Panasonic DP240E, DP241E, DP242E User guide

INSTRUCTION MANUAL
LED DisplayDigital Pressure Sensor
DP2 Series
For use outside Japan
Thank you very much for purchasing Panasinic products. Read this Instruction Manual carefully and thoroughly for the correct and optimum use of this product. Kindly keep this manual in a convenient place for quick reference.
MJE-DP2 No.0048-50V
WARNING
Never use this product as a sensing device for personnel protection.
In case of using sensing devices for personnel protection, use products which meet laws and standards, such as
OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country. In case this sensor is used within Japan, SI unit must be used since use of pressure units in Japan is restricted to SI units.
1
SPECIFICATIONS
Vacuum pressure
Type
Asian North American (Note)
Model No.
European
Item Type of pressure Rated pressure range Set pressure range -0.050 to 1.000MPa-5.0 to 100.0kPa5.1 to -101.3kPa Pressure withstandability Applicable fluid Non-corrosive gas Selectable units kgf/cm2, bar, psikgf/cm2, bar, psi, mmHg, inHg Supply voltage Current consumption
Comparative outputs
Comparative Output 1 Comparative Output 2
Output modes
Short-circuit protection
Analog voltage output
Displayable pressure range
Comparative Output 1
Operation indicators
Comparative Output 2
Ambient temperature
Overvoltage category
Temperature characteristics
Asian Standard Flat IP67 types: Rc (PT)
Pressure
North American
port
European Flat IP67 types: G (PF)
Material
Note:
2
CAUTIONS
Standard Flat
DP2-20
DP2-20F(-P)
Asian North American (Standard NPN output, Flat, IP67 types)
NPN open-collector transistor Maximum sink current: 100mA
Applied voltage: 30V DC or less (between comparative output and 0V)
・ ・Residual voltage: 1V or less (at 100mA sink current)
Equipped with 4 types of modes: hysteresis mode, window comparator mode, dual output mode, automatic sensitivity setting mode (selectable by key operation)
Front case: ABS, Rear case: PPS (glass fiber reinforced), Display surface: Acrylic Pressure port attachment: Die-cast zinc alloy [Light weight type: POM (glass fiber reinforced), pressure port is brass (nickel plated)] Front cover (IP67 type only): Polycarbonate
Standard type: 95g approx., Flat type: 120g approx., IP67 type: 370g approx., Light weight type: 70g approx.Weight
DP2 series is designed for use with non-corrosive gas. It cannot be used for liquid or corrosive gas.
T
his product has been developed / produced for
industrial use only.
Use within the rated pressure range. Do not apply pressure exceeding the pressure
withstandability value. The diaphragm will get damaged and correct operation shall not be maintained. Make sure to carry out the wiring in the power supply
off condition.
Take care that wrong wiring will damage the sensor.
Verify that the supply voltage variation is within the rating. If power is supplied from a commercial switching
regulator, ensure that the frame ground (F.G.) terminal of the power supply is connected to an actual ground.
In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the vicinity of this sensor, connect the frame ground (F.G.) terminal of the equipment to an actual ground
-101kPa type
DP2-40N DP2-60N DP2-40E DP2-60E
0.4V or less (at 16mA sink current)
1 digit (However, variable in hysteresis mode and 2 digits when using psi unit)Hysteresis
Output voltage: 1 to 5V (over rated pressure range) Zero-point: within 1V ±5% F.S. Span: within 4V ±5% F.S. Linearity: within ±1% F.S. Output impedance: 1kΩ approx.
Standard Flat Light weight types: IP40 (IEC), IP67 type: IP67 (IEC)Protection
-10 to +50 (No dew condensation or icing allowed), Storage: -10 to +60
Over ambient temperature range -10 to +50: within ±1% F.S. of detected pressure at 20
Standard type: NPTF 1/8female thread, Flat IP67 types: NPT 1/8 female thread
0.15mm2 5-core oil resistant cabtyre cable, 2m long (IP67 type: 5m long)Cable
Hexagon-socket-head plug for pressure port: 1 No. (Standard type only), Pressure unit label: 1 No.Accessories
Light weight
IP67 Standard StandardFlat IP67 Flat IP67
DP2-60 DP2-80 DP2-21 DP2-41 DP2-61 DP2-22 DP2-42 DP2-62
3
DP2-21F(-P)
- -
12 to 24V DC % Ripple P-P 10% or less
Within ±0.2% F.S. ±1 digitRepeatability
1
/2 digit red LED display (Sampling rate: 4 times/sec. approx.)Display
LED bar display in steps of 10% F.S. approx.Analog bar display
Orange LED (lights up when Comparative Output 1 is ON)
Green LED (lights up when Comparative Output 2 is ON)
35 to 85% RH, Storage: 35 to 85% RHAmbient humidity
DP2-41N DP2-61N DP2-41E DP2-61E
Gauge pressure
+10
-15
50mA or less
2.5ms or lessResponse time Incorporated
Output voltage (V)
2Pollution degree II
2,000m or lessUsable altitude
1
/8 female thread, Light weight type: M5 female thread
Do not use during the initial transient time (0.5 sec.)
after the power supply is switched on. Do not run the wires together with high-voltage lines or
power lines or put them in the same raceway. This can cause malfunction due to induction.
This product is suitable for indoor use only. Avoid use of standard type, flat type and light weight type
of sensor in places where steam and dust is excessive. Take care that the sensor does not come in contact
with water, oil, grease, or organic solvents, such as, thinner, etc. Do not insert wires, etc, into the pressure port. The
diaphragm will get damaged and correct operation shall not be maintained.
Do not operate the keys with pointed or sharp objects.
Make sure that stress by forcible bend or pulling is not applied directly to the sensor cable joint.
Extension up to total 100m is possible with 0.3mm more, cable. However, in case of using this product as a CE Marking conformity product, the power wire connected to this product must be within 10m.
Positive pressure
DP2-22F(-P)
<
North American (Standard PNP output type), European
PNP open-collector transistor
Maximum source current: 100mAApplied voltage: 30V DC or less
Residual voltage: 2V or less (at 100mA source current)
5
1
Pressure
1
/8 female thread
(between comparative output and +V)
1MPa type100kPa type
DP2-42N DP2-62N
DP2-42E DP2-62E
0 to 1.000MPa0 to 100.0kPa0 to -101.3kPa
1.47MPa490kPa
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
-0.050 to 1.000MPa-5.0 to 100.0kPa5.1 to -101.3kPa
2
>
, or
3
SETTING OF PRESSURE LEAD DIRECTION AND PIPING
Standard type
Setting of pressure lead direction
The pressure lead direction can be changed by dismantling the pressure port attachment and changing the mounting direction. The tightening torque of the hexagon-socket-head bolt (length 9mm or less) should be 0.29N・m or less.
Please make sure to close any unused pressure port with
Note:
Pressure port attachment
Hexagon-socket­head plug
the hexagon-socket-head plug supplied as accessory.
Piping
When connecting a hexagon-socket-head plug or coupling to the pressure port, hold the hexagonal part of the pressure port with a 12mm spanner and make sure that the tightening torque is 9.8Nm or less. Also, in order to prevent any leakage, wind a sealing tape on the coupling when connecting. However, sealing tape is not required for North American type using NPTF is required if NPT
1
/8 coupling is used.)
Flat type, Light weight type
Setting of pressure lead direction
The pressure lead direction can be changed by dismantling the pressure port attachment and changing the mounting direction. The tightening torque of the hexagon-socket-head bolt (length 9mm or less) should be 0.29Nm or less.
Pressure port attachment
Main body
Pressure port
Piping
When connecting a coupling to the pressure port, hold the pressure port attachment with a 16mm (Light weight type: 10mm) spanner and make sure that the tightening torque is 9.8Nm or less (Light weight type: 1.47N・m or less). Also, in order to prevent any leakage, wind a sealing tape on the coupling when connecting.
IP67 type
Piping for pressure measurement inlet port
When connecting a coupling to the pressure measurement inlet port, hold the pressure port attachment with a spanner and make sure that the tightening torque is 9.8Nm or less. Also, in order to prevent any leakage, wind a sealing tape on the coupling when connecting.
Piping for atmospheric pressure inlet port
If there is a possibility of water entering into the sensor enclosure through the atmospheric pressure inlet port, connect a tube to the atmospheric pressure inlet port through a M5 coupling and extend the other end of the tube to a safe place. In this case, ensure that this end of the tube does not get clogged.
Fitting of front cover
Insert the bosses on the front cover into the guide holes at the bottom of the pressure port attachment, and push in the direction of the
Hook
arrow to fit the hook. When removing the front cover, release the hook first.
Main body
Hexagon­socket­head bolts
Pressure ports
12mm spanner
1
/8 coupling. (Sealing tape
Hexagon-socket­head bolts
2-φ4.3mm mounting holes
16mm (light weight type: 10mm) spanner
Safe place, where there is no exposure to water
Atmospheric pressure inlet port
M5 coupling
Tube
Pressure measurement inlet port
Guide holes
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
4
MOUNTING OF STANDARD TYPE SENSOR
A sensor mounting bracket MS-DPX and MS-DPX-4 (optional) may be used. When mounting the sensor with the sensor mounting bracket, etc., the tightening torque should be 1.2N・m or less.
<MS-DPX>
<MS-DPX-4>
Sensor mounting bracket MS-DPX-4 (optional)
Note: In case mounting brackets or screws other than the
Note:
Note:
M4 (length 6mm) pan head screw (attached with MS-DPX)
Spring washer (attached with MS-DPX)
Sensor mounting bracket MS-DPX (optional)
Spring washer (attached with MS-DPX-4)
M4 (length 6mm) pan head screw (attached with MS-DPX-4)
sensor mounting bracket shown in the figure above are used, the length of the screws inserted into the pressure port attachment should be 5mm or less. If the length of the screws is longer than 5mm, the sensor may be damaged.
Panel mounting bracket MS-DPX-2 (optional) and a front protection cover DPX-04 (optional) are also available.
Front protection cover
DPX-04 (optional)
5
I/O CIRCUIT DIAGRAM
NPN output type
D
1kΩ
ZD1
Tr1
ZD2
Sensor circuit
ZD3
Tr2
DP2-20
–101.3kPa
OUT2OUT1
0-ADJ
MODE
Panel mounting bracket MS-DPX-2 (optional) (Suitable for 1 to 3.2mm thick panel)
Color code
(Brown) +V
(Gray) Analog voltage output
(Note)
(Black) Comparative Output 1
(White) Comparative Output 2
(Blue) 0V
100mA max.
100mA max.
Load
Load
Users’ circuitInternal circuit
+
-
12 to 24V
+10
  %
-15
The analog voltage output is not incorporated with a short-circuit protection circuit. Do not directly connect a power supply or a capacitive load. When using the analog voltage output, take care to connect external equipment of proper input impedance. Also, when a cable extension is used, voltage drop due to cable resistance should be taken into account.
Symbols...D: Reverse supply polarity protection diode
D1, ZD2, ZD3: Surge absorption zener diode
Z
r1, Tr2: NPN output transistor
T
PNP output type
Color code
D
Tr1
ZD1
Tr2
1kΩ
Sensor circuit
(Brown) +V
(Black) Comparative Output 1
ZD2
(White) Comparative Output 2
(Gray) Analog voltage output (Note)
ZD3
(Blue) 0V
Users’ circuitInternal circuit
100mA max.
100mA max.
Load
Load
+
-
12 to 24V
+10
  %
-15
The analog voltage output is not incorporated with a short-circuit protection circuit. Do not directly connect a power supply or a capacitive load. When using the analog voltage output, take care to connect external equipment of proper input impedance. Also, when a cable extension is used, voltage drop due to cable resistance should be taken into account.
Symbols...D: Reverse supply polarity protection diode
D1, ZD2, ZD3: Surge absorption zener diode
Z
r1, Tr2: PNP output transistor
T
6
FUNCTIONAL DESCRIPTION
DP2-20
-101.3kPa
OUT2OUT1
0-ADJ
MODE
Description Function
DC
DC
1
/2 digit LED
3
display (Red) Comparative Output 1
operation indicator (Orange)
Comparative Output 2
operation indicator (Green)
Increment key
( )
Decrement key
( )
Mode selection key
MODE
( )
7
ERROR MESSAGES
When an error occurs, take the following corrective action.
Error message
8
ANALOG BAR DISPLAY
Pressure changes are displayed in an analog fashion by using LED bars.
Hence, any sudden changes in pressure can be detected at a glance. The analog bar display shows the measured pressure,
irrespective of the pressure unit, in steps of 10% F.S. approx.
Please refer to ' SETTING Initial setting' for the
Displays measured pressure, settings, error messages and key-protect status.
Lights up when Comparative Output 1 is ON.
Lights up when Comparative Output 2 is ON.
In the initial setting mode, pressing
the key changes the settable digit. In the Set Value 1, 2 modes,
pressing the key changes the set value to the high pressure side in case of positive pressure type sensor and to the high vacuum side in case of vacuum pressure type sensor. In the sensing mode, if the key is
pressed continuously for 4 sec. or more, the display shows peak hold value.
In the initial setting mode, pressing
the key changes the set conditions. In the Set Value 1, 2 modes,
pressing the key changes the set value to the low pressure side in case of positive pressure type sensor and to the low vacuum side in case of vacuum pressure type sensor. In the sensing mode, if the key is
pressed continuously for 4 sec. or more, the display shows bottom hold value. Pressing the key changes the selected
mode to sensing mode, Set Value 1 (P1) set mode and Set Value 2 (P2) set mode. In the sensing mode, if the key is
pressed continuously for about 3 sec., key-protect can be set/released. In the sensing mode, if the mode selection
key is pressed while pressing the increment key ( ), the initial setting mode is obtained.
Cause
Overcurrent due to short-circuit.
Pressure is being applied during zero-point adjustment.
Applied pressure exceeds the upper limit of displayable pressure range.
Positive
pressure
type
Applied pressure exceeds the lower limit of displayable pressure range.
Vacuum
pressure
type
Applied pressure exceeds the lower limit of displayable pressure range.
Positive
pressure
type
Applied pressure exceeds the upper limit of displayable pressure range.
pressure
type
Vacuum
11
procedure to change to analog bar display.
Analog bar display for positive pressure type sensor
Atm. pressure condition
DP2-21
100kPa
OUT2OUT1
MODE
0-ADJ
DP2-21
High pressure condition
100kPa
OUT2OUT1
MODE
0-ADJ
Analog bar display for vacuum pressure type sensor
Atm. pressure condition
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
DP2-20
High vacuum condition
-101.3kPa
OUT2OUT1
MODE
0-ADJ
In the sensing mode, if both the keys are pressed
simultaneously, zero-point adjustment is done.
Corrective action
Switch off the power supply and check the load.
Applied pressure at the pressure port should be brought to atmospheric pressure and zero-point adjustment should be done again.
Applied pressure should be brought within the rated pressure range.
DP2-21
100kPa
OUT2OUT1
MODE
0-ADJ
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
9
OUTPUT MODES & THEIR CHARACTERISTICS
Hysteresis mode ( )
The common hysteresis of the comparative outputs
can be set, as desired, with the set values.
ON
Comparative Output 1
OFF
ON
Comparative Output 2
OFF
0
Set Value 1 (P1) Set Value 2 (P2)
Window comparator mode ( )
The comparative outputs can be turned ON or OFF by a pressure
which is within the pressure range set by Set Value 1 and Set Value 2.
ON Comparative Output 1
OFF
ON Comparative Output 2
OFF
0
Set Value 1 (P1)
When operating in window comparator mode ( ) Set Value 1 (P1) and Set Value 2 (P2) should be set with a difference of 3 digits or more. However, when the pressure unit is set to 'psi' ( ), the difference should be 6 digits or more.
Dual output mode ( )
The outputs can be put to different use such as detection of
different kinds of objects, control function, alarm function etc.
Hysteresis
ON Comparative Output 1
OFF
ON Comparative Output 2
OFF
0
Set Value 1 (P1) Set Value 2 (P2)
Automatic sensitivity setting mode ( )
Using actual objects, if the pressure values for OK objects
and NG objects are input, then the sensor is automatically set to the optimum pressure value (mid-value).
ON Comparative Output 1
OFF
ON Comparative Output 2
OFF
0
Set Value 1 (P1) Set Value 2 (P2)
10
PRESSURE UNITS
The pressure unit can be selected as per customer's requirement.
In case of positive pressure type, the pressure unit can be
changed from International System of Units (SI) 'kPa' or 'MPa'
2
', 'bar' or 'psi'. In case of vacuum pressure type, the
to 'kgf/cm pressure unit can be changed from International System of Units (SI) 'kPa' to 'kgf/cm
When the pressure unit is changed, the set values
and the measured value are automatically converted. Please refer to ' SETTING Initial setting' for
the procedure to change the pressure unit.
inHg
mmHg psi bar
Note:
'MPa' in case of DP2-22, DP2-42 and DP2-62.
Hysteresis
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
Hysteresis Hysteresis
Set Value 2 (P2)
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
Hysteresis: 1 digit
2 digits when using psi unit
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
Hysteresis
Set Value 3 (P3)
2
', 'bar', 'psi', 'mmHg' or 'inHg'.
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
11
International System of Units (SI)
kPa (Note)
: Positive pressure type: Vacuum pressure type
Hysteresis:
1 digit or more 2 digits or more when using psi unit
Hysteresis: 1 digit
2 digits when using psi unit
Hysteresis: 1 digit
2 digits when using psi unit
kgf/cm
2
11
SETTING
●●If key-protect has been set, make sure to release
key-protect before operating the keys. (Please refer to
15
' KEY-PROTECT FUNCTION' for the procedure.) The conditions which are set are stored in an EEPROM. Please note that the EEPROM has a life span and its guaranteed life is 100,000 write operation cycles.
Setting procedure
Zero-point adjustment
Adjust zero-point
Initial setting
Set [Display], [Output mode], and [Unit]
Pressure value setting
Enter Set Value 1 (P1) Set Value 2 (P2) Set Value 3 (P3)
Measurement
Commence measurement on completion of setting
Zero-point adjustment
The displayed pressure when the pressure port is left
open is adjusted to zero.
Set to sensing mode
DP2-20
-101.3kPa
The sensor will automatically enter the
sensing mode when power is supplied.
OUT2OUT1
The figure on the left shows the display
MODE
0-ADJ
when the pressure unit and display are set to 'kPa' and 'digital display', respectively.
Perform zero-point adjustment
DP2-20
-101.3kPa
Let the pressure port be at atmospheric pressure (i.e.,
no applied pressure condition), and press, simultane-
OUT2OUT1
ously, the increment and decrement keys continuously.
MODE
0-ADJ
is displayed and, when the fingers are
released, zero-point adjustment is completed and the sensor returns to the sensing mode.
DP2-20
-101.3kPa
0-ADJ
If pressure has been applied during zero-point
adjustment, is displayed when
OUT2OUT1
the keys are pressed. Bring the applied
MODE
pressure to atmospheric pressure (i.e., no applied pressure condition) and carry out the zero-point adjustment once again.
Initial setting
Pressure [Unit], [Display] and [Output mode] of the
comparative outputs are set.
Set to initial setting mode
DP2-20
-101.3kPa
In the sensing mode, press key while
pressing key.
OUT2OUT1
MODE
0-ADJ
Initial setting is displayed.
If sensor is being used for the first
time, is displayed.
MODE
Set initial conditions
DP2-20
-101.3kPa
The settable digit blinks.
The settable digit changes when key
OUT2OUT1
is pressed.
MODE
0-ADJ
DP2-20
-101.3kPa
Change the setting of each digit as
desired.
OUT2OUT1
The setting is changed when key is
MODE
0-ADJ
pressed.
Change with key.
3rd digit 2nd digit
1st digit
Unit Output mode Display
: kPa or MPa
: kgf/cm
: bar
Positive
pressure type
: psi
: mmHg
pressure type
Vacuum
: inHg
2
: Hysteresis mode
: Window comparator mode
: Dual output mode
: Automatic sensitivity setting mode
: Digital display
: Analog bar display
Set to sensing mode
DP2-20
-101.3kPa
Press key.
OUT2OUT1
MODE
0-ADJ
MODE
The sensor returns to sensing mode
after the initial conditions have been set. Since the initial conditions which
have been set are stored in an EEPROM, they are not erased even if the power supply is switched off. The figure on the left shows the display
when the unit and display are set to 'kPa' and 'digital display', respectively.
Setting of pressure values
For the case when output mode is set to either the hysteresis mode ( ), window comparator mode ( ) or dual output mode ( ).
[Set Value 1 (P1)] and [Set Value 2 (P2)] of the
comparative outputs are set.
The setting of Set Value 2 (P2) with respect to Set Value 1
(P1) can only be towards the high pressure side in case of the positive pressure type sensor and only towards the high vacuum side in case of the vacuum pressure type sensor.
Set Value 1 (P1) and Set Value 2 (P2) can be made common for all the output modes. However, when a changeover is made to the automatic sensitivity setting mode, since Set Value 3 (P3) has not been set, make sure to carry out the pressure value settings for the automatic sensitivity mode.
Set to Set Value 1 (P1) set mode
DP2-20
-101.3kPa
In the sensing mode, press key. ・・and Set Value 1 (P1) which
OUT2OUT1
MODE
0-ADJ
is being set are displayed alternately.
MODE
The figure on the left shows the
Displayed alternately
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
display of a vacuum pressure type sensor when the pressure unit has been set to 'kPa'.
Enter Set Value 1 (P1)
DP2-20
-101.3kPa
Enter using key and key.
In case of the positive pressure type
OUT2OUT1
sensor, if key is pressed once the set
MODE
0-ADJ
value changes towards the high
Displayed alternately
pressure side by 1 digit and if key is
Displayed alternately
DP2-20
0-ADJ
pressed once the set value changes towards the low pressure side by 1 digit. In case of the vacuum pressure type
-101.3kPa
sensor, if key is pressed once the set value changes towards the high
OUT2OUT1
vacuum side by 1 digit and if key is
MODE
pressed once the set value changes towards the low vacuum side by 1 digit.
If key or key is pressed continu­ously, the set value changes quickly.
If the set pressure range is exceeded, either (upper limit exceeded) or
(lower limit exceeded) is displayed.
Displayed alternately
Set to Set Value 2 (P2) set mode
DP2-20
-101.3kPa
In the Set Value 1 (P1) set mode, press
MODE
key.
and Set Value 2 (P2) which is
being set are displayed alternately.
Displayed alternately
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Enter Set Value 2 (P2)
DP2-20
Displayed alternately
DP2-20
-101.3kPa
Using key and key, enter in a
manner similar to that for entering Set
OUT2OUT1
Value 1 (P1).
MODE
0-ADJ
0-ADJ
If the set pressure range is exceeded, either (upper limit exceeded) or
(lower limit exceeded) is displayed.
-101.3kPa
OUT2OUT1
MODE
Displayed alternately
If the output mode has been set to the window comparator mode ( ) in the initial setting mode, Set Value 1 (P1) and Set Value 2 (P2) should be set with a difference of 3 digits or more. However, when unit is set to 'psi', the difference should be 6 digits or more.
Displayed alternately
Set to sensing mode
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
MODE
Press key.
・・The sensor returns to sensing
mode after Set Value 1 (P1) and Set Value 2 (P2) have been set. Since the values which have been set are stored in an EEPROM, they are not erased even if the power supply is switched off.
For the case when the output mode is set to automatic sensitivity setting mode ( )
Comparative outputs' [Set Value 1 (P1)], [Set Value 2
(P2)] and [Set Value 3 (P3)] are set.
The setting of Set Value 2 (P2) with respect to Set Value 1
(P1) can only be towards the high pressure side in case of the positive pressure type sensor and only towards the high vacuum side in case of the vacuum pressure type sensor.
Set Value 3 (P3) is automatically set to the mid-value of Set Value 1 (P1) and Set Value 2 (P2). However, if Set Value 1 (P1) is set to a value on the vacuum pressure side for a positive pressure type sensor or to the positive pressure side for a vacuum pressure type sensor, Set Value 3 (P3) is automatically set to the mid-value of 'zero' (atmospheric pressure) and Set Value 2 (P2). Further, if both, Set Value 1 (P1) and Set Value 2 (P2) are set to a value on the vacuum pressure side for a positive pressure type sensor or to the positive pressure side for a vacuum pressure type sensor, Set Value 3 (P3) is automatically set to 'zero' (atmospheric pressure).
The automatically set Set Value 3 (P3) can be changed manually.
Since display of error messages is not possible during pressure value setting in the automatic sensitivity setting mode, make sure that the sensor is used within the rated pressure range.
Set to Set Value 1 (P1) set mode
DP2-20
-101.3kPa
In the sensing mode, press key. ・・and Set Value 1 (P1) which
OUT2OUT1
MODE
0-ADJ
is being set are displayed alternately.
MODE
The figure on the left shows the display of a vacuum pressure type sensor when the pressure
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
unit has been set to 'kPa'.
Enter Set Value 1 (P1)
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Within the required permissible
pressure range, having created a pressure state which is nearest to the atmospheric pressure, press key.
The pressure value at the time of
pressing key is entered as Set Value 1 (P1). Set Value 1 (P1) and
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
are displayed alternately.
If the set pressure range is exceeded, either (upper limit exceeded) or (lower limit exceeded) are displayed and Set Value 1 (P1) is set automatically to the upper or lower limit of the set pressure range.
The setting of Set Value 1 (P1) can be repeated several times in the Set Value 1 (P1) set mode.
Set to Set Value 2 (P2) set mode
DP2-20
-101.3kPa
In the Set Value 1 (P1) set mode, press
MODE
key.
and Set Value 2 (P2) which is
being set are displayed alternately.
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Enter Set Value 2 (P2)
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Within the required permissible pressure
range, having created a pressure state which is nearest to the high pressure end (for a positive pressure type sensor) or the high vacuum end (for a vacuum pressure type sensor), press key.
The pressure value at the time of
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
pressing key is entered as Set Value 2 (P2). Set Value 2 (P2) and
are displayed alternately.
If the set pressure range is
exceeded, either (upper limit exceeded) or (lower limit exceeded) are displayed and Set Value 2 (P2) is set automatically to the upper or lower limit of the set pressure range. The setting of Set Value 2 (P2)
can be repeated several times in the Set Value 2 (P2) set mode.
Set to Set Value 3 (P3) set mode
DP2-20
-101.3kPa
In the Set Value 2 (P2) set mode, press
MODE
key.
and the automatically set Set Value
3 (P3) are displayed alternately. In case
Set Value 1 (P1) = -50.0kPa Set Value 2 (P2) = -100.0kPa then Set Value 3 (P3) =
-50.0+(-100.0) 2
=-
Digits smaller than the displayed digits are discarded.
75.0kPa
Displayed alternately
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
In case Set Value 3 (P3) is to be changed
The automatically set Set Value 3 (P3) can be manually changed to a value between Set Value 1 (P1) and Set Value 2 (P2). However Set Value 3 (P3) cannot be set to a value on the vacuum pressure side for a positive pressure type sensor or to the positive pressure side for a vacuum pressure type sensor.
Hysteresis
Changeable range
Set Value 1 (P1) Set Value 2 (P2)
Set Value 3 (P3)
-101.3kPa
Enter using key and key.
In case of a positive pressure type
OUT2OUT1
sensor, if key is pressed once, the
MODE
set value changes towards the high
Hysteresis: 1 digit
2 digits when psi unit is used
High pressure (Positive pressure type) High vacuum (Vacuum pressure type)
Comparative Output 1
OFF
Comparative Output 2
OFF
DP2-20
ON
ON
0
0-ADJ
pressure side by 1 digit and if key is
Displayed alternately
DP2-20
0-ADJ
pressed once, the set value changes towards the low pressure side by 1 digit. In case of a vacuum pressure type
-101.3kPa
sensor, if key is pressed once the set value changes towards the high
OUT2OUT1
vacuum side by 1 digit and if key is
MODE
pressed once the set value changes towards the low vacuum side by 1 digit.
If key or key is pressed continu­ously, the set value changes quickly.
If the set pressure range is exceeded, either (upper limit exceeded) or
(lower limit exceeded) is displayed.
Set to sensing mode
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
MODE
Press key.
The sensor returns to the sensing mode
after Set Value 1 (P1), Set Value 2 (P2) and Set Value 3 (P3) have been set. Since the values which have been
set are stored in an EEPROM, they are not erased even if the power supply is switched off.
12
PROCEDURE FOR CHECKING SET VALUES
The conditions which have been set in the initial
setting and the pressure settings can be checked by the following procedure.
Procedure to check initial conditions
Set to sensing mode
MODE
Press key while pressing
key.
Sensor enters initial setting mode
Initial conditions which have been set are displayed and can be checked.
MODE
Press key.
Sensor returns to sensing mode
Procedure to check set values
Set to sensing mode
MODE
Press key.
Sensor enters Set Value 1 (P1) set mode
Set Value 1 (P1) which has been set is displayed and can be checked.
MODE
Press key.
Sensor enters Set Value 2 (P2) set mode
Set Value 2 (P2) which has been set is displayed and can be checked.
MODE
Press key.
In case of auto-matic sensitivity setting mode only
Sensor enters Set Value 3 (P3) set mode
Set Value 3 (P3) which has been set is displayed and can be checked.
MODE
Press key.
Sensor returns to sensing mode
Please note that if any key, except key, is pressed in
MODE
any setting mode, the set conditions shall get changed.
13
CONVERSION OF PRESSURE UNITS
In the DP2 series, the conversion to different units is automatically done on changing the setting of the pressure unit. However, this conversion can also be obtained by multiplying the values by the coefficients given in the following table.
Conversion procedure
For example, if 2kPa is to be expressed in kgf/cm2, since 1kPa=1.01972×10-2kgf/cm2, 2kPa becomes 2×1.01972×10-2 0.020kgf/cm
2
Conversion table for pressure units
kPa MPa kgf/cm2 bar
1kPa
1MPa
1kgf/cm
1bar
1psi
1mmHg
(1Torr)
1inHg
1atm
14
PEAK HOLD & BOTTOM HOLD FUNCTIONS
Peak hold and bottom hold functions enable the display
of the peak value (maximum pressure value in case of
1 1×10
3
1×10
2
9.80665×10
2
1×10
6.89473
1.33322×10-11.33322×10-41.35951×10-31.33322×10-31.93368×10
3.3864 3.3864×10
1.01325×1021.01325×10
-3
1.01972×10-21×10-21.45038×10
1 1.01972×10 1×10
-2
9.80665×10
1×
10-1
1
9.80665×10-11.42234×10
1.01972 1 1.45038×10
6.89473×10-37.03065×10-26.89473×10
-3
3.4531×10-23.3864×10
-1
1.03323 1.01325 1.46960×10
the positive pressure type sensor and maximum vacuum pressure value in case of the vacuum pressure type sensor) and the bottom value (minimum pressure value in case of the positive pressure type sensor and minimum vacuum pressure value in case of the vacuum pressure type sensor) of the varying measured pressure. These functions are convenient for finding the
pressure variation range or for determining the reference for pressure settings.
・・Please note that the peak value and the bottom value
data is erased when it is no longer displayed. The response time of the comparative outputs becomes slower during the peak hold and bottom hold display.
Peak hold display
Initiating peak hold display
DP2-20
-101.3kPa
In the sensing mode, keep key
pressed until is displayed. (4 sec.
OUT2OUT1
approx.) When the finger is released
MODE
after is displayed, the peak value and are displayed alternately.
If the applied pressure exceeds the
displayable pressure range, error
-101.3kPa
message ( or ) and
are displayed alternately. In this
case, bring back the applied pressure
OUT2OUT1
to within the rated pressure range.
MODE
The figure on the left shows the
display of a vacuum type sensor when
Displayed alternately
0-ADJ
DP2-20
0-ADJ
the pressure unit has been set to 'kPa'.
Ending peak hold display
DP2-20
-101.3kPa
Press key.
(Sensor returns to sensing mode.)
OUT2OUT1
MODE
0-ADJ
Bottom hold display
Initiating bottom hold display
DP2-20
-101.3kPa
In the sensing mode, keep key pressed until is displayed. (4 sec.
OUT2OUT1
approx.) When the finger is released
MODE
Displayed alternately
0-ADJ
DP2-20
0-ADJ
after is displayed, the bottom value and are displayed alternately.
If the applied pressure exceeds the
displayable pressure range, error message ( or ) and
-101.3kPa
OUT2OUT1
MODE
are displayed alternately. In this case, bring back the applied pressure to within the rated pressure range. The figure on the left shows the
display of a vacuum type sensor when the pressure unit has been set to 'kPa'.
1.45038×1027.50062×1030.2953×10
-2
1 5.17147×10 2.036
-2
0.4912 2.5400×10 1 3.342×10
15
KEY-PROTECT FUNCTION
Key-protect is a function which prevents any
unintentional change in the conditions which have been entered in each setting mode by making the sensor not to respond to the key operations.
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
・・Since the key-protect information is stored in an
EEPROM, it is not erased even if the power supply is switched off. Please take care to remember if the key-protect function has been set.
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
When the keys are to be operated, make sure that key-protect is released.
16
LABEL FOR CHANGE IN PRESSURE UNIT
When a pressure unit other than 'kPa' or 'MPa' has
been selected in the initial setting mode, the label (supplied as accessory) which corresponds to the selected unit should be stuck at the position shown in the figure below.
Pressure unit label (accessory)
101.3kPa
1.033kgf/cm
14.70psi
1.013bar
760mmHg
29.9inHg
圧力センサ用 単位切り換え銘板
17
INTENDED PRODUCTS FOR CE MARKING
The models listed under ' SPECIFI-CATIONS' come with CE Marking. As for all other models, please contact our office.
Contact for CE
Panasonic Marketing Europe GmbH Panasonic Testing Center
Winsbergring 15, 22525 Hamburg,Germany
mmHg
(Torr)
-1
7.50062 0.2953
inHgpsi atm
3
7.35559×1022.8959×10
7.50062×1022.953×10
-2
1 3.9370×10
-2
7.60000×1022.9921×10 1
Setting of key-protect
In the sensing mode, press key
continuously for about 3 sec. and release it immediately when is displayed.
Key-protect is set and the sensor returns to the sensing mode.
Release of key-protect
In the sensing mode, press key continuously for about 3 sec. and release it immediately when is displayed.
Key-protect is released and the sensor returns to the sensing mode.
2
100kPa
1.020kgf/cm
14.50psi
1.000bar
2
1MPa
10.20kgf/cm
145.0psi
10.00bar
N2L58
2
Stick the pressure unit label at the position shown.
1
9.86923×10
9.86923
9.67841×10
9.86923×10
6.80457×10
1.31579×10
DP2-20
0-ADJ
MODE
MODE
–101.3kPa
Ending bottom hold display
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Press key.
(Sensor returns to sensing mode.)
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan Phone: +81-568-33-7861 FAX: +81-568-33-8591
For sales network, please visit our website.
© Panasonic Industrial Devices SUNX Co., Ltd. 2015
PRINTED IN JAPAN
OUT2OUT1
MODE
-3
-1
-1
-2
-3
-2
Loading...