Quadra-Fire QV36B-A, QV32B-A User Manual

Models: QV32B-A QV36B-A
READ THIS MANUAL BEFORE INSTALLING OR OPERA TING THIS APPLIANCE. THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE.
WARNING: IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTL Y, A FIRE OR EXPLOSION MAY RESULT CAUS­ING PROPERTY DAMAGE, PER­SONAL INJURY, OR DEA TH.
Installers Guide
Underwriters
Laboratories Listed
WARNING: IMPROPER INSTALLA­TION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAM­AGE. REFER TO THIS MANUAL. FOR ASSIST ANCE OR ADDITIONAL INFOR­MATION CONSULT A QUALIFIED IN­ST ALLER, SERVICE AGENCY , OR THE GAS SUPPLIER.
- Do not store or use gasoline or other flam­mable vapors and liquids in the vicinity of this or any other appliance.
- What to do if you smell gas
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call
the fire department.
- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Quadra-Fire, a brand of Hearth & Home Technologies 1445 North Highway, Colville, WA 99114
Printed in U.S.A. Copyright 2006
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 481 1534, 5000162, 5016609, 5076254, 51 13843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or other U.S. and foreign patents pending.
In the Commonwealth of Massachusetts:
• installation must be performed by a licensed plumber or gas fitter;
See T able of Content s for location of additional Commonwealth of Massachusetts requirements.
1.This appliance may be installed in an af­termarket, permanently located, manufac­tured (mobile) home, where not prohibited by local codes.
2. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Please contact your Quadra-Fire dealer with any questions or concerns. For the number of your nearest Quadra-Fire dealer, please visit www .quadrafire.com.
1Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
SAFETY AND WARNING INFORMATION
READ and UNDERSTAND all instructions carefully
!
before starting the installation. FAILURE TO FOLLOW these installation instructions may result
in a possible fire hazard and will void the warranty.
Prior to the first firing of the fireplace, READ the
!
Using Your Fireplace section of the Owners Guide.
DO NOT USE this appliance if any part has been
!
under water. Immediately CALL a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.
THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
!
Installation and repair should be PERFORMED by a qualified service person. The appliance and venting
!
system should be INSPECTED before initial use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is IMPERATIVE that the unit’s control compartment, burners, and circulating air passageways adequate combustion and ventilation air.
BE KEPT CLEAN to provide for
These units MUST use one of the vent systems described in the Installing the Fireplace section of
!
the Installers Guide. NO OTHER vent systems or components MAY BE USED.
This gas fireplace and vent assembly MUST be
!
vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance MUST USE a separate vent system. Common vent systems are
PROHIBITED.
INSPECT the external vent cap on a regular basis to
!
make sure that no debris is interfering with the air flow.
The glass door assembly MUST be in place and
!
sealed, and the trim door assembly MUST be in place on the fireplace before the unit can be placed into safe operation.
DO NOT OPERATE this appliance with the glass
!
door removed, cracked, or broken. Replacement of the glass door should be performed by a licensed or qualified service person. DO NOT strike or slam the glass door.
Always KEEP the appliance clear and free from
!
combustible materials, gasoline, and other flammable vapors and liquids.
NEVER OBSTRUCT the flow of combustion and
!
ventilation air. Keep the front of the appliance CLEAR of all obstacles and materials for servicing and proper operations.
Due to the high temperature, the appliance should be LOCATED out of traffic areas and away from
!
furniture and draperies. Clothing or flammable material SHOULD NOT BE PLACED on or near the appliance.
Children and adults should be ALERTED to the
!
hazards of high surface temperature and should ST AY A WA Y to avoid burns or clothing ignition. Y oung children should be CAREFULL Y SUPERVISED when they are in the same room as the appliance.
The glass door assembly SHALL ONLY be
!
replaced as a complete unit, as supplied by the gas fireplace manufacturer. NO SUBSTITUTE material may be used.
DO NOT USE abrasive cleaners on the glass door
!
assembly. DO NOT ATTEMPT to clean the glass door when it is hot.
Turn off the gas before servicing this appliance. It is recommended that a qualified service technician
!
perform an appliance check-up at the beginning of each heating season.
Any safety screen or guard removed for servicing
!
must be replaced before operating this appliance.
DO NOT place furniture or any other combustible household objects within 36 inches of the fireplace
!
front.
2 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
TABLE OF CONTENTS
Safety and Warning Information ......................................................... 2
Service Parts Lists.................................................................................4
Section 1: Approvals and Codes.......................................................... 9
Appliance Certification ............................................................................. 9
Installation Codes .................................................................................... 9
High Altitude Installations ........................................................................ 9
Requirements for the Commonwealth of Massachusetts........................ 10
Section 2: Getting Started .................................................................. 11
Introducing the Village Collection Gas Fireplaces .................................. 1 1
Pre-installation Preparation.................................................................... 11
Section 3: Installing the Fireplace..................................................... 14
Constructing the Fireplace Chase .......................................................... 14
Step 1 Locating the Fireplace........................................................... 14
Step 2 Framing the Fireplace ........................................................... 15
Step 3 Installing the Vent System .................................................... 18
A. Vent System Approvals ................................................... 18
B. Installing V ent Components............................................. 28
C. Vent Termination .............................................................. 31
Step 4 Positioning, Leveling, and
Securing the Fireplace .......................................................... 34
Step 5 The Gas Control Systems..................................................... 34
Step 6 The Gas Supply Line............................................................. 35
Step 7 Gas Pressure Requirements................................................. 35
Î
Í
Step 8 Wiring the Fireplace .............................................................. 36
Step 9 Finishing ............................................................................... 37
Step 10 Installing Trim, Logs, and Ember Material ............................. 3 7
Shutter Settings.................................................................... 37
Placing the Ember Material................................................... 38
Step 1 1 Before Lighting the Fireplace................................................. 38
Step 12 Lighting the Appliance ........................................................... 39
After the Installation ............................................................................... 39
Section 4: Maintaining and Servicing Your Fireplace .................... 40
Section 5: Troubleshooting ............................................................... 41
Limited Lifetime Warranty ...................................................................... 43
Î = Contains updated information.
3Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Service Parts
QV32B-A
Î
(NG , LP) Exploded Parts Diagram
Beginning Manufacturing Date: 6-03
Ending Manufacturing Date: ______
4
1
5
3
Part number list on following page.
2
6
8 Log Set Assembly
12
11
7
13
9
10
4 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
(NG , LP) Service Part s List
QV32B-A
IMPORTANT: THIS IS DA TED INFORMA TION. The most current information is located on your
Î
dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.
ITEM STANDING PILOT IGNITION SERIAL # PART NUMBER
Burner Orifice NG (#38C) 582-838 Y Burner Orifice LP (1.55mmC) 582-8155 Y
1 Andirons, Cast 80784 2 Burner 3 Glass Door Assembly GLA-550TRS Y
4 Log Grate 2014-001 5 Base Pan NG, LP 2014-100
6 Refractory Kit (Sold as set only) BRICK-293-2 7 J unc tio n Box 100-250A Y 8 Log Set Assembly LOGS-2014 Y 9Log 1 SRV2014-701
10 Log 2 SRV2014-703 11 Log 3 SRV2014-702 12 Log 4 SRV780-707 13 Log 5 SRV2014-704
Pilot Orifice NG Pilot Orifice LP
Thermocouple
Thermopile Lava Rock 060-721
Mineral Wool 050-721 Exhaus t R es t ric t or 530-299 Glass Latch Assembly 386-122A Y
Regulator NG
Regulator LP
ACCESSORIES
Fan Kit GFK-160A Wall Switch Kit, Off-white WSK-21-HTI Wall Switch Kit, White WSK-21-W-HTI
Conversion Kit NG
Conversion Kit LP Door Front - Remington Ave. DF-32RA-BK
Door Front - Remington Ave. DF-32RA-HP Door Front - Sun Prairie Operable DF-32SPO-BK Door Front - Sun Prairie Operable DF-32SPO-HP Door Front - Sun Prairie Operable DF-32SPO-VC Do o r Fro nt - Town S quare DF-32TS-BK Do o r Fro nt - Town S quare DF-32TS-HP Door Front - Harmony Hall DF-32HH-B K
Hood, Black SRV550-175 Hood, Hammered Pewter SRV550-175-HP Hood, Hammered Pewter SRV550-175-HP
Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
2014-004 2014-014
446-505 2103-116 446-517 2103-117 446-511 2103-511
060-512 2103-512
060-518 230-1570 060-519 230-1520
NGK-2014 NGKS-2014 LPK-2014 LPKS-2014
AVAILABLE
TO SHIP IN
24 HOURS
Í
Y
Y Y
Y
Y
Y Y
Y Y
Y
Y
5Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Service Parts
QV36B-A
Î
(NG , LP) Exploded Parts Diagram
2
Beginning Manufacturing Date: 6-03
Ending Manufacturing Date: ______
1
3
4
7
6
5
8 Log Set Assembly
12
13
9
10
11
6 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
(NG, LP) Service Parts List
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your
dealers VIP site. When ordering, supply serial and model numbers to ensure correct service parts.
ITEM STANDING PILOT IGNITION SERIAL # PART NUMBER
Î
Burner Orifice NG (#38C) 582-838 Y Burner Orifice LP (1.55mmC) 582-8155 Y
1 Andirons, C ast 80784 2Burner 3 G las s Do or As se mb ly GLA-550TRS Y
4 Log Grate 2014-001 5 Base Pan NG, LP 2014-100
6 Refractory Kit (Sold as set only) BRICK-293-2 7 J unc ti on B ox 100-250A Y 8 Log Set Assembly LOGS-2014 Y 9 Log 1 SRV2014-701
10 Log 2 SRV2014-703 11 Log 3 SRV2014-702 12 Log 4 SRV780-707 13 Log 5 SRV2014-704
Pilot Orifice NG Pilot Orifice LP
Thermocouple
Thermopile Lava Rock 060-721
Mineral Wool 050-721 Exhaus t R e s tr i c t o r 530-299 Glass Latch Assembly 386-122A Y
Regulator NG Regulator LP
ACCESSORIES
Fan Kit GFK-160A Wall Switch Kit, Off-white WSK-21-HTI Wall Switch Kit, White WSK-21-W-HTI
Conversion Kit NG
Conversion Kit LP Doo r F ront - Re m i ng to n Ave. DF-32RA-BK
Doo r F ront - Re m i ng to n Ave. DF-32RA-HP Door Front - Sun Prairie Operable DF-32SPO-BK Door Front - Sun Prairie Operable DF-32SPO-HP Door Front - Sun Prairie Operable DF-32SPO-VC Doo r F ro nt - Town Squa re DF-32TS-BK Doo r F ro nt - Town Squa re DF-32TS-HP Doo r F ro nt - Harm o ny Ha ll DF -3 2 HH-B K
Hood, Black SRV550-175 Hood, Hammered Pewter SRV550-175-HP Hood, Hammered Pewter SRV550-175-HP
Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
Pre 10-06 Post 10-06 Pre 10-06 Post 10-06
2014-004 2014-014
446-505 2103-116 446-517 2103-117 446-511 2103-511
060-512 2103-512
060-518 230-1570 060-519 230-1520
NGK-20 1 4 NGKS -2 0 1 4 LPK-2014 LPKS-2014
QV36B-A
AVAILABLE
TO SHIP IN
24 HOURS
Í
Y
Y Y
Y
Y
Y Y
Y Y
Y
Y
7Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Service Parts
QV32B-A, QV36B-A
Î
Standing Pilot Ignition
Valve Assembly
13
10
11
12
(NG , LP) Exploded Parts Diagram
5
8
9
7
1
Beginning Manufacturing Date: 6-03
Ending Manufacturing Date: ______
6
4
3
2
AVAILAB LE
TO S HIP IN
24 HOURS
ITEM DESCRIPTION SERIAL # PART N UMBE R
1ON/OFF Rocker Switch 060-521A Y
2Valve NG
2 Valve LP 3 Flexible Gas Connector 530-302A Y
4 Valve Plate Gasket 530-431 5Burner Neck Gasket 2046-407
6Pilot Assembly NG 6 Pilot Assembly LP
7Wire Assembly 049-552a 8 Valve Bracket 9 Fle x B all Valve As s embly 302-320A Y
10 Piezo Ignitor 291-513 Y
11 Pilot Control Knob 12 Flame Control Knob 13 Control Panel
14 Shutter Bra c ket Assem b ly 2026-017 Y
Pilot Bracket Shutter Sleeve 2026-130
PRE 10-06 POST 10-06
PRE 10-06 POST 10-06
PRE 10-06 POST 10-06 PRE 10-06 POST 10-06
PRE 10-06 POST 10-06
PRE 10-06 POST 10-06 PRE 10-06 POST 10-06 PRE 10-06 POST 10-06
PRE 10-06 POST 10-06
060-522 230-0710
060-523 230-0720
530-510A 2103-010 530-511A 2103-011
2025-101 2025-101, 2044-155
291-530 571-531 291-531 571-534 291-119 291-125
2065-117 N/A
Y
Y
Y Y
8 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
1
Approvals and Codes
Appliance Certification
The Village Collection fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the applicable laboratories.
Certification
MODELS: QV32B-A, QV36B-A LABORA TORY : Underwriters Laboratories TYPE: Vented Gas Fireplace Heater STANDARD: ANSI Z21.88•CSA2.33•UL307B
NOTE: THESE MODELS ARE UL LISTED TO UL307B, THE ST ANDARD FOR GAS-BURNING HEATING APPLI­ANCES FOR MANUFACTURED HOMES AND RECRE-
A TIONAL VEHICLES.
Installation Codes
The fireplace installation must conform to local codes. Before installing the fireplace, consult the local building code agency to ensure that you are in compliance with all applicable codes, including permits and inspections.
High Altitude Installations
U.L. Listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2,000 feet in the U. S. A. and in Canada.
When installing this appliance at an elevation above 2,000 feet, it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a 2000 foot elevation in the U.S.A. or 10% for elevations between 2000 and 4500 feet in Canada. If the heating value of the gas has been reduced, these rules do not apply . To identify the proper orifice size, check with the local gas utility.
If installing this appliance at an elevation above 4,500 feet (in Canada), check with local authorities.
In the absence of local codes, the fireplace installation must conform to the National Fuel Gas Code ANSI Z223.1 (in the United States) or the CAN/CGA-B149 Installation Codes (in Canada). The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes with the National Electric Code ANSI/NFPA No. 70 (in the United States), or to the CSA C22.1 Canadian Electric Code (in Canada).
These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.
9Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.
Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, includ­ing but not limited to decks and porches, the following re­quirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall hori­zontal vented gas fueled equipment. It shall be the respon­sibility of the property owner to secure the services of qual­ified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and bat­tery back-up may be installed on the next adjacent floor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFP A 720 and be ANSI/UL 2034 listed and IAS certified.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installa­tion unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFP A 54 as adopted by the Board; and
• Product Approved side wall horizont ally vented gas fu­eled equipment installed in a room or structure sepa­rate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall hor­izontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installa­tion of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be sat­isfied by the manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the ex­haust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
10 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
2
Getting Started
Introducing the Village Collection Gas Fireplaces
The Village Collection direct vent gas fireplaces are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.
The information contained in this Installers Guide, unless noted otherwise, applies to all models and gas control systems. Gas fireplace diagrams, including the dimensions, are shown in this section.
Pre-install Preparation
This gas fireplace and its components are tested and safe when installed in accordance with this Installers Guide. Report to your dealer any parts damaged in shipment, particularly the condition of the glass. Do not install any
unit with damaged, incomplete, or substitute parts.
The vent system components and trim doors are shipped in separate packages. The gas logs are packaged separately and must be field installed.
Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit. Failure to follow these instructions will void the owner’s warranty and may present a fire hazard.
The Quadra-Fire Warranty will be voided by , and Hearth & Home Technologies disclaims any responsibility for, the following actions:
• Installation of any damaged fireplace or vent system
component.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Hearth & Home
T echnologies .
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not manu-
factured and approved by Hearth & Home T echnologies, not withstanding any independent testing laboratory or other party approval of such component part or acces­sory.
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARD.
When planning a fireplace installation, it’s necessary to determine:
Where the unit is to be installed.
The vent system configuration to be used.
Gas supply piping.
Electrical wiring.
Framing and finishing details.
Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
If the fireplace is to be installed on carpeting or tile, or on any combustible material other than wood flooring, the fireplace should be installed on a metal or wood panel that extends the full width and depth of the fireplace.
11Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
15-5/16
(389mm)
30-11/16 (779mm)
1/2
(13mm)
40
(1016mm)
GAS LINE
ACCESS
5-1/16
(129mm)
(402mm)
2-1/8
(55mm)
15-7/8
(905mm)
35-5/8
36-1/8
(917mm)
40-15/16
(1040mm)
Ø 6-5/8
(168mm)
8-3/4
(223mm)
25
(635mm)
16-3/8
(414mm)
3-9/16
(90mm)
ELECTRICAL
ACCESS
6-7/8
(174mm)
Ø 8
(203mm)
37-3/4
(960mm)
GAS
ACCESS
RATING PLATE/
LABELS
TOP
STANDOFFS
GAS
CONTROLS
ELECTRICAL
ACCESS
Figure 1. Diagram of the QV36B-A
12 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
12-7/8
(326mm)
25-11/16
(653mm)
1/2
(13mm)
35-7/16
(901mm)
GAS LINE
ACCESS
2-1/8
(55mm)
5-1/16
(129mm)
15-7/8
(402mm)
32-1/8
(815mm)
31-1/8
(790mm)
36
(913mm)
Ø6-5/8
(168mm)
8-13/16
(223mm)
21-7/16
(545mm)
16-3/8
(414mm)
Ø8
(203mm)
32-9/16
(828mm)
3-1/3
(90mm)
ELECTRICAL
ACCESS
6-7/8
(174mm)
GAS
ACCESS
RATING PLATE/
LABELS
TOP
STAN DOFFS
GAS
CONTROLS
ELECTRICAL
ACCESS
Figure 2. Diagram of the QV32B-A
13Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Installing the Fireplace
3
Constructing the Fireplace Chase
A chase is a vertical box-like structure built to enclose the gas fireplace and/or its vent system. Vertical vent s that run on the outside of a building may be, but are not required to be, installed inside a chase.
3” MIN. (76mm)
B
A
E
D
CAUTION: TREA TMENT OF FIREST OP SPACERS AND CONSTRUCTION OF THE CHASE MA Y V ARY WITH THE TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES. THEREFORE, YOUR LOCAL BUILD­ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS.
Factory-built fireplace chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.
This means that the walls, ceiling, base plate and cantilever floor of the chase should be insulated. V apor and air infiltra­tion barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, the inside sur­faces may be sheetrocked and taped for maximum air tight­ness.
T o further prevent draft s, the firestops should be caulked to seal gaps. Gas line holes and other openings should be caulked or stuffed with insulation. If the unit is being in­stalled on a cement slab, a layer of plywood may be placed underneath to prevent conducting cold up into the room. Be sure to include spark arrestors for woodburning units if they are required.
THE CHASE SHOULD BE CONSTRUCTED SO THA T ALL CLEARANCES TO THE FIREPLACE ARE MAINT AINED AS SPECIFIED WITHIN THIS INST ALLERS GUIDE.
Step 1. Locating the Fireplace
The following diagram shows space and clearance require­ments for locating a fireplace within a room.
Clearance Requirements
The top and back of the fireplace are defined by stand-offs. The minimum clearance to a perpendicular wall extending past the face of the fireplace is 3 inches (76mm). The back of the fireplace may be recessed 16 1/4 inches (413mm) into combustible construction.
C
1/2 “ MIN. (13mm)
ABC*D*E*
QV36B-A 42” 16 1/4” 31 7/8” 4 5 ” 63 3/4” QV32B-A 37” 16 1/4” 29 3/8” 41 1/2” 58 3/4”
*If venting with (2) 900 elbows off rear of unit the dimensions C, D and E will change.
Figure 4. Fireplace Dimensions, Locations, and Space Requirements
Minimum Clearances
from the Fireplace to Combustible Materials
Inches mm
Glass Front......................................3 6........ 91 4
Floor .................................................0........... 0
Rear ................................................ 1/2 ........ 13
Sides .............................................. 1/2 ........ 13
Top (QV36B-A) .............................3 1/4 ....... 83
(QV32B-A) .............................1 1/2....... 3 8
Ceiling* ............................................31........ 787
* The clearance to the ceiling is measured from the top
of the unit, excluding the standoffs (see Figure 37).
The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the com­bustible construction, NOT from the screw heads that se­cure the unit together.
Minimum Clearances
from the Vent Pipe to Combustible Materials
Inches mm
Vertical Sections. ............. 1 ................ 25
Horizontal Sections
Top..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
At Wall Firestops
Top..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
For minimum clearances, see the direct vent termination clearance in Figures 30 and 31.
14 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Step 2. Framing the Fireplace
E
Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommo­date wall coverings and fireplace facing material. The dia­gram below shows framing reference dimensions.
NON-COMBUSTIBLE ZON
IS DEFINED BY 3” ABOVE THE
ELBOW FOR THE ENTIRE
WIDTH AND DEPTH (BEHIND THE
FRONT HEADER) OF THE FIREBOX.
3
WALL STUD
CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DET AILS BEFORE FRAMING .
3 1/2”
Framing should be constructed of 2 X 4 lumber or heavier.
The framing headers may rest on the fireplace stand-offs.
VENT
FRAMING
HOLE
WARNING:
To ensure proper clearances the front framing header must be installed on its narrow edge and to the front of the frame.
B
C
A
*The center of the framing hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.
Model A B C D E *
QV36B-A 42” 38-1/4” 16-1/4” 41” 27-7/8” QV32B-A 37” 33” 16-1/4” 36-1/2” 24-3/8”
Figure 5. Framing Dimensions
E
D
15Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
12-3/16
MAX.
DVP12
12
2
MIN.
6
4
DVP4
DVP6
14-1/4
24
9-7/8
DVP12A
10-1/4
DVP45
45.0
36
48
O
DVP24
DVP36
11-1/4
7-1/4
1-1/4 TYP
1/2 TYP
NOTE: PIPES OVERLAP 1-1/4 INCHES
(34.93mm) A T EACH JOINT.
12-9/16
P
V
D
9
8-9/16
T
S
0
Figure 6. DVP-Series Direct Vent Component Specifications (5-inch inner pipe / 8-inch outer pipe)
16 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
DVP48
9 1/4
6 5/8
6 1/2
6 3/8
6 3/8
6 1/2
9 5/8
8 3/4
17-24
SL-09D
SL-45D
SL-12/17D (SL12-17D)
12-17
23 3/4
6 5/8
SL-24D
SL-90D
35 3/4
9 5/8
SL-36D
SL-48D
47 3/4
SL-17/24D
(SL17-24D)
SL-FLEX-10
SL-FLEX-5
SL-FLEX-3
36”
(914mm)
11 3/4
60”
(1524mm)
SL-12D
120”
(3048mm)
6 1/2
5 3/4
6 5/8
SL-06D
NOTE: PIPES OVERLAP 1-3/8 INCHES
(34.93mm) A T EACH JOINT.
SL-FLEX-2
24”
(610mm)
Figure 7. SL D-Series Direct Vent Component Specifications (4-inch inner pipe / 6 5/8-inch outer pipe)
17Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Step 3. Installing the Vent System
A. Vent System Approvals
These models have vent starting collars on both the top and the back of the unit. Depending upon the installation, decide which ONE set of starting collars will be used to attach the vent system. The starting collar sealing cap must remain on the starting collar NOT used.
These models use SL-D-series, direct vent components when using the TOP vent collars. This pipe is tested and listed as an approved component of the fireplace. The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall. There is no required pitch for horizontal vent runs.
These models also use DVP-series direct vent components when using the REAR vent collars.
The flame and ember appearance may vary based on the type of fuel burned and the venting configuration used.
WARNING: YOU MUST NOT MIX DVP-SERIES
!
AND SL D-SERIES COMPONENTS IN ANY VENT SYSTEM CONFIGURA TION.
Identifying Vent Components
Approved vent system components are labeled for identifi­cation. NO OTHER VENTING SYSTEMS OR COMPO- NENTS MAY BE USED. Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide. Figure 8 shows vent system components and terminations.
The vent systems installed on this gas fireplace may in­clude one, two, or three 90° elbow assemblies. The rela­tionships of vertical rise to horizontal run in vent configura­tions using 90° elbows MUST BE strictly adhered to. The rise to run relationships are shown in the venting drawings and tables. Refer to the diagrams on the next several pages.
NOTE: Two 45° elbows may be used in place of one 90° elbow. Maximum and minimum rise to run ratios must always be maintained in the vent system when
using 45° elbows.
Vent System T ermination Kit s
DVP-SERIES
DVP-TVHW
DVP-TRAP
DVP-TB1
(Required to have a minimum of 3 feet of vertical in the vent system)
**
PVK-80
(For use with both DVP and SL-D venting)
SL D-SERIES
DVP-TV
HORIZONTAL TERMINATION
WALL
FIRESTOP
90 DEGREE ELBOW
Vent System Component s
VERTICAL TERMINATION
CEILING FIRESTOP
STORM COLLAR
ROOF FLASHING
HORIZONTAL PIPE SUPPORT
(SL-Series)
PIPE LENGTH
WALL BRACKET
(SL-Series)
SLK-SNKD
(There
MUST be a 25% reduction in total H when using the snorkel cap except when using the simple up and out installation (see Fig. 9)
SLK-01TRD SLK-01TRF
*
SLK-991DA
* For use with flex vent only.
SL-FLEX2-01TRF
Figure 8. Vent System Components and Termination Kits
18 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Flex Vent
V
The flex vent must be supported with the spacing between support intervals not exceeding 4 feet, with no more than ½ inch sag between supports.
A support is required at each change in venting direction, and in any location where it is necessary to maintain the necessary clearance to combustibles. A simple “up and out” installation (Figure 9) requires only enough support to main­tain the necessary clearance to combustibles. However, the vent attachment point and the firestop location are consid­ered to be supports.
TERMINATION
3” CLEARANCE
FLEX-VENT
CAP
1”
CLEARANCE
CAP
STRAIGHT UP
VERTICAL VENTING
V (FT .)
45' MAX.
NOTE: For vertical venting over 20 feet a restrictor plate is recommended for improved flame appearance.
Use SL D-Series
components only .
Figure 9.
STRAIGHT OUT HORIZONT AL VENTING
H
Max. Run
36" (914 mm)
Use DVP-Series
components only .
H
Figure 10. Straight up Vertical Venting
90-DEGREE
ELBOWS
Use two 900 elbows for corner installations. The use of two 900 elbows in a corner installa­tion will affect space requirements (see Fig. 4)
Figure 11. Straight Out Horizontal Venting
19Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V H 1' MIN. (305mm) 2' MAX. (610mm) 2' MIN. (610mm) 4' MAX. (1.22m) 3' MIN. (914mm) 6' MAX. (1.86m) 4' MIN. (1.22m) 8' MAX. (2.4m) V+H=40' MAX. (12.4m) H = 8' MAX. (2.4m)
Use DVP-Series
components only .
Figure 12. Venting with One 90° Elbow
V
H
Use SL D-Series
components only .
VENTING WITH ONE (1) 90o ELBOW NATURAL GAS
V (MIN.)
90o Elbow on Top 1 FT (305mm) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 5 FT (1.52m)
H MAX. = 16 FT (4.8m) V + H MAX. = 40 FT (12.2m)
VENTING WITH ONE (1) 90o ELBOW PROPANE
V (MIN.) H (MAX.)
90o Elbow on Top NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m)
H MAX. = 16 FT (4.8m) V + H MAX. = 40 FT (12.2m)
H (MAX.)
2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m)
H
V
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installa­tion (see Figure 9).
Figure 13. Venting with One 90° Elbow
20 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V H H + H
V
1
1' MIN. (305 mm) 2' MAX. (610 mm) 4' MAX. (1.22m) 2' MIN. (610 mm) 4' MAX. (1.22 m) 8' MAX. (2.4m) 3' MIN. (914 mm) 6' MAX. (1.86 m) 12' MAX. (3.6m) 4' MIN. (1.22 m) 8' MAX. (2.48 m) 16' MAX. (4.8m)
V+H+H1 = 40' MAX. (12.4 m) H = 8' MAX. (2.48 m) H+H1 = 16' MAX. (4.8m)
H
1
Use DVP-Series
components only .
V (FT) H + H1 (FT)
1' MIN. (305 mm) 2' MAX. (610 mm) 2' MIN. (610 mm) 4' MAX. (1.22 m)
3' MIN. (914 mm) 6' MAX. (1.86 m) 4' MIN. (1.22 m) 8' MAX. (2.48 m)
V
H + H V + H + H
= 40' (12.2m) MAX.
1
= 8' MAX. (2.48 m)
1
H
H
1
H
Figure 14. Venting with Two 90° Elbows
21Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
VENTING WITH TWO (2) 90o ELBOWS NATURAL GAS
V (MIN.)
90o Elbow on Top 1 FT (305mm) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 5 FT (1.52m)
MAX. = 16 FT (4.8m) V + H + H1 MAX. = 40 FT (12.2m)
H + H
1
H + H1 (MAX.)
2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m)
VENTING WITH TWO (2) 90o ELBOWS PROP ANE
V (MIN.) H + H1 (MAX.)
90o Elbow on Top NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m)
H + H1 MAX. = 16 FT (4.8m) V + H + H1 MAX. = 40 FT (12.2m)
H
1
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 9).
Use SL D-Series
components only .
V
H
Figure 15. Venting with Two 90° Elbows
22 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V
VENTING WITH TWO (2) 90o ELBOWS NATURAL GAS
V (MIN.)
90o Elbow on Top 1 FT (305mm) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 5 FT (1.52m)
H MAX. = 16 FT (4.8m) V + V
H (MAX.)
2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m)
+ H MAX. = 40 FT (12.2m)
1
VENTING WITH TWO (2) 90o ELBOWS PROP ANE
V (MIN.) H (MAX.)
90o Elbow on Top NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m)
H MAX. = 16 FT (4.8m) V + V
+ H MAX. = 40 FT (12.2m)
1
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installa­tion (see Figure 9).
H
V
1
Use SL D-Series components only .
Figure 16. Venting with Two 90° Elbows
23Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V H H + H
V
1' MIN. (305 mm) 2' MAX. (610mm) 4' MAX. (1.22m)
1
2' MIN. (610 mm) 4' MAX. (1.22m) 8' MAX. (2.48m) 3' MIN. (914 mm) 6' MAX. (1.86m) 12' MAX. (3.72m) 4' MIN. (1.22 m) 8' MAX. (2.48m) 16' MAX. (4.8m)
V1+V+H+H1 = 40' MAX. (12.4m) H = 8' MAX. (2.48m) H+H1 =16' MAX. (4.8m)
V
1
H
1
H
H
2
Use DVP-Series
components only .
V H H + H1 + H
2
1' MIN. (305 mm) 2' MAX. (610 mm) 4' MAX. (1.22m) 2' MIN. (610 mm) 4' MAX. (1.22 m) 8' MAX. (2.48m) 3' MIN. (914 mm) 6' MAX. (1.86 m) 12' MAX. (3.72m) 4' MIN. (1.22 m) 8' MAX. (2.48 m) 16' MAX. (4.8m)
V+H+H1+H2 = 40' MAX. (12.4 m) H = 8' MAX. (2.48m) H + H1 + H2 = 16' MAX. (4.8m)
V
H
1
H
Figure 17. Venting with Three 90° elbows
24 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V1V
VENTING WITH THREE (3) 90o ELBOWS
NATURAL GAS
V (MIN.) H (MAX.) H + H1 (MAX.)
90o Elbow on T op 2 FT (610mm) 4 FT (1.22m) 1 FT (305mm) 3 FT (914mm) 6 FT (1.86m) 2 FT (610mm) 4 FT (1.22m) 8 FT (2.48m) 3 FT (914mm) 6 FT (1.86m) 12 FT (3.72m) 4 FT (1.22m) 8 FT (2.48m) 16 FT (4.8m) 5 FT (1.52m) 16 FT (4.8m) 16 FT (4.8m)
V + H + V
+ H1 MAX. = 40 FT (12.2m)
1
H
1
VENTING WITH THREE (3) 90o ELBOWS
PROPANE
V (MIN.) H (MAX.) H + H1 (MAX.)
o
90
Elbow on T op NOT ALLOWED NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 4 FT (1.22m) 2 FT (610mm) 4 FT (1.22m) 8 FT (2.48m) 3 FT (914mm) 6 FT (1.86m) 12 FT (3.72m) 4 FT (1.22m) 8 FT (2.48m) 16 FT (4.8m) 5 FT (1.52m) 16 FT (4.8m) 16 FT (4.8m)
V + H + V
+ H1 MAX. = 40 FT (12.2m)
1
H
Use SL D-Series
components only .
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 9).
Figure 18. Venting with three 90° elbows
25Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V
VENTING WITH THREE (3) 90o ELBOWS NA TURAL GAS
Model: QV32B-A
V (MIN.) H + H1 (MAX.)
o
Elbow on Top 2 FT (610mm)
90 1 FT (305mm) 3 FT (914mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m)
H + H
MAX. = 16 FT (4.8m) V + V1 + H + H1 MAX. = 40 FT (12.2m)
1
Model: QV36B-A H + H
(MAX.)
1
2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m)
VENTING WITH THREE (3) 90o ELBOWS PROPANE
V (MIN.) H + H1 (MAX.)
o
90
Elbow on Top NOT ALLOWED 1 FT (305mm) 2 FT (610mm) 2 FT (610mm) 4 FT (1.22m) 3 FT (914mm) 6 FT (1.86m) 4 FT (1.22m) 8 FT (2.48m) 5 FT (1.52m) 16 FT (4.8m)
H + H
MAX. = 16 FT (4.8m) V + V1 + H + H1 MAX. = 40 FT (12.2m)
1
V
1
H
1
H
Use SL D-Series
components only .
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 9).
Figure 19. Venting with three 90° elbows
26 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
V
H
VENTING WITH FOUR (4) 90° ELBOWS
1
NATURAL AND PROP ANE GAS
V (MIN.) H (MAX.)
2' (609mm) 5' (1.52m)
V + V1 + V2 + H + H1 MAX. = 40' (12.2m)
V
2
1
V1 (MIN.) H1 (MAX.) V2 (MIN.)
5' (1.52m) 5' (1.52m) 4.5' (1.37m)
H
V
Figure 20. Venting with Four 90° elbows
Use SL D-Series
components only .
NOTE: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installa­tion (see Figure 9).
27Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
B. Installing V ent Component s
After determining which set of starting collars will be used (top or rear), follow venting instructions accordingly .
Venting Out the Rear V ent (See Figure 21) Remove the installed rear seal cap from the rear starting collars
by cutting the strap at each end. Remove the insulation inside the 5” collar. Follow the vent configuration tables accordingly .
Remove the 5” diameter heat shield from the 5” diameter collar by sliding it out.
DVP Series V enting Only:
1. Attaching the Venting to the Fireplace
Refer to Cinch Pipe and Termination Cap installation in­structions.
WARNING: ENSURE THAT THE FIBERGLASS
!
GASKET SUPPLIED WITH THE FIREPLACE SEALS BETWEEN THE FIRST VENT COMPONENT AND THE OUTER FIREPLACE WRAP .
WARNING: THE TOP HEAT SHIELD (INSIDE
!
THE FIREBOX) MUST REMAIN A TTACHED IF THE VENT SYSTEM IS ATTACHED TO THE REAR ST ARTING COLLARS. SEE FIGURE 21.
Venting Out the Top Vent
Remove the top vent collar seal cap by cutting the strap at each end. Remove the insulation inside BOTH the 4” diameter and 6 5/8” diameter collars. (See Figure 21).
Remove the 4” diameter heat shield from the 4” diameter collar by sliding it out.
Y ou have to take the glass off for positioning the logs when the unit is finally installed in place and finished around it. Att ach vent system to the top starting collars.
WARNING: THE REAR VENT COLLAR SEAL
!
CAP MUST REMAIN A TT ACHED TO THE REAR VENT COLLARS IF THE VENT SYSTEM IS A TT ACHED TO THE TOP ST ARTING COLLARS. SEE FIGURE 21.
WARNING: FAILURE T O REMOVE INSULATION
!
IN THE SET OF COLLARS YOU ARE USING COULD NEGATIVELY AFFECT FIREPLACE PERFORMANCE.
If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and
Vent Termination.
2. Continue Adding V ent Component s
Refer to Cinch Pipe and Termination Cap installation in­structions.
• Continue adding vent components, locking each succeed­ing component into place.
• Ensure that each succeeding vent component is secure­ly fitted and locked into the preceding component in the vent system.
• 90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an el­bow does not end up in a locked position with the pre­ceding component, attach with a minimum of two (2) sheet metal screws.
3. Install Support Brackets
Refer to Cinch Pipe and Termination Cap installation in­structions.
Go to Step 4 Install Firestops.
WARNING: YOU MUST LEAVE THE INSULA-
!
TION IN PLACE IN THE SET OF COLLARS YOU ARE NOT USING . F AILURE TO DO THIS COULD CAUSE A FIRE.
SEAL
CAP
Venting
Out T op
HEAT
SHIELD
INSULATION,
DISCARD
BOTH
PIECES
Insert screwdriver
or similar object
here to remove cap.
CUT HERE
Venting
Out Rear
HEAT
SHIELD
DISCARD
INSULATION
SEAL
CAP
Figure 21.
28 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
SL-D and SL-Flex Series Venting Only:
1. Attach the First Vent Component to the Starting Collars
To attach the first vent component to the starting collars of the fireplace:
• Lock the vent components into place by sliding the con­centric pipe sections with four (4) equally spaced interior beads into the fireplace collar or previously installed com­ponent end with four (4) equally spaced indented sections.
• When the internal beads of each outer pipe line up, ro­tate the pipe section clockwise about one-quarter (1/4) turn. The vent pipe is now locked together .
• Slide the ceramic fiber pad over the first vent section and place it flush to the fireplace (see Figure 1). This will prevent cold air infiltration. High temp caulk may be used to hold the part in place. Continue to add vent compo­nents.
Figure 22. Adding V enting Components
3. Install Support Brackets For Horizontal Runs - The vent system must be supported
every five (5) feet of horizontal run by a horizontal pipe support. T o inst all support brackets for horizontal runs:
• Place the pipe supports around the vent pipe.
• Nail the pipe supports to the framing members.
If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and
Vent Termination.
2. Continue Adding V ent Component s
• Continue adding vent components, locking each succeed­ing component into place.
• Ensure that each succeeding vent component is secure­ly fitted and locked into the preceding component.
• 90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an el­bow does not end up in a locked position with the pre­ceding component, attach with a minimum of two (2) sheet metal screws.
For Vertical Runs - The vent system must be supported every eight (8) feet (2.4m) above the fireplace flue outlet by wall brackets. To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws.
WALL BRACKET
WALL STUD
8 FT. (2.4m)
FLUE
OUTLET
1 INCH MIN.
(25.4mm)
Figure 23. Installing Support Brackets
Go to Step 4 Install Firestops.
29Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
DVP, SL-D and SL-Flex Series Venting:
V
STEP 4. Install Firestops For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.
NOTE: Model DVP-TRAP or SLK-01TRD does not need an exterior firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through either interior or exterior walls:
For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.
T o install firestops for vertical runs that pass through ceilings:
• Position a plumb bob directly over the center of the verti­cal vent component.
• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
Cut a 12” x 10“ (305mm x 25mm) hole through the wall for DVP-series or a 10” x 10” (254mm x 254mm) hole for SL-D­series pipe. The center of the framing hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.
• Position the firestops on both sides of the hole previ­ously cut and secure the firestops with nails or screws.
• The heat shields of the firestops MUST BE placed to­wards the top of the hole.
• Continue the vent run through the firestops.
NOTE: There must be NO INSULA TION or other combustibles inside the framed firestop opening.
10"
(254mm)
1" (25.4 mm)
12"(DVP) or 10" (SL)
(305mm or 254mm)
• Check the floor above for any obstructions, such as wir­ing or plumbing runs.
• Reposition the fireplace and vent system, if necessary, to accommodate the ceiling joists and/or obstructions.
• Cut a 10-inch X 10-inch (254mm X 254mm) hole through the ceiling, using the centerpoint previously marked.
• Frame the hole with framing lumber the same size as the ceiling joists.
NOTE: There must be NO INSULA TION or other combustibles inside the framed firestop opening.
10" (254mm) 10" (254mm)
CHIMNEY HOLE
ENT PIPE
Figure 24. Hole and Vent Pipe
HEAT SHIELD
INTERIOR
FIRESTOP
TRIM HEAT SHIELD IF TOO LONG , ADD TO SHIELD IF TOO SHORT
EXTERIOR FIRESTOP
Figure 25. Heat Shield, Interior & Exterior Firestops
EXISTING CEILING JOISTS
CEILING
NEW FRAMING MEMBERS
Figure 26. Hole & New Framing Members
30 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.
JOIST
CEILING
NAILS (4 REQUIRED)
NAILS (3 REQUIRED)
CEILING FIRESTOP
Figure 27. Ceiling Firestop (Ceiling Side)
C. Vent Termination
SL-Series Venting Only:
For Horizontal Terminations - To attach and secure the
termination to the last section of horizontal vent:
• Rotate and interlock the ends as described at the begin­ning of the Installing V ent Components section.
• The termination kit should pass through the wall firestops from the exterior of the building.
• Adjust the termination cap to its final exterior position on the building.
For trapezoidal cap termination kits:
• Using screws secure the cap to the exterior wall through the flanges in the cap.
For DVP Venting Only:
Refer to Cinch Pipe and Termination Cap installation in­structions.
If the area above the ceiling IS an attic, position and secure the firestop on top of the previously framed hole.
NOTE: Keep insulation away from the vent pipe at least 1 inch (25mm).
NAILS (3 REQUIRED)
RAFTER
CEILING CEILING FIRESTOP
Figure 28. Attic Firestop
For All V enting:
WARNING: THE TERMINA TION CAP MUST BE
!
POSITIONED SO THA T THE ARROW IS POINT ­ING UP .
WARNING: VENTING TERMINALS SHALL
!
NOT BE RECESSED INTO A W ALL OR SID­ING . VENT TERMINATION CLEARANCES MUST BE FOLLOWED TO AVOID FIRE DANGER. SEE VENT TERMINA TION MINIMUM CLEARANCES DI­AGRAM ON FOLLOWING P AGE.
7 1/4"
(184mm)
Figure 29. Trapezoid Termination Cap
31Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
O
V
N
G
v
D
E
v
B
L
v
B
v
F
v
A
B
v
B
v
A
= VENT TERMINAL
V
X
= AIR SUPPLY INLET
A = 12" ....................... clearances above grade, veran-
(See Note 1)
da, porch, deck or balcony
B = 12" ....................... clearances to window or door
that may be opened, or to per­manently closed window.
D* = 18" ....................... vertical clearance to unventilat-
ed soffit or to ventilated soffit lo­cated above the terminal
*30” min. .............. for vinyl clad soffits and below
electrical service
F = 9" ........................ clearance to outside corner
G = 6" ......................... clearance t o inside corner
H = 3 ft. (Canada) ...... not to be installed above a gas
meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator I = 3 ft. (U.S.A.)
6 ft. (Canada) ...... clearance to gas service regu-
lator vent outlet J = 9" (U.S.A.)
12" (Canada) ........ clearance to non-mechanical air
supply inlet to building or the
combustion air inlet to any other
appliance
R
H
U.S.
(3 FT)
M
I
X
v
J or K
P
Q
(See Note 2)
S
Electrical
V
V
T
Service
D*
V
S
= AREA WHERE TERMINAL IS NOT PERMITTED
K = 3 ft. (U.S.A.)
6 ft. (Canada) ......... clearance to a mechanical
air supply inlet
L** = 7 ft.......................... clearance above paved
(See Note 1)
sidewalk or a paved driveway located on
public property
M*** = 18" ......................... clearance under veranda,
porch, deck or balcony
N = 6” ........................... non-vinyl sidewalls
12” ......................... vinyl sidewalls
O = 18” ......................... non-vinyl soffit and overhang
42” ......................... vinyl soffit and overhang
P = 8 ft.
Q
______________________________________________________________________
1 cap 3 feet 2 x Q
______________________________________________________________________
2 caps 6 feet 1 x Q
______________________________________________________________________
3 caps 9 feet 2/3 x Q
______________________________________________________________________
MIN
4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
= (2 / # termina t i on c a p s ) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
S = 6" MIN................... clearance from sides of elec-
(See Note 5)
trical service
T = 12" MIN. ................ clearance above electrical
(See Note 5)
service
** a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on
a minimum of 2 sides beneath the floor.
NOTE 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap shield is suggested.
NOTE 2: Termination in an alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.
Figure 30. Vent Termination Minimum Clearances
NOTE 3: Local codes or regulations may require different
clearances. NOTE 4: T ermination caps may be hot. Consider their proximity to
doors or other traffic areas. NOTE 5: Location of the vent termination must not interfere with
access to the electrical service. WARNING: In the U.S: V ent system termination is NOT permitted
in screened porches. You must follow side wall, overhang and ground clearances as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.
Heat-N-Glo assumes no responsibility for the improper perfor­mance of the fireplace when the venting system does not meet these requirements.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
32 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
For Vertical Terminations - To locate the vent and install
V
the vent sections:
• Locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint.
• Make the outline of the roof hole around the centerpoint nail.
• The size of the roof hole framing dimensions depend on the pitch of the roof. There MUST BE a 1-inch (25.4mm) clear­ance from the vertical vent pipe to combustible materials.
• Mark the roof hole accordingly.
T o seal the roof hole, and to divert rain and snow from the vent system:
• Attach a flashing to the roof using nails, and use a non­hardening mastic around the edges of the flashing base where it meets the roof.
• Attach a storm collar over the flashing joint to form a water-tight seal. Place non-hardening mastic around the joint, between the storm collar and the vertical pipe.
• Slide the termination cap over the end of the vent pipe and snap into place.
• Cover the opening of the installed vent pipes.
• Cut and frame the roof hole.
• Use framing lumber the same size as the roof rafters and install the frame securely . Flashing anchored to the frame must withstand heavy winds.
• Continue to install concentric vent sections up through the roof hole and up past the roof line until you reach the appropriate distance above the roof.
WARNING: MAJOR U.S. BUILDING CODES
!
SPECIFY MINIMUM CHIMNEY AND/OR VENT HEIGHT ABOVE THE ROOF TOP. THESE MIN­IMUM HEIGHTS ARE NECESSARY IN THE INTER­EST OF SAFETY . SEE THE FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS, PROVIDED THE TERMI­NA TION CAP IS A T LEAST TWO (2) FEET (20 INCH­ES FOR DVP PIPE) FROM A VERTICAL W ALL AND 2-FEET BELOW A HORIZONTAL OVERHANG .
NOTE: This also pertains to vertical vent systems in­stalled on the outside of the building.
2 FT. MIN.
TERMINATION
CAP
2 FT. MIN.
20” MIN.
(DVP PIPE)
LOWEST
DISCHARGE
OPENING
12
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
Roof Pitch H (min.) ft.
flat to 6/12 1.0 6/12 to 7/12 1.25 over 7/12 to 8/12 1.5 over 8/12 to 9/12 2.0 over 9/12 to 10/12 2.5 over 10/12 to 1 1/12 3.25 over 1 1/12 to 12/12 4.0 over 12/12 to 14/12 5 .0 over 14/12 to 16/12 6 .0 over 16/12 to 18/12 7 .0 over 18/12 to 20/12 7 .5 over 20/12 to 21/12 8 .0
HORIZONTAL
OVERHANG
ERTICAL
WALL
X
ROOF PITCH
IS X/ 12
Figure 31. Minimum Height from Roof to Lowest Discharge Opening
33Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Step 4. Positioning, Leveling, and Securing the Fireplace
The diagram below shows how to properly position, level, and secure the fireplace.
WARNING:
To ensure proper clearances the front framing header must be installed on its narrow edge and to the front of the frame.
NAILING TABS (BOTH SIDES)
Step 5. The Gas Control System
WARNING: THIS UNIT IS NOT FOR USE WITH
!
SOLID FUEL.
The type of gas control system used with this model is Standing Pilot Ignition.
Standing Pilot Ignition System
This system includes millivolt control valve, standing pilot, thermopile/thermocouple flame sensor, and piezo ignitor .
WARNING: 110-120 VAC MUST NEVER BE
!
CONNECTED TO A CONTROL VALVE IN A MILLIVOL T SYSTEM.
STANDING PILOT
Figure 32. Proper Positioning, Leveling, and Securing of a Fireplace
• Place the fireplace into position.
• Level the fireplace from side to side and from front to back.
• Shim the fireplace with non-combustible material, such as sheet metal, as necessary.
• Secure the fireplace to the framing using nails or screws through the nailing tabs.
Figure 33. Gas Control System
34 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Step 6. The Gas Supply Line
V
NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality . (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber).
NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13mm) hook-up at the unit.
MANUAL
SHUT-OFF VALVE
FLEX CONNECTOR
This gas fireplace is designed to accept a 1/2 inch (13mm) gas supply line. To install the gas supply line:
• A listed (and Commonwealth of Massachusetts approved)
1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substi­tuting for these components, please consult local codes for compliance.
• Locate the gas line access hole in the outer casing of
the fireplace.
• The gas line may be run from either side of the fireplace
provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox.
• Open the fireplace lower grille, insert the gas supply line
through the gas line hole, and connect it to the shut-off valve.
• When attaching the pipe, support the control so that the
lines are not bent or torn.
• After the gas line installation is complete, use a soap
solution to carefully check all gas connections for leaks.
WARNING: DO NOT USE AN OPEN FLAME
!
TO CHECK FOR GAS LEAKS.
• Insert insulation from the outside of the fireplace and
pack the insulation tightly to totally seal between the pipe and the outer casing.
• At the gas line access hole the gap between the supply
piping and gas access hole can be plugged with non­combustible insulation to prevent cold air infiltration.
GAS VALVE
USE WRENCH ON SHUT-OFF
ALVE WHEN TIGHTENING GAS LINE
Figure 34. Gas Supply Line
Step 7. Gas Pressure Requirements
Pressure requirements for these gas fireplaces are shown in the table below.
Pressure Natural Gas Propane
Minimum 5.0 inches 11.0 inches Inlet Pressure w.c. w.c.
Maximum Inlet 14.0 inches 14.0 inches Gas Pressure w.c. w.c.
Manifold 3.5 inches 10.0 inches Pressure w.c. w.c.
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. Use a small flat blade screwdriver to crack open the screw in the center of the tap. Position a rubber hose over the tap to obtain the pressure reading.
The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).
35Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
STANDING
PILOT
WHT
VALVE
REMOTE SWITCH
PIGTAIL
ON
OFF
ON/OFF SWITCH
RED
Î
Figure 35. Standing Pilot Ignition Wiring Diagram
Step 8. Wiring the Fireplace
NOTE: Electrical wiring must be installed by a licensed electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF AB­SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE­VENT ACCIDENT AL FIREPLACE OPERA TION.
For Standing Pilot Ignition Wiring Appliance Requirements
This appliance DOES NOT require 110-120 V AC to operate.
WARNING: DO NOT CONNECT 110-120 V AC TO
!
THE GAS CONTROL V AL VE OR WALL SWITCH OR THE APPLIANCE WILL MALFUNCTION AND THE V AL VE WILL BE DESTROYED.
OPTIONAL WALL SWITCH,
THERMOSTAT OR REMOTE
Optional Accessories
Optional fan and remote control kits require that 110-120 VAC be wired to the factory installed junction box before the fireplace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a wall. Run a maximum of 25 feet (7.8 m) or less length of 18 A.W.G. minimum wire and connect it to the fireplace ON/ OFF switch pigtails.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC­TION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERA TION. VERIFY PROPER OPERATION AFTER SERVICING.
ROMEX CONNECTOR
14/2WG
COVER PLATE
OUTSIDE FIREBOX
T
H
W
K
L
Figure 36. Fan Wiring Diagram
Î
B
W
B
H
L
T
K
GRN WIRE INSIDE BOX
COPPER
GROUND ATT ACHED TO GRN SCREW WITH GRN WIRE
BLOWER
36 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
SENSOR
SWITCH
FAN
RECEPTACLE
SPEED
CONTROL
Step 9. Finishing
Figure 37 shows the minimum vertical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace. See Figures 3 and 4 for other fireplace clearances.
Only non-combustible materials may be used to cover the black fireplace front.
WARNING: WHEN FINISHING THE FIREPLACE,
!
NEVER OBSTRUCT OR MODIFY THE AIR IN­LET/OUTLET GRILLES IN ANY MANNER.
CEILING
Hearth Extensions
A hearth extension may be desirable for aesthetic reasons. However, ANSI or CAN/CGA testing st andards do not require hearth extensions for gas fireplace appliances.
Step 10. Installing Trim, Logs and Ember Material
Installing the Trim
Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but MUST NEVER overlap onto the front face. The joints between the finished wall and the fireplace top and sides can only be sealed with a 300° F . (149° C) minimum sealant.
12"
11"
10"
9"
8"
7"
6"
5"
4"
3"
2"
3”
2”
1”
1”
TOP FRONT EDGE
OF FIREPLACE
6”
5”
4"
10”
9”
8”
7”
11”
31”
12”
Figure 37. Minimum Vertical and Maximum Horizontal Dimensions of Combustibles above Fireplace
CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND (TOP AND SIDES) ARE SEALED, A 300° F. MINIMUM SEALANT MATE­RIAL MUST BE USED. THESE JOINTS ARE NOT RE­QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF NEEDED) CAN BE APPLIED AS FACING T O THE FIRE­PLACE SURROUND (SEE FIGURE 38).
WARNING: WHEN FINISHING THE FIREPLACE,
!
NEVER OBSTRUCT OR MODIFY THE AIR INLET/ OUTLET GRILLES IN ANY MANNER.
Install optional marble and brass trim surround kits as desired. Marble, brass, brick, tile, or other non-combustible materials can be used to cover up the gap between the sheet rock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When overlapping on both sides, leave enough space so that the bottom grille can be opened and the trim door removed.
Positioning the Logs
If the gas logs have been factory installed they should not need to be positioned. If the logs have been packaged separately, refer to the instructions that accompany the logs. Save the log instructions with this manual.
If sooting occurs, the logs might need to be repositioned slightly to avoid excessive flame impingement.
Shutter Settings
Model NG LP
___________________________________________
QV32B-A 1/16” 3/8”
___________________________________________
QV36B-A 1/16” 3/8”
TOP SEAL
JOINT
SIDE SEAL
JOINT
0”
Figure 38. Sealant Material
FINISH MATERIAL
MAY BE COMB USTIBLE
- TOP AND SIDES OF UNIT
0”
37Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Placing the Ember Material
Ember material is shipped with this gas fireplace. The bag labeled Glowing Embers (050-721) is standard glowing ember material. T o place the ember material:
• Remove the door by lifting it up and away from the unit.
• Unlatch the latches at the top and bottom of the glass.
• Remove the glass from the unit (see Figure 44).
• Place dime size pieces of ember material about 1/2 inch apart near port holes in burner top. Do NOT press em­bers into burner ports. Cover the top of the burner with a single layer of ember material. For best performance do NOT place embers on the ports at the rear of the burner (see Figure 45).
• Save the remaining ember materials for use during fire­place servicing. The bag of embers provided is sufficient for 3 to 5 applications.
• Reinstall and latch the glass and door on the unit.
CAUTION: THE GLASS MUST BE SECUREL Y LA TCHED BEFORE OPERA TING THE UNIT .
Step 1 1. Before Lighting the Fireplace
Before lighting the fireplace, be sure to do the following: Remove all paperwork from underneath the fireplace. Review safety warnings and cautions
• Read the Safety and Warning Information section at the beginning of this Installers Guide.
Double-check for gas leaks
• Before lighting the fireplace, double-check the unit for possible gas leaks.
Double-check vent terminations and front grilles for obstructions.
• Before lighting the fireplace, double-check the unit for possible obstructions that could be blocking the vent ter­minations or the front grilles.
Double-check for faulty components
• Any component that is found to be faulty MUST BE re­placed with an approved component. T ampering with the fireplace components is DANGEROUS and voids all war­ranties.
A small amount of air will be in the gas supply lines. When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and will operate normally .
LATCHES
(BOTH TOP
AND BOTTOM)
GLASS
ASSEMBLY
Figure 44. Glass Assembly
GLASS SPECIFICA TIONS:
QV32B-A and QV36B-A CERAMIC
Figure 45. Placement of the Ember Material
Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines, unless the gas valve has been turned to the OFF position, in which case the air would have to be purged.
NOTE: The fireplace should be run for 3 to 4 hours on the initial start-up. T urn it off and let it cool completely . Remove and clean the glass. Replace the glass and run the fireplace for an additional 8 hours. This will help to cure the products used in the paint and logs.
During this break-in period it is recommended that some windows in the house be opened for air circulation. This will help avoid setting off smoke detectors, and help eliminate any odors associated with the fireplace’s initial burning.
WARNING: PLEASE REFER TO THE USER’S
!
MANUAL FOR ALL CAUTIONS, SAFETY, AND WARNING INFORMA TION PERT AINING TO THE LIGHTING AND OPERA TION OF THE FIREPLACE.
38 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Step 12. Lighting the Appliance
You’ve reviewed all safety warnings, you’ve checked the appliance for gas leaks, you know the vent system is
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJUR Y , OR LOSS OF LIFE.
ST ANDING PILOT IGNITION
A. This appliance (standing pilot version) has a pilot
that must be lighted by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all around the appli-
ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHA T TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instruc­tions.
• If you cannot reach your gas supplier, call the fire department.
C.Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempt­ed repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas con­trol which has been under water.
unobstructed, and you’ve checked for faulty components. Now you’re ready to light the appliance.
LIGHTING INSTRUCTIONS
STANDING PILOT CONTROLS
1. To access controls, open the lower grille.
2. Turn the gas control valve knob to the OFF position. To do this, you must turn the knob clockwise press in and continue turning clockwise NOTE: Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do not force.
3. WAIT AT LEAST FIVE (5) MINUTES TO CLEAR OUT ANY GAS. If you have unsuccessfully tried to light the fireplace, wait longer, espe­cially if you are using LP gas. Then smell for gas, including near the floor. If you then smell gas, STOP! Follow "B" in the safety informa­tion on previous page. If you don't smell gas, go to the next step.
4. The pilot should not require accessing for lighting purposes. The pilot is located inside the combustion chamber. If it is necessary to access the pilot, re­move the trim door and glass door.
THERMOCOUPLE PILOT THERMOPILE
5. To put the control in the PILOT position, turn the control knob counter­clockwise
6. To light the pilot press the control knob and then press the red or black piezo button once every second. The piezo makes a clicking sound. It may be necessary to repeat this step. If the pilot does not light after 10 seconds, go back to step 2. The control knob should be held down for a MINUTE after pilot ignition.
• If the control knob does not pop out when released, STOP! Shut off
the gas supply to the fireplace control valve, and IMMEDIATELY call your service technician or gas supplier.
• If the pilot will not stay lit after two tries, turn the control knob to the
“OFF” position and call your service technician or gas supplier.
7. After the pilot has been lit, the burner can be turned on by turning the knob counter-clockwise
8. Set the ON/OFF switch to the “ON” position.
9. Close the lower grille.
to the PILOT position.
to the PILOT position, and then
to the OFF position.
to the “ON” position.
TO TURN OFF
GAS APPLIANCE
1. Open the lower grille.
2. Set ON/OFF switch to “OFF”.
3. Turn the valve control knob clockwise then depress knob and continue turning to “OFF” position.
4. Close the lower grille.
to the “Pilot” position,
When you light your fireplace, you may notice: This gas appliance produces heat which does have an associ-
ated odor or smell. If you feel this odor is excessive it may require the initial 3-4 hour continuous burn on high followed by a second burn up to 12 hours to fully drive off any odor from paint and lubricants used in the manufacturing process.
During this break-in period it is recommended that some windows in the house be opened for air circulation. This will help avoid setting off smoke detectors, and help eliminate any odors associated with the fireplace’s initial burning.
Additionally, for the first few minutes after each lighting, vapor may condense and fog the glass and flames may be blue. After a few minutes this moisture will disappear and within 15-30 minutes the flames should become yellow.
Noise caused by metal expanding and contracting as it heats up and cools down, similar to the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of your fireplace.
After the Installation
LEA VE THIS INSTALLA TION MANUAL WITH THE
!
APPLIANCE FOR FUTURE REFERENCE.
39Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Maintaining and Servicing Your Fireplace
4
Fireplace Maintenance
Although the frequency of your fireplace servicing and main­tenance will depend on use and the type of installation, you should have a qualified service technician perform an appli­ance check-up at the beginning of each heating season. See the table below for specific guidelines regarding each fireplace maintenance task.
IMPORT ANT : TURN OFF THE GAS BEFORE SERVICING YOUR FIREPLACE.
Replacing old ember material Frequency: Once annually , during the checkup. By: Qualified service technician. Task: Brush away loose ember material near the burner.
Replace old ember material with pieces of Mystic Ember following the directions in Placing Ember Material. New ember material should be placed on top of the burner. Save the remaining ember material and repeat this procedure at your next servicing. For more information, see Placing
Ember Material.
Checking Vent System Frequency: Before initial use and at least annually
thereafter, more frequently if possible.
By: Qualified service technician/Home owner. Task: Inspect the external vent cap on a regular basis to
ensure that no debris is interfering with the flow of air. Inspect entire vent system for proper function.
Cleaning Glass Frequency: After the first 3 to 4 hours of use. As necessary
after initial cleaning.
By: Home owner. Task: Remove and clean glass af ter the first 3 to 4 hours of
use. After the initial cleaning, clean as necessary , particularly after adding new ember (flame colorant) material. Film deposits on the inside of the glass should be cleaned off using a household glass cleaner. NOTE: DO NOT handle
or attempt to clean the glass when it is hot and DO NOT use abrasive cleaners.
Cleaning Burner and Controls Frequency: Once annually . By: Qualified service technician. Task: Brush or vacuum the control compartment, fireplace
logs and burner areas surrounding the logs.
Checking Flame Patterns, Flame Height Frequency: Periodically .
By: Qualified service technician/Home owner. T ask: Make a visual check of your fireplace’ s flame patterns.
Make sure the flames are steady - not lifting or floating. See Figure 46. The thermopile/thermocouple tips should be covered with flame. See Figure 33.
MAKE SURE THE FLAMES ARE STEADY—NOT LIFTING OR FLOATING.
Figure 46. Burner Flame Patterns
40 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
5
Symptom Po ssible Caus e Corrective Action
1. After repe a ted
triggering of the red
or black piezo button,
the spark ignitor will
not light the pilot.
2. The pilot will not sta y li t after carefully
following the lighting
instructions.
With proper installation, operation, and maintenance your gas fireplace will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the corrective action to be taken. This troubleshooting
Troubleshooting
a. Defective ignitor. Check the spark at the electrode and pilot. If no spark and electrode wire is
b. Defective pilot or misaligned electrode
(spark at electrode).
c. No gas or low gas
pressure.
d. No LP in tank. Check the LP (propane) tank. You may be out of fuel. a. Defective
thermocouple.
guide can only be used by a qualified service technician.
properly connected, replace the ignitor. Usi ng m a tc h, li g ht the p ilo t. If the pi lo t lights , turn off the p ilot and tri gge r the re d or
black piezo button again. If the pilot lights, an improper gas/air mixture caused the bad lighting and a longer purge period is recommended. If the pilot will not light, ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a strong spark. If the gap is OK, replace the pilot.
Check the remote shut-off valvess from the fireplace. Usually, there is a valve near
the gas main. There can be more than one (1) valve between the fireplace and the
main.
Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the pilot for maximum flame impingement.
Ensure that the thermocouple connection at the gas valve is fully inserted and tight (hand tighten plus 1/4 turn).
3. The pilo t is burning, there is no gas burner, the valve knob is in the ON position, and the ON/OFF switch is in
the ON position.
Disconnect the thermocouple from the valve, place one millivolt meter lead wire on
the tip of the thermcouple and the other meter lead wire on the thermocouple
copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less
than 15mV, replace the thermocouple.
b. Defective valve. If the thermo coup le is produci ng more tha n 1 5 m i llivolts , re p lace faulty valve.
a. ON/OFF switch or wires defective.
b. Thermopile may not be ge ner at ing
suffi c ie nt milli vo lta ge.
c. D efec tive valve . Turn the valve k nob to the ON p ositi on. Pla c e the ON/OFF s witch i n the ON
d. Plugged burner orifice.
e. Wall switch or wires are defective.
Check the ON/OFF switch and wires for proper connections. Place the jumper wires across the terminals at the switch. If the burner comes on, replace the defective switch. If the switch is OK, place the jumper wires across the switch wires at the gas valve. If the burner comes on, the wires are faulty or connections are bad.
If the pilot flame is not close enough physically to the thermopile, adjust the pilot
flame.
Be sure the wire connections from the thermopile at the gas valve terminals are
tig ht a nd tha t the therm o p ile is fully inserted i nto the p ilo t b rack et.
Che c k the therm o pi le with a millvolt me ter. Ta k e the re ading a t TH-TP &TP
terminals of the gas valve. The meter should read 325 millivolts minimum, while holding the valve knob depressed in the pilot position, with the pilot lit, and the ON/OF F s witc h i n the OFF p o s ition. Re p la c e the fa ulty thermo p ile if the re a di ng is below the sp e cifie d minimum.
Wi th the p ilo t in the ON position, d isc onnect the the rm o pi le le ad s fro m the va lve. Take a reading at the thermopile leads. The reading should be 325 millivolts minimum. Replace the thermopile if the reading is below the minimum.
po s iti o n. Chec k the m illi volt m e ter a the ther mopile te rm inals. The m illi vo lt me ter should read greater than 125mV. If the reading is acceptable, and if the burner does not come on, replace the gas valve.
Check the burner orifice for stoppage. Remove stoppage.
Follow the corrective action in Symptom and Possible Cause 1.a above. Check
the switch and wiring. Replace where defective.
41Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Troubleshooting (continued)
Symptom Possible Cause Corrective Action
3. (Continued) f. High limit switch is defective or
has reached its maximum
temperature.
4. Frequent pilot outage problem.
5. The pilot and main burner extinguish while in operation.
6. Glass soots. a. Flame impingement. Adjust the log set so that the flame does not excessively impinge on it.
7. Flame burns blue
and lifts off burner.
a. Pilot flame may be too high or
too low, or blowing (high),
causing pilot safety to drop out. a. No LP in tank. Check the LP (propane) tank. Refill the fuel tank. b. Inner vent pipe leaking exhaust
gases back i nto the system. c. Horizontal vent improperly
pitched. d. Glass too loose and air tight
packet leaks in corners after usage.
e. Bad thermopile or
thermocouple. f. Improper vent cap installation. Check for proper installation and freedom from debris or blockage.
b. Improper venturi setting. Adjust the air shutter at the base of the burner. c. Debris around venturi. Inspect the opening at the base of the burner. NO MATERIAL SHOULD
a. Insufficient oxygen being supplied.
Allow the unit to cool. If the burner remains lit after the fireplace warms up, the switch is good.
Clean and adjust the pilot flame for maximum flame impingement on thermocouple. Follow lighting instructions carefully.
Check for gas leaks.
The horizontal vent cap should slope down only enough to prevent any water from entering the unit. The maximum downwards lope is 1/4 inch.
Tighten the corner.
Replace if necessary.
BE PLACED IN THIS OPENING. Ensure that the vent cap is installed properly and free of debris. Ensure
that the vent system joints are tight and have no leaks. Ensure that no debris has been placed at the base of, or in the area of
the air holes in the center of the base pan beneath the burner. Ensure that the glass is tightened properly on the unit, particularly on top
corner s.
42 Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Lifetime Warranty
LIMITED LIFETIME WARRANTY
The Hearth & Home Technologies limited Lifetime Warranty guarantees that the following components will work as designed for the lifetime of the stove or Hearth & Home Technologies will repair or replace them. These items include but are not limited to steel and cast iron components, all gas burners, gas logs, combustion chambers, heat exchanger systems, stainless steel firebox components, plating, doors, glass damaged by thermal breakage, steel baffle supports, steel and ceramic baffles and manifold tubes. Labor is for the first five years.
THREE YEAR WARRANTY
Our EZ Clean firepots are covered under Hearth & Home Technologies three-year warranty program. Labor is for 3 years.
TWO YEAR WARRANTY
All electrical components such as but not limited to blowers, wiring, vacuum switches, speed controls, control boxes, thermodisc switches, igniters, pilot assembly, gas valves, thermostats and remotes are covered under Hearth & Home Technologies two-year warranty program. Effective April, 2005 igniters are also covered under the two year warranty. Labor is for two years.
ONE YEAR WARRANTY
Porcelain and powdercoat finishes are warranted against manufacturer defects for one year. Labor to repair or replace these parts is covered for one year, reimbursed per our warranty service fee schedule.
CONDITIONS
This warranty is nontransferable and is made to the original retail purchaser only provided that the purchase was made through an authorized dealer of Hearth & Home Technologies. It must be installed and operated at all times in accordance with the Installation and Operating Instructions furnished with this product, as well as any applicable local and national codes. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
Labor to repair or replace items covered under the limited Lifetime Warranty will be covered for the first five years per our warranty service fee reimbursement schedule. Parts covered under the limited Lifetime Warranty will be covered for the lifetime of the appliance up to a maximum of ten (10) years after Hearth & Home Technologies discontinues the model and two (2) years for optional accessories. Adjustments, regular maintenance, cleaning and temporary repairs do not qualify for a service call fee and will not be covered. The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a service call fee, and will not be covered.
This limited Lifetime Warranty does not extend to or include surface finish on the appliance, door gasketing, glass gasketing, glass, firebrick, pellet logs, kaowool or other ceramic insulating materials. It does not cover installation or operational-related problems such as overfiring, use of corrosive driftwood, downdrafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate venting or ventilation, excessive offsets, or negative air pressures caused by mechanical systems such as furnaces, fans, clothes dryers, etc.
Any installation, construction, transportation, or other related costs or expenses arising from defective part(s), repair, replacement, etc., will not be covered by this warranty, nor will Hearth & Home Technologies assume responsibility for them. Further, Hearth & Home Technologies will not be responsible for any incidental, indirect, or consequential damages, except as results in damage to the interior or exterior of the building in which this appliance is installed. This limited Lifetime Warranty does not apply to the venting components, hearth components or other accessories used in conjunction with the installation of this product not manufactured by Hearth & Home Technologies
This warranty is void if the stove has been overfired or operated in atmospheres contaminated by chlorine, fluorine, or other damaging chemicals, the stove is subjected to prolonged periods of dampness or condensation, or there is any damage to the stove or other components due to water or weather damage which is the result of, but not limited to, improper chimney or venting installation. Hearth & Home Technologies may, at its discretion, fully discharge all obligations with respect to this warranty by either repairing or replacing the unit, or refunding the wholesale price of the defective part(s).
This limited Lifetime Warranty is effective on all appliances sold after May 1, 2002 and supersedes any and all warranties currently in existence.
250-8620J 12/05
43Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Loading...