E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV3P
Safety relay for monitoring E-STOP
pushbuttons, safety gates and light
barriers.
Approvals
PNOZ XV3P
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 2 safety contacts (N/O), delay-on
de-energisation
` Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Reset button
– Light barriers
` Delay-on de-energisation, fixed or
selectable
` Delay time can be cancelled via re-
set button
` LED indicator for:
– Switch status channel 1/2
– Supply voltage
– Reset circuit
` Plug-in connection terminals (either
cage clamp terminal or screw terminal)
` See order reference for unit types
Unit description
The safety relay meets the requirements of EN 60204-1 and IEC 602041 and may be used in applications with
` E-STOP pushbuttons
` Safety gates
` Light barriers
The max. category the safety contacts
can achieve in accordance with EN
954-1 is stated in the technical details.
Safety features
The relay conforms to the following
safety criteria:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effecti-
ve in the case of a component failure.
` The correct opening and closing of
the safety function relays is tested
automatically in each on-off cycle.
` The unit has an electronic fuse.
Block diagram
A1 A2
=
Power
=
S11 S12
Reset/
Start
S13 S14
S21 S22
InputInput
Reset/
Start
S33 S34
S31 S32
Input
Reset
t
Y39 Y40
K3
K1
K4
K2
13 23 33
14 24 34
47 57
48 58
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-313-12/04
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV3P
Function description
` Single-channel operation: no red-
undancy in the input circuit, earth
faults in the reset and input circuit
are detected.
` Dual-channel operation without de-
tection of shorts across contacts:
redundant input circuit, detects
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
Timing diagram
POWER
Reset/Start
Reset t
v
Input
Output safe
Output safe del
and, with a monitored reset, in
the reset circuit too.
` Dual-channel operation with detec-
tion of shorts across contacts: redundant input circuit, detects
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
the reset circuit too,
– shorts between contacts in the
input circuit.
1 2
t4
t1 t2
t1
t3 t2
t3
t1
` Automatic start: Unit is active once
the input circuit has been closed.
` Monitored reset: Unit is active once
the input circuit is closed and once
the reset circuit is closed after the
waiting period has elapsed
(see technical details).
` Increase in the number of available
contacts by connecting contact expander modules or external contactors/relays.
t2
t3 t4 t3
t2t1
Key
` Power: Supply voltage
` Reset/start: Reset circuit S13-S14,
S33-S34
` Reset t
: Y39-Y40
v
` Input: Input circuits S11-S12, S21-
S22, S31-S32
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are in-
stantaneous safety contacts, outputs 47-48, 57-58 are delay-on deenergisation safety contacts.
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resi-
R
lmax
stance (see technical details)
` Output safe: Safety contacts, in-
stantaneous 13-14, 23-24, 33-34
` Output safe del: Safety contacts,
delayed 47-48, 57-58
` c: Automatic reset
` d: Monitored reset
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
: Switch-on delay
` t
1
: Delay-on de-energisation
` t
2
: Delay time
` t
3
` t4: Waiting period
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-313-12/04Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV3P
Preparing for operation
` Supply voltage
Supply voltage AC DC
` Input circuit
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts across
contacts
S21
S22
S12
S11
S32
S31
S1
S21
S22
E-STOP
with detection of shorts across contacts
S11
S12
Safety gate
without detection of shorts across
contacts
S21
S22
S12
S11
S32
S31
S1
S21
S22
S11
S12
S32
A1
A2
S11
S12
S32
S22
S32
S31
S21
S1
L+
L-
S1
S1
S2
Safety gate
with detection of shorts across contacts
Light barrier
with detection of shorts across contacts via ESPE
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S21
S22
S11
S12
S22
S21
S32
S31
S12
S32
S1
NSG-D-2-313-12/04
S2
24 V DC