REMKO PGM Series, PGM 30 E, PGM E Series, PGM 30, PGM 60 E Operating And Installation Instructions

...
Operating and installation instruction
REMKO PGM (E) series
Propane gas heating systems
PGM 30 (E), PGM 60 (E)
This product is not suitable as a main heater.
Edition GB - Q04 Read the instructions prior to performing any task!
Contents
Safety notes 4
Unit description 5
Installation instructions 6
Gas connection 7-9
Commissioning 9-10
Shutdown 11
Care and maintenance 11-12
Troubleshooting 13
Intended use 14
Customer service and guarantee
Environmental protection and recycling 14
Exploded view of PGM 30
Spare parts list for PGM 30 17
Exploded view of PGM 60 18
Replacement parts list for PGM 60 19
Maintenance protocol 20
Technical data
Electrical wiring diagram 22
21
14
16
Carefully read this operating manual prior to commissioning/using the unit! This operating manual is a translation of the German original.
These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO PGM (E) series
Safety notes
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations when using the units.
The units have been subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can arise from the units if they are used improperly or not as intended by untrained personnel! Please observe the following information:
The units may only be operated
by persons that have been instructed in their operation
The power plug must be pulled
out of the mains socket before maintenance and repair work
The units must be installed such that they are stable on a non­combustible surface
It is necessary to ensure that no flammable objects or materials can be drawn in
This unit can be used by children above the age of 8, as well as by people with impaired physical, sensory or mental capabilities or a lack ofexperience and knowledge if they are supervised or have received instruction in the safe operation of the unit, and if they understand the associated potential hazards. Children must never play with the unit.
Cleaning and user maintenance must not be carried out by unsupervised children.
The units must be installed and
operated in such a way that personnel are not endangered
by exhaust gases and radiant heat and no fires may occur
Portable liquid gas tanks must be installed such that they are stable and upright
Liquid gas tanks must never be used whilst lying horizontal during unit operation
All unit electrical cables must be protected against damage, e.g. by animals
The units must then only
be operated in areas where the units can be supplied with an adequate amount of air for combustion
The units must only be installed in well-ventilated spaces and away from flammable materials. Personnel must not remain in the installation area
Appropriate prohibition signs should be put up at the entrances!
A safety zone of 1.5 m must
be maintained around the units, incl. to non-combustible items
A minimum distance of 3 m must be maintained from the unit outlet
The unit outlet must not be restricted or fitted with hoses or pipes
Never insert foreign objects in the unit
The air intake grille must always be kept free of dirt and loose objects
The units must not be exposed to direct jets of water e.g. pressure washers, etc.
CAUTION
The units must not be used for heating living spaces in residential buildings.
!
CAUTION
If there is a gas leak, immediately close the shut-off valve to the gas supply system, switch off the gas heater, unplug the power plug, open windows/doors for ventilation and seek the cause of the gas leak in order to neutralise this. Do not use the unit again before the gas leak has been eliminated!
4
Unit description
The units are mobile fan-assisted air heaters (WLE) directly fired with liquid gas, without a heat exchanger.
The units operate without an exhaust gas connection and are designed exclusively for commercial use.
The units are equipped with integrated power regulation for the stepless control of the heating capacity, quiet and low-maintenance axial fans, robust gas burners with thermal monitoring, electric solenoid valve, piezo ignition and mains cable with earthed safety plug.
The units are intended exclusively for manual operation and cannot be thermostatically controlled.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations and are simple to operate.
The units are EC type-tested, DVGW-registered and approved for EU countries.
The units may be used among other things for the following:
Drying newly completed
buildings
Spot heating of outdoor
workplaces
Spot heating workplaces
in open, non-flammable manufacturing facilities and halls
Temporarily heating enclosed
spaces with a sufficient fresh air supply
De-icing machines, vehicles and
non-combustible warehoused goods
Maintaining the temperature
of frost-sensitive parts
Operating sequence
After switching on the units, the supply air fan is put into operation and the electric solenoid valve is opened. However, the gas supply to the burner remains closed at this point. Only after actuating the pressure pin of the safety pilot is the gas supply to the gas burner enabled. The liquid gas is now transported through the gas nozzle under pressure into the mixing tube. Here, the liquid gas is enriched with a quantity of oxygen determined based on the respective burner output. The gas/air mixture produced in this way is ignited at the burner head by an electric ignition spark. The ignition spark is generated through the manual actuation of the piezo igniter. The heating of the thermocouple activates the thermal monitoring of the flame in operation. The pressure pin of the safety pilot must now be released. In the event of any irregularities or if the flame is extinguished, the gas supply is interrupted.
A safety temperature limiter (STB) interrupts with an overheating of the gas supply and interlocks all unit functions.
Regulation of the min/max heating capacity can be implemented on a stepless basis during unit operation on the integrated “power regulation”.
NOTE
For optimum operation the units should not be operated above an ambient temperature of 25 °C.
Monitoring the units
It is possible to safely monitor all functions with the safety devices of the units. In the event of irregularities or if the flame is extinguished, the units are switched off and interlocked.
Safety temperature limiter (STB)
The units are equipped with a safety temperature limiter (STB), which interrupts the gas supply in case of overheating and electrically interlocks the unit.
A manual reset of the STB can only be implemented after the units have cooled down.
CAUTION
If the safety temperature limiter has been triggered, the cause of the malfunction must be identified and rectified before a reset is performed.
The STB is reset by actuating the reset key 2.
1. Unscrew the protective cap 1.
2
1
2. Push in the pressure pin 2.
3. Screw the protective cap 1 back on again.
CAUTION
Safety devices must not be bypassed or disabled.
5
REMKO PGM (E) series
Installation instructions
The safety regulations of the accident prevention and insurance associations, the respective regional building regulations and the combustion appliances regulations apply to operation of the units. For example, for Germany:
Combustion plant order (FeuVo)
for the individual federal states
Accident prevention regulations
DGUV Regulation 79 “Use of liquid gas”
Workplace directives ASR 5
Workplace regulations §§ 5
and 14
Outdoor installation
The operation of the units
must not present a hazard or unreasonable loading
The unit operator must
ensure that it is not possible for unauthorised persons to manipulate either the unit or the power supply
To prevent damage due
to inclement weather, units installed outdoors must be adequately protected
Installation in enclosed, well­ventilated rooms
The units are designed without
an exhaust gas connection according to type, and can only be used in enclosed rooms on a conditional basis
Reliable extraction of
the combustion gases must be guaranteed in all cases in order to exclude impermissible contamination of the room air with hazardous substances
The fresh air supply required
for trouble-free combustion must be ensured. It is practical to have the fresh air supply provided by windows and doors or through appropriately dimensioned openings in the outside wall
The units must not operate
continuously whilst unattended
The units may only be operated in rooms if:
a sufficient quantity of air is supplied to the units for the combustion
these are well ventilated and aerated
the proportion of substances
harmful to health in the breathing air is at a harmless level
There is good natural ventilation and aeration if:
1.
the room volume in m3 is at least 30 times the nominal heating capacity kW of all of the units operating in the space, and if the natural change of air is guaranteed by windows and doors or
constantly open ventilation
2. openings are present for incoming and exhaust air in the vicinity of the ceiling and floor, whose size in m2 is at least
0.003 times the nominal heating capacity in kW of all of the units operating in the space.
!
CAUTION
For use in public buildings,
national regulations must
be observed.
CAUTION
The units must only be
installed in well ventilated
spaces and not in living areas
or similar recreational areas.
6
Gas connection
The gas connection / unit operation must take place exclusively on the basis of the accident prevention regulation DGUV 79 “ as well as the respective local construction and fire prevention regulations.
The fuel supply must be installed in accordance with DIN 4755 for oil-fired warm air heaters, DVGW Code of Practice G 600 for gas­fired warm air heaters and TRF for liquid gas.
The units are operated with liquid gas in accordance with DIN 51622. They require a constant connection pressure of 1.5 bar. It is prohibited to exceed or undershoot the connection pressure.
CAUTION
A constant unit connection pressure of 1.5 bar (1500 mbar) must be guaranteed, also in continuous operation.
When using longer hose lines, consider the respective pressure loss
Only use components that have
been tested and are suitable for the respective purpose, such as gas hose, pressure controller and hose breakage protection or leak gas protection
Use of liquid gas”
unit
,
CAUTION
Before all work on the gas supply and when replacing gas cylinders, all shut-off valves must be closed and no ignition sources are permitted in the immediate vicinity.
The use of longer hose lines is permissible if:
- special operational reasons exist
- appropriate additional safety measures are observed and the hose lengths are kept as short as possible
Hose lines must be
fundamentally protected against chemical, thermal and mechanical damage
In particular, torsional stress
must be avoided
The units may only be operated
out of the gas phase
The units must be serviced
by qualified persons only
Only original spare parts may
be used for repairs
Unit parts that are prone to
wear and ageing (e.g. gas hoses) must be replaced at regular intervals
Gas connection nipple on
the unit - G1/4 LH - KN
All common gas cylinder sizes
are permitted for the gas supply. However, a gas cylinder with at least 11 kg filling weight is recommended. For longer operation and nominal heat outputs above 50 kW, it is recommended that the gas be drawn from several gas cylinders in parallel. (Multi­cylinder accessories set)
NOTE
This does not apply if the correct condition is confirmed by an expert.
CAUTION
The units must not be used
below ground level
in basements, without suitable gas monitoring equipment.
NOTE
It is prohibited to exceed or undershoot the required connection pressure.
, e.g.
If possible, the length of the gas hose should not exceed 2 m
Only pressure controllers with
a fixed outlet pressure setting are permitted. The units may only be operated out of the gas phase
When selecting the hose, make
sure that the pressure class is sufficient
7
REMKO PGM (E) series
Connecting the gas supply
1. Connect pressure controller to the gas cylinder or gas supply system.
Observe left-handed thread!
2. Open cylinder valve(s) or shut­off valve of the supply line.
With simultaneous discharge from multiple gas cylinders, all valves must be opened.
3. Push the unlock button on the hose breakage protection after opening the valve(s).
This process is also necessary after every cylinder change.
4. Check all gas connections for leak-tightness using suitable media.
for example with:
Soap solution or
leak detection
spray.
Assembly note
During the assembly or disassembly of the gas hose, it is necessary to counter-hold by the gas connection nipple with an open-end wrench size 17, whilst observing the left-handed thread. This process also applies to the pressure controller, hose breakage protection and all further gas components.
Tighten gas hose: Turn the union nut anticlockwise
counter-hold
Loosen gas hose: Turn the union nut clockwise
counter-hold
the unit
Icing up of gas cylinders
With insufficiently dimensioned gas supply systems, there is a risk of the pressurised gas cylinder icing up. Due to the reduction of the gas pressure, it is no longer possible to guarantee the correct gas supply to the unit.
Crystalline frost formation on the gas cylinder(s) must not be defrosted with naked flames, glowing objects, radiators, etc.
In order to avoid the gas cylinder(s) icing up, it is necessary to configure the gas supply in accordance with the unit connection value, the time in operation and the ambient temperature of the supply tank.
Attachment multi-cylinder set (accessory)
NOTE
Because these are ball nipple screw connections in accordance with DIN 4815, part 2, only appropriate, fitting hoses may be used.
NOTE
Only hoses for liquid gas in accordance with DIN EN 16436-1, pressure class 30 may be used for construction site operations.
8
In order to ensure a regular gas take-off insofar as possible, all cylinder valves must be open. The cylinder battery can be expanded with ease, through the use of additional sets.
Legend:
1 = Gas hose to the unit 2 = Hose breakage protection 3 = Gas pressure controller 4 = HP hose 0.4 m 5 = T-connection 6 = Cylinder valve
6
5
6
4
6
4
1
2
3
5
s
s
s
s
s
s
Commissioning
Tank gas systems
When connecting the units to tank gas systems, ensure sufficient pipe dimensions depending on the pipe length. A sufficient gas supply to the consumer system can be ensured through the use of an evaporator.
In order to guarantee the faultless unit function, it is advisable to install a permanently set pressure controller with 1.5 bar outlet pressure and corresponding gas throughput (see unit name plate), as well as a shut-off device tailored and approved for the respective pre-pressure.
In order to avoid malfunctions of the unit’s control and safety equipment due to harmful substances such as rust and dust from the gas supply line or tank(s), it has proven to be essential to install gas filters before the control and safety equipment of the units (see DIN EN 676 and TRF 88 section 5).
The units should be checked for visible defects on the operating
Connecting the units to the electrical power supply
and safety devices as well as proper installation and correct electrical and gas connections before commissioning.
1. Move the operating switch to the "0" (off) position.
A person, who has been adequately trained in the handling of the units and the use of liquid gas per DGUV 79, must be tasked with operation and monitoring of the units.
2. Connect the unit's power plug to a properly installed and fused mains socket. Connect 230 V/50 Hz.
CAUTION
In the event of defects that endanger the operational safety of the units, operation of the units must be discontinued immediately and
NOTE
The electrical connection for the units must be made at a separate feed point with a residual current device in accordance with VDE 0100, Section 55.
the supervisor informed!
Before the unit start, ensure that the gas supply cylinders are correctly secured and are not positioned directly in the heat radiated by the units. The pressurised gas tanks must be positioned to the side / rear of the unit.
NOTE
Installation work on the tank gas systems and the supply lines may only be performed by qualified specialist personnel.
CAUTION
Before all work on the gas supply and when replacing gas cylinders, all shut-off valves must be closed and no ignition sources are permitted in the immediate vicinity.
CAUTION
The tanks must never be heated or de-iced through the unit hot air flow.
There is a risk of explosion!
CAUTION
Pressurised gas tanks must not lie horizontal when used during unit operation.
Gas outlet in the liquid phase.
9
REMKO PGM (E) series
Heating mode
1. Move the operating switch to the "I" position.
The supply air fan starts up.
CAUTION
Before executing the ignition process, check to ensure the correct function of the supply air fan.
2. Push in the pressure pin 2 of the safety pilot and hold down.
2
3. With pressure pin 2 depressed, after approx. 2 to 3 sec.actuate the piezo igniter 3.
If necessary, actuate the piezo igniter multiple times.
4. After a flame appears, depress the pressure pin 2 for a further approx. 10-15 sec. until the thermal flame monitoring is activated.
5. If the flame goes out when the pressure pin 2 is released, repeat the ignition process.
Observe a waiting time of approx. 1 minute.
3
Setting and controlling the heating capacity
The desired or required heating capacity can be steplessly set on the “power regulation”.
Turning to the left:
higher heating capacity
Turning to the right:
lower heating capacity
The heating capacity can also be steplessly changed during unit operation.
Safety distances
For safe operation, a 1 m safety
distance must be maintained around the unit
A minimum distance of 3 m must be maintained from the unit outlet
CAUTION
It is essential to observe the necessary safe distances from flammable and fire hazardous materials.
Ventilate
In this operating mode, the supply air fan runs permanently. The units can be used for air recirculation or ventilation purposes.
1. Close the shut off valve(s) of the gas supply system and allow the gas flame to burn out.
2. Move the operating switch to the "II" (Ventilate) position.
No heating operation is possible in this operating mode.
NOTE
Overpressure and underpressure in the installation area should be avoided as this will inevitably lead to combustion­related faults.
With a repeat ignition process, hold the pressure pin for a little longer if necessary.
CAUTION
The units must not be used
below ground level
in basements, without suitable gas monitoring equipment.
10
, e.g.
Flooring and ceilings must be
fire retardant
CAUTION
In case of a gas leak, halt unit operation immediately. All gas shut-off valves must be closed and the units disconnected from the power supply.
CAUTION
It must be ensured that supply air can be freely sucked in and that heated air can be blown out without obstruction. The unit intake and outlet must not be restricted or fitted with hoses or pipes.
Shutdown
Care and maintenance
1. Close the shut off valve(s) of the gas supply system and allow the gas flame to burn out.
2. Move the operating
switch to the "0" (off) position.
3. If the units are inactive for longer periods, disconnect them from the mains power supply.
NOTE
Regular care and maintenance, at the latest after every heating period, is the basic requirement for a long service life and malfunction-free operation of the units.
In accordance with the operating conditions, the units must be checked as and when required, but at least every two years, by a specialist to ensure that they are in a condition that is safe to use.
The results of this test must be recorded in a test certificate. The test certificate must be stored until the next test and presented for inspection by authorised persons on request.
Check the inlet and outlet grille
for contamination on a regular basis
Check hoses and seals for
damage on a regular basis
Replace damaged hoses, seals,
etc. immediately
Clean the gas burner, gas
nozzle and the combustion air openings regularly
Check ignition and ionisation
electrodes regularly and adjust and clean if necessary
CAUTION
Before undertaking any work on the unit, the gas supply must be shut off and the power plug must be removed from the mains socket.
Keep the units free of dust and
other deposits
Only clean the units with a dry
or moistened cloth
Never use direct jets of water.
such as high-pressure cleaners etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
NOTE
Replace defective or damaged parts immediately and exclusively with original spare parts.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
CAUTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
11
REMKO PGM (E) series
Disassembling and cleaning the gas burner
1. Switch off the gas supply to the unit and remove the power plug from the mains socket.
2. Remove the protective outlet grille, exterior cladding and inspection cover.
3. Undo the clamping screw 6 of the nozzle holder.
4. Remove the ignition cable from
the ignition electrode 4.
5. Detach the capillary tube 3
of the thermocouple from the safety pilot.
6. Loosen the clamping screw 5 on the electrode bracket and carefully draw out the ignition electrode.
7. Carefully pull the thermocouple with capillary tube down and out.
Be aware of the extremely sensitive capillary tube here!
10. Carefully clean the gas burner with a suitable brush and possibly compressed air.
11. Clean the gas nozzle if necessary.
Do not use any sharp-edged objects!
12. Carefully remove deposits or soiling in the unit base.
13. After all cleaning work on the gas burner, carefully refit all parts in reverse order.
14. After using the gas nozzle, tighten the clamping screw 6 again.
15. Adjust the ignition electrode and thermocouple in accordance with the sketch and tighten the clamping screw 5 of the electrode bracket.
16. Carefully refit all parts of the unit in reverse order.
CAUTION
Gas burner
B
A
4
5
6
Unit type A B C
PGM 30 PGM 60
All dimensions in mm
Legend:
1 = Gas burner 2 = Thermocouple 3 = Capillary tube
(fixed component of the thermocouple) 4 = Ignition electrode 5 = Clamping screw (electrodes) 6 = Clamping screw (gas nozzle)
approx. 3 approx. 15 approx. 20 approx. 3 approx. 15 approx. 35
2
3
1
C
8. Carefully remove any adhered deposits from the ignition electrode and thermocouple.
9. Detach the fastening screws of the gas burner and remove the complete gas burner from the unit.
12
A functional inspection of the entire unit including leak testing of all gas-conveying connections must be conducted
for example with:
Soap solution or
leak detection
spray.
NOTE
A strongly yellowy flame indicates an inadequate fresh air supply or dirt inside the unit.
Troubleshooting
Malfunctions: Cause:
The unit does not start.
The unit switches off during operation.
The fan runs, but the gas supply is blocked or no flame appears.
The flame extinguishes after the pressure pin of the safety pilot is released.
The gas supply is interrupted, or the flame is extinguished.
The unit consumes too much fuel.
The unit cannot be switched off.
The heating capacity drops in permanent operating mode.
1 – 2 – 3 – 4 – 7
2 – 4 – 7 – 12 – 13
4 – 5 – 8 – 9 – 12
8 – 10 – 11
4 – 6 – 7 –10 – 11 – 12 – 13
12 – 15
3 – 14
13
Cause: Remedial measures:
1. The unit is not connected to the electricity supply.
2. The fan motor is overloaded or the supply air fan runs irregularly or is blocked.
3. The operating switch is defective.
4. No gas pressure.
Connect the plug with an appropriate socket (230V/50Hz). Replace the plug if it is defective.
Check the motor, fan blade and drive clutch.
Replace the operating switch.
Check whether the gas supply to the unit is present. Check the contents of the gas cylinders. Check the gas hose for damage. Disengage or replace the hose breakage protection.
5. No ignition sparks are generated.
6. The protective intake grille of the supply air fan is contaminated.
7. The temperature limiter triggers a switch-off.
8. The safety pilot does not open the gas supply or keep it open.
9. The piezo igniter is defective.
10. The thermocouple or temperature limiter are defective.
11. Loose or dirty connection between the safety pilot and
thermocouple.
12. The pressure controller is defective or an incorrect pressure controller
is fitted, or the hose breakage protection (Sbs) has locked.
13. The gas cylinder(s) is (are) iced up due to an excessively high gas take-off and low temperatures.
14. The solenoid valve does not close - Close the gas supply.
15. Leaky gas line.
Set the ignition electrode in accordance with specifications. Check the ignition cable. Check the porcelain insulation of the electrode.
Clean the protective intake grille.
Check the protective intake and outlet grilles (clean if necessary). Check whether the fresh air supply is sufficient.
Replace the safety pilot.
Replace the piezo igniter.
Check the thermocouple or temperature limiter and replace if necessary
Check the connection and clean if necessary.
Fit an original pressure controller. Disengage or replace the hose breakage protection.
Replace the gas cylinder(s) and connect 2-3 cylinders with the multi­cylinder set, EDP no. 1014050.
Allow the flame to burn out. Set the operating switch to the "0" position and remove the power plug from the mains socket. Replace the solenoid valve.
Use foaming media to search for the leak and remedy this.
13
REMKO PGM (E) series
Intended use Customer service and
guarantee
The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (not for living space heating in private use) on the basis of their structural design and equipment.
According to DIN EN 1596, the device definition is “warm air heaters not intended for domestic use without heat exchangers with forced convection”.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or their representative complete and return the "certificate of guarantee" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units were tested at the factory several times to verify their correct function.
However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Environmental pro­tection and recycling
Disposing of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in sturdy transport packaging made from cardboard and polystyrene. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
Disposal of the old unit
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any manufacturer liability or guar­antee claims are voided.
!
CAUTION
Copyright
The redistribution, even
in part, or the use of this
documentation for purposes
other than intended is
prohibited without the written
authorisation of
REMKO GmbH
& Co. KG
.
NOTE
Adjustment and maintenance work may only be carried out by authorised and qualified technicians.
The manufacturing process for the units is subject to continuous quality control.
Only high-grade materials are processed, the majority of which are recyclable.
You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner.
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point.
14
15
REMKO PGM (E) series
Exploded view of PGM 30 (E)
31
29
32
33 34
28
1
2
27
26
25
24
30
23
15
19
17
21
12
20
14
19
18
15
9
14
12
16
13
10
35
37
36
11
10
9
7
8
6
3
4
5
6
16
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Description EDP no.
1 Transport handle 1101142 2 Exterior cladding PGM 30 1101405 2a Exterior cladding PGM 30 E 1101477 3 Combustion chamber 1121186 4 Completion panel, front 1101479 5 Protective outlet grille 1101383 6 Safety temperature limiter 1101197 7 Inspection cover 1101385 8 Terminal block 6x 1101366 9 Thermocouple 1101164 10 Ignition cable 1101283 11 Ignition electrode 1101180 12 OT elbow union 1101316 13 Gas nozzle 1101159 14 Gas supply pipe Z/D 1101452 15 Gas supply pipe M/R 1101441 16 Piezo igniter 1101364 17 Gas control 1101411 18 Screw connection M10x1 1101409 19 Gas supply pipe R/Z 1101451 20 IT elbow union 1101468 21 Safety pilot 1101169 23 GE-screw connection 1101396 24 Solenoid valve 1101376 25 Gas connection nipple 1101134 26 Adjusting knob, cpl. 1101192 27 Operating switch 1101188 28 Strain relief 1101267 29 Mains cable with plug 1101320 30 Completion panel, rear 1101480 31 Fan motor 1108049 32 Drive clutch B 6 Ø 1108455 33 Fan blade 1101392 34 Clutch plate 1101375 35 Gas burner 1101417 36 Grommet 1101304 37 Retaining clip 1101395 xx Pressure controller with hose breakage protection 1101470 xx 2 linear m. Gas hose 1101419 xx 2 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1101174 xx 5 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1108410 xx 10 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1108411 xx Multi-cylinder set (2-3 cylinders) 1014050 xx T-connection for multi-cylinder set 1101177 xx Nylon seal for T-connection 1101178 xx HP hose 0.4 m for multi-cylinder set 1101179
xx = not illustrated
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
17
REMKO PGM (E) series
Exploded view of PGM 60 (E)
36
37
38
39
41
34
1
2
3
28
16 22
11
35
21
20
27
33
17
24
23
32
15
14
13
31
29
26
19
8
18
12
30
22
16
4
7
8
24
9
10 12
11
40
5
6
18
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Description EDP no.
1 Transport handle 1101142 2 Exterior cladding PGM 60 1101420 2a Exterior cladding PGM 60 E 1101461 3 Insulation 1101421 4 Combustion chamber 1101422 5 Gas burner 1101423 6 Protective outlet grille 1101424 7 Gas nozzle 1101426 8 Gas supply pipe Z/D 1101458 9 OT elbow union 1101316 10 Ignition electrode 1101280 11 Ignition cable 1101283 12 Thermocouple 1101164 13 Support, front 1101427 14 Unit base 1101428 15 Inspection cover 1101469 16 Gas supply pipe R/Z 1101459 17 IT elbow union 1101468 18 Safety pilot 1101169 19 GE-screw connection 1101359 20 Gas control 1101412 21 Screw connection M10x1 1101409 22 Gas supply pipe M/R 1101441 23 Support, rear 1101249 24 Safety temperature limiter 1101197 26 GE-screw connection 1101396 27 Solenoid valve 1101376 28 Piezo igniter 1101364 29 Gas connection nipple 1101134 30 Adjusting knob, cpl. 1101192 31 Strain relief 1101267 32 Operating switch 1101188 33 Terminal block, 6x 1101366 34 Grommet 1101304 35 Mains cable with plug 1101320 36 Protective intake grille 1101432 37 Fan motor 1101254 38 Drive clutch B 8 ø 1101255 39 Fan blade 1101150 40 Retaining clip 1101395 41 Clutch plate 1101375 xx Pressure controller with hose breakage protection 1101470 xx 2 linear m. Gas hose 1101419 xx 2 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1101174 xx 5 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1108410 xx 10 linear m. HP gas hose (version for construction site operation per DIN 4815 part 1, pressure class 30) 1108411 xx Multi-cylinder set (2-3 cylinders) 1014050 xx T-connection for multi-cylinder set 1101177 xx Nylon seal for T-connection 1101178 xx HP hose 0.4 m for multi-cylinder set 1101179
xx = not illustrated
When ordering replacement parts, please always state the EDP no. and unit number (see name plate)!
19
REMKO PGM (E) series
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Combustion chamber cleaned
Gas burner cleaned
Ignition electrode adjusted
Gas hose checked for damage
Gas-transporting parts checked for leak-tightness
Safety equipment checked
Safety devices checked
Unit checked for damage
All fastening screws checked
Electrical safety check
Test run
Comments: ..........................................................................................................................................................
.............................................................................................................................................................................
.............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
17. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
20
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
Technical data
Series PGM 30 (E) PGM 60 (E)
Nominal heat load max
. kW 26.00 55,00
Nominal heat capacity P
Minimum heat capacity P
nom
min
Air volume flow m
kW 26.00 55,00
kW 10.00 25,00
3
/h 725 1310
Fuel Liquid gas
Fuel/gas type Cat I
3P
Energy efficiency ratio A A
Unit connection pressure bar 1.5 1,5
Unit connection value kg/h 0.78 - 2.0 1,95 - 4,27
Auxiliary power consumption
at nominal heating capacity el
at minimum heating capacity el
in Standw-By mode el
Pilot flame power requirement P
Thermal efficiency at nominal heating capacity
Thermal efficiency at minimum heating capacity
η
th,nom
η
th,min
max
min
SB
pilot
kW 0.070 0.100
kW 0.070 0.100
kW 0.000 0.000
kW N/A N/A
% 100.0 100,0
% 100.0 100,0
Type of room temperature control
two or more manually adjustable stages,
no room temperature control
Power supply V/Ph/Hz 230/1~/50 230/1~/50
Rated current consumption A 0.6 0,95
Electrical protection
provided by the customer)
(
A 10 10
Enclosure class IP 11 11
Sound pressure level L
pA
1m
dB(A) 56 - 69 62 - 72
1)
Dimensions: Length mm 450 650
Width mm 260 320
Height mm 410 510
Weight kg 12 20
Product ID number CE-0085AP0240
1)
Noise measurement in acc. with DIN 45635 - 01 - KL 3 in heating mode
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
21
REMKO PGM (E) series
Electrical wiring diagram
PE L1 N
S
L1 N
5 4
STB
3
2 1
KL
3
2 16
A3
A2
A1
M
1 ~
B6
B5
B4
TE
Z
TMV
PZ
C
1
Legend: KL
= Terminal block
M = Fan motor MV = Solenoid valve PZ = Piezo igniter
MV
S = Operating switch
STB = Safety temperature limiter
TE = Thermocouple
TMV = Safety pilot (thermo-electric gas valve)
Z = Ignition electrode
22
23
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Hotline within Germany
+49 (0) 5232 6 06-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...