Parr Instrument ETLM-HTML User Manual

559M
Installation Instructions for External Temperature Limit Module (ETLM)

Meter Installation in 4848 Reactor Controller

Unplug the power cord of the 4848 Controller. 1. Remove the (2) screws located on the top/front cover at the rear corners of the controller. Gen­tly lift the cover forward, which is hinged at the bottom, taking care not to apply tension on any internal wiring.
If applicable, remove and discard the black hole 2. plug on the sloped front panel above the “TEM­PERATURE” text. This can be done by pinching the clasps on the back of the plug from the inside of the front plate.
Insert the meter (2082E) through the panel cut-3. out, from outside in, making sure the rubber gasket is on the outside of the controller front panel. (If wires are preinstalled, remove the terminal connector by releasing the tabs on the sides of the module and gently pulling the termi­nal connector off. Reference photos below.) Slide the white mounting bracket onto the module with the mounting screws pointing towards the front panel. Slide the mounting bracket forward until it touches the controller panel. The clasps on the mounting bracket should align with the groves on the module. Gently tighten the screws until the module is held into place. (If removed, reat­tach the terminal connector.)
Terminal Connector Removal
HTML Installation
Meter Installation in 4848 Reactor Controller (Continued)
Meter Installation Diagram
2
Parr Instrument Company

Wiring Installation in 4848 Reactor Controller

BLACK T3
WHITE
6
2 X 1541E BEAD
RED
-
+
WHITE T4
DPM (ETLM)
7
8
2
1
EXTERNAL TEMPERATURE LIMIT
1398E2
4
12
11
2082E
10
YELLOW
9
#7 RED WIRE FROM 2083E PRIMARY TEMPERATURE CONTROL REF
T/C JACK
Example: T_=Terminal Block position_
T/C
115V or 230V
ALARM
RS485
1119E SOLID STATE RELAY (position 3)
T7 BLUE
T6 ORANGE
T2 WHITE
T5 BLACK
Non-latching
alarm
HTML Installation
Picture of 2082E Pin Out
Wiring Diagram for 2082E Meter
7 8 9 10 11 12 1 2 3 4 5 6
2082E Pin Out
(Pin 5 is blank)
www.parrinst.com
3
HTML Installation
Wiring Installation in 4848 Reactor Controller (Continued)
Warning: Take care not to apply too much torque when tightening down on wires. This can cause them to weaken and break.
Take the black and white cable, with both ends 1. stripped, from the kit and attach one end to the 2082E meter. Connect the white wire #6 to pin 11 and black wire #7 to pin 12.
Attach the other stripped end of white wire #6 to terminal block position #4 and the black wire #7 to terminal block position #3.
Note: The terminal block position can be opened up using a small fl at head screw driver to release the tension from the spring inside the block so you can press the wire against the spring.
Find the free orange wire #1 from the kit and 4. attach one end to pin 8 on the 2082E meter. The other end attaches to terminal block position #6.
Find the free blue wire #2 from the kit and attach 5. one end to pin 7 on the 2082E meter. The other end attaches to terminal block position #7.
Locate the thermocouple jack on the back of the 6. 4848 Controller labeled “TEMPERATURE INPUT”. Slip one 1541E bead on the red and the white wire. Attach the 1398E2 internal thermocouple wire to the jack by wrapping the wires around the posts and tightening them.
Wago Terminal Block
Find the free black wire #4 from the kit and at-2. tach one end to pin 1 on the 2082E meter. The other end attaches to terminal block position #5.
Find the free white wire #3 from the kit and at-3. tach one end to pin 2 on the 2082E meter. The other end attaches to terminal block position #2.
T/C Jack
Locate the 2083E Primary Temperature Meter. 7. There is a red wire connected between pin 2 and the 1119E solid state relay (position 3). Remove the tabbed end of this wire from the 1119E and attach it to the 2082E ETLM meter on pin 9.
Back of 2083E
Primary Temperature Meter
4
Parr Instrument Company
HTML Installation
Locate the free yellow wire #5 from the kit and 8. attach one end to pin 10 on the 2082E meter. The other end attaches to the 1119E solid state relay (position 3).
Pin Outs:
2082E Color: Attaches to:
Pin 1 Black Terminal Block 5 Pin 2 White Terminal Block 2 Pin 3 Pin 4 White T/C jack + Pin 5 Pin 6 Red T/C jack ­Pin 7 Blue Terminal Block 7 Pin 8 Orange Terminal Block 6 Pin 9 Red 2083E Primary Temp
Meter Pin 10 Yellow 1119E SSR (3) Pin 11 White Terminal Block 4 Pin 12 Black Terminal Block 3
* White (Type – J), Yellow (Type – K), Blue (Type – T), Black (RTD) ** Red (Type – J, Type – K, Type – T), White (RTD)
SSR Position 3
Final Steps:
Close the controller and replace the two screws on the top plate. Plug the 4848 controller back in, and turn it on.
It is useful to check that the settings on the display are set correctly. Check these against the defaults listed in the back of these instructions.
www.parrinst.com
5
HTML Installation

Factory Default Settings - ETLM

Keys command:
Press “SET” to select 1. Press return key move to next operation mode2. Up/Down arrow keys to adjust value or select 3. type
Main Screen: SV = 375
Press return key and release
Operation Mode
r-S Run Run/Stop
SP 0** Decimal point position
AL1H 375 Upper-limit alarm 1 AL1L 0 Lower-limit alarm 1
LoC OFF
Out1
** If using a type-J or type-K thermocouple, SV = 0 If using an RTD, SV = 1
Press and hold down “SET” for 5-sec
Select type/value
- (read­only)
Comment
Lock mode(lock all keys or only up/down arrow able to use)
Heater Output %
Operation Mode
SALA OFF System alarm CoSH ON Communication write
C-Sl ASCII Format type C-no 4 Communication address bPS 9600 Communication baud
LEn 7 Data length setting PrtY Even Parity bit setting StoP 1 Stop bit setting
** If using a type-J thermocouple, InPt = J If using a type-K thermocouple, InPt = K
Select type/value
Comment
function that able to use
set point from software
rate

High Temperature Module - ETLM

Press “SET” and release
Operation Mode
At OFF Auto Tuning ON/OFF HtPd 5 Heat cycle control tPoF 0 Inaccuracy adjustment
Select type/value
Comment
Operation Mode
InPt J** Input type tPUn C Temperature unit tP-H 800 Upper-limit temperature
tP-L 0 Lower-limit temperature
CTRL ON/OFF Control mode (ON/OFF,
PROG) S-HC Heat Heat/Cool control ALA1 6 Alarm operates when
6
Select type/value
Parr Instrument Company
Comment
range
range
MANUAL, PID and PID
PV value is higher than AL1H value
This page intentionally left blank.
HTML Installation
www.parrinst.com
7
Revision 05/12/11
Loading...