Philips ELI-S-20 Installation Instructions Manual

ELI-S-20
20 OR 25 W BACKUP MICRO INVERTER
Installation Instructions
UNIVERSAL INPUT, SINE WAVE OUTPUT,
ELI SERIES EMERGENCY LIGHTING EQUIPMENT INVERTER SINUSODIAL
INSTALLATION INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on the orange/black and yellow/black output leads prior to installation, inverter connector must be open. Join inverter connector after the backup micro inverter has been installed and before the AC power is supplied.
2. For use with fluorescent, incandescent or LED fixtures up to 20 W (0°C to 50°C including driver/ballast) at unity power factor for UL and CSA. This product is also rated up to 25 W (0°C to 45°C including driver/ballast) at unity power factor for UL only.
3. Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and auxiliary power supplies and inverter connector of the backup micro inverter before servicing.
5. This backup micro inverter is for factory or field installation.
6. An AC power source (120, or 277 VAC, 60 Hz) ahead of any wall switch is required to provide battery charging current.
7. Do not install near gas or electric heaters.
8. This product is for use with indoor or damp locations where ambient temperature is 0°C to 50°C. Not suitable for wet or hazardous locations.
9. This is a sealed unit. Integral battery is not replaceable. Replace entire unit when necessary.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:
NRTL/C
SAVE THESE INSTRUCTIONS
THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
A Division of Philips Electronics North America Corporation
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine
11/09/12
© Philips Emergency Lighting
70100901
INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON THE ORANGE/BLACK AND YELLOW/BLACK OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. JOIN INVERTER CONNECTOR AFTER INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.
NOTE: Make sure that the necessary branch circuit wiring is available. An unswitched
source of power is required. The unswitched and switched power source must be fed from the same branch circuit.
INSTALLING THE BACKUP MICRO INVERTER
> The backup micro inverter will be located between the AC power sources and the AC ballast/driver as shown in
wiring diagram section of instructions.
> NOTE: The backup micro inverter may be installed in close proximity to the fixture or remote from the fixture.
The maximum remote distance using 16 AWG wire is 250 ft. Contact the factory for more information.
> The AC power is fed to the backup micro inverter.
> The AC ballast/driver receives power from the backup micro inverter. Identify the output wires of the backup
micro inverter by the presence of the orange/black and yellow/black leads.
STEP 1 DISCONNECT AC POWER FROM FIXTURE
> Disconnect all power sources from lighting fixture and ensure they are locked out during installation or
maintenance.
> Disconnect power leads from the AC ballast/driver.
> Select a suitable location for the backup micro inverter and install such that its output leads can connect to
the input leads of the AC ballast/driver.
> See Illustration 1, for typical installation and select appropriate mounting method.
STEP 2 CONNECT THE BACKUP MICRO INVERTER TO THE PROPER LINE VOLTAGE
> Verify that the inverter connector (red and white) is disconnected. Note that the unswitched hot connects to
the black input lead of the backup micro inverter.
STEP 3
WIRING THE BACKUP MICRO INVERTER
> Use the wiring diagram found on page 4 as reference.
> Connect the AC power source leads to the input of the backup micro inverter.
> Connect the output leads of backup micro inverter to the AC ballast/driver.
> Wire the AC ballast/driver with the lamp in accordance with manufactures installation instructions. No ballast/
driver is necessary for incandescent lamp application.
> Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code and
any local regulations.
> Connect the indicator LED by matching violet and brown leads.
> In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And DC Power Supply (Backup Ballast Inverter Connector) Before Servicing.”