Mitsubishi LonWorks Interface, LMAP-03U TECHNICAL MANUAL

0 (0)

Echelon®, LON®, LONWORKS®, Neuron®, 3150® and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries.

LonMakerTM and the Lon Users logo are trademarks of Echelon Corporation.

Mitsubishi LonWorks Interface, LMAP-03U TECHNICAL MANUAL

Contents

 

1. Introduction..........................................................................................................................

2

1.1

Purpose of this manual ............................................................................................................................

2

1.2

Terminology used in this manual..............................................................................................................

2

2. Product Outline.....................................................................................................................

3

2.1

Outline and features.................................................................................................................................

3

2.2

List of products.........................................................................................................................................

4

2.3

Function ...................................................................................................................................................

4

2.4

Specification .............................................................................................................................................

5

3. System Design Flow ..............................................................................................................

7

4. Designing the LMAP03U.........................................................................................................

8

4.1

Selecting the air conditioners...................................................................................................................

8

4.2

Selecting the function.............................................................................................................................

10

4.3

Selecting the system control parts .........................................................................................................

12

4.4

Object.....................................................................................................................................................

14

4.5

Restrictions on system configuration .....................................................................................................

16

5. Design and Operation of LONWORKS System ..........................................................................

18

5-1 Constructing the LONWORKS network .................................................................................................

18

5.2

Function relating to installing .................................................................................................................

19

5.3

Operation at power recovery..................................................................................................................

20

5.4

Response restrictions on Poll (Fetch) demand......................................................................................

24

5.5

Operation/setting of air conditioner ........................................................................................................

25

5.6

State monitoring .....................................................................................................................................

27

5.7

Measurement (Analog value).................................................................................................................

29

5.8

Trouble/alarm monitoring .......................................................................................................................

30

5.9

Emergency stop .....................................................................................................................................

31

APPENDIX 1. Outline of Functions – Network Variables..................................................................

32

APPENDIX 2. Outline of Functions – Configuration Properties..........................................................

53

1

1. Introduction

1.1 Purpose of this manual

This manual provides design information and restrictions required by the system designing in constructing the LONWORKS ® network system using LM ADAPTER. For the items not described here, please refer to the

literatures shown below.

 

LM ADAPTER installation work

: "Installation Manual of LM ADAPTER"

M-NET wiring and designing

: DATA BOOK of air conditioner and the like

Network variable specification

: "Network Variables Specification" of LM ADAPTER

1.2 Terminology used in this manual

This manual uses abbreviations for product names and unit classification partially. The main abbreviations are given below. For the terminology relating to the LONWORKS, please see the Appendix of this manual.

LMAP

: LM ADAPTER

BMS

: Building management system

SC

: System controller

IC

: Indoor unit

OC

: Outdoor unit

RC

: Local remote controller

 

<MA remote controller (PAR-20MAU, etc.)>

 

<ME remote controller (PAR-F27MEA-US, etc)>

MA

: Local remote controller <MA remote controller (PAR-20MAU, etc.)>

ME

: Local remote controller <ME remote controller (PAR-F27MEA-US, etc)>

TR

: Central controller

2

2. Product Outline

2.1 Outline and features

The LM ADAPTER is a communication interface to connect the Mitsubishi Electric made products for M-NET use with the LONWORKS network. Only one LM ADAPTER can control and monitor indoor units up to 50 sets.

Since the LONWORKS network is an open protocol, connection with the Building management system (BMS) and other products usable with LONWORKS can be performed easily thus allowing construction of various systems including "Schedule operation," "Interlocked operation" and "Energy saving control".

<Features>

-Maximum 50 sets indoor units connectable with one LM ADAPTER

-Operation/monitoring with local remote controllers

-Standard Network Variables Type (SNVT) and enriched function (network variables)

-Various Configuration Properties (CP) essential for network construction

Building management

system (BMS)

LONWORKS network

LMAP

System remote controller

Power supply unit

control centralized NET-M

line Transmission

OC

M-NET indoor-outdoor transmission line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC

 

 

IC

 

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MA

 

 

 

 

 

 

 

 

 

 

ME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC

 

 

 

 

 

 

 

OC:Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

IC :Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

MA:MA remote controller

 

 

 

 

 

 

 

 

 

 

 

 

ME:ME remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Make sure to install the local remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller or system controller.

Figure 1-1. System configuration diagram (Example)

3

2.2 List of products

The air conditioners controllable with LM ADAPTER are shown below.

Model name

Objective models for control

 

 

LMAP03U 1

CITY MULTI, LOSSNAY

2.3 Function

The basic functions of LM ADAPTER are outlined as below.

Items2

 

Details

 

 

 

Emergency stop

 

Stopping all air conditioners. Not prohibiting local remote controller operation.

 

 

 

ON/OFF

 

Operating/monitoring ON/OFF state.

 

 

 

Mode

 

Operating/monitoring the operation mode set for air conditioners & LOSSNAYs.

 

 

 

SetPoint

 

Operating/monitoring the temperature set of air conditioners.

 

 

 

Fanspeed

 

Operating/monitoring the fan airflow rate setting.

 

 

 

Local remote controller prohibit

Operating/monitoring the operation prohibit of local remote controllers.

(ON/OFF, operation mode, temperature setting, batch)

 

 

 

 

 

Forced thermostat OFF

 

Operating/monitoring the forced thermostat OFF of air conditioners.

 

 

 

Filter sign/Run time for filter

 

Resetting/monitoring the integrated data of filter operation time.

 

 

 

 

 

Setting the local remote controller.

Local remote controller setting

(Time, temperature setting range, simplified locking, actual operation mode display, room

 

 

temperature display)

 

 

 

Defrosting state

 

Outputting the defrosting status of all air conditioners.

 

 

 

Failure/alarm

 

Outputting the failure of air conditioners, control panels and humidifiers.

 

 

 

LM ADAPTER

 

Outputting the communication error if existed between LM ADAPTER and air conditioners.

abnormal communication state

 

 

 

 

Air conditioner (charging)

information

Outputting each state of the operation/thermostat/auxiliary heater of air conditioners.

(thermostat status)

 

 

 

 

 

 

Air conditioner (charging)

information

Outputting the capacity code of air conditioners.

(capacity code)

 

 

 

 

 

 

Space temperature status

 

Outputting the outlet and inlet temperature of each air conditioner.

 

 

 

1North America model

2The applicable function differs depending on the objective models for control.

4

2.4 Specification

(1) Product specification

 

Items 1

 

Specification

Dimension

 

340mm(Height) x 360mm(Width) x 59.6mm(Depth)

 

 

 

13 7/16(Height) x 14 3/16(Width) x 2 3/8(Depth) in

 

 

 

 

 

Weight

 

3.4 kg / 7 ½ lb

 

 

 

 

 

 

Power source

 

~ 208 – 230V (60Hz)

 

 

 

 

 

 

Power consumption

 

10 W

 

 

 

 

 

Data holding

 

Memorizing binding information, address information on air conditioners

 

 

 

and set values in nonvolatile memory. Input/output variables are not

 

 

 

held.

 

 

 

 

 

 

Environmental

Temperature

Operating

- 15 to 43 / 5 to 109 °F

 

condition

 

 

 

 

 

Non operating

- 20 to 60 / - 4 to 140 °F

 

 

 

 

 

 

Humidity

 

30 to 95 %RH (No condensation allowed)

 

 

 

 

Installation method

 

Mountable in horizontal or vertical direction

 

 

 

For vertical installation, locate in the direction of the pasted seal.

 

 

 

 

External finish

 

Galvanized steel plate

 

 

 

 

 

Alias

 

100 pieces

 

 

 

 

 

Explicit message

 

Not applicable yet

 

 

 

 

Neuron ID

 

Indicated on the seal attached to circuit board (differs by product)

 

 

 

Program ID

 

Indicated on the seal attached to circuit board (differs by product)

 

 

 

 

Neuron chip

 

TMPN3150 10MHz

1 piece

 

 

 

 

Network transceiver

 

FTT-10A (Free topology 78kbps)

1 piece

 

 

 

 

 

(2) Performance

Items 2 3

Specification

Mean communication capacity

2.5 input / second

 

 

Peak communication capacity

50 input / second (for 1 second)

 

 

Response capacity for poll demand

15 demand / second

 

 

1For the detail specification of the LONWORKS network, see the data published by Echelon. "FTT-10A Free Topology Transceiver User's Guide"

2Transmitting with an interval time exceeding the capacity hinders normal receiving. Please take a sufficient interval.

3The Ack Service is recommended for your network service.

5

(3) External dimension

6

3. System Design Flow

The following indicates design flow to construct the system of the LONWORKS network by LM ADAPTER.

Step 1: Selecting the air conditioners (objective equipment for control, restrictions, etc.).

Step 3: Selecting the system control parts

(Quantity of LM ADAPTER, other system controllers, etc.).

Step 4: Determining the air conditioner addresses.

Step 5: Constructing the LONWORKS system.

7

4. Designing the LMAP03U

This section summarizes the air conditioners controllable with LM ADAPTER and various restrictions to be applied. For the details of air conditioning equipment, please refer to the manual of each air conditioner.

4.1 Selecting the air conditioners

4.1.1 Controllable quantity

One LM ADAPTER can control indoor units up to 50 sets. The number of LOSSNAY (including ventilation units) is to be included in this figure.

4.1.2 Range of group control

When using other SC in combination, the control can be performed within the group range set by the SC. When not using other SC in combination, group control cannot be performed.

BMS

LONWORKS network

System remote controller

Power supply unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

centralizeNET-M linetransmission

OC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M-NET indoor-outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC

 

 

 

 

IC

 

 

 

 

 

IC

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control

Group1

 

 

 

 

 

 

 

Group2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ME

 

 

 

 

 

 

 

 

ME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Make sure to install a local remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group3

 

 

 

 

 

controller or system controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4-1. System configuration (Example)

8

4.1.3 Objective equipment for control

The following table lists the objective air conditioners for control.

Some indoor units own the plural M-NET addresses. For counting the connected numbers, refer to the table below.

O : Controllable

x : Uncontrollable

: Controllable depending on connected models

 

 

 

 

 

Function

LMAP03U

 

Counting method of connected quantity

 

Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CITY MULTI

Quantity of indoor unit

 

 

 

 

 

 

PAC for general purpose/industrial application

×

 

 

 

 

 

 

 

 

K-control unit 1

×

 

 

 

4.1.4 Connecting location

Connect LM ADAPTER to the centralized system transmission line of air conditioners.

4.1.5 Restriction on M-NET transmission wiring

As the M-NET transmission line has restrictions on its wiring length, wire materials, etc. in accordance with the system configuration, the design should be conducted taking the transmission lines of air conditioners and control equipment into your consideration. For detail, please refer to the manuals such as the "DATA BOOK" of each air conditioner.

1 Unable to control/monitor even by connecting the K-transmission converter.

9

4.2 Selecting the function

The list below shows the operation/monitor function of LM ADAPTER.

(1) Operation/Setting

 

: With function

●: Individual : Without function

 

 

 

 

 

 

 

 

 

 

CITY

 

 

Function

 

 

MULTI

 

 

 

 

 

 

 

 

 

 

 

 

 

Request All OFF (Emergency stop)

 

 

 

 

 

 

 

 

 

 

Request On/Off

 

 

 

 

Request Mode

 

 

 

 

 

 

 

 

 

 

SetPoint

 

 

 

 

Request LOSSNAY Mode

 

 

 

 

 

 

 

 

 

 

Operation/Setting

Request Fanspeed

 

 

 

Request Local Prohibit On/Off 1

 

 

 

Request Local Prohibit Mode 1

 

 

 

Request Local Prohibit SetPoint 1

 

 

 

Request Collective Operation Prohibit 1

 

 

 

 

 

 

 

 

Request Forced Thermostat OFF

 

 

 

 

 

 

 

 

 

 

Filter Sign Reset

 

 

 

 

Time Stamp 2

 

 

 

 

Request Limit Temperature Setting Range 2

 

 

 

 

Request Simplified Locking 2

 

 

 

1Applicable only at using of MA remote controller (PAR-20MAA) for a local remote controller.

2Applicable only at using of ME remote controller (PAR-F27MEA) for a local remote controller.

10

(2) Monitoring/Measuring

 

: With function

●: Individual : Without function

 

 

 

 

 

 

 

 

CITY

 

 

Function

 

MULTI

 

 

 

 

 

 

 

 

 

 

 

Emergency state

 

 

 

On/Off run state

 

 

 

 

 

 

 

 

Collective On/Off state

 

 

 

Mode state

 

 

 

 

 

 

 

 

SetPoint state

 

 

 

LOSSNAY Mode state

 

 

 

 

 

 

 

 

 

Fanspeed state

 

 

 

Local Prohibit On/Off state 1

 

 

 

Local Prohibit Mode state 1

 

 

Measuring/Monitoring

Space Temperature

 

 

 

Local Prohibit SetPoint state 1

 

 

 

Collective Local Prohibit state 1

 

 

 

Forced Thermostat OFF state

 

 

 

Filter Run Time

 

 

 

 

 

 

 

 

Alarm state

 

 

 

Collective Alarm for Indoor Unit

 

 

 

 

 

 

 

 

Collective Alarm for LM ADAPTER

 

 

 

Error Code

 

 

 

 

 

 

 

 

Error Unit Address

 

 

 

Thermostat On/Off state_1

 

 

 

 

 

 

 

 

Thermostat On/Off state_2

 

 

 

Model Code

 

 

 

 

 

 

 

 

Defrost state

 

 

 

 

 

 

 

1 Applicable only at using of MA remote controller (PAR-20MAA) for a local remote controller.

11

4.3 Selecting the system control parts

Using the system controller (SC) together other than LM ADAPTER allows connecting operation. Some rules to be observed for this purpose are introduced below.

4.3.1 Master controller and slave controller

When LM ADAPTER is used together with other system controller inside a system under own control, it is essential to set a slave SC(requiring a DIP-SW change). In this case, set it so that the control range of LM ADAPTER is included within the control range of the system controller (air conditioner) which is to be the master SC.

 

 

 

 

 

 

 

 

 

M-NET centralized control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master SC

 

 

 

 

 

 

 

 

 

 

OC

 

 

M-NET indoor-outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System remote

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

unit

 

 

 

 

IC

 

 

IC

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave SC

 

 

 

 

LMAP

 

 

 

 

 

MA

 

 

 

 

 

 

 

 

ME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4-2. System configuration of system controller

(1) In the case when the control range of the LM ADAPTER is covering that of plural system controllers, make sure to install the Master system controller that covers the LM ADAPTER control range.

 

 

 

Master SC

 

LM ADAPTER

 

LM ADAPTER

 

control range

 

control range

SC1

SC2

SC1

SC2

control

control

control

control

range

range

range

range

(2) In the case when the LM ADAPTER control range is covering the control range of the system controller partially, install the system controller so that it covers the entire control range of LM ADAPTER.

 

 

 

SC2

 

 

 

control range

SC1

LM ADAPTER

SC1

LM ADAPTER

control range

control range

control range

control range

12

4.3.2 Local remote controller

The local remote controller includes ME remote controller (PAR-F27MEA, etc.) to be connected to the M-NET indoor-outdoor transmission line of air conditioners and MA remote controller (PAR-20MAA, etc.) to be connected to each indoor unit. Each remote controller provides a different function usable by LM ADAPTER and a different system construction method.

 

 

 

 

 

 

 

 

 

M-NET centralized control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master SC

 

 

 

 

 

 

 

 

 

 

OC

 

 

 

 

M-NET indoor-outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System remote

 

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

 

 

contoller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

unit

 

 

 

 

 

IC

 

 

 

IC

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave SC

 

 

 

 

LMAP

 

 

 

 

 

 

MA

 

 

 

 

 

 

 

 

ME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4-3. System configuration of local remote controller

(1) Comparison of function by local remote controllers

The usable function (network variables) by LM ADAPTER differs depending on the model of the local remote controllers (MA remote controller/ME remote controller).

Function (NV names)

MA remote

ME remote

controller

controller

 

 

Request Local Prohibit (ON/OFF , Mode , SetPoint)

1

Local Prohibit State (ON/OFF , Mode , SetPoint)

1

Request Collective Local Prohibit

 

1

Collective Local Prohibit State

 

1

Time Stamp

 

×

2

Request Limit Temperature Setting Range

×

2

Request Simplified Locking

 

×

2

○ : With function

: Possible with limitation

×: Without function

(2) Caution on a system without using remote controller

The following problems will be incurred when the operation/monitoring is done only from the BMS (centralized monitoring system) without using the local remote controller. Therefore, please be sure to install a local remote controller or system controller without fail.

Test run can not be applied to air conditioners until the BMS has started up.

Air conditioners can not be operated or monitored when trouble is generated on the BMS and LM ADAPTER.

The detail of the trouble i.e. the stopping of indoor units can not be clarified.

The operation/setting of the items other than that controlled by the BMS cannot be performed.Interlocked setting of LOSSNAY and air conditioners can not be performed.

1Applicable to some model of CITY MULTI air conditioners ( manufactured after January 2003 ) even when using ME remote controller.

2Applicable when only using ME remote controller for the standard models except the medium temperature models.

13

4.3.3 External contact input/output

The external contact input/output function is not provided to LM ADAPTER.

4.3.4 Power supply to M-NET transmission line

The M-NET centralized system controller line should be powered. For the system using other system controller or that with LOSSNAY only, the power supply unit for transmission line is required. In accordance with the system configuration, the setting of LM ADAPTER and outdoor units should partially be changed. Please conduct the setting operation by referring to the "Installation Manual" of LM ADAPTER. For the power supply capacity of the power supply unit and the selection of the unit, please refer to the manuals (like DATA BOOK) of each air conditioner.

 

Installation of power supply unit

 

 

 

 

Individual

With SC

 

 

 

 

 

LMAP02-E

Not required

Required

LMAP03U

 

 

 

 

 

4.4 Object

4.4.1 Network variables and objects

The network variables provided allows the LA ADAPTER to operate/monitor plural equipment (indoor unit, LOSSNAY, etc.) The functional profile (object) represents the network variables collected for each objective equipment to be controlled. Here the objects and network variables are outlined, and the relationship with air conditioners is explained. For the detail of each object and the specification of the network variables, please refer to the "Network Variables Specification" of each product.

(1) Object configuration of LM ADAPTER

Node

Indoor [0]

Indoor [1]

Indoor [50]

Object

 

 

 

For node object

For collective variables

 

For indoor unit

and configuration property

 

 

 

14

(2) Object and equipment address

The object for indoor units is individually related with the objective equipment for control. The object (Indoor [1] ~ Indoor [50]) corresponds to the indoor unit (LOSSNAY, ventilation unit, Mr. SLIM) with the M-NET address of 01 ~ 50 being set to each equipment.

Outdoor unit

IC

IC

IC

 

051

001

002

003

 

M-NET centralized

 

 

 

 

 

control transmission line

 

 

 

 

 

 

 

M-NET Indoor-outdoor

 

 

 

transmission line

Legend

 

 

 

 

 

 

 

 

OC:Outdoor unit

Indoor [1]

Indoor [2]

 

Indoor [3]

IC:Indoor unit

 

 

 

 

IC

 

 

 

 

05

 

 

 

 

M-NET

 

 

 

 

address

 

Object of LM ADAPTER

 

 

4.4.2 Network variables and air conditioner address

LM ADAPTER owns the network variables for each air conditioner. The network variables include set/monitor of an air conditioner individually and to set/monitor of all air conditioners collectively.

Please set so that the M-NET address of the objective air conditioner for control will agree to the name of the variable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IC

 

IC

 

 

IC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

051

 

 

001

 

002

 

 

003

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M-NET centralized

 

 

 

 

 

 

 

 

 

 

 

 

 

control transmission line

 

 

 

 

 

 

 

M-NET Indoor-outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmission line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor [1]

 

 

Request On/Off

nviOnOff_001

 

 

 

 

 

 

 

 

 

 

 

 

 

On/Off run state

nvoOnOff_001

 

 

 

 

 

 

 

 

 

 

 

 

 

SetPoint

nviSetP_001

 

 

 

 

 

 

 

 

 

 

 

 

 

SetPoint state

nvoSetP_001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For No.1 indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network variable name → Function name + M-NET address (3-digit display)

 

 

 

 

 

 

 

 

 

 

 

 

 

Relationship between M-NET address and Network variables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

4.5 Restrictions on system configuration

The restrictions in constructing the system by LM ADAPTER are outlined here. 4.5.1 Restrictions by system configuration

(1) Group control

In the case when the group setting of indoor units are carried out by the local remote controller or system controller, the operation from the BMS is performed as follows.

Group setting

Operation

Monitoring

 

 

 

No setting

every unit

every unit

(individual)

 

 

 

 

 

Setting by the local

every unit

 

remote controller

Required to issue a same command to all

every unit

 

indoor units

 

 

 

 

Setting by the system

Principal 1 unit in the same group

 

controller

When using “Forced Thermostat OFF” is

every unit

 

required to request into indoor units individual

 

 

 

 

4.5.2 Restrictions by control items

(1) Operation prohibit

When using together the system controller that can set to prohibit the local remote controller operation, make the controller for setting of operation prohibit one unit, either LM ADAPTER (BMS) or the system controller.

Operation prohibit can not be applied to other system controllers by LM ADAPTER (from BMS)

Although air conditioners can not be operated by the local remote controller of which operation is being prohibited, they can be operated by LM ADAPTER (BMS) or other system controllers.

1 At the unit of lowest address in the same group

16

(2) Emergency stop

The emergency stopping of LM ADAPTER stops all air conditioners together, however it does not set the operation prohibit of the local remote controller allowing the operation from other system controller or local remote controller. To prohibit operation from the local remote controller, therefore, set it by entering

[Request Collective Local Prohibit] (collective).

*Operating to run during emergency stopping only results in immediate stopping.

(3) Operation mode

In the case of cooling/heating selectable models of CITY MULTI, the operation mode will be determined by the principle of the "Priority for former pressing." Under the circumstance, a same command should be issued to all indoor units within a same refrigerant system to change the operation mode.

Indoor unit 1

Cool

Heat (Inoperable)

Cool (Inoperable)

 

 

 

Indoor unit 2

Cool

 

Heat

 

 

 

Outdoor unit

Cool

 

Heat

 

 

 

17

5. Design and Operation of LONWORKS System

This section introduces the mechanism, function and operating method of LM ADAPTER in configuring the system of LONWORKS network by LM ADAPTER. As the operating method shown here represents just one of the examples, you are kindly requested to carry out your designing to meet the system configuration or operation in the actual system.

5-1 Constructing the LONWORKS network

The flow of installation procedure for LONWORKS network is shown below.

Step 1: Addressing (to determine the address of each node)

Step 2: Binding (to connect network variables)

Step 3: Configuration (for optimum service of each connection, adjustment of re-transmission frequency and interval)

(1) Addressing

An address is assigned to each node (equipment applicable to LONWORKS) on the LONWORKS network. Set this address by using the install tool. Setting by using LM ADAPTER is not necessary.

(2) Binding

The network variables between each node should be related with the exclusive tool like LonMaker for Windows ® or the like.

(3) Configuration

For the configuration property of LM ADAPTER, the initial value was set at factory shipment. The set value may be changed depending on the configuration or operation of the network.

Node Address = 1

Node Address = 2

BMS

Indoor [1]

Binding of network variables

18

5.2 Function relating to installing

(1) Service pin (Service switch)

The service pin is used at the installation of LONWORKS network.

Pressing the service pin sends out the service pin-message (control message including Neuron ID and Program ID) to the network.

(2) Service LED

The service ID indicates the present state of the product.

In the case of LM ADAPTER under the shipment state (Non-configured state), the service LED is blinking.

(3) WINK

Upon receipt of the WINK message from the LONWORKS network, LM ADAPTER blinks the maintenance LED 001 for about 10 seconds.

(4) Commission

After completing the binding, the set detail is reflected on the node. Doing this way allows communication between the nodes on the LONWORKS network.

(5) XIF

To design the LONWORKS network, the configuration information of each node, interface (network variables), etc. are required. When the product is already in your hand, such information can be obtained from the LONWORKS network. Without the product, however, you may get it from XIF (eXternal Interface File) locating the interface information of the product.

19

5.3 Operation at power recovery

5.3.1 Outline of LM ADAPTER operation

After the power source is applied (the same as the power recovery after instantaneous power stop/power failure), LM ADAPTER requires a time for initialization to collect the connection and operation state of air conditioners up to 50 sets to be controlled. As the operation timing differs depending on the setting of configuration property, you are kindly requested to carry out designing to meet the system operation.

 

 

 

 

Power ON

 

Relating configuration property

LMAP

 

 

 

 

 

 

 

 

 

- Send Start Time nciStartOutTm

 

power source

 

 

 

 

 

 

 

 

 

- Send Heartbeat Start Time nciStartHrtBt

 

 

 

 

 

 

Communication

 

- Initialize Start Time nciInitStartTm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciSet_1

 

 

 

 

 

 

 

 

Neuron chip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operating state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Send Heartbeat Start Time

 

 

 

 

 

 

 

 

 

 

 

nciStartHrtBt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Event output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

(B)

(C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

 

(B)

(C)

 

 

 

 

 

 

 

 

 

 

Operation/setting from BMS

 

Not applicable

 

Applicable

Applicable

 

 

 

 

 

 

 

 

 

 

Monitoring by Poll (Fetch) from BMS

 

Not applicable

 

Applicable

Applicable

 

 

 

 

 

 

 

 

 

 

Output from LM-AP at changing

 

Not applicable

 

Not applicable

Applicable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20