Mitsubishi LGH-RX5, AG-150A, PZ-60DR-E, PZ-41SLB-E, PZ-52SF-E TECHNICAL MANUAL

0 (0)

Lossnay

Remote Controller

1. Summary

Technical manual detailing the control and operation of commercial-type Lossnay units (LGH-RX5-E Series).

Possible System Configurations

(1) When using only the Lossnay remote controller. (2) Linking Lossnay and City Multi units.

(3) Linking Mr. Slim.

(4) Lossnay central control systems.

(5) Linking with external equipment (BMS).

2. Applicable Models

Lossnay (LGH-RX type)

These models have temperature sensors at return stale indoor air (RA) and outside air intake (OA) sides and can automatically switch to ventilation (Lossnay/By-pass) mode.

LGH-15RX5 -E

LGH-25RX5-E

LGH-35RX5-E

LGH-50RX5 -E

LGH-65RX5-E

 

 

 

 

 

LGH-80RX5-E

LGH-100RX5 -E

LGH-150RX5-E

LGH-200RX5-E

 

 

 

 

 

 

Lossnay Remote Controller (PZ-60DR-E)

It is possible to control all of the function of LGH-RX5-E, such as, Extra-Low-fan speed, weekly timer. Use when operating from 1 to 15 Lossnay units together at the same time.

PZ-60DR-E is not M-NET control, however, LGH-RX5-E can be use with PZ-60DR-E in the M-NET system. (Refer to page C-78).

Lossnay Remote Controller (PZ-41SLB-E)

Use when operating from 1 to 15 Lossnay units together at the same time. When using M-NET transmission to operate from a centralized remote controller, use the PZ-60DR-E OR PZ-52SF-E.

It can start and stop the unit, change fan speed, and switch the ventilation mode. It also includes indicators that show errors and when filter maintenance is required Function is limited in case of LGH-RX5-E (Refer to page C-91).

Lossnay M-NET Remote Controller (PZ-52SF-E)

Use with Mitsubishi Electric Air conditioner Network system (MELANS) (Refer to page C-92). Because the remote controller is power-supplied using the M-NET transmission line, it cannot be linked with Mr. Slim and other such systems that do not use M-NET. It can start and stop the unit, change fan speed, and switch the ventilation mode. It also includes indicators that show errors and when filter maintenance is required Function is limited in case of LGH-RX5-E (Refer to page C-92).

Please refer to the technical documentation for City Multi, Mr. Slim systems and the central controller (MELANS).

C-3

3. Terminology

Interlocked Lossnay

A Lossnay linked to City Multi or Mr. Slim indoor units that has been set to interlocked group setting to receive signals and operate via indoor unit’s remote controller. (Remote controller to indoor unit to Lossnay.)

Non interlocked Lossnay

A Lossnay that is not set to interlocked group setting with City Multi or Mr. Slim indoor units. It operates using direct operating signals from the Lossnay remote controller and/or centralized remote controller.

Ventilation Mode

Controls the Lossnay damper and permits selection of heat recovery (heat exchange), By-pass or auto modes.

Timer control. (PZ-60DR-E)

PZ-60DR-E has weekly timer and simple timer.

• weekly timer : The operation pattern for each day of the week and the air-volume by time zone can be set (up to eight zones per day).

• simple timer : Three setting is available , start-timer only, stop time only or start & stop.

Delayed Operation

A Lossnay that has been set to interlocked group setting with the indoor unit will have its operation delayed for 30 minutes after the operation of the indoor unit. When using PZ-41SLB-E, delayed operation can be set for 10, 20, 30, 40, 50 and 60 minutes.

External Control Input

An input signal from an external device used to operate Lossnay. It is compatible with 12V-24V DC or uncharged a-contact signal.

Switching High Low or Extra-Low fan speed is available by external input (CO2 sensor or other equipment is connected).

Switching By-pass is available by external input.

Operation Mode

Used for selecting enabling/disabling of the on/off control signal from an external device, and for setting interlocked operation of the external device and Lossnay.

Please Refer to page C-23 for details.

(

ON/OFF interlock:

Enables both “ON → OFF” and “OFF → ON” external signals.

ON interlock:

Enables “OFF → ON” external signal. Disables

“ON → OFF” external signal.

OFF interlock:

Enables “ON → OFF” external signal. Disables

“OFF → ON” external signal.

External control priority:

Same as on/off interlock but the OFF signal from the remote controller is ignored when the

external control signal is ON.

Setting Pulse Input

When the control signal from the external device outputs a pulse such as the one shown below, pulse input setting is performed by Lossnay. (Optional setting DIP switch 2-2 ON)

200 ms or more

Operation in Cold Areas

When the outdoor air is less than -10°C, continuous fan operation for drawing in supply air is cancelled and intermittent operation is started.

RA (Return Air)

Abbreviation for return air, which is the air drawn in from inside.

OA (Outdoor Air)

Abbreviation for outdoor air, which is the air drawn in from outside.

C-4

4. System Features and Examples

4.1Features

Classification

 

Item

Notes/Cautions

Control

Multiple unit operation

Maximum 15 units with PZ-60DR-E & PZ-41SLB-E; 16

 

 

 

units with PZ-52SF-E or other M-NET controllers.

 

Remote controller operation

Last condition priority before turning off the unit.

 

External device operation and external

Signal : 12VDC, 24VDC, uncharged a-contact.

 

 

pulse control

 

 

External monitor signal output and sup-

Uncharged a-contact (external monitor/supply air fan

 

 

ply air fan monitor output

monitor change).

 

External control operation mode setting

ON/OFF, ON, OFF and external control priority ON/OFF

 

 

 

mode.

 

Timer control

Weekly timer & simple timer available for PZ-60DR-E.

 

Delayed start

Delayed time can be varied only when the PZ-41SLB-E is

 

 

 

connected.

 

Automatic recovery following power sup-

Automatic power recovery is fixed when PZ-60DR-E or

 

 

ply interruption (*1)

PZ-41SLB-E is connected.

 

Power supply start/stop function

Function cannot be performed when PZ-41SLB-E is con-

 

 

 

nected.

 

High/low/Extra-Low change input

Uncharged a-contact (Remote display adaptor (PAC-SA88HA-E) is required.)

 

Remote/local control change

Uncharged a-contact (Remote ON/OFF adaptor (PAC-SE55RAE) is

 

 

 

required.)(Function cannot be performed when using PZ-41SLB-E.)

 

M-NET air conditioning operation.

Only when M-NET transmission cable is connected.

 

System controller by Mitsubishi building

Only when M-NET transmission cable is connected.

 

 

air control management system

 

 

Interlocked with Mr. Slim

Function cannot be performed with PZ-41SLB-E.

 

 

 

 

Function

Lossnay (heat recovery) ventilation/auto-

Also external By-pass switcing is available(Remote dis-

 

 

matic By-pass ventilation switch

play adaptor (PAC-SA88HA-E) is required).

 

For cold area operation

 

 

 

 

 

Installation

Two non polar wires for remote controller

For PZ-60DR-E, PZ-41SLB-E connection: ø 0.65 to 1.2

 

 

 

PVC cable or 0.3 mm2 to 1.25 mm2 strand wire.

 

 

 

For M-NET connection: 1.25 mm2 to 2.00 m2 shielded

 

 

 

wire or equivalent.

 

Address setting unnecessary

Excluding central controller system (except automatic

 

 

 

address).

 

Test operation switch

For Lossnay single unit test operation.

 

 

 

 

Maintenance

Filter maintenance display

Filter, core maintenance display for PZ-60DR-E.

 

 

(remote controller display)

 

 

Inspection display

Error code indication for PZ-60DR-E.

 

 

(remote controller, control board LED)

 

 

M-NET power supply display

 

 

 

(control board LED)

 

 

 

 

 

*1 The operation condition is saved, and when the power is turned off and then back on, the operation condition returns to the previous requested condition. (When using PZ-60DR-E, PZ-41SLB-E, the start/stop condition from an external device is not saved.)

C-5

4.2System Examples

Basic System (Refer to page C-11)

One Lossnay with one remote controller

Non-polar

Lossnay

Two wires

 

Power supply

Remote controller

PZ-60DR-E or PZ-41SLB-E

A simple system in which Lossnay is operated independently with one remote controller.

Multiple Lossnay units with one remote controller

Non-polar

Lossnay

Two wires

(Main)

 

 

Power supply

 

Lossnay

Remote

(Sub)

controller

 

PZ-60DR-E or

Power supply

PZ-41SLB-E

 

Up to 15 Lossnay units can be controlled at one time with one remote controller.

Two remote controller system with one Lossnay

Non-polar

 

Two wires

Lossnay

 

Power supply

Remote controller

PZ-60DR-E or PZ-41SLB-E

Lossnay can be controlled from two remote locations.

The remote controller gives priority to the last operation function request.

with an Air Conditioning Unit

(Refer to page C-13)

Operation

 

Operating with Mr. Slim

Lossnay

Power supply

Power supply

Mr. Slim Remote (indoor unit) controller

The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E) cannot be used with this system.

Use MA remote controller of Mr.Slim for switching Lossnay ON/OFF or the fan speed.

The ventilation mode is “automatic ventilation”.

Operating with an External Device (Refer to page C-22)

Operating with an external device

 

Non-polar

Lossnay

● Selection of inter-

Two wires

 

locked operation

 

 

 

Power supply

mode is possible.

 

● Delayed start inter-

Remote controller

 

locked operation is

PZ-60DR-E or

 

possible.

PZ-41SLB-E

Power supply

Indoor unit

Remote controller

Lossnay operation will be performed via the external device.

Level signal or pulse signal input (12V DC, 24V DC, uncharged a-con- tact) is possible.

System

City Multi and Lossnay Interlocked System

M-NET

Centralized Management System

 

 

 

Air conditioning device and system control

Outdoor unit

Indoor

Lossnay

 

Indoor

Indoor Lossnay

Lossnay

Indoor

Lossnay

Indoor

 

 

unit

Indoor

 

 

unit

 

 

unit

 

unit

unit

 

 

unit

MA remote controller

 

MA remote controller

MA remote controller

MA remote controller

 

MA remote controller

Interlock-Group 1

Interlock-Group 2

Interlock-Group 3

Interlock-Group 4

 

Interlock-Group 5

Refrigerant 1

 

 

 

Refrigerant 2

 

 

 

 

Outdoor unit

 

 

 

 

 

Outdoor unit

 

 

 

 

Lossnay

 

 

 

 

Indoor

Lossnay

 

Indoor

Indoor

Indoor unit

Indoor

Lossnay

unit

 

 

 

unit

 

 

 

 

 

unit

 

 

unit

 

MA remote

 

 

 

 

 

 

 

 

MA remote controller

 

MA remotecontroller

controller

 

 

 

 

 

 

 

 

Interlock-Group 1

 

Interlock-Group 2

 

Interlock-Group 3

 

Group setting

Interlocked operation setting

● One Lossnay can be interlocked with 16 indoor units. In addition, PZ-60DR-E (non M-NET) can be connected for each Lossnay units.

Centralized controller

Power Lossnay

Lossnay

Lossnay Lossnay Lossnay

Lossnay

Lossnay

Lossnay

supply

 

 

 

 

 

unit

 

 

 

 

 

Lossnay

 

Lossnay

Lossnay

 

Lossnay

remote controller

 

remote controller

remote controller

remote controller

PZ-60DR-E

 

PZ-60DR-E

PZ-60DR-E

PZ-60DR-E

Group 1

Group 2

Group 3

Group 4

Group 5

 

Detailed control such as start/stop, fan speed Extra-Low and ventilation mode control is possible from the Lossnay remote controller PZ-60DR-E.

PZ-52SF-E (M-NET remote controller) can be used instead of PZ-60DR-E. However, function is limited and connecting position is different.

Start/stop, fan speed and ventilation mode control is possible from the centralized controller.

Controller can set up the group including maximum of 16 indoor or Lossnay units.

C-6

Two remote controller system with multiple Lossnay units

Power supply

Power supply

Remote controller

PZ-60DR-E or

PZ-41SLB-E

It is also possible to operate two remote controller units when using multiple Lossnay units.

Interlocking multiple units

When the operation signal is an uncharged a-contact signal

Lossnay

 

 

A/C

A/C

A/C

Power supply

Power supply

Power supply

Power supply

Remote controller

Air conditioning

 

Air conditioning

Air conditioning

PZ-60DR-E or

unit side remote

unit side remote

unit side remote

PZ-41SLB-E

controller

 

controller

 

controller

 

Interlocking is possible from multiple air conditioning units, etc. (excluding pulse input)

(Separately sold parts are necessary depending on the operation signal).

Interlocking/individual combined systems

Interlock settings are possible with the inclusion of a group setting. (Joint use of the air conditioner remote controller and Lossnay remote controller is possible.)

 

 

Operation settings

 

Centralized

 

Indoor unit of

Lossnay (02)

controller

Outdoor

air conditioner

 

(000)

(01)

 

unit (51)

 

 

 

 

 

 

MA remote

Lossnay remote

 

 

controller

controller

 

 

 

(PZ-60DR-E)

 

 

Group 1

Group 2

( ) address

Applicable indoor units are C type or later (for use with MA remote controller) models

Set the different groups of indoor unit of air conditioner and Lossnay unit.

Use Lossnay remote controller PZ-60DR-E or PZ-41SLB-E .

(Do not use PZ-52SF-E).

Lossnay transmission connection terminal

Remote controller input terminal

2

1

TM4 PZ-60DR-E

Transmission wires

Setting

Change the setting on the main/sub switch (SW1) on the second and subsequent Lossnay units to “Sub”.

 

 

 

 

Main/Sub selection

 

 

 

-E)

 

switch

Power

 

 

 

(SW1)

 

 

Power

Main Sub

supply

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device (Factory setting: main)

Power

Lossnay

 

 

 

 

 

supply

 

 

 

Connect to

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

Second

controller

 

 

 

(PZ-60DR-E)

 

 

 

 

 

 

Lossnay

 

 

 

 

 

Power

 

 

 

Connect

supply

 

 

 

to third

MAX 15 units

 

 

 

Lossnay

 

 

 

 

 

 

 

 

Transmission cable

Use Lossnay remote controller PZ-60DR-E .

(Do not use PZ-41SLB-E).

Lossnay transmission connection terminal

M-NET transmission cable input terminal block

TB5

A B S

 

 

 

 

 

 

 

 

Remote controller

 

 

 

 

 

 

 

 

Shielded wire

 

 

 

 

 

 

 

 

input terminal

M-NET

transmission cable

and PZ-52SF-E

2

1

TM4 PZ-60DR-E

Transmission wires

Address Setting

SA1 SA2

10 digit

1 digit

Address setting switch

When the address number has been changed, the data in the memory is automatically reset.

C-7

(Refer to page C-11)

4.3System Selection

Interlocked with City Multi (Refer to page C-14)

Lossnay operation when indoor unit is stopped

Lossnay stopping when indoor unit is operating

 

 

 

Switching Lossnay fan speed

 

 

When interlocked with indoor unit for compatibility with both R22, R407C and R410A

High/Low

 

When interlocked with indoor unit for other than the above

Fixed to high

Ventilation mode

Fixed to automatic

Filter maintenance indicator

Lossnay error indicator

Delayed operation

External control operating mode selection

×

Number of indoor units for interlocked group setting with one Lossnay unit

16 units

Number of Lossnay units for interlocked group setting with one indoor unit

One unit

* All Lossnay functions including Extra-Low fan speed can be controlled from PZ-60DR-E.

Interlocked with Mr. Slim (Refer to page C-13)

When using A-control remote controller

 

Lossnay operation when indoor unit is stopped

 

Lossnay stopping when indoor unit is operating

×

 

Lossnay fan speed switching

High/Low

Other common items

 

 

Lossnay error indicator

×

 

Ventilation mode

Fixed to automatic

 

 

 

 

Filter maintenance indicator

×

 

Delayed operation

 

External control operating mode selection

×

 

Number of indoor units for interlocked group setting with one Lossnay unit

One unit

 

Number of Lossnay units for interlocked group setting with one indoor unit

One unit

Incase of PZ-60DR-E

 

 

 

 

 

 

Air

 

 

Air

Lossnay

 

 

conditioner

 

 

conditioner

 

 

 

MA remote

 

 

 

M-NET transmission cable

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

PZ-60DR-E can be used

Incase of PZ-52SF-E

Air conditioner

MA remote controller

Mr.Slim (A-control)

indoor unit

Remote controller

Air

Lossnay

conditioner

 

M-NET transmission cable

PZ-52SF-E can be used

Lossnay unit

Lossnay remote

LGH-RX type

controller

 

PZ-60DR-E,

 

PZ-41SLB-E

 

cannot be used.

Slim-Lossnay connecting cable (Enclosed accessory with Lossnay unit)

Independent Lossnay Unit (Not interlocked with City Multi or Mr. Slim systems.)

Start/Stop

Fan speed switching

High/Low/Extra Low

Ventilation mode

Heat ex. /

By-pass/ Auto

 

Filter maintenance indicator

Lossnay error indicator

Delayed operation

External control operating mode selection

Number of Lossnay units

15 units

Number of remote controllers

Two units

* All Lossnay functions including Extra-Low fan speed can be controlled from PZ-60DR-E.

Lossnay unit

LGH-RX type

 

 

 

 

 

External signal source

 

 

 

 

 

 

 

 

 

 

for interlocking

Lossnay remote controller

to the Lossnay

(PZ-60DR-E, PZ41SLB-E)

 

Interlocked with external device (BMS) (Refer to page C-22)

Start/Stop

Fan speed switching

Fixed to high

 

 

Ventilation mode switching

Fixed to automatic

Filter maintenance indicator

×

Lossnay error indicator

×

Delayed operation

External control operating mode selection

*● : Available

×: Not Available

External signal source for interlocking

to the Lossnay

Lossnay unit

LGH-RX type

C-8

Centralized Controller System

Centralized controller

AG-150A

Outdoor unit

Interlocked with

City Multi indoor units

Indoor unit

LOSSNAY RX5

Indoor unit

Power supply unit

 

 

(PAC-SC51KUA)

 

M-NET remote

M-NET remote

LOSSNAY remote

controller

controller

controller

 

PZ-60DR-E

 

Interlocked with

Mr. Slim indoor units

Mr.Slim

Mr.Slim

LOSSNAY RX5

indoor unit

 

outdoor unit

 

 

 

 

Mr.Slim

 

 

remote controller

 

LOSSNAY units only

LOSSNAY RX5

LOSSNAY RX5

LOSSNAY remote

LOSSNAY remote

controller

controller

PZ-60DR-E

PZ-60DR-E

Interlocked with external devices

LOSSNAY RX5

Ext. signal source

LOSSNAY remote controller PZ-60DR-E

C-9

Mitsubishi LGH-RX5, AG-150A, PZ-60DR-E, PZ-41SLB-E, PZ-52SF-E TECHNICAL MANUAL

Reference: Remote controller for the Lossnay and indoor unit

Refer to the technical documentation related to the Remote controller for the indoor unit.

Remote controllers for Lossnay unit

Lossnay remote controller

Lossnay remote controller

Lossnay M-NET remote controller

(PZ-60DR-E)

(PZ-41SLB-E)

(PZ-52SF-E)

*non M-NET protocol

*non M-NET protocol

 

Advanced Lossnay remote controller.

With Lossnay interlock switches

Without Lossnay interlock switches

 

and indicators.

 

and indicators.

 

2CONTROLLERS

INTERLOCKED

CENTRAL INTERLOCKED

 

AUTO

 

HEAT EX.

 

BY-PASS HEAT EX.

 

BY-PASS

 

 

 

AUTO

 

CHECK

FILTER

CHECK

 

NOT AVAILABLE FILTER

 

SETTING

MIN. DELAYED

 

 

 

ON/OFF

 

DELAY START

FILTER

FILTER

 

 

PZ-41SLB-E

 

Remote controllers for City Multi indoor unit

MA remote controller (PAR-21MAA)

*non M-NET protocol With Lossnay interlock switches and indicators.

TIME SUN MON TUE WED THU FRI SAT

TIMER

Hr

ON

AFTER

AFTER

OFF

ERROR CODE

 

FUNCTION

 

 

FILTER

 

 

WEEKLY

 

 

SIMPLE

ONLY1Hr.

 

AUTO OFF

 

TEMP.

 

 

ON/OFF

 

MENU

ON/OFF

 

FILTER

BACK

MONITOR/SET

DAY

 

CHECK TEST

PAR-21MAA

CLOCK

OPERATION

CLEAR

ME remote controller (PAR-F27MEA)

Without Lossnay interlock switches and indicators.

 

CENTRALLY CONTROLLED

1Hr.

 

 

DAILY

ON OFF

 

 

 

AUTO OFF

CLOCK

 

 

 

 

REMAINDER

 

FILTER

 

 

 

 

CHECK MODE

STAND BY

 

 

 

TEST RUN

 

ERROR CODE

NOT AVAILABLE

LIMIT TEMP.

DEFROST

 

 

TEMP.

 

ON/OFF

 

 

CLOCK→ON→OFF

 

FILTER

 

 

 

 

 

 

 

 

CHECK TEST

PAR-F27MEA

TIMER SET

 

 

Remote controllers for Mr. Slim indoor unit

PAR-21MAA

TIME SUN MON TUE WED THU FRI SAT

TIMER

Hr

ON

AFTER

AFTER

OFF

 

ERROR CODE

 

ONLY1Hr.

FUNCTION

FILTER

WEEKLY

SIMPLE

AUTO OFF

 

TEMP.

 

 

ON/OFF

 

MENU

ON/OFF

 

FILTER

BACK

MONITOR/SET

DAY

 

CHECK TEST

PAR-21MAA

CLOCK

OPERATION

CLEAR

C-10

4.4Basic System

4.4.1 System Summary

Design Example 1 Basic system

Non-polar

Lossnay

Two wires

 

Power supply

Remote controller

PZ-60DR-E or PZ-41SLB-E

This is a simple system.

A Lossnay is operated independently with one remote controller.

Design Example 2 Lossnay control of multiple units

Non-polar

Two wires

Remote controller PZ-60DR-E or PZ-41SLB-E

Lossnay (Main)

Power supply Lossnay

(Sub) Power supply

Up to 15 Lossnay units can be controlled at one time with one remote controller switch.

Design Example 3 Two remote controllers system

● The Lossnay can be controlled

Non-polar

 

from two remote locations.

 

● The remote controller gives pri-

Two wires

Lossnay

ority to the last touch.

 

 

 

 

Power supply

 

Remote controller

 

 

PZ-60DR-E or PZ-41SLB-E

 

4.4.2 Operation of Multiple Units

Feature

One remote controller can operate from one to 15 Lossnay units. PZ-60DR-E has many functions.such

as Extra-Low fan speed, however, PZ-41SLB has limited function.

 

 

 

Ordered part

Remote controller

PZ-60DR-E, PZ-41SLB-E

 

 

 

 

 

Also connect the power to the second and following Lossnay units.

Notes

The maximum extension of the transmission cable is 500 m or less (between Lossnay and remote

 

controller switch, between Lossnay and Lossnay).

 

 

 

The main or Sub setting on the Lossnay is necessary.

 

 

 

When operating multiple Lossnay units

 

 

 

 

Main/Sub selection

 

 

 

-E)

 

switch

Power

 

 

 

(SW1)

 

 

Power

Main Sub

supply

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device (Factory setting: main)

Power

Lossnay

 

 

 

 

 

supply

 

 

 

Connect to

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

Second

controller

 

 

 

(PZ-60DR-E)

 

 

 

 

 

 

Lossnay

 

 

 

 

 

Power

 

 

 

Connect

supply

 

 

 

to third

MAX 15 units

 

 

 

Lossnay

 

 

 

 

 

 

 

 

Transmission cable

(1)Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to Unit 3 and so on up to a maximum of 15 units using a transmission cable (PVC insulated PVC jacketed and either between 0.65 and 1.2, or between 0.3 mm2 and 1.25 mm2 in cross section).

(2)Change the setting on the main/sub switch (SW1) on the second and subsequent Lossnay units to “Sub”.

CAUTION:

Don’t tighten screws of terminal block with a torque larger than 0.5 Nm. It could damage the PCB.

Note:

Up to four 0.3 mm2 stranded wires or 0.65 PVC wires can be connected to one input terminal.

For other types of wire, up to two can be connected.

The operation signal and pulse signal can be connected to the external device of the main Lossnay only.

Connect the power to each respective Lossnay unit.

When the LGH-150RX5 and LGH-200RX5 types are connected, they operate at low fan speed even if extra low fan speed is selected.

C-11

4.4.3 Operation with two Remote controllers

 

Characteristics

 

Remote controller

Note

Lossnay can be operated from two remote locations.

 

 

 

 

 

 

 

 

• Use only up to two remote controllers

Lossnay conditions can be checked from two remote

 

Lossnay remote controller

(Operation will not go normally if three

 

locations.

 

 

PZ-60DR-E, PZ-41SLB-E

remote controller switches are con-

The remote controller gives priority to the last touch.

 

 

 

 

 

 

 

 

nected.)

 

 

 

 

 

 

 

 

 

 

 

 

System Example

 

 

 

 

 

 

 

 

 

 

 

Transmission

 

 

 

 

 

 

 

 

 

 

 

cable extension

Lossnay

Lossnay

 

 

is 500 m or less

 

 

0.65 to 1.2

 

 

 

 

 

 

 

 

 

 

MAX 15 units.

 

PVC cable or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3 mm2 to 1.25 mm2

 

 

 

 

Power supply

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

strand wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

PZ-60DR-E or PZ-41SLB-E

 

Lossnay

Lossnay

 

 

 

 

 

 

MAX 15 units.

 

Power supply

Power supply

 

 

 

Remote controller

 

 

Transmission

PZ-60DR-E or PZ-41SLB-E

 

 

cable extension

 

 

 

 

 

is 500 m or less

 

 

Lossnay

Lossnay

0.65 to 1.2

 

 

PVC cable or

 

 

 

 

 

0.3 mm2 to 1.25 mm2

 

 

 

 

 

strand wire.

 

 

Power supply

Power supply

 

 

 

 

Remote controller

Remote controller

 

 

 

PZ-60DR-E or

PZ-60DR-E or

 

 

 

PZ-41SLB-E

PZ-41SLB-E

 

 

Operation Method

The operation is the same with each remote controller. In this case, the Lossnay gives operating priority to the last button push.

C-12

4.5Interlocking with Mr. Slim

4.5.1 Interlocked Mr. Slim and Lossnay System

Features

● It is possible to Interlock Mr. Slim indoor units with Lossnay operation.

System Example

Mr. Slim outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mr.Slim indoor unit

 

 

 

 

Lossnay unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slim-Lossnay LGH-RX type

 

 

 

 

 

 

 

 

 

 

 

 

connection cable

 

 

 

 

 

 

 

 

 

 

 

 

(Enclosed accessory with Lossnay unit)

Remote controller

 

 

 

Lossnay Function Table (Interlocked settings)

Item

Details

 

 

Number of indoor units that can be set to interlocked opera-

One unit

tion with one Lossnay unit in each group

 

 

 

Number of Lossnay units that can be set to interlocked oper-

One unit

ation with one indoor unit

 

 

 

Operation of Lossnay unit only

Possible

(When indoor unit is stopped)

 

 

 

Independent Lossnay unit start and stop

Not possible

(When indoor unit is operating)

 

 

 

Delayed operation

30 minutes delayed operation of Lossnay when indoor unit

(Optional setting)

cooling/heating operation is started (Lossnay Dip-SW setting).

 

 

Switching fan speed

High/Low

 

 

Ventilation mode

Fixed to automatic

 

 

Filter indicator

Not possible

 

 

Error

Not possible

 

 

Restrictions and precautions

* The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E)

 

cannot be used on systems interlocked with Mr. Slim.

 

 

C-13

4.6Combining with City Multi

4.6.1Independent Lossnay System with Lossnay M-NET Remote Controller and MELANS

Features

The Mitsubishi Electric air-conditioner network system (MELANS) can operate and monitor each group of Lossnay units and City Multi indoor units.

Can also use the Lossnay M-NET remote controller to operate.

System Examples: 1 (Lossnay Non M-NET Remote Controller PZ-60DR-E)

The following groups can be configured.

Centralized controller (000)

 

 

 

 

 

 

(

) address

 

 

 

 

 

 

 

M-NET

 

 

 

 

 

 

 

 

Power

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

(001)

(002)

(003)

(004)

(005)

(006)

(007)

(008)

supply

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

Lossnay remote

 

Lossnay remote

 

Lossnay remote

Lossnay remote

 

controller PZ-60DR-E

 

controller PZ-60DR-E

 

controller PZ-60DR-E

controller PZ-60DR-E

 

Group1

Group2

Group3

 

 

Group4

Group5

 

M-NET

Outdoor unit (059)

Indoor

Lossnay

Indoor

unit

(010)

unit

(009)

 

(011)

MA Remote

Lossnay remote

MA Remote

controller

controller

controller PZ-60DR-E

 

 

Group6

 

Group7

Indoor

Lossnay

Lossnay

Lossnay

Indoor

unit

(013)

(014)

(015)

unit

(012)

 

 

 

(016)

 

Lossnay remote

Lossnay remote

MA Remote

 

controller

 

controller PZ-60DR-E

controller PZ-60DR-E

 

 

 

 

Group8

 

Group9

Group 1 : One Lossnay unit and one Lossnay remote controller. Group 2 : Without a Lossnay remote controller.

Group 3 : Multiple Lossnay units and one Lossnay remote controller. Group 4 : One Lossnay unit and two Lossnay remote controllers. Group 5 : Multiple Lossnay units and two Lossnay remote controllers.

Group 6 : One Lossnay unit is interlocked to one indoor unit(PZ-60DR-E is not necesally).

Group 7 : One Lossnay unit is interlocked to multiple indoor units(PZ-60DR-E is not neccesally).

Group 8 : Multiple Lossnay units connected to indoor unit transmission cable side and one Lossnay remote controller.

Group 9 : Without Lossnay units.

Group setting

Interlocked operation setting

Caution:

Hard wire connection from PZ-60DR-E is required independent from M-NET line. If change the Group setting in the future, it is required to change the wiring of PZ-60DR-E.

In this application, Lossnay remote controller PZ-41SLB-E cannot be used.

C-14

System Examples: 2 (Lossnay M-NET Remote Controller PZ-52SF-E)

The following groups can be configured.

● Further information please refer LGH-RX4 Technical Manual.

Centralized controller (000)

( ) address

 

Power

 

 

 

 

 

 

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

 

Lossnay

Lossnay

(001)

(002)

(003)

(004)

(005)

(006)

 

(007)

(008)

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

(101)

 

 

(103)

 

(106)

(156)

(107)

(157)

 

 

 

 

 

 

 

 

 

 

 

Lossnay M-NET remote

 

Lossnay M-NET remote

 

Lossnay M-NET remote

Lossnay M-NET remote

 

 

 

 

 

 

 

 

 

 

 

 

controller PZ-52SF-E

 

controller PZ-52SF-E

 

controller PZ-52SF-E

controller PZ-52SF-E

 

 

 

 

 

 

 

 

 

Group1

Group2

Group3

 

 

Group4

 

Group5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(059)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

Lossnay

Indoor

 

 

 

Indoor

Lossnay

Lossnay

Lossnay

Indoor

 

 

 

 

unit

 

 

 

(010)

unit

 

 

 

unit

(013)

(014)

(015)

unit

 

 

 

 

(009)

 

 

 

 

 

(011)

 

 

 

 

(012)

 

 

 

(016)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MA Remote

 

MA Remote

 

 

 

Lossnay M-NET remote

MA Remote

 

controller

 

controller

 

 

 

controller PZ-52SF-E (114)

controller

 

Group6

 

Group7

 

 

 

Group8

 

Group9

Group 1 : One Lossnay unit and one Lossnay M-NET remote controller. Group 2 : Without a Lossnay M-NET remote controller.

Group 3 : Multiple Lossnay units and one Lossnay M-NET remote controller. Group 4 : One Lossnay unit and two Lossnay M-NET remote controllers. Group 5 : Multiple Lossnay units and two Lossnay M-NET remote controllers. Group 6 : One Lossnay unit is interlocked to one indoor unit.(PZ-60DR-E is not

necesally)

Group 7 : One Lossnay unit is interlocked to multiple indoor units.(PZ-60DR-E is not neccesally)

Group 8 : Multiple Lossnay units connected to indoor unit transmission cable side and one Lossnay M-NET remote controller.

Group 9 : Without Lossnay units.

Group setting

Interlocked operation setting

Caution:

If change the Group setting in the future, no need to change the M-NET wiring, Just change the address setting from centralized controller.

In this application, Lossnay remote controller PZ-41SLB-E cannot be used.

C-15

Lossnay Function Table (Group Setting)

Item

Details

 

 

Number of Lossnay remote controllers and/or MELANS

Five units

(Number of Lossnay remote controller(PZ-60DR-E or PZ-

remote controllers that can be connected to one Lossnay unit

52SF-E) is two units max.)

 

 

 

Operation of two remote controllers in one group

Possible

 

 

Switching fan speed

High/Low (Extra-Low from PZ-60DR-E)

 

 

Ventilation mode

Heat exchange / By-pass / Automatic

 

 

Filter maintenance indicator

3000 hours / No display

 

 

Error

Display

 

 

Controller Function Table

 

 

 

Local Remote

 

 

MELANS Series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lossnay

Lossnay

Remote

 

Simple

Group

System

Schedule

ON/OFF

Centralized

 

Model

remote

remote

 

remote

remote

remote

remote

 

controller

controller

controller

controller

controller

controller

timer

controller

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

PZ-52SF-E

PZ-60DR-E

PAR-21MAA

PAC-SE51CRA

PAC-SC30GRA

PAC-SF44SRA

PAC-YT34STA

PAC-YT40ANRA

AG-150A

 

 

(M-NET)

 

PAR-F27MEA

PAC-YT51CRA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of controllable (Groups/Units)

1 Group/16 Units

1 Group/15 Units

 

 

 

 

50 Group/50 Units

50 Group/50 Units

16 Group/50 Units

50 Group/50 Units

 

 

 

 

 

 

 

 

 

 

 

 

 

Start/Stop

«

«

 

 

 

 

n

n

n

n

Operation

Switching air volume

«

«

 

 

 

 

n

×

×

n

 

 

 

 

 

 

Switching Ventilation mode

«

«

 

 

 

 

n

×

×

n

 

Priority instructions to local remote

×

×

 

 

 

 

n

*1

×

n

 

controller (Local permitted)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status (Operation/Stop)

«

«

 

 

 

 

n

n

n

n

 

Switching air volume

«

«

 

 

 

 

«

×

×

«

Monitoring

Error information

«

«

 

 

 

 

n

n

×

n

 

Ventilation mode

«

«

Not applicable with non-interlocked

«

×

×

«

 

Error

«

«

Lossnay units

 

n

n

«

n

 

 

 

 

 

 

 

 

 

 

 

 

 

Filter maintenance indicator

«

«

 

 

 

 

«

×

×

«

 

Local permitted

«

«

 

 

 

 

«

×

×

«

 

Weekly

×

«

 

 

 

 

×

«

×

«

Scheduling/ Recording

Minimum setting (minutes)

×

1

 

 

 

 

×

5

×

1

 

Stop/Starts per day

×

16

 

 

 

 

×

16

×

24

 

Stop/Starts per week

×

112

 

 

 

 

×

112

×

24x7*2

 

 

 

 

 

 

 

 

 

 

 

 

 

Error record

×

«

 

 

 

 

«

×

×

«

Switches and display

 

n: Group/batch

 

 

« : Group only (or function available)

 

 

 

: Available under some condition

× : Not available

 

 

 

 

 

*1 Available as a scheduled operation

 

 

 

 

 

 

 

*2 You can set a schedule for the year and a weekly schedule for individual seasons.

For details about the operation and display of the Lossnay remote controller (PZ-60DR-E), Refer to page C-78.

For details about the operation and display of the Lossnay M-NET remote controller (PZ-52SF-E), Refer to page C-92.

For details about the operation and display of the centralized controller (AG-150A), Refer to page C-93.

C-16

4.6.2 City Multi and Lossnay Interlocked System

Characteristics

It is possible to interlock City Multi indoor units with Lossnay operation.

Independent Lossnay operation can also be performed using MA remote controller or ME remote controller.

Non M-NET Lossnay remote controller PZ-60DR-E can be used with any Lossnay units in this application.

System Examples

The following groups can be configured.

Single Refrigerant System

Outdoor unit (051)

Non M-NET Lossnay remote controller PZ-41SLB-E cannot be used with any group in this application.

( ) address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

Lossnay

Indoor

 

 

 

 

Indoor Lossnay

Indoor

 

 

Lossnay

Indoor

 

 

 

Lossnay

Indoor

 

 

 

unit

 

 

(002)

unit

 

 

 

 

unit

(005)

unit

 

(007)

unit

 

 

 

(009)

unit

 

 

 

(001)

 

 

 

(003)

 

 

 

 

(004)

 

(006)

 

 

 

 

(008)

 

 

 

 

(010)

 

 

 

MA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

MA Remote

 

 

 

MA Remote

MA Remote

 

MA Remote

controller

 

controller

 

 

 

controller

controller

 

controller

Group1

 

Group2

 

 

Group3

 

 

 

Group4

 

 

 

Group5

Group 1 : One Lossnay unit is interlocked to one indoor unit. Group 2 : One Lossnay unit is interlocked to multiple indoor units.

Group 3 : One indoor unit with two remote controllers is interlocked to one Lossnay unit. Group 4, 5 : Multiple groups are interlocked to one Lossnay unit.

Group setting

Interlocked operation setting

Multiple Refrigerant Systems

 

( ) address

Refrigerant 1

Refrigerant 2

Outdoor unit (051)

Outdoor unit (055)

Indoor

Lossnay

Indoor

Lossnay

Indoor

Indoor

Indoor

Lossnay

unit

(002)

unit

(004)

unit

unit

unit

(008)

(001)

 

(003)

 

(005)

(006)

(007)

Group setting

MA Remote

 

MA Remote

 

 

MA Remote

 

Interlocked

controller

 

controller

 

 

controller

 

Group1

 

Group2

 

 

Group3

 

operation setting

 

 

 

 

 

Group 1 : One Lossnay unit is interlocked to one indoor unit.

Group 2 : One Lossnay unit is interlocked to multiple indoor units (with different refrigerants). Group 3 : One Lossnay unit is interlocked to multiple indoor units (with same refrigerant).

C-17

Lossnay Function Table (Interlocked Settings)

 

Item

Details

 

 

 

Number of indoor units that can be set to interlocked opera-

16 units per group

tion with one Lossnay unit in each group

 

 

 

 

Number of Lossnay units that can be set to interlocked oper-

one unit

ation with one indoor unit

 

 

 

 

Independent Lossnay start/stop operation

Possible

 

 

 

Delayed operation

30-minutes delayed operation when indoor unit cooling/heat-

(Optional setting by Lossnay PCB)

ing operation is started

 

 

 

Fan speed switching

Indoor unit compatible with both R22,

High/Low

 

R407C and R410A

 

 

 

 

 

Units other than the above

Fixed to high

 

 

 

Ventilation mode

Fixed to automatic

 

 

 

Filter maintenance indicator

3000 hours / No display

 

 

 

Error

Display

 

 

 

Restrictions and precautions

* Lossnays cannot be interlocked to the indoor units using

 

 

K-transmission converter.

 

 

 

Note:

● In case of PZ-60DR-E is installed, additional function is available.

Lossnay Controller Function Table

 

 

Local Remote

 

 

MELANS Series

 

 

Lossnay

Lossnay Remote

Simple

Group

System

Schedule

ON/OFF

Centralized

Model

remote

remote

remote

remote

remote

remote

controller controller controller controller controller controller

timer

controller controller

 

 

PZ-52SF-E

PZ-60DR-E

PAR-21MAA PAC-SE51CRA

PAC-SC30GRA PAC-SF44SRA PAC-YT34STA PAC-YT40ANRA

AG-150A

 

 

 

 

PAR-F27MEA PAC-YT51CRA

 

 

 

 

 

No. of controllable (Groups (G)/Units)

1 Group/16 Units

1 Group/15 Units

1 Group/16 Units

1 Group/16 Units

8 Group/16 Units

50 Group/50 Units 50 Group/50 Units

16 Group/50 Units 50 Group/50 Units

Operation

Start/Stop

«

«

«

«

n

n

n

n

n

Switching air volume

«

«

«

×

«

«

×

×

«

 

 

Switching ventilation mode

«

«

×

×

×

×

×

×

×

 

Prohibit Local

×

×

×

×

×

n

*2

×

n

 

 

 

Status (Operation/Stop)

«

«

«

×

«

*1

n

n

n

 

 

Monitoring

Switching air volume

«

«

«

×

«

×

×

×

«

Error information

«

«

«

«

n

n

n

×

n

 

Ventilation mode

«

«

×

×

×

×

×

×

×

 

Error

«

«

«

«

n

n

n

n

n

 

Filter maintenance indicator

«

«

«

×

«

«

×

×

«

 

Permit/Prohibit for remote control

×

«

«

«

«

«

×

×

«

Scheduling/ Recording

Weekly

×

«

×

×

×

×

«

×

«

Stop/Starts per day

×

16

2

×

×

×

16

×

24

 

 

Stop/Starts per week

×

112

×

×

×

×

112

×

24x7*3

 

Minimum setting (minutes)

×

1

10

×

×

×

5

×

1

 

Error record

×

«

×

×

×

«

×

×

«

Switches and display

n: Group/batch

« : Group only (or function available)

 

: Available under some condition

× : Not available

 

*1

Does not display which interlocked Lossnay unit is operating in which group

 

*2

Available as schedule operation

 

 

*3

You can set a schedule for the year and a weekly schedule for individual seasons.

For details about the operation or display of the remote controller (PAR-F27MEA, PAR-21MAA), please refer to the specific remote controller manuals.

C-18

4.6.3MA Remote Controller/ME Remote Controller in Combination with Lossnay Non-M-NET Remote Controller (PZ-60DR-E)

System

Combining MA, ME and Lossnay Non M-NET remote controllers is permitted.

● In case of combination with Lossnay M-NET remote controller (PZ-52SF-E) please refer LGH-RX4 Technical Manual.

Combining Indoor Unit of Air Conditioner Remote Control and Lossnay Remote Control

Indoor Unit

Lossnay LGH-RX5 type

 

 

Model for MA remote control (Type C or later)

«

 

 

Model for other than MA remote control (Type B or earlier)

×

 

 

« : Compatible × : Incompatible

 

System Examples: 1

Centralized controller (000)

Interlocked operation setting

Power

 

Indoor unit of

Lossnay

 

Outdoor unit

air conditioner

(002)

 

supply

(001)

 

 

(051)

 

 

unit

 

 

 

 

 

 

 

 

 

MA remote

Lossnay remote

 

 

 

controller

controller

 

 

 

(101)

PZ-60DR-E

( ) address

Setting Method

(1)Make the Group setting for the indoor unit.

(2)Make the Group setting for the Lossnay unit.

(3)Set the indoor unit and Lossnay unit for interlocked operation.

When using the centralized controller, make both the Group setting and operation setting with centralized controller.

Characteristics

(1)When the indoor unit is set for interlocked operation in one group:

Interlocked Lossnay operation is possible with indoor unit remote controller. In this case, operation can switch between High/Low/Off. It is possible to switch Lossnay operation only between High/Low/Off with the indoor unit remote controller.

It is possible to controll the Lossnay unit from Lossnay remote controller PZ-60DR-E. More additional function such as Extra Low fan speed is available.

(2)When two or more indoor units in different groups are set for interlocked operation, the Lossnay will operate if at least one group operates. The Lossnay will stop operation if all groups stop operation.

It is possible to switch the Lossnay only between High/Low when other groups are operating with indoor unit remote controller.

It is possible to controll the Lossnay unit from Lossnay remote controller PZ-60DR-E. More additional function such as Extra Low fan speed is available.

Note:

If the display on the MA, ME or other indoor unit remote controllers is cancelled, the indoor unit remote controller will not show the ventilation display even if Lossnay is operating via the Lossnay remote controller PZ-60DR-E.

Note:

Power supply limitation of transmission cable for indoor unit.

Indoor units + ME remote controllers (compact remote controllers) is less than or equal to 40 units.

Indoor units are less than or equal to 20 units.

(MA remote controllers and Lossnay units are not included in the 20 units, listed above.)

C-19

System Examples: 2

A sophisticated system including City Multi can also be configured.

Centralized controller (000)

( ) address

M-MET

 

Power

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

 

Lossnay Lossnay(008)

 

(001)

(002)

(003)

(004)

(005)

 

(006)

 

(007)

 

supply

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

Lossnay remote

 

Lossnay remote

 

 

 

Lossnay remote

Lossnay remote

 

Outdoor unit

controller PZ-60DR-E

 

controller PZ-60DR-E

 

 

 

controller PZ-60DR-E

controller PZ-60DR-E

 

Group1

Group2

Group3

 

 

 

Group4

 

Group5

 

(059)

 

 

 

 

 

M-MET

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Lossnay

Indoor unit

Indoor unit

Lossnay

 

Lossnay

Lossnay

Indoor unit

 

(009)

(010)

(011)

(012)

(013)

 

 

(014)

(015)

 

(016)

 

 

(109)

 

(111)

 

 

 

 

 

 

(116)

 

ME

Lossnay remote

ME

 

Lossnay remote

 

Lossnay remote

 

ME

 

remote controller

controller PZ-60DR-E

remote controller

controller PZ-60DR-E

 

controller PZ-60DR-E

 

remote controller

 

Group6

 

Group7

 

 

 

Group8

 

Group9

 

 

 

 

 

 

 

 

 

 

 

Group setting

 

 

 

 

 

 

 

 

 

 

 

Interlocked

 

 

 

 

 

 

 

 

 

 

 

operation setting

Group 1

: One Lossnay unit and one Lossnay remote controller.

 

 

 

 

 

 

Group 2

: Without Lossnay remote controller.

 

 

 

 

 

 

 

Group 3

: Multiple Lossnay units and one Lossnay remote controller.

 

 

 

 

 

Group 4

: One Lossnay unit and two Lossnay remote controllers.

 

 

 

 

 

 

Group 5

: Multiple Lossnay units and two Lossnay remote controllers.

 

 

 

 

 

Group 6

: One Lossnay unit is interlocked to one indoor unit. (PZ-60DR-E is not necessary)

 

 

Group 7

: One Lossnay unit is interlocked to multiple indoor units. (PZ-60DR-E is not necessary)

Group 8

: Multiple Lossnay units connected to an indoor unit transmission cable

 

 

 

and one Lossnay remote controller.

 

 

 

 

 

 

 

Group 9

: Without Lossnay units.

 

 

 

 

 

 

 

 

 

Note:

Hard wire connection from PZ-60DR-E is required independent from M-NET line. If change the Group setting in the future, it is required to change the wiring of PZ-60DR-E.

Do not use Lossnay remote controller PZ-41SLB-E.

C-20

4.6.4 When Using the LONWORKS® Compatible Adaptor (LMAP02-E) to Connect to LONWORKS®

By using the LON® adaptor (model name: LMAP02-E) to connect to LONWORKS®, it is possible to control and observe Lossnay operation on a building management system.

* For specifications and functions of the LON® adaptor, refer to the materials regarding the LONWORKS® compatible adaptor.

Table of Functions

 

 

Individual Lossnay

Interlocked Lossnay

 

Contents

(Lossnay not set

(Lossnay set for

 

for interlocked

interlocked opera-

 

 

 

 

operation)

tion with City Multi)

 

 

 

 

 

ON/OFF

«

×

Operation

Switch fan to High/Low

«

×

Switch ventilation mode

«

×

 

 

Prohibit local ON/OFF operation

«

×

 

Operation condition

«

×

 

Fan speed

«

×

Monitoring

Ventilation mode (conditions)

«

×

Errors

«

«

 

 

Filter maintenance indicator

«

×

 

Prohibit local ON/OFF operation

«

×

« : Available ×: Not Available

System Example

(Using M-NET)

 

 

M-NET

 

Building

LMAP02-E

 

 

management

 

Lossnay

Lossnay

system

 

 

 

 

LONWORKS

 

Lossnay

Lossnay

 

 

remote controller

remote controller

 

 

PZ-60DR-E

PZ-60DR-E

 

LMAP02-E

 

 

 

M-NET

Lossnay

Lossnay

 

 

Lossnay

Lossnay

 

 

remote controller

remote controller

 

 

PZ-60DR-E

PZ-60DR-E

Connect the M-NET transmission cable to TB5 A,B of the Lossnay terminal block. (Refer to page C-71). The Lossnay remote controller (PZ-41SLB-E) cannot be used with this system.

Up to 50 units can be connected with one LMAP02-E.

For details about the system or connection cables of the LMAP02-E, refer to its technical materials.

*LONWORKS® is a registered international trademark, registered in the U.S.A. to the Echelon Corporation.

C-21

5.Examples of Applications Using Various Input and Output Terminals

Various applications are possible by using the input/output terminals and connectors as shown below.

Input/Output Specifications

 

Terminal

 

Specification

Page

 

 

 

 

1

External control input

TM2 is the input terminal block for start/stop the Lossnay unit using external

C-26/C-27

 

terminal block for

equipment, such as a Mr. Slim (A-control) indoor unit or the BMS (Building

C-28/C-73

 

start/stop the Lossnay

Management System).

 

 

 

 

unit

Use voltage (12V-24V DC) or uncharged a-contact for signal input.

 

 

 

(Both voltage and no-voltage signals are compatible with pulse input; a pulse

 

 

(TM2 1 2 3)

signal duration of 200 ms or more is needed. Set DIP switch 2-2 to ON.)

 

 

 

 

 

2

Lossnay operation moni-

Output terminal during Lossnay unit operation. (uncharged a-contact signal output.)

C-26/C-27

 

tor output terminal block

Output delay function 1 is possible by DIP switch 2-8

C-70/C-74

 

or

Contactor rating:

Max 240V AC,

2A

 

 

Output delay function 1

 

24V DC,

2A

 

 

 

 

Min 220V AC,

100mA

 

 

(TM4 9 0)

 

5V DC,

100mA

 

 

 

 

 

3

Lossnay malfunction

Output terminal during Lossnay unit malfunction. (uncharged a-contact signal output.)

C-26/C-27

 

monitor output terminal

Contactor rating:

Max 240V AC,

1A

 

 

block

 

24V DC,

1A

 

 

 

 

Min 220V AC,

100mA

 

 

(TM3 7 8)

 

5V DC,

100mA

 

 

 

 

 

4

By-pass monitor output

Output terminal during Lossnay unit malfunction. (uncharged a-contact signal output.)

C-26/C-27

 

terminal block

Output delay function 2 is possible by DIP switch 5-6

C-75

 

or

Contactor rating:

Max 240V AC,

1A

 

 

Output delay function 2

 

24V DC,

1A

 

 

 

 

Min 220V AC,

100mA

 

 

(TM3 6 7)

 

5V DC,

100mA

 

 

 

 

 

 

5

External control input

Input connector for switching By-pass.

 

C-28/C-29

 

connector for By-pass

Establish the wire connection by inserting the optional remote display adaptor

C-70

 

(CN 16)

(PAC-SA88HA-E) in the connector CN16 (Ventilation mode selector).

 

 

 

 

 

6

External control input

Input connector for switching Hight/Low/Extra-Low fan speed.

C-28/C-70

 

connector for fan speed

Using marketed CO2 sensor, etc., make connection by inserting the optional

 

 

(CN 16)

remote display adaptor (PAC-SA88HA-E) in the connector CN16.

 

 

 

 

 

 

 

Lossnay Main/Sub Setting

If multiple Lossnay system begin operation by one signal from an indoor unit of air conditioner or the like, make sure the unit connected to the signal cable from the indoor unit of air conditioner is set to “Main,” and all the others are set to “Sub.”

 

 

 

 

Main/Sub selection

 

 

41SLB-E)

 

switch

Power

 

 

(SW1)

 

 

Power

Main Sub

supply

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device (Factory setting: main)

Power

Lossnay

 

 

 

 

 

supply

 

 

 

Connect to

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

Second

controller

 

 

 

(PZ-60DR-E)

 

 

 

 

 

 

Lossnay

 

 

 

 

 

Power

 

 

 

Connect

supply MAX 15 units

 

 

 

to third

Transmission cable

Lossnay

C-22

5.1External Control Operating Mode Selection

There are four modes when operating using signals from external equipment.

1.ON/OFF interlock (the chosen function from either external signal or remote control switch has priority)

2.ON interlock

3.OFF interlock

4.External priority ON/OFF interlock

Operating Signal

Mode

When external signal is level signal.

When external signal is pulse signal.

(Optional setting)

 

 

ON/OFF

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inter-

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ON/OFF] button pressed

lock

[ON/OFF] button pressed

 

 

 

 

 

 

 

 

 

Operating Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition Stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition Stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inter-

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ON/OFF] button pressed

lock

[ON/OFF] button pressed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

Operating

 

 

 

 

 

 

 

 

 

Operating

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition

Stopped

 

 

 

 

 

 

 

 

 

 

condition

Stopped

 

 

 

 

 

 

 

 

 

 

 

OFF

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inter-

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ON/OFF] button pressed

lock

[ON/OFF] button pressed

 

 

 

 

 

 

 

 

 

 

 

Operating

Operating

 

 

 

 

 

 

 

 

 

 

Operating

Operating

 

 

 

 

 

 

 

 

 

 

 

 

condition

Stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

condition

Stopped

 

 

 

 

 

 

 

 

 

 

External

External signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

priority

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON/OFF

Remote controller

 

 

 

 

 

 

 

 

This mode does not exist.

 

 

 

 

 

 

 

 

inter-

[ON/OFF] button pressed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lock

Operating

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition

Stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting Method

When PZ-41SLB-E is used, use the remote controller to set. (Refer to page C-91)

When PZ-41SLB-E is not used, use the DIP switch 5-7,8 to set. (Refer to page C-76)

C-23

5.2Delayed Interlocked Operation

It is possible to delay operation of the Lossnay if an external device is operating. (Energy saving capability.)

<When PZ-41SLB-E is used> (Refer to page C-91, Remote controller to be set)

Choose from 10, 20, 30, 40, 50, and 60 minute delayed Lossnay operation.

Delayed operation does not occur if the Lossnay operation was cancelled within the last two hours.

(When turned off for a short time, during a lunch break, for example, if the direction to restart operation is given within two hours, the Lossnay will restart immediately.)

● If an operation button is pressed on the remote controller while the delay timer is operating, the delayed operation is cancelled and normal operation begins.

<When PZ-41SLB-E is not used>

Delays Lossnay operation for 30 minutes.when City Multi or Mr.Slim starts operating or when a external device starts operating. (Refer to page C-74)

5.3Multiple External Device Operation (PZ-60DR-E, PZ-41SLB-E, M-NET)

When there are multiple air conditioners or other external devices

Characteristics

Ordered parts

 

Notes

Lossnay operates at the same time as

Remote controller

Can receive level signal, uncharged

any of the external devices.

 

 

a-contact external signals.

 

 

If the external device is a pulse sig-

 

 

 

nal or charged signal, multiple con-

 

 

 

nections cannot be made.

 

 

 

 

System Example

When the Operation Signal is a Uncharged a-contact Level Signal.

(Signal cable between Lossnay and remote controller must be more than 500 m.)

φ 0.65 to 1.2 PVC cable or

0.3 mm2 to 1.25 mm2 strand wire.

 

 

 

Uncharged a-contact

Uncharged a-contact

Uncharged a-contact

Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit of

 

 

 

 

Indoor unit of

 

 

 

 

 

Indoor unit of

 

 

 

 

 

air conditioner 1

 

 

 

air conditioner 2

 

 

 

 

air conditioner 4

 

 

 

 

 

Power supply

Power supply

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lossnay Remote

Indoor unit

Indoor unit

Indoor unit

controller

remote controller

remote controller

remote controller

PZ-60DR-E

 

 

 

* Illustration shows an example when using PZ-60DR-E

C-24

5.4Multiple Lossnay Units Interlocked with One Indoor Unit (M-NET only)

[Example: System 1]

Set the Main/Sub switch of the Lossnay connected to the M-NET transmission cable to “Main,” set the other Lossnay units to “Sub,” and connect 1 and 2 of the Lossnay remote controller (PZ-60DR-E or PZ-41SLB-E) transmission cable terminal (TM4) to the corresponding terminal on the next unit.

M-NET transmission cable

 

 

Indoor unit

 

 

TM4

TM4

TM4

MA remote

 

 

controller

 

 

Lossnay

Lossnay

Lossnay

(Main)

(Sub)

(Sub)

Lossnay Remote controller

 

 

PZ-60DR-E or PZ-41SB-E

 

 

Note:

Make the setting of the first Lossnay unit and the indoor unit to be interlocked.

It is not necessary to set the address or control for other Lossnay units, directly.

Malfunctions of the Lossnay units for sub units will not appear on the remote controller.

[Example: System 2]

When you want to also monitor and manage the Sub set Lossnay malfunctions via a centralized controller, wire all of the TM4 of Lossnays, set the main/sub switch of the Lossnay of the smallest address to “Main”, and set other Lossnays at “Sub.” From the centralized controller, set indoor unit and Lossnays group registration, respectively, and set the interlock with an indoor unit and a Lossnay of the smallest address in a group.

Centralized controller AG-150A

Power supply unit

M-NET

TB5

TB5

TB5

transmission cable

 

 

 

 

 

Indoor unit

Main

 

Sub

 

Sub

(001)

Lossnay

Lossnay

Local

 

Lossnay

 

 

 

(010)

(011)

transmission

(012)

 

 

 

cable

 

 

MA

Lossnay

TM4

 

 

 

remote

remote

 

 

 

 

controller

controller

 

 

 

 

Group1

PZ-60DR-E Group2

 

 

 

 

Interlocked setting

The inside of ( ) is an address number.

[Example: System 3]

Use the Lossnay remote controller to set the indoor units of air conditioner and Lossnay units to separate groups. Both interlocked operation of an indoor unit of air conditioner and Lossnay units can be performed independently by connecting the remote display output for the indoor unit and the external control input for the Lossnay unit.

M-NET

External control input (TM2)

transmission cable

 

Indoor unit

Lossnay

Lossnay

Lossnay

 

Lossnay remote controller

 

MA remote

(PZ-60DR-E)

 

 

Remote display output

 

 

controller

 

 

Note:

Do not make the setting of the indoor and Lossnay units to be interlocked, because the ventilation switch on the MA remote controller will become invalid, and the error indicator for the Lossnay unit will appear only on the Lossnay remote controller.

C-25

5.5Operation monitor output (Refer to page C-70)

[Example System]

M-NET transmission cable

 

Lossnay

 

Indoor unit

Electrically operated damper/

 

 

Booster fan etc.

 

MA remote

Operation monitor output (TM4

)

controller

5.6Malfunction monitor output (Refer to page C-69)

[Example System]

M-NET transmission cable

Indoor unit

MA remote controller

Lossnay

Malfunction indicator (Lamp or monitoring unit) Malfunction monitor output (TM3 )

5.7By-pass operation monitor output (Refer to page C-69)

[Example System]

M-NET transmission cable

Indoor unit

MA remote controller

Lossnay

By-pass operation indicator (Lamp or booster fan etc) By-pass Operation monitor output (TM3 )

5.8Connection Method

1. When using Mitsubishi Mr.Slim air conditioner with MA Remote controller. (Refer to page C-67)

Lossnay External controller input (TM2)

Slim-Lossnay connection cable

123

(Enclosed accessory)

 

 

CN2L

 

White

 

Mr. Slim (Indoor unit)

 

Red

Within 500 m

Printed circuit board

 

Connect the interlocking cable connector side to CN2L on the circuit board for the indoor Mr.Slim unit, then connect the lead wire side to the 1 and 2. of the input terminal block (TM2) for the Lossnay external controller input. (No polarity)

2. When the external device has a charged operating signal of 12 VDC or 24 VDC. (Refer to page C-68)

Lossnay External control input (TM2)

123

 

0.5 mm2 to 1 mm2 sheathed PVC cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 or 24 VDC

Overall connection extension length

(Follow the operation manual for the external equipment.)

Connect the operating signal (wire) from the external device via the remote output to 1 and 2. on the external control input terminal block (TM2). (No polarity)

C-26

3. When the external device has an uncharged a-contact signal.(Refer to page C-68)

Lossnay External controller input (TM2)

1230.5 mm2 to 1 mm2 sheathed PVC cable External device

Uncharge a-contact

Within 500 m

Connect the operating signal (wire) from the external device via the remote output to 1 and 3 on the external control input terminal block (TM2).

Caution:

If an optocoupler or any othe type of polar coupler is used at the uncharged a-contact, connect the positive side to 3 and the negative side to 1.

4. Multiple uncharged a-contacts.

Remote output component

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External device

 

 

 

 

 

 

 

 

 

 

 

 

operation switch

 

 

 

 

 

 

 

 

 

 

 

Power

 

Lossnay

 

 

 

External

 

 

 

 

 

 

 

 

1

 

 

 

device

 

 

 

External control

2

 

 

 

 

 

 

 

External device

input (TM2)

3

 

 

 

 

 

 

 

operation switch

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

External

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External device

 

 

 

 

 

 

 

 

 

 

 

 

operation switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

External

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device

 

 

 

 

 

 

 

 

500 m or less

 

 

 

 

 

External device

 

 

 

 

 

 

 

 

 

 

operation switch

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the operating signal (wire) from the external device via the remote output to 1 and 3 on the external control input terminal block (TM2).

Caution:

If an optocoupler or any othe type of polar coupler is used at the uncharged a-contact, connect the positive side to 3 and the negative side to 1.

5. When connect to an Electrically operated damper, or take Operation monitor output.

 

Power Supply

 

 

 

 

 

 

Monitor output

 

 

 

 

terminal (TM4)

 

 

 

Electrically

0

 

 

 

 

operated

 

 

 

 

 

 

damper

9

 

Contactor rating

 

 

 

 

 

 

 

 

 

 

Max

240 VAC,

2 A

 

 

 

 

 

24 VDC,

2 A

 

 

 

 

 

 

 

 

 

Min

220 VAC,

100 mA

Lamp

 

 

 

 

5 VDC,

100 mA

 

 

 

 

 

 

 

Connect the power supply cable from the Electrically operated damper to 9 and 0 of the monitor output terminal block (TM4) with reference to the wire connection diagram.

Operation monitor output with delay function 1 can be possible. (Refer to function setting 6 (refer to C-74) “Setting for TM4 9 0”).

Note:

Don’t tighten screws of terminal block with a torque larger than 0.5Nm. It could damage the PCB.

Response times to external input signals are as shown in the following table.

External Signal

Response Time

 

 

Level Signal

Max. 7 sec.

 

 

Pulse Signal

Max. 200 msec

 

 

6. When take Malfunction monitor output, or take By-pass operation monitor output (Refer to page C-75)

Bypass operation indicator

 

 

 

 

 

Power

Monitor output terminal

 

 

 

TM3

By-pass operation signal

Lamp or

Supply

 

6

contactor rating

 

 

 

monitoring unit

 

 

 

 

Max

240 VAC,

1A

 

 

7

 

 

 

24 VDC,

1A

 

 

 

 

Malfunction indicator

 

8

Min

220 VAC,

100 mA

 

 

 

5 VDC,

100 mA

Malfunction signal

C-27

7. ON/OFF power operation without using the remote controller.

Switch

TM1

Power source for LOSSNAY

Lossnay

TM2

1 2 3

Connect as shown in the wiring diagram to the left.

When the Switch ON, the LOSSNAY unit will begin to operate.

*LOSSNAY FAN speed can be selected (High/Low) through DIP switch 2-4 and 2-5.

*Ventilation mode (LOSSNAY/By-pass) is set to automatic.

5.9When switching High/Low/Extra-Low fan speed externally (when CO2 sensor or other equipment is connected)

Using marketed CO2 sensor, etc., make connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16 (High/Low selector) as shown by the figure.

● To force High fan speed externally

CO2 sensor, etc.

 

Remote display

 

 

 

 

(When CO2

 

adaptor (Optional)

Lossnay

increases: Closed)

PAC-SA88HA-E

control board

SW1

 

Brown 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red 2

 

 

 

 

 

 

 

 

Orange 3

 

 

 

 

 

 

 

 

Yellow 4

 

 

 

 

 

 

 

 

Green 5

 

 

 

Fan speed/

 

 

 

 

 

Ventilation

SW1: High fan speed operation switch

 

 

 

 

 

mode selection

 

 

 

 

Not used. Insulate completely.

(When closed: For High fan speed operation)

Max wiring length 10 m

When SW1 is “ON”, fan speed of the Lossnay will be set to “High”(Extra-High) regardless of the remote control setting. Use this in such a way that it ventilates at Low or Extra-Low fan speed normally, and when the external sensor detects contamination of indoor air, it changes to High (Extra High) fan speed operation.

● To force Low fan speed externally

CO2 sensor, etc.

Remote display

 

 

(When CO2

adaptor (Optional)

Lossnay

increases: Closed)

PAC-SA88HA-E

control board

 

Brown 1

 

 

SW1

Red 2

 

 

Orange 3

 

 

 

 

 

 

Yellow 4

 

Fan speed/

 

 

 

Green 5

 

 

 

Ventilation

 

 

 

mode selection

SW1: Low fan speed operation switch

Not used. Insulate completely.

(When closed: For Low fan speed operation)

Max wiring length 10 m

When SW1 is "ON", fan speed of the Lossnay will be set to “Low” regardless of the remote control setting.

Use this in such a way that it ventilates at High fan speed normally, and when the external sensor detect that the indoor air contamination is low, it changes to Low fan speed operation.

● To force Extra-Low fan speed externally

CO2 sensor, etc.

Remote display

 

 

(When CO2

adaptor (Optional)

Lossnay

increases: Closed)

PAC-SA88HA-E

control board

 

Brown 1

 

 

 

Red 2

 

 

SW1

Orange 3

 

 

Yellow 4

 

Fan speed/

 

 

 

 

Green 5

 

 

 

Ventilation

 

 

 

mode selection

SW1: Low fan speed operation switch

Not used. Insulate completely.

(When closed: For Low fan speed operation)

Max wiring length 10 m

When SW1 is "ON", fan speed of the Lossnay will be set to “Extra-Low” regardless of the remote control setting.

Use this in such a way that it ventilates at High fan speed normally, and when the external sensor detects that the indoor air contamination is low, it changes to Extra-Low fan speed operation.

*For the LGH-150RX5 and LGH-200RX5 types, fan speed of the Lossnay will be “Low”.

C-28

1When using PZ-60DR-E or PZ-41SLB-E to connect multiple Lossnay units

Connect the sensor to the Lossnay set to “Main”.

It is not necessary to connect to any Lossnay with the “Sub” setting.

Connect any sensor, etc., with the external change input to the Lossnay unit set to “Main”.

Any Lossnay with the “Sub” setting will operate at the same High/Low setting as the Lossnay with the “Main” setting when there is sensor signal input.

Main

Sub

Sub

Lossnay

Lossnay

Lossnay

(Main)

(Sub)

(Sub)

CO2 sensor

PZ-60DR-E or PZ-41SLB-E

2When using M-NET for a group of multiple units

Even if the units are in the same group, you can only change operation to High/Low for Lossnay units connected to the sensor.

CASE 1 : PZ-60DR-E

 

 

CASE 2 : PZ-52SF-E

 

 

Main

Sub

Sub

 

 

 

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

PZ-60DR-E

CO2 sensor

 

PZ-52SF-E

CO2 sensor

CO2 sensor CO2 sensor

 

Group

 

 

Group

Note:

● When using the M-NET system, the fan speed being input by the sensor signal will not be displayed on the remote controller.

5.10 When switching By-pass externally

Establish the wire connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16 (Ventilation mode selector).

 

Remote display

Lossnay

 

adaptor (Optional)

 

PAC-SA88HA-E

control board

 

Brown 1

 

 

 

Red 2

 

 

 

Orange 3

 

 

 

 

 

SW1

Yellow 4

 

Fan speed/

 

Green 5

 

 

 

 

 

 

Ventilation

 

 

 

mode selection

SW1: Bypass ventilation operation switch

Not used. Insulate completely.

(When closed: For Bypass ventilation operation)

Max wiring length 10 m

With SW1 is “ON”, the ventilation mode of Lossnay is changed to the By-pass ventilation regardless of the setting on the remote controller.

*When the outdoor air temperature drops lower than 8°C, it changes to the heat exchanger ventilation. (Display of the remote controller does not change.)

5.11 When using the remote/local switching and the ON/OFF input (level signal)

The remoto controller (PZ-41SLB-E) cannot be used.Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in CN32 on the Lossnay control PCB.

Remote control circuit

supply

SW2

power

SW1

Relay

 

Remote ON/OFF

adaptor Lossnay control Relay circuit (PAC-SE55RA-E) board

Orange 1

X

X

Red 2

 

 

 

Y

Y

Brown 3

 

 

 

Max wiring length 10 m

SW1: When this is ON, Lossnay cannot turn ON/OFF by the Remote Controller (PZ-60DR-E, PZ-52SF-E).

SW2: When SW1 is ON, Lossnay can be turned ON by setting SW2 at ON or turned OFF by setting SW2 at OFF.

SW1: Remote/local selector switch

SW2: ON/OFF switch

X, Y : Relay (Contactor rating DC 1 mA)

C-29

5.12When connecting to the City Multi, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air-Conditioner Network System

(MELANS)

If centralized control is performed according the wire connection shown in this section, the remote controller (PZ-41SLB-E) cannot be used.

M-NET transmission cable input terminal block

TB5

A B S

Shielded wire

M-NET transmission cable

● One shielded wire is connected to TB5 S on the PCB on terminal.Address setting is required. (Refer to function setting section.)

M-NET transmission cable: Connect any of the City Multi indoor unit, or Mitsubishi Electric Air-Conditioner Network System (MELANS) - to the Lossnay.

● Connecting positions are different for the Remote Controller PZ-60DR-E and PZ-52SF-E.

PZ-60DR-E:

Connect to TM4 1, 2 on the PCB. (Refer to page C-71 “When connecting with Remote Controller (PZ-60DR-E)”.)

PZ-52SF-E:

Connect to TB5 A , B on the same terminal block as for theM-NET transmission wires.

Securely connect the M-NET transmission wires to TB5 A B .(No-Polar) Type: (Shielded wire, CVVS/CPEVS)

Wire diameter: 1.25 mm2 to 2.0 mm2

When interlocking with Mitsubishi Free Plan air conditioner

● Incase of PZ-60DR-E

● Incase of PZ-52SF-E

 

Indoor unit

Indoor unit

Indoor unit

Indoor unit

 

of air conditioner

of air conditioner

of air conditioner

of air conditioner

 

 

Lossnay

 

Lossnay

 

MA remote

M-NET transmission

MA remote

M-NET transmission

 

controller

 

controller

cable

cable

PZ-52SF-E

PZ-60DR-E

 

 

 

 

When connecting to PZ-60DR-E and MELANS

● Connect the power feeding unit.

(Optional)

Power

MELANS

Lossnay

supply unit

M-NET transmission cable

PZ-60DR-E

*Limit the total length of transmission wires no longer than 500 m. Limit the wiring length between Lossnay and the power supply unit (Optional) or the outdoor unit no longer than 200 m.

CAUTION:

Don’t tighten screws on the terminal block with a torque larger than 0.5 Nm. It may damage the PCB.

Always use shielded wires only for the M-NET transmission wires, and finish the shield properly.