Thank you very much for purchasing Panasinic products.
Read this Instruction Manual carefully and thoroughly for
the correct and optimum use of this product. Kindly keep
this manual in a convenient place for quick reference.
MJE-DP2 No.0048-50V
WARNING
Never use this product as a sensing device for personnel protection.
●
In case of using sensing devices for personnel protection, use products which meet laws and standards, such as
●
OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
In case this sensor is used within Japan, SI unit must be used since use of pressure units in Japan is restricted to SI units.
●
1
SPECIFICATIONS
Vacuum pressure
Type
Asian
North American (Note)
Model No.
European
Item
Type of pressure
Rated pressure range
Set pressure range-0.050 to 1.000MPa-5.0 to 100.0kPa5.1 to -101.3kPa
Pressure withstandability
Applicable fluidNon-corrosive gas
Selectable unitskgf/cm2, bar, psikgf/cm2, bar, psi, mmHg, inHg
Supply voltage
Current consumption
Comparative outputs
Comparative Output 1
Comparative Output 2
Output modes
Short-circuit protection
Analog voltage
output
Displayable pressure range
Comparative Output 1
Operation
indicators
Comparative Output 2
Ambient temperature
Overvoltage category
Temperature characteristics
AsianStandard ・ Flat ・ IP67 types: Rc (PT)
Pressure
North American
port
EuropeanFlat ・ IP67 types: G (PF)
Material
Note:
Model Nos. of North American standard type having the suffix '-P' are PNP output type.
2
CAUTIONS
StandardFlat
DP2-20
DP2-20F(-P)
-
Asian
North American (Standard NPN output, Flat, IP67 types)
DP2 series is designed for use with non-corrosive gas.
It cannot be used for liquid or corrosive gas.
T
his product has been developed / produced for
●
industrial use only.
●
Use within the rated pressure range.
Do not apply pressure exceeding the pressure
●
withstandability value. The diaphragm will get damaged
and correct operation shall not be maintained.
Make sure to carry out the wiring in the power supply
●
off condition.
●
Take care that wrong wiring will damage the sensor.
●
Verify that the supply voltage variation is within the rating.
If power is supplied from a commercial switching
●
regulator, ensure that the frame ground (F.G.) terminal
of the power supply is connected to an actual ground.
●
In case noise generating equipment (switching
regulator, inverter motor, etc.) is used in the vicinity of
this sensor, connect the frame ground (F.G.) terminal
of the equipment to an actual ground
-101kPa type
-
DP2-40N DP2-60N
DP2-40E DP2-60E
0.4V or less (at 16mA sink current)
1 digit (However, variable in hysteresis mode and 2 digits when using psi unit)Hysteresis
Output voltage: 1 to 5V (over rated pressure range)
Zero-point: within 1V ±5% F.S.
Span: within 4V ±5% F.S.
Linearity: within ±1% F.S.
Output impedance: 1kΩ approx.
Do not use during the initial transient time (0.5 sec.)
●
after the power supply is switched on.
Do not run the wires together with high-voltage lines or
●
power lines or put them in the same raceway. This can
cause malfunction due to induction.
●
This product is suitable for indoor use only.
Avoid use of standard type, flat type and light weight type
●
of sensor in places where steam and dust is excessive.
Take care that the sensor does not come in contact
●
with water, oil, grease, or organic solvents, such as,
thinner, etc.
Do not insert wires, etc, into the pressure port. The
●
diaphragm will get damaged and correct operation
shall not be maintained.
●
Do not operate the keys with pointed or sharp objects.
●
Make sure that stress by forcible bend or pulling is not
applied directly to the sensor cable joint.
●
Extension up to total 100m is possible with 0.3mm
more, cable. However, in case of using this product as
a CE Marking conformity product, the power wire
connected to this product must be within 10m.
Positive pressure
DP2-22F(-P)
<
North American (Standard PNP output type), European
PNP open-collector transistor
・Maximum source current: 100mA
・Applied voltage: 30V DC or less
・
Residual voltage: 2V or less (at 100mA source current)
5
1
Pressure
1
/8 female thread
(between comparative output and +V)
1MPa type100kPa type
DP2-42N DP2-62N
-
DP2-42E DP2-62E
0 to 1.000MPa0 to 100.0kPa0 to -101.3kPa
1.47MPa490kPa
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
-0.050 to 1.000MPa-5.0 to 100.0kPa5.1 to -101.3kPa
2
>
, or
3
SETTING OF PRESSURE LEAD
DIRECTION AND PIPING
Standard type
●
Setting of pressure lead direction
・
The pressure lead
direction can be changed
by dismantling the
pressure port attachment
and changing the
mounting direction. The
tightening torque of the
hexagon-socket-head
bolt (length 9mm or less)
should be 0.29N・m or
less.
Please make sure to close any unused pressure port with
Note:
Pressure port
attachment
Hexagon-sockethead plug
the hexagon-socket-head plug supplied as accessory.
●
Piping
・
When connecting a
hexagon-socket-head plug
or coupling to the pressure
port, hold the hexagonal
part of the pressure port
with a 12mm spanner and
make sure that the
tightening torque is 9.8N・m or less. Also, in order to
prevent any leakage, wind a sealing tape on the
coupling when connecting.
However, sealing tape is not required for North
American type using NPTF
is required if NPT
1
/8 coupling is used.)
Flat type, Light weight type
●
Setting of pressure lead direction
・
The pressure lead direction can be changed by dismantling
the pressure port attachment and changing the mounting
direction. The tightening torque of the hexagon-socket-head
bolt (length 9mm or less) should be 0.29N・m or less.
Pressure port attachment
Main body
Pressure port
●
Piping
・
When connecting a coupling
to the pressure port, hold the
pressure port attachment
with a 16mm (Light weight
type: 10mm) spanner and
make sure that the tightening
torque is 9.8N・m or less
(Light weight type: 1.47N・m
or less). Also, in order to prevent any leakage, wind a
sealing tape on the coupling when connecting.
IP67 type
●
Piping for pressure measurement inlet port
・
When connecting a coupling to the pressure measurement
inlet port, hold the pressure port attachment with a spanner
and make sure that the tightening torque is 9.8N・m or less.
Also, in order to prevent any leakage, wind a sealing
tape on the coupling when connecting.
●
Piping for atmospheric pressure inlet port
・
If there is a possibility of
water entering into the
sensor enclosure through
the atmospheric pressure
inlet port, connect a tube
to the atmospheric
pressure inlet port through
a M5 coupling and extend
the other end of the tube
to a safe place. In this
case, ensure that this end
of the tube does not get
clogged.
●
Fitting of front cover
・
Insert the bosses on the front cover into the guide
holes at the bottom of the pressure port attachment,
and push in the
direction of the
Hook
arrow to fit the
hook.
When removing
the front cover,
release the hook
first.
Main body
Hexagonsockethead bolts
Pressure
ports
12mm spanner
1
/8 coupling. (Sealing tape
Hexagon-sockethead bolts
2-φ4.3mm mounting holes
16mm
(light weight type: 10mm)
spanner
Safe place,
where there is no
exposure to water
Atmospheric
pressure inlet port
M5 coupling
Tube
Pressure measurement
inlet port
Guide holes
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
4
MOUNTING OF STANDARD
TYPE SENSOR
●
A sensor mounting bracket MS-DPX and MS-DPX-4
(optional) may be used.
When mounting the sensor with the sensor mounting
bracket, etc., the tightening torque should be 1.2N・m
or less.
<MS-DPX>
<MS-DPX-4>
Sensor mounting
bracket
MS-DPX-4 (optional)
Note: In case mounting brackets or screws other than the
Note:
Note:
M4 (length 6mm) pan head screw
(attached with MS-DPX)
Spring washer
(attached with MS-DPX)
Sensor mounting bracket
MS-DPX (optional)
Spring washer
(attached with MS-DPX-4)
M4 (length 6mm) pan head screw
(attached with MS-DPX-4)
sensor mounting bracket shown in the figure above
are used, the length of the screws inserted into the
pressure port attachment should be 5mm or less. If
the length of the screws is longer than 5mm, the
sensor may be damaged.
●
Panel mounting bracket MS-DPX-2 (optional) and a front
protection cover DPX-04 (optional) are also available.
Front protection cover
DPX-04 (optional)
5
I/O CIRCUIT DIAGRAM
●
NPN output type
D
1kΩ
ZD1
Tr1
ZD2
Sensor circuit
ZD3
Tr2
DP2-20
–101.3kPa
OUT2OUT1
0-ADJ
MODE
Panel mounting bracket
MS-DPX-2 (optional)
(Suitable for 1 to 3.2mm thick panel)
Color code
(Brown) +V
(Gray) Analog
voltage output
(Note)
(Black) Comparative Output 1
(White) Comparative Output 2
(Blue) 0V
100mA max.
100mA max.
Load
Load
Users’ circuitInternal circuit
+
-
12 to 24V
+10
%
-15
The analog voltage output is not incorporated with a
short-circuit protection circuit. Do not directly connect
a power supply or a capacitive load. When using the
analog voltage output, take care to connect external
equipment of proper input impedance.
Also, when a cable extension is used, voltage drop
due to cable resistance should be taken into account.
The analog voltage output is not incorporated with a
short-circuit protection circuit. Do not directly connect
a power supply or a capacitive load. When using the
analog voltage output, take care to connect external
equipment of proper input impedance.
Also, when a cable extension is used, voltage drop
due to cable resistance should be taken into account.
When an error occurs, take the following corrective action.
●
Error message
8
ANALOG BAR DISPLAY
Pressure changes are displayed in an analog fashion by using LED bars.
●
Hence, any sudden changes in pressure can be detected at a glance.
The analog bar display shows the measured pressure,
●
irrespective of the pressure unit, in steps of 10% F.S. approx.
Please refer to ' SETTING ② Initial setting' for the
Displays measured pressure, settings,
error messages and key-protect status.
Lights up when Comparative Output 1 is ON.
Lights up when Comparative Output 2 is ON.
In the initial setting mode, pressing
・
the key changes the settable digit.
In the Set Value 1, 2 modes,
・
pressing the key changes the set
value to the high pressure side in
case of positive pressure type sensor
and to the high vacuum side in case
of vacuum pressure type sensor.
In the sensing mode, if the key is
・
pressed continuously for 4 sec. or more,
the display shows peak hold value.
In the initial setting mode, pressing
・
the key changes the set conditions.
In the Set Value 1, 2 modes,
・
pressing the key changes the set
value to the low pressure side in
case of positive pressure type sensor
and to the low vacuum side in case
of vacuum pressure type sensor.
In the sensing mode, if the key is
・
pressed continuously for 4 sec. or more,
the display shows bottom hold value.
Pressing the key changes the selected
・
mode to sensing mode, Set Value 1 (P1)
set mode and Set Value 2 (P2) set mode.
In the sensing mode, if the key is
・
pressed continuously for about 3 sec.,
key-protect can be set/released.
In the sensing mode, if the mode selection
・
key is pressed while pressing the increment
key ( ), the initial setting mode is obtained.
Cause
Overcurrent due to
short-circuit.
Pressure is being
applied during
zero-point adjustment.
Applied pressure exceeds
the upper limit of
displayable pressure range.
Positive
pressure
type
Applied pressure exceeds
the lower limit of
displayable pressure range.
Vacuum
pressure
type
Applied pressure exceeds
the lower limit of
displayable pressure range.
Positive
pressure
type
Applied pressure exceeds
the upper limit of
displayable pressure range.
pressure
type
Vacuum
11
procedure to change to analog bar display.
Analog bar display for positive pressure type sensor
Atm. pressure condition
DP2-21
100kPa
OUT2OUT1
MODE
0-ADJ
DP2-21
High pressure condition
100kPa
OUT2OUT1
MODE
0-ADJ
Analog bar display for vacuum pressure type sensor
Atm. pressure condition
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
DP2-20
High vacuum condition
-101.3kPa
OUT2OUT1
MODE
0-ADJ
③
⑥
In the sensing mode, if both the keys are pressed
simultaneously, zero-point adjustment is done.
Corrective action
Switch off the power
supply and check the
load.
Applied pressure at the pressure
port should be brought to
atmospheric pressure and zero-point
adjustment should be done again.
Applied pressure should
be brought within the
rated pressure range.
DP2-21
100kPa
OUT2OUT1
MODE
0-ADJ
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
9
OUTPUT MODES & THEIR
CHARACTERISTICS
Hysteresis mode ( )
● The common hysteresis of the comparative outputs
can be set, as desired, with the set values.
ON
Comparative
Output 1
OFF
ON
Comparative
Output 2
OFF
0
Set Value 1 (P1)Set Value 2 (P2)
Window comparator mode ( )
The comparative outputs can be turned ON or OFF by a pressure
●
which is within the pressure range set by Set Value 1 and Set Value 2.
ON
Comparative
Output 1
OFF
ON
Comparative
Output 2
OFF
0
Set Value 1 (P1)
When operating in window comparator mode ( ) Set
Value 1 (P1) and Set Value 2 (P2) should be set with a
difference of 3 digits or more. However, when the
pressure unit is set to 'psi' ( ), the difference should be 6
digits or more.
Dual output mode ( )
The outputs can be put to different use such as detection of
●
different kinds of objects, control function, alarm function etc.
Hysteresis
ON
Comparative
Output 1
OFF
ON
Comparative
Output 2
OFF
0
Set Value 1 (P1)Set Value 2 (P2)
Automatic sensitivity setting mode ( )
Using actual objects, if the pressure values for OK objects
●
and NG objects are input, then the sensor is automatically
set to the optimum pressure value (mid-value).
ON
Comparative
Output 1
OFF
ON
Comparative
Output 2
OFF
0
Set Value 1 (P1)Set Value 2 (P2)
10
PRESSURE UNITS
The pressure unit can be selected as per customer's requirement.
●
In case of positive pressure type, the pressure unit can be
●
changed from International System of Units (SI) 'kPa' or 'MPa'
2
', 'bar' or 'psi'. In case of vacuum pressure type, the
to 'kgf/cm
pressure unit can be changed from International System of
Units (SI) 'kPa' to 'kgf/cm
When the pressure unit is changed, the set values
・
and the measured value are automatically converted.
Please refer to ' SETTING ② Initial setting' for
・
the procedure to change the pressure unit.
inHg
mmHgpsibar
Note:
'MPa' in case of DP2-22□, DP2-42□ and DP2-62□.
Hysteresis
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
HysteresisHysteresis
Set Value 2 (P2)
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
Hysteresis: 1 digit
2 digits when using
psi unit
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
Hysteresis
Set Value 3 (P3)
2
', 'bar', 'psi', 'mmHg' or 'inHg'.
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
11
International System
of Units (SI)
kPa (Note)
: Positive pressure type: Vacuum pressure type
Hysteresis:
1 digit or more
2 digits or more
when using psi unit
Hysteresis: 1 digit
2 digits when using
psi unit
Hysteresis: 1 digit
2 digits when using
psi unit
kgf/cm
2
11
SETTING
●●If key-protect has been set, make sure to release
key-protect before operating the keys. (Please refer to
15
' KEY-PROTECT FUNCTION' for the procedure.)
The conditions which are set are stored in an EEPROM.
Please note that the EEPROM has a life span and its
guaranteed life is 100,000 write operation cycles.
Setting procedure
①
Zero-point
adjustment
Adjust
zero-point
②
Initial
setting
Set [Display],
[Output mode],
and [Unit]
③
Pressure
value setting
Enter
Set Value 1 (P1)
Set Value 2 (P2)
Set Value 3 (P3)
Measurement
Commence
measurement
on completion
of setting
① Zero-point adjustment
● The displayed pressure when the pressure port is left
open is adjusted to zero.
Set to sensing mode
DP2-20
-101.3kPa
・The sensor will automatically enter the
sensing mode when power is supplied.
OUT2OUT1
The figure on the left shows the display
MODE
0-ADJ
when the pressure unit and display are set
to 'kPa' and 'digital display', respectively.
Perform zero-point adjustment
DP2-20
-101.3kPa
Let the pressure port be at atmospheric pressure (i.e.,
・
no applied pressure condition), and press, simultane-
OUT2OUT1
ously, the increment and decrement keys continuously.
MODE
0-ADJ
is displayed and, when the fingers are
・
released, zero-point adjustment is completed
and the sensor returns to the sensing mode.
DP2-20
-101.3kPa
0-ADJ
If pressure has been applied during zero-point
・
adjustment, is displayed when
OUT2OUT1
the keys are pressed. Bring the applied
MODE
pressure to atmospheric pressure (i.e., no
applied pressure condition) and carry out the
zero-point adjustment once again.
② Initial setting
● Pressure [Unit], [Display] and [Output mode] of the
comparative outputs are set.
Set to initial setting mode
DP2-20
-101.3kPa
In the sensing mode, press key while
・
pressing key.
OUT2OUT1
MODE
0-ADJ
Initial setting is displayed.
・
If sensor is being used for the first
・
time, is displayed.
MODE
Set initial conditions
DP2-20
-101.3kPa
The settable digit blinks.
・
The settable digit changes when key
・
OUT2OUT1
is pressed.
MODE
0-ADJ
DP2-20
-101.3kPa
Change the setting of each digit as
・
desired.
OUT2OUT1
The setting is changed when key is
・
MODE
0-ADJ
pressed.
Change with key.
3rd digit2nd digit
1st digit
UnitOutput modeDisplay
: kPa or
MPa
: kgf/cm
: bar
Positive
pressure type
: psi
: mmHg
pressure type
Vacuum
: inHg
2
: Hysteresis
mode
: Window
comparator
mode
: Dual output
mode
: Automatic
sensitivity
setting mode
: Digital
display
: Analog
bar
display
Set to sensing mode
DP2-20
-101.3kPa
・ Press key.
OUT2OUT1
MODE
0-ADJ
MODE
The sensor returns to sensing mode
・
after the initial conditions have been set.
Since the initial conditions which
・
have been set are stored in an
EEPROM, they are not erased even
if the power supply is switched off.
The figure on the left shows the display
・
when the unit and display are set to
'kPa' and 'digital display', respectively.
③ Setting of pressure values
For the case when output mode is set to either the hysteresis
mode ( ), window comparator mode ( ) or dual output mode ( ).
● [Set Value 1 (P1)] and [Set Value 2 (P2)] of the
comparative outputs are set.
The setting of Set Value 2 (P2) with respect to Set Value 1
・
(P1) can only be towards the high pressure side in case of
the positive pressure type sensor and only towards the high
vacuum side in case of the vacuum pressure type sensor.
・
Set Value 1 (P1) and Set Value 2 (P2) can be made common
for all the output modes. However, when a changeover is
made to the automatic sensitivity setting mode, since Set
Value 3 (P3) has not been set, make sure to carry out the
pressure value settings for the automatic sensitivity mode.
Set to Set Value 1 (P1) set mode
DP2-20
-101.3kPa
・In the sensing mode, press key.
・・and Set Value 1 (P1) which
OUT2OUT1
MODE
0-ADJ
is being set are displayed
alternately.
MODE
The figure on the left shows the
Displayed
alternately
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
display of a vacuum pressure
type sensor when the pressure
unit has been set to 'kPa'.
Enter Set Value 1 (P1)
DP2-20
-101.3kPa
・
Enter using key and key.
・
In case of the positive pressure type
OUT2OUT1
sensor, if key is pressed once the set
MODE
0-ADJ
value changes towards the high
Displayed
alternately
pressure side by 1 digit and if key is
Displayed
alternately
DP2-20
0-ADJ
pressed once the set value changes
towards the low pressure side by 1 digit.
In case of the vacuum pressure type
-101.3kPa
sensor, if key is pressed once the
set value changes towards the high
OUT2OUT1
vacuum side by 1 digit and if key is
MODE
pressed once the set value changes
towards the low vacuum side by 1 digit.
・
If key or key is pressed continuously, the set value changes quickly.
If the set pressure range is exceeded,
either (upper limit exceeded) or
(lower limit exceeded) is displayed.
Displayed
alternately
Set to Set Value 2 (P2) set mode
DP2-20
-101.3kPa
In the Set Value 1 (P1) set mode, press
・
MODE
key.
and Set Value 2 (P2) which is
being set are displayed alternately.
Displayed
alternately
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Enter Set Value 2 (P2)
DP2-20
Displayed
alternately
DP2-20
-101.3kPa
・Using key and key, enter in a
manner similar to that for entering Set
OUT2OUT1
Value 1 (P1).
MODE
0-ADJ
0-ADJ
If the set pressure range is exceeded,
either (upper limit exceeded) or
(lower limit exceeded) is displayed.
-101.3kPa
OUT2OUT1
MODE
Displayed
alternately
If the output mode has been set to the window
comparator mode ( ) in the initial setting mode, Set
Value 1 (P1) and Set Value 2 (P2) should be set with a
difference of 3 digits or more. However, when unit is set
to 'psi', the difference should be 6 digits or more.
Displayed
alternately
Set to sensing mode
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
MODE
・Press key.
・・The sensor returns to sensing
mode after Set Value 1 (P1) and
Set Value 2 (P2) have been set.
Since the values which have been
set are stored in an EEPROM,
they are not erased even if the
power supply is switched off.
For the case when the output mode is set to automatic
sensitivity setting mode ( )
● Comparative outputs' [Set Value 1 (P1)], [Set Value 2
(P2)] and [Set Value 3 (P3)] are set.
The setting of Set Value 2 (P2) with respect to Set Value 1
・
(P1) can only be towards the high pressure side in case of
the positive pressure type sensor and only towards the high
vacuum side in case of the vacuum pressure type sensor.
・
Set Value 3 (P3) is automatically set to the mid-value of Set
Value 1 (P1) and Set Value 2 (P2). However, if Set Value 1 (P1)
is set to a value on the vacuum pressure side for a positive
pressure type sensor or to the positive pressure side for a
vacuum pressure type sensor, Set Value 3 (P3) is automatically
set to the mid-value of 'zero' (atmospheric pressure) and Set
Value 2 (P2). Further, if both, Set Value 1 (P1) and Set Value 2
(P2) are set to a value on the vacuum pressure side for a
positive pressure type sensor or to the positive pressure side
for a vacuum pressure type sensor, Set Value 3 (P3) is
automatically set to 'zero' (atmospheric pressure).
・
The automatically set Set Value 3 (P3) can be changed manually.
・
Since display of error messages is not possible during pressure
value setting in the automatic sensitivity setting mode, make
sure that the sensor is used within the rated pressure range.
Set to Set Value 1 (P1) set mode
DP2-20
-101.3kPa
・In the sensing mode, press key.
・・and Set Value 1 (P1) which
OUT2OUT1
MODE
0-ADJ
is being set are displayed
alternately.
MODE
The figure on the left shows the
display of a vacuum pressure
type sensor when the pressure
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
unit has been set to 'kPa'.
Enter Set Value 1 (P1)
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Within the required permissible
・
pressure range, having created a
pressure state which is nearest to the
atmospheric pressure, press key.
The pressure value at the time of
・
pressing key is entered as Set
Value 1 (P1). Set Value 1 (P1) and
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
are displayed alternately.
・
If the set pressure range is
exceeded, either (upper limit
exceeded) or (lower limit
exceeded) are displayed and Set
Value 1 (P1) is set automatically
to the upper or lower limit of the
set pressure range.
・
The setting of Set Value 1 (P1)
can be repeated several times in
the Set Value 1 (P1) set mode.
Set to Set Value 2 (P2) set mode
DP2-20
-101.3kPa
In the Set Value 1 (P1) set mode, press
・
MODE
key.
and Set Value 2 (P2) which is
being set are displayed alternately.
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Enter Set Value 2 (P2)
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
Within the required permissible pressure
・
range, having created a pressure state
which is nearest to the high pressure
end (for a positive pressure type sensor)
or the high vacuum end (for a vacuum
pressure type sensor), press key.
The pressure value at the time of
・
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
pressing key is entered as Set
Value 2 (P2). Set Value 2 (P2) and
are displayed alternately.
If the set pressure range is
・
exceeded, either (upper limit
exceeded) or (lower limit
exceeded) are displayed and Set
Value 2 (P2) is set automatically
to the upper or lower limit of the
set pressure range.
The setting of Set Value 2 (P2)
・
can be repeated several times in
the Set Value 2 (P2) set mode.
Set to Set Value 3 (P3) set mode
DP2-20
-101.3kPa
In the Set Value 2 (P2) set mode, press
・
MODE
key.
and the automatically set Set Value
・
3 (P3) are displayed alternately.
In case
・
Set Value 1 (P1) = -50.0kPa
Set Value 2 (P2) = -100.0kPa
then
Set Value 3 (P3) =
-50.0+(-100.0)
2
=-
Digits smaller than the displayed
digits are discarded.
75.0kPa
Displayed
alternately
DP2-20
OUT2OUT1
MODE
0-ADJ
-101.3kPa
OUT2OUT1
MODE
0-ADJ
In case Set Value 3 (P3) is to be changed
The automatically set Set Value 3 (P3) can be manually
changed to a value between Set Value 1 (P1) and Set Value 2
(P2). However Set Value 3 (P3) cannot be set to a value on the
vacuum pressure side for a positive pressure type sensor or to
the positive pressure side for a vacuum pressure type sensor.
Hysteresis
Changeable
range
Set Value 1 (P1)Set Value 2 (P2)
Set Value 3 (P3)
-101.3kPa
・
Enter using key and key.
・
In case of a positive pressure type
OUT2OUT1
sensor, if key is pressed once, the
MODE
set value changes towards the high
Hysteresis: 1 digit
2 digits when psi
unit is used
High pressure
(Positive pressure type)
High vacuum
(Vacuum pressure type)
Comparative
Output 1
OFF
Comparative
Output 2
OFF
DP2-20
ON
ON
0
0-ADJ
pressure side by 1 digit and if key is
Displayed
alternately
DP2-20
0-ADJ
pressed once, the set value changes
towards the low pressure side by 1 digit.
In case of a vacuum pressure type
-101.3kPa
sensor, if key is pressed once the
set value changes towards the high
OUT2OUT1
vacuum side by 1 digit and if key is
MODE
pressed once the set value changes
towards the low vacuum side by 1 digit.
・
If key or key is pressed continuously, the set value changes quickly.
If the set pressure range is exceeded,
either (upper limit exceeded) or
(lower limit exceeded) is displayed.
Set to sensing mode
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
MODE
・Press key.
The sensor returns to the sensing mode
・
after Set Value 1 (P1), Set Value 2 (P2)
and Set Value 3 (P3) have been set.
Since the values which have been
・
set are stored in an EEPROM,
they are not erased even if the
power supply is switched off.
12
PROCEDURE FOR CHECKING SET VALUES
● The conditions which have been set in the initial
setting and the pressure settings can be checked by
the following procedure.
Procedure to check initial conditions
Set to sensing mode
MODE
Press key
while pressing
key.
Sensor enters initial setting mode
Initial conditions which have been set
are displayed and can be checked.
MODE
Press key.
Sensor returns to sensing mode
Procedure to check set values
Set to sensing mode
MODE
Press key.
Sensor enters Set Value 1 (P1) set mode
Set Value 1 (P1) which has been set
is displayed and can be checked.
MODE
Press key.
Sensor enters Set Value 2 (P2) set mode
Set Value 2 (P2) which has been set
is displayed and can be checked.
MODE
Press key.
In case of auto-matic
sensitivity setting
mode only
Sensor enters Set Value 3 (P3) set mode
Set Value 3 (P3) which has been set
is displayed and can be checked.
MODE
Press key.
Sensor returns to sensing mode
Please note that if any key, except key, is pressed in
MODE
any setting mode, the set conditions shall get changed.
13
CONVERSION OF PRESSURE UNITS
●
In the DP2 series, the conversion to different units is automatically done on changing the setting of the pressure unit.
However, this conversion can also be obtained by multiplying the values by the coefficients given in the following table.
Conversion procedure
・
For example, if 2kPa is to be expressed in kgf/cm2, since 1kPa=1.01972×10-2kgf/cm2, 2kPa becomes 2×1.01972×10-2
≒0.020kgf/cm
2
Conversion table for pressure units
kPaMPakgf/cm2bar
1kPa
1MPa
1kgf/cm
1bar
1psi
1mmHg
(1Torr)
1inHg
1atm
14
PEAK HOLD & BOTTOM HOLD FUNCTIONS
Peak hold and bottom hold functions enable the display
●
of the peak value (maximum pressure value in case of
the positive pressure type sensor and maximum vacuum
pressure value in case of the vacuum pressure type
sensor) and the bottom value (minimum pressure value
in case of the positive pressure type sensor and
minimum vacuum pressure value in case of the vacuum
pressure type sensor) of the varying measured pressure.
These functions are convenient for finding the
●
pressure variation range or for determining the
reference for pressure settings.
・・Please note that the peak value and the bottom value
data is erased when it is no longer displayed.
The response time of the comparative outputs becomes
slower during the peak hold and bottom hold display.
Peak hold display
Initiating peak hold display
DP2-20
-101.3kPa
・In the sensing mode, keep key
pressed until is displayed. (4 sec.
OUT2OUT1
approx.) When the finger is released
MODE
after is displayed, the peak value
and are displayed alternately.
If the applied pressure exceeds the
・
displayable pressure range, error
-101.3kPa
message ( or ) and
are displayed alternately. In this
case, bring back the applied pressure
OUT2OUT1
to within the rated pressure range.
MODE
The figure on the left shows the
・
display of a vacuum type sensor when
Displayed
alternately
0-ADJ
DP2-20
0-ADJ
the pressure unit has been set to 'kPa'.
Ending peak hold display
DP2-20
-101.3kPa
・Press key.
(Sensor returns to sensing mode.)
OUT2OUT1
MODE
0-ADJ
Bottom hold display
Initiating bottom hold display
DP2-20
-101.3kPa
・
In the sensing mode, keep key
pressed until is displayed. (4 sec.
OUT2OUT1
approx.) When the finger is released
MODE
Displayed
alternately
0-ADJ
DP2-20
0-ADJ
after is displayed, the bottom value
and are displayed alternately.
If the applied pressure exceeds the
・
displayable pressure range, error
message ( or ) and
-101.3kPa
OUT2OUT1
MODE
are displayed alternately. In this
case, bring back the applied pressure
to within the rated pressure range.
The figure on the left shows the
・
display of a vacuum type sensor when
the pressure unit has been set to 'kPa'.
1.45038×1027.50062×1030.2953×10
-2
15.17147×102.036
-2
0.49122.5400×1013.342×10
15
KEY-PROTECT FUNCTION
● Key-protect is a function which prevents any
unintentional change in the conditions which have
been entered in each setting mode by making the
sensor not to respond to the key operations.
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
・・Since the key-protect information is stored in an
EEPROM, it is not erased even if the power supply
is switched off.
Please take care to remember if the key-protect
function has been set.
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
When the keys are to be operated, make sure that
key-protect is released.
16
LABEL FOR CHANGE IN
PRESSURE UNIT
● When a pressure unit other than 'kPa' or 'MPa' has
been selected in the initial setting mode, the label
(supplied as accessory) which corresponds to the
selected unit should be stuck at the position shown
in the figure below.
Pressure unit label (accessory)
-101.3kPa用
-1.033kgf/cm
-14.70psi
-1.013bar
-760mmHg
-29.9inHg
圧力センサ用 単位切り換え銘板
17
INTENDED PRODUCTS FOR
CE MARKING
●
The models listed under ' SPECIFI-CATIONS'
come with CE Marking.
As for all other models, please contact our office.
Contact for CE
●
Panasonic Marketing Europe GmbH Panasonic
Testing Center
Winsbergring 15, 22525 Hamburg,Germany
mmHg
(Torr)
-1
7.500620.2953
inHgpsiatm
3
7.35559×1022.8959×10
7.50062×1022.953×10
-2
13.9370×10
-2
7.60000×1022.9921×101
Setting of key-protect
In the sensing mode, press key
・
continuously for about 3 sec. and release
it immediately when is displayed.
Key-protect is set and the sensor
returns to the sensing mode.
Release of key-protect
・
In the sensing mode, press key
continuously for about 3 sec. and release
it immediately when is displayed.
Key-protect is released and the
sensor returns to the sensing mode.
2
100kPa用
1.020kgf/cm
14.50psi
1.000bar
2
1MPa用
10.20kgf/cm
145.0psi
10.00bar
N2L58
2
Stick the pressure
unit label at the
position shown.
1
9.86923×10
9.86923
9.67841×10
9.86923×10
6.80457×10
1.31579×10
DP2-20
0-ADJ
MODE
MODE
–101.3kPa
Ending bottom hold display
DP2-20
-101.3kPa
OUT2OUT1
MODE
0-ADJ
・Press key.
(Sensor returns to sensing mode.)