Mitsubishi PLFY-P32VAM-E.UK, PLFY-P40VAM-E.UK, PLFY-P50VAM-E.UK, PLFY-P63VAM-E.UK, PLFY-P80VAM-E.UK Service Manual

...
0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

July 2006

No. OC313

REVISED EDITION-B

TECHNICAL & SERVICE MANUAL

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

[Model names] [Service Ref.]

PLFY-P32VAM-E

PLFY-P32VAM-E.UK

 

PLFY-P40VAM-E

PLFY-P40VAM-E.UK

 

PLFY-P50VAM-E

PLFY-P50VAM-E.UK

 

PLFY-P63VAM-E

PLFY-P63VAM-E.UK

 

PLFY-P80VAM-E

PLFY-P80VAM-E.UK

 

PLFY-P100VAM-E

PLFY-P100VAM-E.UK

 

PLFY-P125VAM-E

PLFY-P125VAM-E.UK

 

Revision:

RoHS PARTS LIST is added.

Some descriptions have been modified.

Please void OC313 REVISED EDITION-A.

Note:

This manual does not cover outdoor units.

When servicing them, please refer to the outdoor unit’s service manual.

RoHS compliant products have <G> mark on the spec name plate.

For servicing of RoHS compliant products, refer to the RoHS Parts List.

CONTENTS

1. SAFETY PRECAUTION···········

2. PART NAMES AND FUNCTIONS ······

3. SPECIFICATIONS·············

4. 4-WAY AIR FLOW SYSTEM ·········

5. OUTLINES AND DIMENSIONS·······

6. WIRING DIAGRAM············

7. REFRIGERANT SYSTEM DIAGRAM ·····

8. TROUBLE SHOOTING···········

9. DISASSEMBLY PROCEDURE·······

10 . PARTS LIST················ INDOOR UNIT 11. RoHS PARTS LIST ············

12. OPTIONAL PARTS ············

1 SAFETY PRECAUTION

CAUTIONS RELATED TO NEW REFRIGERANT

Cautions for units utilizing refrigerant R407C

Do not use the existing refrigerant piping.

The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.

Use “low residual oil piping”

If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.

Store the piping to be used during installation indoors with keep both ends sealed until just before brazing.

(Store elbows and other joints in a plastic bag.)

If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.

Use ESTR , ETHER or HAB as the lubricant to coat flares and flange connection parts.

If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.

[1] Cautions for service

Use liquid refrigerant to charge the system.

If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.

Do not use a refrigerant other than R407C.

If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.

Use a vacuum pump with a reverse flow check valve.

The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.

Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

2

[2] Refrigerant recharging

(1) Refrigerant recharging process

1Direct charging from the cylinder.

·R407C cylinder are available on the market has a syphon pipe. ·Leave the syphon pipe cylinder standing and recharge it.

(By liquid refrigerant)

Unit

Gravimeter

(2) Recharge in refrigerant leakage case

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release the refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

[3] Service tools

Use the below service tools as exclusive tools for R407C refrigerant.

No.

Tool name

Specifications

 

 

 

1

Gauge manifold

·Only for R407C.

 

 

 

 

 

·Use the existing fitting SPECIFICATIONS. (UNF7/16)

 

 

 

 

 

·Use high-tension side pressure of 3.43MPa·G or over.

 

 

 

2

Charge hose

·Only for R407C.

 

 

 

 

 

·Use pressure performance of 5.10MPa·G or over.

 

 

 

3

Electronic scale

 

 

 

4

Gas leak detector

·Use the detector for R134a or R407C.

 

 

 

5

Adapter for reverse flow check.

·Attach on vacuum pump.

 

 

 

6

Refrigerant charge base.

 

 

 

7

Refrigerant cylinder.

·For R407C ·Top of cylinder (Brown)

 

 

·Cylinder with syphon

 

 

 

8

Refrigerant recovery equipment.

 

 

 

3

Cautions for units utilizing refrigerant R410A

Do not use the existing refrigerant piping.

The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.

Use “low residual oil piping”

If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.

Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)

If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.

Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.

If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.

Charge refrigerant from liquid phase of gas cylinder.

If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.

Do not use refrigerant other than R410A.

If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.

Use a vacuum pump with a reverse flow check valve.

Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.

Use the following tools specifically designed for use with R410A refrigerant.

The following tools are necessary to use R410A refrigerant.

 

Tools for R410A

Gauge manifold

 

Flare tool

Charge hose

 

Size adjustment gauge

Gas leak detector

 

Vacuum pump adaptor

Torque wrench

 

Electronic refrigerant

 

 

charging scale

 

 

 

Keep the tools with care.

If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.

Do not use a charging cylinder.

If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.

Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.

4

[1]Cautions for service

(1)Perform service after collecting the refrigerant left in unit completely.

(2)Do not release refrigerant in the air.

(3)After completing service, charge the cycle with specified amount of refrigerant.

(4)When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.

[2]Additional refrigerant charge

When charging directly from cylinder

·Check that cylinder for R410A on the market is syphon type.

·Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

Unit

Gravimeter

[3] Service tools

Use the below service tools as exclusive tools for R410A refrigerant.

No.

 

Specifications

1

Gauge manifold

·Only for R410A

 

 

 

 

 

·Use the existing fitting specifications. (UNF1/2)

 

 

 

 

 

·Use high-tension side pressure of 5.3MPa·G or over.

 

 

 

2

Charge hose

·Only for R410A

 

 

 

 

 

·Use pressure performance of 5.09MPa·G or over.

3Electronic scale

4

Gas leak detector

·Use the detector for R134a, R407C or R410A.

 

 

 

5

Adaptor for reverse flow check

·Attach on vacuum pump.

6Refrigerant charge base

7 Refrigerant cylinder

·Only for R410A

Top of cylinder (Pink)

 

 

Cylinder with syphon

8Refrigerant recovery equipment

5

Mitsubishi PLFY-P32VAM-E.UK, PLFY-P40VAM-E.UK, PLFY-P50VAM-E.UK, PLFY-P63VAM-E.UK, PLFY-P80VAM-E.UK Service Manual

2 PART NAMES AND FUNCTIONS

Indoor Unit

Filter

Remove dust and pollutants from return air

Horizontal Air Outlet

Sets airflow horizontal automatically during cooling or dehumidifying.

Grille

Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.

Air Intake

Returns air from room.

Wired remote controller

On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

Operation buttons

Set Temperature buttons

 

 

 

Down

 

 

 

Up

 

 

 

Timer Menu button

 

 

 

(Monitor/Set button)

 

 

 

Mode button (Return button)

 

 

 

 

 

TEMP.

 

Set Time buttons

 

 

 

Back

 

MENU

ON/OFF

Ahead

BACK

MONITOR/SET

DAY

 

Timer On/Off button

PAR-21MAA

CLOCK

(Set Day button)

 

 

 

Opening the

 

 

 

door.

 

 

 

 

 

ON/OFF button

 

 

Fan Speed button

 

 

Filter

button

 

 

(<Enter> button)

 

ON/OFF

Test Run button

 

 

 

 

 

 

Check button (Clear button)

 

FILTER

 

 

 

CHECK

TEST

 

 

OPERATION

 

Airflow Up/Down button

CLEAR

 

 

 

 

 

Louver button

 

 

(

 

Operation button)

 

 

 

 

To preceding operation

 

 

 

 

number.

 

 

Ventilation button

 

 

(

Operation button)

 

 

 

 

To next operation number.

6

Display

For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.

Identifies the current operation

Shows the operating mode, etc.

*Multilanguage display is supported.

“Centrally Controlled” indicator

Indicates that operation of the remote controller has been prohibited by a master controller.

“Timer Is Off” indicator

Indicates that the timer is off.

Temperature Setting

Shows the target temperature.

Day-of-Week

Shows the current day of the week.

Time/Timer Display

Shows the current time, unless the simple or Auto Off timer is set.

If the simple or Auto Off timer is set, shows the time remaining.

TIME SUN MON TUE WED THU FRI SAT

TIMER

Hr

ON

AFTER

AFTER

OFF

ERROR CODE

 

FUNCTION

˚F˚C

 

FILTER

˚F˚C

 

 

WEEKLY

ONLY1Hr.

 

SIMPLE

 

AUTO OFF

Up/Down Air Direction indicator

The indicator shows the direction of the outcoming airflow.

“One Hour Only” indicator

Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.)

The indicator goes off after one hour, at which time the airflow direction also changes.

Room Temperature display

Shows the room temperature.

Louver display

Indicates the action of the swing louver. Does not appear if the louver is stationary.

(Power On indicator)

Indicates that the power is on.

“Sensor” indication

Displayed when the remote controller sensor is used.

“Locked” indicator

Indicates that remote controller buttons have been locked.

“Clean The Filter” indicator

Comes on when it is time to clean the filter.

Timer indicators

The indicator comes on if the corresponding timer is set.

Fan Speed indicator

Shows the selected fan speed.

Ventilation indicator

Appears when the unit is running in Ventilation mode.

Caution

Only the Power on indicator lights when the unit is stopped and power supplied to the unit.

If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available” message.

If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.

When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.

7

3 SPECIFICATIONS

3-1. SPECIFICATIONS

Item

 

 

Power

V·Hz

Cooling capacity

kW

Heating capacity

kW

characteristic

 

Input

 

Cooling

kW

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

kW

Electric

 

Current

 

Cooling

A

 

 

Heating

A

 

 

 

 

 

 

 

 

 

 

 

 

 

Exterior

(munsell symbol)

 

 

 

 

Height

mm

 

 

 

 

Dimensions

 

Width

mm

 

 

 

 

Depth

mm

Heat exchanger

 

 

Fan No

 

 

F

 

Air flow W3

k/min

a

 

 

External

 

n

 

Pa

 

static pressure

 

 

Fan motor

kW

 

 

output

 

 

Insulator

 

 

Air filter

 

 

 

 

sideGas

[mm(in.)

 

Pipe

 

dimensions

Liquidside

[mm(in.)

Unit drain pipe size

[mm

Noise level W3

dB

Product weight

kg

 

 

 

 

 

 

PLFY-P32VAM-E.UK PLFY-P40VAM-E.UK PLFY-P50VAM-E.UK PLFY-P63VAM-E.UK

Single phase 220-230-240V 50Hz

Single phase 220V 60Hz

3.6

4.5

 

5.6

 

7.1

4.0

5.0

 

6.3

 

8.0

0.12

0.14

 

 

0.16

0.12

0.14

 

 

0.16

0.59

0.68

 

 

0.78

0.59

0.68

 

 

0.78

Unit : Galvanized sheets with gray heat insulation

Grills : ABS resin

Munsell<0.70Y 8.59/0.97>

258<30>

840<950>

840<950>

Cross fin

Turbo fan 1

14-13-12-11

16-14-13-12

18-16-15-14

 

 

 

0

0.070

Polyethylene sheet

 

PP honey comb fabric

[12.7(1/2")

 

[12.7(1/2") / [15.88(5/8")

 

(Compatible)

[6.35(1/4")

 

[6.35(1/4")/[9.52(3/8")

 

(Compatible)

O.D.32 (PVC pipe VP-25 connectable)

31-29-28-27

32-30-28-27

22<5>

[15.88(5/8")

[9.52(3/8")

33-31-29-28

24<5>

Note 1.

Rating conditions(JIS B 8616)

 

 

Cooling :

Indoor :

D.B. 27°C

W.B. 19.0°C

 

 

outdoor :

D.B. 35°C

 

 

Heating :

Indoor :

D.B. 20°C

 

 

 

outdoor :

D.B. 7°C

W.B. 6°C

Note 2.

The number indicated in < > is just for the grille.

W 3.

Air flow and the noise level are indicated as High-Medium1-Medium2-Low.

8

Item

 

 

Power

V·Hz

Cooling capacity

kW

Heating capacity

kW

characteristic

 

Input

 

Cooling

kW

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

kW

Electric

 

Current

 

Cooling

A

 

 

Heating

A

 

 

 

 

 

 

 

 

 

 

 

 

 

Exterior

(munsell symbol)

 

 

 

 

Height

mm

 

 

 

 

Dimensions

 

Width

mm

 

 

 

 

Depth

mm

Heat exchanger

 

 

Fan No

 

 

F

 

Air flow W3

k/min

a

 

 

External

 

n

 

Pa

 

static pressure

 

 

Fan motor

kW

 

 

output

 

 

Insulator

 

 

Air filter

 

 

 

 

sideGas

[mm(in.)

 

Pipe

 

dimensions

Liquidside

[mm(in.)

Unit drain pipe size

[mm

Noise level W3

dB

Product weight

kg

 

 

 

 

 

 

PLFY-P80VAM-E.UK

PLFY-P100VAM-E.UK

 

PLFY-P125VAM-E.UK

 

 

 

 

 

Single phase 220-230-240V 50Hz

 

 

Single phase 220V 60Hz

 

9.0

11.2

 

14.0

10.0

12.5

 

16.0

0.18

0.30

 

0.34

0.18

0.30

 

0.34

0.86

1.43

 

1.64

0.86

1.43

 

1.64

 

 

 

 

Unit : Galvanized sheets with gray heat insulation Grills : ABS resin

Munsell<0.70Y 8.59/0.97>

258<30>

 

298<30>

 

 

840<950>

 

 

 

840<950>

 

 

 

 

Cross fin

 

 

 

Turbo fan 1

 

22-20-18-16

 

 

29-27-24-21

 

27-25-22-19

 

 

0

 

 

0.070

 

 

 

 

0.120

 

 

 

Polyethylene sheet

 

 

 

PP honey comb fabric

 

15.88(5/8")

 

 

 

[15.88(5/8") / [19.05(3/4")

 

(Compatible)

 

 

9.52(3/8")

 

 

 

O.D.32 (PVC pipe VP-25 connectable)

 

37-35-32-30

 

 

43-41-38-35

 

41-39-36-33

 

24<5>

 

32<5>

 

 

 

 

 

 

Note 1.

Rating conditions(JIS B 8616)

 

 

Cooling :

Indoor :

D.B. 27°C

W.B. 19.0°C

 

 

outdoor :

D.B. 35°C

 

 

Heating :

Indoor :

D.B. 20°C

 

 

 

outdoor :

D.B. 7°C

W.B. 6°C

Note 2.

The number indicated in < > is just for the grille.

W 3.

Air flow and the noise level are indicated as High-Medium1-Medium2-Low.

9

3-2. ELECTRICAL PARTS SPECIFICATIONS

Model

Symbol PLFY-P32VAM-E.UK PLFY-P40VAM-E.UK PLFY-P50VAM-E.UK PLFY-P63VAM-E.UK

 

Parts name

 

 

 

Room temperature

TH21

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

thermistor

 

 

 

Liquid pipe thermistor

TH22

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

Gas pipe thermistor

TH23

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

Fuse

FUSE

 

250V 6.3A

(Indoor controller board)

 

 

 

 

 

 

 

6-pole OUTPUT 70W

Fan motor

MF

 

D17B6P70MS

 

 

(with inner-thermostat)

 

OFF 130: i 5:

 

Inner-thermostat

 

 

 

 

ON 90: i 20:

 

 

 

Fan motor capacitor

C

 

3.0+ 440V

Vane motor

MV

 

MSBPC20M04

 

DC12V 300"/phase

 

 

 

Drain-up mechanism

DP

 

PLD-12230ME-1

INPUT 12/10.8W 24R/Hr

 

 

Drain sensor

DS

Thermistor resistance 0:/6k", 10:/3.9k", 20:/2.6k", 25:/2.2k", 30:/1.8k", 40:/1.3k"

Linear expansion valve

LEV

DC12V Stepping motor drive port dimension 5.2" (0~2000pulse)

 

EDM-40YGME

 

 

 

Electric heater

H2

 

240V 21.8W

(Condensation proof)

 

 

 

 

Power supply terminal

TB2

(L, N, ;) Rated to 330V 30A W

block

 

 

 

Transmission terminal

TB5

(M1, M2, S) Rated to 250V 20A W

block

 

 

 

MA remote controller

TB15

(1, 2) Rated to 250V 10A W

terminal block

 

 

 

W Note : Refer to WIRING DIAGRAM for the supplied voltage.

10

Model

Symbol

PLFY-P80VAM-E.UK

PLFY-P100VAM-E.UK

PLFY-P125VAM-E.UK

 

Parts name

 

 

 

 

 

Room temperature

TH21

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

thermistor

 

 

 

 

 

Liquid pipe thermistor

TH22

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

Gas pipe thermistor

TH23

Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"

Fuse

FUSE

 

250V 6.3A

 

(Indoor controller board)

 

 

 

 

 

 

 

 

 

6-pole OUTPUT 70W

 

6-pole OUTPUT 120W

Fan motor

MF

D17B6P70MS

 

D176P120MS

 

 

 

 

(with inner-thermostat)

 

 

OFF 130: i 5:

 

Inner-thermostat

 

 

 

 

ON 90: i

20:

 

 

 

 

Fan motor capacitor

C

3.5+ 440V

 

7.0+ 440V

Vane motor

MV

 

MSBPC20M04

 

 

DC12V 300"/phase

 

 

 

 

 

Drain-up mechanism

DP

 

PLD-12230ME-1

 

 

INPUT 12/10.8W 24R/Hr

 

 

 

Drain sensor

DS

Thermistor resistance 0:/6k", 10:/3.9k", 20:/2.6k", 25:/2.2k", 30:/1.8k", 40:/1.3k"

Linear expansion valve

LEV

DC12V Stepping motor drive port dimension 5.2" (0~2000pulse)

 

EDM-80YGME

 

 

 

 

 

Electric heater

H2

 

240V 21.8W

 

(Condensation proof)

 

 

 

 

 

 

 

Power supply terminal

TB2

 

(L, N, ;) Rated to 330V 30A W

block

 

 

 

 

 

 

Transmission terminal

TB5

 

(M1, M2, S) Rated to 250V 20A W

block

 

 

 

 

 

 

MA remote controller

TB15

 

(1, 2) Rated to 250V 10A W

terminal block

 

 

 

 

 

 

W Note : Refer to WIRING DIAGRAM for the supplied voltage.

4 4-WAY AIR FLOW SYSTEM

4-1. PLACEMENT OF THE AIR OUTLETS

For this grille, the blowout direction comes in 11 patterns.

Also, by setting the dip switches (SWA and SWB) on the circuit board to the appropriate settings, you can adjust the air flow and speed. Select the settings from Table according to the location in which you want to install the unit.

1) Decide on the pattern of the airflow direction.

<Table 1>

4-direction

3-direction

directionBlowout pattern

Pattern 1 Factory setting

Pattern 4 One air outlet

 

fully closed

 

 

 

 

 

 

 

 

 

 

 

2-direction

Note1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For 3 and 2-directional,

 

 

 

 

Pattern 6

Two air outlet

please use the air outlet

 

 

 

 

 

 

 

 

 

fully closed

shutter plate (option).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Be sure to secure insulation material by tape and such
{125
Burring hole pitch
{100
(Cut out hole)
Ceiling surface
~

2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the up switches (SWA, SWB) on the circuit board to the appropriate setting.

• Correspondence of ceiling heights to numbers of air outlets.

-P32·P40·P50·P63·P80VAM-E

 

SWA

1

2

3

 

Standard

High ceiling 1 High ceiling 2

direction

2.7m

3.0m

3.5m

direction

3.0m

3.3m

3.5m

direction

3.3m

3.5m

-P100·P125VAM-E

 

 

SWA

1

2

3

 

Standard

High ceiling 1 High ceiling 2

direction

3.2m

3.6m

4.2m

direction

3.6m

4.0m

4.2m

direction

4.0m

4.2m

4-2. FRESH AIR INTAKE (Installation of site)

At the time of installation, use the duct holes (cutout) located at the positions shown in following diagram, as and when required.

Note :

Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement (Option)

Fresh air intake hole

Fresh air intake hole diagram

3 - {2.8 Burring hole

120_

w158

Refrigerant pipe

Drain pipe

_ 120

4-3. INTERLOCKING OPERATION METHOD WITH DUCT FAN (Booster fan)

Whenever the indoor unit is operating, the duct fun also operates.

(1)Connect the optional multiple remote controller adapter(PAC-SA88HA-E)to the connector CN51 on the indoor controller board.

(2)Drive the relay after connecting the 12V DC relay between the Yellow and Orange connector lines.

MB: Electromagnetic switch power relay for duct fan.

X:Auxiliary relay (For DC 12V, coil rating : 1.0W or below)

CN51

5

Green

 

on

 

 

Yellow

 

indoor

 

 

 

controller

1

 

Orange

MB

board

Connector (5P)

Red

 

 

Package side

Brown

 

 

Multiple remote

Installation at site

 

 

 

 

 

 

 

 

 

 

controller adapter

Be sure to secure insulation

Indoor controller board

 

PAC-SA88HA-E

material by tape and such

 

 

 

 

 

 

 

Distance between indoor

 

 

 

CN51

controller board and relay

 

 

 

must be within 10m.

Multiple remote controller adapter PAC-SA88HA-E

CN51

12