Pentair 221, 222 Installation Manual

0 (0)
Pentair 221, 222 Installation Manual

Keystone Figure 221/222 Butterfly Valve

Installation and Operating Instructions

Before installation or maintenance, these instructions must be fully read and understood.

Please read these instructions carefully.

!This symbol indicates important messages and safety instructions.

Potentially dangerous practices:

disregarding instructions.

improper use of product.

use of insufficiently qualified personnel.

Application pressure/temperature must not be higher than the pressure/ temperature limits shown on the technical data sheet.

Introduction

The Keystone Figure 221/222 is a rubber lined butterfly valve which has a maximum working pressure of 250 psi over a temperature range of -20°F to +250°F, depending on seat material. The Figure 221/222 utilizes a molded seat design.

Flange and pipeline compatibility

Keystone butterfly valves are designed for installation between ANSI Class 125/150 flat or raised faced flanges. Gaskets are not required. Lined pipe, heavy wall pipe or flanges must have a minimum allowable inside diameter at the centered body face to clear the disc sealing edge when opening the valve.

Weld neck flanges (flange ID approximates flange bore) are recommended to ensure maximum valve performance; however, slip-on flanges may be used.

Do not weld near the valve, as this will result in serious damage to the valve.

!Safety related information

1.If in any doubt regarding any aspect of Figure 221/222 valves, contact your local Tyco Flow Control sales office for guidance.

2.Only use properly qualified personnel for installation.

3.Ensure that the pipeline is fully drained or vented before removing the valve from the pipeline.

4.Use appropriate protective equipment/clothing, such as goggles, safety shoes, industrial gloves.

5.This product is not intended for use in areas where external fire is a potential hazard.

6.The piping design must take into account the following factors and any other factors which are not listed here, but known to be relevant to the safe operation of the installation.

6.1.Valve weights which are shown in the technical data sheet.

6.2.Formation of condensate in gas pipelines.

6.3.Elimination of turbulence and vortex potential at the valve.

6.4.Pipeline vibrations.

6.5.The piping design should preclude the occurrence of water hammer at the valve.

7.The valve design has not taken into account earthquake loading or traffic vibration.

8.The normal shelf life of the Figure 221/222 valve seat is 5 years under clean, dry ambient and conditions without UV exposure prior to installation.

9.Tighten all flange bolts as per the nominated flange standards using the diagonal sequence method.

Flow Control

Total Flow Control Solutions™

Copyright © 2008 Tyco Flow Control. All rights reserved.

KEYMC-6254-US-0810

 

 

Keystone Figure 221/222 Butterfly Valve

Installation and Operating Instructions

Installation Instructions

Installation in pipeline

Figure 221/222 valves are bi-directional and there is no need to identify upstream and down stream orientation. These valves can be installed in vertical or horizontal pipelines and any intermediate orientation.

There is no restriction on the valve stem position (vertical, horizontal or oblique), although for slurry service and media, which have a tendency to deposit sediment, the recommended installation position is with the stem horizontal and the lower disc edge opening downstream.

Do not use flange gaskets or sealing compounds. The Keystone seat face design eliminates the need for gaskets.

Maintenance

Routine maintenance or lubrication are not required.

Installation in an existing system

1.Consideration should be given to the location of the valves in t he piping system. The valve should not be placed too close to other valves, elbows, etc. as its performance may be affected. It is recommended that the valve have a minimum of six pipe diameters upstream and four pipe diameters downstream between it and other valves, elbows, etc. in the piping system.

2.Ensure that the flanges are clean, undamaged and compatible with the valve.

3.Check that the gap between the flanges can accommodate the valve face to face dimension.

4.Spread the flanges using suitable tooling such as flange spreaders to enable ease of insertion of the valve between the flanges.

!Warning: Do not use the valve as a lever.

5.Open the valve until the disc is free of the seat but still within the valve body (about 5° open).

6.Loosely insert two or more flange bolts through the holes in the lower part of the flanges to help support the valve.

7.Carefully slide the valve between the flanges, center the valve body with the pipeline axis, and insert the remaining flange bolts.

8.Open the valve fully, checking that the disc edge does not interfere with the pipeline bore.

9.Remove any flange spreaders that have been used and at the same time tighten the flange bolts “hand tight”. Ensure that the valve remains centered to the pipeline axis by slowly closing the valve (clockwise rotation of the disc stem) to check that adequate clearance has been maintained between the disc edge and the pipeline bore.

10.Re-open the valve (counter clockwise rotation of the disc stem) and tighten all flange bolts as per flange standards using the diagonal sequence method.

11.Operate the valve to the desired position.

Copyright © 2008 Tyco Flow Control. All rights reserved.

KEYMC-6254

Open

Flow

Preferred Mounting

Existing system

1.Spread the flanges with the adequate tooling. Insert some flange bolts to bear the valve

2.Open the valve and remove the flange spreads.

3.Close the valve clockwise, return to open position and cross-tighten all bolting.

2

Loading...