot the connection pressure.
CAUTION
A constant unit connection pressure of 1.5 bar (1500 mbar) must be guaranteed, also in continuous operation.
■ When using longer hose lines,
consider the respective pressure loss
unit
■ The use of longer hose lines
is permissible if:
- special operational reasons exist
- appropriate additional safety measures are observed and the hose lengths are kept as short as possible
Hose lines must be
fundamentally protected against chemical, thermal and mechanical damage
The units may only be operated
out of the gas phase
The units must be serviced
by qualified persons only
Only original spare parts may
be used for repairs
Unit parts that are prone
to wear and ageing (e.g. gas hoses) must be replaced at regular intervals
There is good natural ventilation and aeration if:
1.
the room volume in m3 is at least 30 times the nominal heating capacity kW of all of the units operating in the space, and if the natural change of air is guaranteed by windows and doors or
2. constantly open ventilation openings are present for incoming and exhaust air in the vicinity of the ceiling and floor, whose size in m2 is at least
0.003 times the nominal heating capacity in kW of all of the units operating in the space.
CAUTION
The units must only be
installed in well ventilated
spaces and not in living areas
or similar recreational areas.
Only use components that have
been tested and are suitable for the respective purpose, such as gas hose, pressure controller and hose breakage protection or leak gas protection
■ If possible, the length of the gas
hose should not exceed 2 m
Only pressure controllers with
a fixed outlet pressure setting are permitted. The units may only be operated out of the gas phase
CAUTION
Before all work on the gas supply and when replacing gas cylinders, all shut-off valves must be closed and no ignition sources are permitted in the immediate vicinity.
NOTE
This does not apply if the correct condition is confirmed by an expert.
CAUTION
The units must not be used
below ground level
in basements, without suitable gas monitoring equipment.
NOTE
It is prohibited to exceed or undershoot the required connection pressure.
, e.g.
6
Connecting the gas supply
Assembly note
Icing up of gas cylinders
1. Connect pressure controller to the gas cylinder or gas supply system.
Observe left-handed thread!
2. Open cylinder valve(s) or shut-off valve of the supply line.
With simultaneous discharge from multiple gas cylinders, all valves must be opened.
3. Push the unlock button on the hose breakage protection after opening the valve(s).
This process is also necessary after every cylinder change.
4. Check all gas connections for leak-tightness using suitable media. For example with:
Soap solution
or leak
detection spray.
During the assembly or disassembly of the gas hose, it is necessary to counter-hold the unit by the gas connection nipple with an open-end wrench size 17, whilst observing the left­handed thread. This process also applies
With insufficiently dimensioned gas supply systems, there is a risk of the pressurised gas cylinder icing up. Due to the reduction of the gas pressure, it is no longer possible to guarantee the correct gas supply to the unit.
to the pressure controller, hose breakage protection and all further gas components.
Crystalline frost formation on the gas cylinder(s) must not be defrosted with naked flames,
Tighten gas hose:
glowing objects, radiators, etc.
Turn the union nut anticlockwise
counter-hold
Loosen gas hose: Turn the union nut clockwise
counter-hold
In order to avoid the gas cylinder(s) icing up, it is necessary to configure the gas supply in accordance with the unit connection value, the time in operation and the ambient temperature of the supply tank.
Attachment multi-cylinder set (accessory)
NOTE
Because these are conical seals in accordance with DIN 4815, part 2, only appropriate, fitting hoses may be used.
NOTE
Only hoses for liquid gas in accordance with DIN 4815, part 1, pressure class 30 may be used for construction site operations.
In order to guarantee a regular gas take-off insofar as possible, all cylinder valves must be open. The cylinder battery can be expanded with ease, through the use of additional sets.
5
6
4
Legend:
1 = Gas hose to the unit 2 = Hose breakage protection 3 = Gas pressure controller
4
6
5
6
4 = HP hose 0.4 m 5 = T-connection 6 = Cylinder valve
1
2
3
s
s
s
7
REMKO PGT
s
s
s
Commissioning
Tank gas systems
When connecting the units to tank gas systems, ensure sufficient pipe dimensions depending on the pipe length. A sufficient gas supply to the consumer system can be ensured through the use of an evaporator.
In order to guarantee the faultless unit function, it is advisable to install a permanently set pressure controller with 1.5 bar outlet pressure and corresponding gas throughput (see unit name plate), as well as a shut-off device tailored and approved for the respective pre-pressure.
In order to avoid malfunctions of the unit’s control and safety equipment due to harmful substances such as rust and dust from the gas supply line or tank(s), it has proven to be essential to install gas filters before the control and safety equipment of the units (see DIN 4788 and TRF 88 section 5).
The units should be checked for visible defects on the operating and safety devices as well as proper installation and correct electrical and gas connections before commissioning.
A person, who has been adequately trained in the handling of the units and the use of liquid gas per VBG 21, must be tasked with operation and monitoring of the units.
CAUTION
In the event of defects that endanger the operational safety of the units, operation of the units must be discontinued immediately and the supervisor informed!
Before the unit start, ensure that the gas supply cylinders are correctly secured and are not positioned directly in the heat radiated by the units. The pressurised gas tanks must be positioned to the side / rear of the unit.
Connecting the units to the electrical power supply
1. Move the operating switch to the "0" (off) position.
2. Connect the unit's power plug to a properly installed and fused mains socket.
230 V/50 Hz
.
NOTE
The electrical connection for the units must be made at a separate feed point with a residual current device in accordance with VDE 0100, Section 55.
NOTE
Installation work on the tank gas systems and the supply lines may only be performed by qualified specialist personnel.
CAUTION
Before all work on the gas supply and when replacing gas cylinders, all shut-off valves must be closed and no ignition sources are permitted in the immediate vicinity.
8
CAUTION
The tanks must never be heated or de-iced through the unit hot air flow.
There is a risk of explosion!
CAUTION
Pressurised gas tanks must not lie horizontal when used during unit operation.
Gas outlet in the liquid phase.
Heating without room thermostat
Setting and controlling the heating capacity
Heating with room thermostat
(Accessories)
The units operate in continuous operation without room temperature regulation.
1. Connect the strapping plug 2 supplied with the thermostat socket 1 on the unit.
1
2
2. Move the operat­ing switch to the "I" (Heating) position.
The supply air fan starts up and the automatic burner starts the unit after approx. 15 seconds.
NOTE on polarity!
If the unit should implement a fault shut-down during the start phase, first check the polarity of the power supply by turning the power plug through 180°.
The desired or required heating capacity can be steplessly set on the “power regulation”.
Turning to the left:
higher heating capacity
Turning to the right:
lower heating capacity
The heating capacity can also be steplessly changed during unit operation.
Safety distances
For safe operation, a 1 m safety
distance must be maintained around the unit
A minimum distance of 3 m must be maintained from the unit outlet
The units operate fully automatically and according to the room temperature.
1. Pull out the strapping plug 2.
2. Connect the plug 3 of the room thermostat 4 with the thermostat socket 1 on the unit.
1
3
3. Place the room thermostat 4 at a suitable location in the room. The thermostat sensor must not be located directly in the warm air flow and must not be placed directly on the cold floor.
4. Set the desired temperature on the room thermostat 4.
4
It may be necessary to repeat this process with a change in position or new socket assignment!
CAUTION
It must be ensured that supply air can be freely sucked in and that heated air can be blown out without obstruction. The unit intake and outlet must not be restricted or fitted with hoses or pipes.
CAUTION
It is essential to observe the necessary safe distances from flammable and fire hazardous materials.
Flooring and ceilings must be
fire retardant
CAUTION
In case of a gas leak, halt unit operation immediately. All gas shut-off valves must be closed and the units disconnected from the power supply.
5. Move the operating
switch to the "I" (Heating) position.
The unit starts automatically after a brief burner pre-ventilation if heat is required and then runs fully automatically.
s
s
s
9
REMKO PGT
s
s
s
Shutdown Care and maintenance
Ventilate
In this operating mode, the supply air fan runs permanently. The units can be used for air recirculation or ventilation purposes.
1. Close the shut off valve(s) of the gas supply system and allow the gas flame to burn out.
2. Move the operating switch to the "II" (Ventilate) position.
1. Close the shut off valve(s) of the gas supply system and allow the gas flame to burn out.
2. Move the operating
switch to the "0" (off) position.
3. If the units are inactive for longer periods, disconnect them from the mains power supply.
NOTE
Regular care and maintenance, at the latest after every heating period, is the basic requirement for a long service life and malfunction-free operation of the units.
In accordance with the operating conditions, the units must be checked as and when required, but at least every two years, by a specialist to ensure that they are in a condition that is safe to use.
The results of this test must be recorded in a test certificate. The test certificate must be stored until the next test and presented for inspection by authorised persons on request.
CAUTION
Thermostatic control as well as heating operation is not possible in this operating mode.
NOTE
Overpressure and underpressure in the installation area should be avoided as this will inevitably lead to combustion­related malfunctions.
NOTE
For optimum operation the units should not be operated above an ambient temperature of 25 °C.
NOTE
Important notes regarding the cooling phase in units with automatic fan run-on (PGT 100 series, PGT 30/60 as option).
The automatic fan run­on serves to avoid heat accumulation inside the unit after the burner is switched off.
For this reason the electrical connection must not be disconnected from the mains power supply before the cooling phase has ended, except in an emergency.
CAUTION
The units must not be used
below ground level
in basements, without suitable gas monitoring equipment.
, e.g.
Before undertaking any work on the unit, the gas supply must be shut off and the power plug must be removed from the mains socket.
Keep the units free of dust and
other deposits
Only clean the units with
a dry or moistened cloth
Never subject to direct jets
of water.
e.g. pressure washers etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
10
Check the inlet and outlet grille
for contamination on a regular basis
Check hoses and seals
for damage on a regular basis
Replace damaged hoses, seals,
etc. immediately
Clean the gas burner,
gas nozzle and the combustion air openings regularly
Check ignition and ionisation
electrodes regularly and adjust and clean if necessary
NOTE
Replace defective or damaged parts immediately and exclusively with original spare parts.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
Disassembling and cleaning the gas burner
1. Switch off the gas supply to the unit and unplug the power plug from the mains socket.
2. Remove the protective outlet grille, exterior cladding and inspection cover.
3. Undo the clamping screw 5 of the nozzle holder.
4. Remove the ignition cable from
the ignition electrode.
5. Detach the ionisation cable from
the ionisation electrode. Be
aware of the cap nut and spring washer!
6. Loosen the clamping screw 4 on the electrode bracket and carefully draw out the ignition and ionisation electrode.
7. Carefully remove any adhered deposits from the ignition and ionisation electrode.
8. Detach the fastening screws of the gas burner and remove the complete gas burner from the unit.
9. Carefully clean the gas burner with a suitable brush and possibly compressed air.
14. Adjust the ignition and ionisation electrode in accordance with the sketch and tighten the clamping screw 4 of the electrode bracket.
The tip of the ionisation electrode must be in the vicinity of the flame.
15. Carefully refit all parts of the unit in reverse order.
CAUTION
A functional inspection of the entire unit including leak testing of all gas­conveying connections must be conducted
for example with:
Soap solution
or leak detection
spray.
Gas burner
B
1
A
CAUTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
NOTE
A strongly yellowy flame indicates an inadequate fresh air supply or dirt inside the unit.
10. Clean the gas nozzle if necessary.
Do not use any sharp-edged objects!
11. Carefully remove deposits or soiling in the unit base.
12. After all cleaning work on the gas burner, carefully refit all parts in reverse order.
13. After using the gas nozzle, tighten the clamping screw 5 again.
3
4
2
5
Unit type A B
PGT 30 PGT 60 PGT 100
approx. 3 mm approx. 15 mm approx. 3 mm approx. 15 mm
approx. 3-4 mm
approx. 30 mm
Legend:
1 = Gas burner 2 = Ionisation electrode 3 = Ignition electrode 4 = Clamping screw (electrodes) 5 = Clamping screw (gas nozzle)
11
REMKO PGT
Troubleshooting
Malfunctions: Cause:
Unit does not start.
Unit switches off during operation. (Fault lamp in the automatic burner lights up)
Fan runs, but the gas supply is blocked or no ignition takes place.
The gas supply is interrupted, or the flame is extinguished.
Unit consumes too much fuel.
Unit cannot be switched off.
Heating capacity drops in permanent operating mode.
Heating capacity cannot be regulated.
1 – 2 – 3 – 4 – 5 – 7 – 10 – 13 – 17 – 18
2 – 6 – 7 – 8 – 9 – 10 – 13 – 14 – 17
7 – 12 – 13 – 14
6 – 7 – 8 – 9 – 10 – 13 – 14 – 17 – 18
13
5 – 15
14
11
Cause: Remedial measures:
1. The unit is not connected to the electricity supply.
2. The fan motor is overloaded or the supply air fan runs irregularly or is blocked.
3. The room thermostat is set too low.
4. No strapping plug in the room thermostat socket.
5. The operating switch is defective.
Connect the plug with an appropriate socket (230V/50Hz).
Check the motor, fan blade and drive clutch and replace if necessary.
The setting must be higher than the current room temperature.
Connect the strapping plug with the thermostat socket.
Shut off the gas supply, unplug the power plug from the mains power socket and replace the operating switch.
6. The polarity of the power plug is incorrect.
7. No gas pressure at the solenoid valve.
8. The ionisation or ignition electrode are incorrectly set.
9. The protective intake grille of the supply air fan is contaminated.
10. Shutdown by safety temperature limiter (STB). The power plug (only PGT 100) was disconnected from the mains power supply before the cooling time had passed.
11. The gas control is faulty or contaminated.
12. The ignition does not work.
13. The pressure controller is defective, an incorrect pressure control­ler is fitted, or the hose breakage protection has interlocked.
14. The gas cylinder(s) is (are) iced up due to an excessively high gas take-off and low temperatures.
15. The solenoid valve does not close.
16. Leaky gas connection.
Check polarity, turn the power plug through 180°.
Check whether the gas supply to the unit is present. Check the level of the gas cylinders. Check the gas hose for damage. Disengage or replace the hose breakage protection.
Settings according to specifications; check the porcelain insulation of the electrodes.
Clean the protective intake grille.
Check the protective intake and outlet grilles (clean if necessary). Check whether the fresh air supply is sufficient. Unlock STB (reset STB).
Replace or clean gas control.
Operating switch to the "I" position (heating mode). Check the ignition cable for damage. Check the electrode settings, check cyclical igniter.
Fit an original pressure controller. Disengage or replace the hose breakage protection.
Replace the gas cylinder(s) and connect 2-3 cylinders with the multi­cylinder set, EDP no. 1014050.
Shut off the gas supply, allow the flame to burn out. Operating switch to the "0" position and remove the power plug from the mains power socket. Replace the solenoid valve.
Use foaming media to search for the leak and remedy this.
17. The fault lamp in the automatic burner lights up.
18. The automatic burner is defective.
12
Reset the automatic burner by pressing the malfunction button.
Replace defective automatic burner.
Intended use Customer service and
guarantee
Environmental pro­tection and recycling
The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (not for living space heating in private use) on the basis of their structural design and equipment.
The unit definition is “commercial drying unit” in accordance with DIN EN 1596.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative complete and return the "certificate of guarantee" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units are tested several times to verify their correct function.
However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Disposing of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in sturdy transport packaging made from cardboard and polystyrene. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
Disposal of the old unit
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any manufacturer liability or guarantee claims are voided.
!
CAUTION
Copyright
Without the written
authorisation of
& Co. KG
even in part, or the use
of this documentation for
purposes other than intended
is prohibited.
REMKO GmbH
, redistribution,
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point.
13
REMKO PGT
PGT 30/60-R07
RT
Electrical wiring diagram
PGT 30 / PGT 60
Legend:
I = Ionisation electrode
KL = Terminal block
M = Fan motor
MV = Solenoid valve
RS = Relay socket
RT = Thermostat socket
S = Operating switch
STB = Safety temperature limiter
Z = Ignition electrode
ZT = Ignition transformer
14
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
I
PGT 100-R07
Electrical wiring diagram
PGT 100
Legend:
HS = Auxiliary relay
I = Ionisation electrode
KL = Terminal block
M = Fan motor
MV = Solenoid valve
NK = Aftercooler thermostat
RS = Relay socket
RT = Thermostat socket
STB = Safety temperature limiter
S = Operating switch
Z = Ignition electrode
ZT = Ignition transformer
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
15
REMKO PGT
Exploded view of PGT 30
29
28
30
27
26
25
25
32
24
33
34 35 36 37
31
21
22
20
23
22
20
18
19
12
38
16
15
39
1
2
40
6
3
4
5
10
11
17
8
9
8
7
14
6
16
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No.
Description EDP no.
1 Transport handle 1101142
2 Exterior cladding 1101440
2a Exterior cladding (stainless steel) 1101463
3 Combustion chamber 1101384
4 Completion panel, front 1101479
5 Protective outlet grille 1101383
6 Safety thermostat 1101197
7 Inspection cover 1101385
8 Ignition cable 1101521
9 Cyclical igniter 1101520
10 Automatic burner base 1102534
11 Automatic burner 1101526
12 Ionisation cable 1101187
14 Terminal block 4x 1101442
15 Ionisation electrode 1101186
16 Ignition electrode 1101180
17 Connection clip 1101181
18 OT elbow union 1101316
19 Gas nozzle 1101159
20 Gas supply pipe M/R 1101444
21 Gas control 1101411
22 Gas supply pipe R/D 1101453
23 Screw connection M10x1 1101409
24 GE-screw connection 1101396
25 Solenoid valve 1101376
26 Gas connection nipple 1101134
No.
Description EDP no.
27 Adjusting knob, cpl. 1101192
28 Strapping plug 1101019
29 Thermostat socket 1101018
30 Operating switch 1101188
31 Strain relief 1101267
32 Mains cable with plug 1101320
33 Completion panel, rear 1101480
34 Fan motor 1108049
35 Drive clutch B 6 Ø 1108455
36 Fan blade 1101392
37 Clutch plate 1101375
38 Gas burner 1101417
39 Grommet 1101304
40 Retaining clip 1101395
xx Run-on relay (accessory) 1105075
xx
Pressure controller with hose breakage protection
1101470
xx 2 linear m. Gas hose 1101419
xx 2 linear m. HP gas hose 1) 1101174
xx 5 linear m. HP gas hose 1) 1108410
xx 10 linear m. HP gas hose 1) 1108411
xx Multi-cylinder set (2-3 cylinders) 1014050
xx T-connection for multi-cylinder set 1101177
xx Nylon seal for T-connection 1101178
xx HP hose 0.4 m 2) 1101179
xx Thermostat plug 1101020
xx = not illustrated
1)
Version for construction site operation per DIN 4815 part 1, pressure class 30
2)
for multi-cylinder set
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
17
REMKO PGT
Exploded view of PGT 60
1
31
31
24
40
19
41
22
42
20
8
43
19
34
44
33
36
14
32
38
35
16
46
21
37
39
2
3
4
30
45
5
6
18
30
25
26
29
28
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
27
23
17
15
8
13
9
14
7
10
11
12
Spare parts list
No.
Description EDP no.
1 Transport handle 1101142
2 Exterior cladding 1101420
2a Exterior cladding (stainless steel) 1101461
3 Insulation 1101421
4 Combustion chamber 1101422
5 Gas burner 1101423
6 Protective outlet grille 1101424
7 Gas nozzle 1101426
8 Gas supply pipe R/D 1101457
9 OT elbow union 1101316
10 Ignition electrode 1101280
11 Ionisation electrode 1101186
12 Ionisation cable 1101187
13 Connection clip 1101181
14 Ignition cable 1101521
15 Support, front 1101427
16 Unit base 1101428
17 Inspection cover 1101469
19 Gas supply pipe M/R 1101441
20 Screw connection M10x1 1101409
21 Terminal block 4x 1101442
22 Gas control 1101412
23 Support, rear 1101249
24 GE-screw connection 1101396
25 Automatic burner base 1102534
26 Automatic burner 1101526
27 Push-button extension 1101524
28 Cover 1101525
29 Nozzle 1101528
No.
Description EDP no.
30 Safety thermostat 1101197
31 Solenoid valve 1101376
32 Thermostat socket 1101018
33 Strapping plug 1101019
34 Gas connection nipple 1101134
35 Adjusting knob, cpl. 1101192
36 Strain relief 1101267
37 Operating switch 1101188
38 Cyclical igniter 1101520
39 Grommet 1101304
40 Mains cable with plug 1101320
41 Protective intake grille 1101432
42 Fan motor 1101254
43 Drive clutch B 8 Ø 1101255
44 Fan blade 1101150
45 Retaining clip 1101395
46 Clutch plate 1101375
xx Run-on relay (accessory) 1105075
xx
Pressure controller with hose breakage protection
1101470
xx 2 linear m. Gas hose 1101419
xx 2 linear m. HP gas hose 1) 1101174
xx 5 linear m. HP gas hose 1) 1108410
xx 10 linear m. HP gas hose 1) 1108411
xx Multi-cylinder set (2-3 cylinders), cpl. 1014050
xx T-connection for multi-cylinder set 1101177
xx Nylon seal for T-connection 1101178
xx HP hose 0.4 m 2) 1101179
xx Thermostat plug 1101020
xx = not illustrated
1)
Version for construction site operation per DIN 4815 part 1, pressure class 30
2)
for multi-cylinder set
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
19
REMKO PGT
Exploded view of PGT 100
44
58
42
51
47
52
29
57
50
45
59
49
46
1
2
3
9
4
5
8
6
10
7
38
12
33
24
43
21
32
24
20
29
23
19
39
22
26
31
53
36
28
25
37
22
8
34
30
18
54
27
17
55
56
14
16
35
11 a/b
40
41
13
15
20
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Designation EDP no.
1 Transport handle 1101680
2 Exterior cladding 1101681
2a Exterior cladding (stainless steel) 1101462
3 Insulation 1101682
4 Grommet 1101304
5 Retaining clip 1101395
6 Aftercooler thermostat 1101683
7 Protective outlet grille 1101684
8 Safety thermostat 1101197
9 Combustion chamber 1101685
10 Interior cladding, front 1101686
11a Cladding support, right 1101631
11b Cladding support, left 1101632
12 Mounting plate 1101687
13 Unit base 1101688
14 Floor panel 1101652
15 Axle 1101653
No. Designation EDP no.
35 Thermostat socket 1101018
36 Adjusting knob, cpl. 1101192
37 Gas connection nipple 1101134
38 Fastening bracket 1102906
39 Gas control 1101692
40 Terminal block 6er 1101366
41 Auxiliary relay 1108038
42 Ignition transformer 1101666
43 Grommet, large 1101677
44 Protective intake grille 1101648
45 Fan blade 1101693
46 Fan housing, cpl. 1101694
47 Fan motor 1101634
49 Gas burner 1101695
50 Gas nozzle 1101659
51 OT elbow union 1101316
52 Ignition cable 1101696
16 Wheel 1102155
17 Locking ring 1101622
18 Hubcap 1101623
19 Push-button extension 1101524
20 Cover 1101525
21 Nozzle 1101528
22 Gas supply pipe M/R 1101441
23 GE-screw connection 1101396
24 Solenoid valve 1101165
25 Automatic burner base 1102534
26 Automatic burner 1101526
27 Inspection cover 1101651
28 Screw connection M10 x 1 1101409
29 Gas supply pipe R/D 1101690
30 Support, rear 1101691
31 Operating switch 1101188
32 Strain relief 1101267
33 Mains cable with plug 1101320
53 Connection clip 1101181
54 Ionisation cable 1101187
55 Ignition electrode 1101698
56 Ionisation electrode 1101697
57 Electrode bracket 1101633
58 Interior cladding, rear 1101450
59 Spacer sleeve 1101699
Without figure:
Pressure controller 1101418
Hose breakage protection 1101664
2 linear m. Gas hose 1101419
2 linear m. HP gas hose
5 linear m. HP gas hose
10 linear m. HP gas hose
1)
1)
1)
1101174
1108410
1108411
Multi-cylinder set (2-3 cylinders), cpl. 1014050
T-connection for multi-cylinder set 1101177
Nylon seal for T-connection 1101178
HP hose 0.4m for multi-cylinder set 1101179
34 Strapping plug 1101019
1)
Version for construction site operation per DIN 4815 part 1, pressure class 30
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
Thermostat plug 1101020
21
REMKO PGT
Maintenance protocol
Unit type: .................................... Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Combustion chamber cleaned
Gas burner cleaned
Ignition electrode adjusted
Gas hose checked for damage
Gas-transporting parts checked for leak-tightness
Safety equipment checked
Safety devices checked
Unit checked for damage
All fastening screws checked
Electrical safety check
Test run
Comments:...........................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
22
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
Technical data
Series PGT 30 (E) PGT 60 (E) PGT 100 (E)
Max. nominal heating capacity kW 26 55 100
Heating capacity, adjustable kW 10 to 26 25 to 55 50 to 100
Air volume m3/h 800 1450 3600
Fuel / gas type Liquid gas cat I
3B/P
Unit connection pressure bar 1.5 1.5 1.5
Unit connection value kg/h 0.78 - 2.0 1.95 - 4.27 3.9 - 7.8
Power supply V/Hz 230/1~/50 230/1~/50 230/1~/50
Max. power consumption W 70 110 325
Elec. Max. current consumption
Electrical protection (provided by the customer)
A 0.5 0.95 2.8
A 10 10 10
Enclosure class IP 44 44 44
Sound pressure level LpA 1m 1) dB (A) 56 - 69 62 - 72 74 - 82
Dimensions: Length mm 450 650 1060
Width mm 260 320 435
Height mm 410 510 620
Weight (without accessories) kg 12 20 47
Product ID number CE-0085AP0240
1)
Noise measurement in acc. with DIN 45635 - 01 - KL 3 in heating mode
Technical data for the automatic burner
Operating voltage 230 V (-15 % + 10 %)
Frequency 50 Hz (40 - 60 Hz)
Safety time 5 seconds
Waiting time after fault shut-down approx. 60 seconds
Permissible ambient temperature – 20° C to + 60 °C
min. required ionisation flow 5 μA
Sensitivity (ionisation flow) 1 μA
Enclosure class IP 44
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
23
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail info@remko.de Internet www.remko.de
Consulting
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation
of being more than just
an excellent, reliable supplier:
REMKO, a partner who helps
to solve problems.
Sales
REMKO offers not just a well-
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO employees in the
field are more than just sales
people: above all, they must
be advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely and
reliably. However, in the event
of a malfunction REMKO
customer service is quickly on
the scene. Our comprehensive
network of experienced dealers
guarantees quick and reliable
service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!
Loading...