The current situation in mechanical system engineering requires an optimisation
of manufacturing costs. Therefore the modular design of machinery and systems
becomes more and more popular. Individual solutions can be found more easily
and at a more favourable price.
Optimum communication between the modules of a system is often achieved by
a fieldbus system for process automation. Lenze offers the following
communication modules for all common fieldbus systems:
l CAN (Lenze system bus)
l CANopen
l PROFIBUS-DP
l INTERBUS
l INTERBUS loop
l DeviceNet
l LON
l AS-i
The communication modules are especially designed for Lenze drive
components and flexible use. You can use the same communication modules for
Lenze servo inverters and Lenze frequency inverters.
This means for you: Easy communication.
You must only learn to know one communication system.
Handling is always the same.
You reduce your costs because you can make use of the knowledge gained once.
Trainings are only required once.
The planning time becomes shorter.
Help for your decision
PROFIBUS-DP
INTERBUS
The decision for a fieldbus systems depends on many different factors. The
following chart will help you to find the solution for your application.
Machines which usebus lengths of more than 100 meters areoften equipped with
INTERBUS or PROFIBUS-DP. The PROFIBUS-DP (Decentralised Periphery) is
always used together with a PLC – and the PROFIBUS master transfers, for
instance, the setpoints to the devices connected to the PROFIBUS (e.g. Lenze
controllers).
The process data is transferred to the sensors and actuators at the baud rate
typical for the PROFIBUS-DP (1.5 Mbit/s). Because of the data transfer method
and a telegram overhead, the bus cycle time at 1.5 Mbit/s is high enough to
control, for instance, conveyors. If the process data must reach sensors and
actuators more quickly, the PROFIBUS can also be operated at a baud rate of
max. 12 Mbit/s.
INTERBUS is mainly used in big systems (many devices connected to the bus
system)- for instance inthe automobile industry. Its ringstructure offers especially
good diagnostics options. It is possibleto find out which device connected to the
bus is electromagnetically intereferred or whether there is an earth fault or short
circuit interferring the INTERBUS cable. Furthermore, INTERBUS has a baud rate
of 500kbit/ s which is more efficient for process data transfer than comparable bus
systems. If you need extremely quick data transfer, INTERBUS can also be
operated at 2 Mbit/s.
L
EDSIBS-1.0-06/ 2003
1.2-1
1
Show/Hide Bookmarks
Preface
1.2
Lenze system bus (CAN)
CANopen
DeviceNet
Introduction
With the servo controller series 9300Lenze hasintroduced the system bus based
on CAN. The functions of the CANopen communication profile have been
integrated into DS301. The main task of the system bus is the exchange of data
between the controllers and the communication with sensors, actuators and
display and operating elements without a higher level control. Furthermore it is
possible to useit for demanding and time critical applications. Here the controllers
are synchronised by means of a system bus.
CAN is available at a reasonable price and is suitable for smaller machines.
CANopen is a specific communication protocol according to CiA (CON inAutomation). Lenze offers communication modules for control with CANopen
master. These modules are compatible with the spec ification DS 301 V4.01.
The American automation manufacturer Allan Bradley developed the DeviceNet
fieldbus which is based on the CAN controller. This c ommunication profile has
been published in the user organisation ODVA. A large number of sensors and
actuators is available. Like CANopen, DeviceNet uses controls with a DeviceNet
master.
LON
AS-i
INTERBUS loop
The company Echelon (USA) developed the Local Operation Network (LON)
which is mainly used for industrial applications and time-critical demands. This
bus system is mainly used for automation in buildings. Every device connected
to thenetwork has its own intelligence, i.e. higher-level controls arenot necessary.
The lowest level of sensors and actuators is often networked by a AS-i bus
(Actuator-Sensor-Interface). It is a reasonably cheap way of transferring binary
signals I/O. The bus system can be handled, planned and installed easily.
Two-core AS-i cables do not only transfer data but also the auxiliary energy
needed for the devices connected to the AS-i bus.
Similar to the AS-i, the INTERBUS loop was developed as sensor/actuator bus.
Digital and analog devices can be easily connected thanks to insulation
displacement connectors. The INTERBUS loop is on a lower level than the
INTERBUS (remote bus). The INTERBUS loop is connected to the INTERBUS via
a bus terminal.
1.2-2
EDSIBS-1.0-06/ 2003
L
Preface
Show/Hide Bookmarks
1
Comparison of industrial fieldbus systems
1.3Comparison of industrial fieldbus systems
CAN / CANOpenDeviceNetPROFIBUS-DPAS-iINTERBUSINTERBUS loopLON
Topology
Bus management
Max. number of
Line with termination
resistors
Multi masterSingle masterSingle masterSingle masterSingle masterOnly togeth er with
6464124 (4 segments, 3
devices (master
and slaves)
Max. distance
between devices
without repeater
Max. distance
between devices
with repeater
Transfer medium
Auxiliary energy
supply via bus
Depending on the baud
rate
1 km (50 kBit/s)
25 m (1 MBit/s)
General length reduction
Depending on the
repeater used
Shielded, twisted pair
cable
Possible via additional
wires in the bus cable
cable
Baud rate
Update time
typical (e.g. 8
10 kBit/s - 1 MBit/s125 kBit/s,
approx. 1,32 ms at
1 MBit/s (high priority)
devices, 4 bytes
user data)
Telegram length
0to8bytes0to8bytes0 to 246 bytes4bits1to64bytesdata;
(user data)
Telegram length
(total)
Bus access
methods
106 bits at 8 bytes user
data
CSMA/CA message
oriented
Lenze communication modules for LENZE basic devices
• 9300 Servo
Inverter and
Servo PLC
• 8200 vector
frequency
inverter
• Frequency
inverter 8200
motec
• Drive PLC
• starttec
on board (only parts of
CANopen)
CANopen 2175
(pluggable)
Function module
System bus (only parts
of CANopen)
E82ZAFCC010
E82ZAFCC100 or
E82ZAFCC210
or pluggable 2175
(CANopen)
2171, 2172 (parts of
CANopen)
Function module
System bus (only parts
of CANopen)
E82ZAFCC001
Function module
System bus (only parts
of CANopen)
E82ZAFCC010
or 2175 (pluggable)
Function module
System bus (only parts
of CANopen)
E82ZAFCC001
Line with termination
resistors
100 m (500 kBit/s)
250 m (250 kBit/s)
500 m (125 kBit/s)
not specified10 km (93.75 kBit/s)300 m (2 repeaters)13 km (remote bus),
Shielded, twisted pair
cable
Possible via additional
wires in the bus cable
250 kBit/s,
500 kBit/s
approx. 2.64 ms at 500
kBit/s (high priority)
106 bits at 8 bytes user
data
CSMA/CA message
oriented
2175 (pluggable)2133 (pluggable)not available2111 and 2113 (both
Function module (in
preparation)
Pluggable 2175
(in preparation )Function module
2175 (pluggable)2133 (pluggable)-2111 and 2113 (both
(in preparation )Function module
Line with termination
resistors
repeaters),
max. 32 per segment
1,2 km (93.75 kBit/s)
100 m (12 MBit/s)
Shielded, twisted pair
cable
Possible via additional
wires in the bus cable
9.6 kBit/s - 12 MBit/s167 kBit/s500 kBit/s or 2 M Bit/s500 kBit/s78 kBit/s - 1.25 MBit/s
approx. 2.5 ms at 500
kBit/s
user data +
6to11bytes
Cyclic p ollingCyclic p ollingTime grid / distributed
Function module
E82ZAFIC010 (can b e
integrated) or 2111 or
2113 (both pluggable)
Function module
E82ZAFIC001 (can b e
integrated)
pluggable)
Function module
E82ZAFIC001 (can b e
integrated)
other
INTERBUS-S; single
master (bu s terminal)
32 slaves32385 devices
10 m (max. 100 m cable
length without repeater)
No repeater requiredAlmostany
Unshielded, twisted pair
cable
Currentsupply viadata
cable (approx. 1.5 A)
at least 2 ms (process
data)
1to64bytesdata;
up to 246 bytes
parameters
user data +
6bytes
Time grid / distributed
shift register
2112 (pluggable)2141 (pluggable)
2112 (pluggable)2141 (pluggable)
--
2112 (pluggable)2141 (pluggable)
--
Multi master
distributed to 255
subnetworks with 127
devices each
2kmat78kBit/s
(twisted pair),
6.1 km at 5.48 kBit/s
(optical fibre plastics)
Expandable by
subnetworks (without
repeaters)
Unshielded and
untwisted pair cable
Radio, optical fibre,
power line
Possible via additional
wires in the bus cable
approx.70ms
1 to 228 bytes data;
typically approx. 11
bytes
max. 255 bytes,
user data + 27 bytes
Modified CSMA/CD
1.3
L
EDSIBS-1.0-06/ 2003
1.3-1
Preface
Show/Hide Bookmarks
1
About this Communication Manual
1.4About this Communication M anual
Target group
Contents
This Manual is for all persons who plan a network for a machine and install,
commission and maintain the network.
This Manual only describes Lenze communication modules for a bus system.
This Manual completes the Mounting Instructions coming with the device.
l The features and functions of the communication modules are described in
detail.
l Typical applications are shown by examples.
l It also contains
– safety instructions which must be observed by any means.
– the most important technical data of the communication module.
– versions of the Lenze devices to be used. These devices are servo
inverters, frequency inverters, drive PLCs or motor starters (starttec).
– notes on troubleshooting and fault elimination.
1.4
How to find information
PaperorPDF
This Manual does not describe the software of different manufacturers. We
cannot take any liability for corresponding information given in this Manual.
Information about the use of the software can be obtained from the
documentation for the master.
The theoretical background is only explained if absolutely necessary to
understand a function of the corresponding communication module.
Every chapter is about a certain topic and gives you all necessary information.
l The table of contents and the index help you to find information on a certain
topic.
l Descriptions and data of Lenze products (controllers, Drive PLC, Lenze
geared motors, motors) are available in the corresponding catalogues,
operating manuals and manuals. You can ask your nearest Lenze
representative to send you the corresponding documents or download
them as PDF files from the Internet.
The Manual is a looseleaf binder. Information about news and changes for our
communication modules can be easily exchanged. Every page can be identified
by date and version.
)
)Note!
))
L
Current documentation and software updates for Lenze products
can be found in the Internet under
http:// www.Lenze.com
EDSIBS-1.0-06/ 2003
1.4-1
Preface
Show/Hide Bookmarks
1
Legal regulations
1.5Legal regulations
Labelling
Manufacturer
CE conformity
Application as directed
Lenze fieldbus modules and function modules are unambiguously identified by
their nameplates.
Lenze Drive Systems GmbH, Postfach 101352, D-31763 Hameln
Conforms to the EC Low Voltage Directive
Fieldbus modules or function modules
l must only be operated as described in this Communication Manual and
under the conditions described.
l are accessory modules which are used as option for Lenze controllers and
Lenze Drive PLCs. More information is given in the chapter: Technical Data.
l must be connected and mounted in a way that they comply their functions
whithout being hazardous for persons.
1.5
Observe all notes given in the chapter Safety information.
Please see all notes and information on the corresponding fieldbus module or
function module given in this Communication Manual. This means:
l Read this part of the Communication Manual carefully before you start
working on the system.
l This Communication Manual must always be available while the fieldbus
module or function module is in operation.
Any other use shall be deemed as inappropriate!
L
EDSIBS-1.0-06/ 2003
1.5-1
1
Show/Hide Bookmarks
Preface
1.5
Liability
Legal regulations
The information, data, and notes in this Communication Manual met the state of
the art at the time of printing. Claims on modifications referring to fieldbus
modules/function modules which have already been supplied cannot be derived
from the information, illustrations, and descriptions given in this Manual.
The specifications, processes, and circuitry described in this Communication
Manual are for guidance only and must be adapted to your own specific
application. Lenze does not take responsibility for the suitability of the process
and circuit proposals.
The indications given in this Communic ation Manual describe the features of the
product without warranting them.
Lenze does not accept any liability for damage and operating interference caused
by:
l Disregarding the Communication Manual
l Unauthorized modifications to the fieldbus module or function module
l Operating faults
l Improper working on and with the fieldbus module/function module
Warranty
Disposal
See Sales and Delivery Conditions of Lenze Drive Systems GmbH.
Warranty claims must be made immediately after detecting defects or faults.
The warranty is void in all cases where liability claims cannot be made.
Materialrecycledispose
MetalDPlasticDAssembled PCBs-D
Short Instructions/Operating
3.4Layout of safety notes3.4-1......................................................
3.1
L
EDSIBS-1.0-06/ 2003
3.1-1
Show/Hide Bookmarks
Safety information
Show/Hide Bookmarks
3
Persons responsible for safety
3.2Persons responsible for safety
Operator
Qualified personnel
An operator is any natural or legal person who uses the drive system or on behalf
of whom the drive system is used.
The operator and his safety personnel are obliged
l to ensure the compliance with all relevant regulations, instructions and
legislation.
l to ensure that only skilled personnel works on and with the 2102IB fieldbus
module.
l to ensure that the personnel has the Operating Instructions available for all
corresponding works.
l to ensure that all unqualified personnel are prohibited from working on and
with the drive system.
Qualified personnel are persons who - because of their education, experience,
instructions, and knowledge about corresponding standards and regulations,
rules for the prevention of accidents, and operating conditions - are authorized by
the person responsible for the safety of the plant to perform the required actions
and who are able to recognize potential hazards.
(Definition for qualified personnel to VDE 105 or IEC 364)
3.2
L
EDSIBS-1.0-06/ 2003
3.2-1
Safety information
Show/Hide Bookmarks
3
General safety information
3.3General safety information
l These safety notes do not claim to be complete. In case of questions and
problems please contact your Lenze representative.
l At the time of delivery the communication module meets the state of the art
and ensures basically safe operation.
l The indications given in these Operating Instructions refer to the stated
hardware and software versions of the communication modules.
l The communication module is a source of danger if:
– unqualified personnel works on and with the communication module
– the communication module is used inappropriately.
l The specifications, proc esses, and circuitry described in these Operating
Instructions are for guidance only and must be adapted to your own
specific application.
l Ensure by appropriate measures that neither personal injury nor damage to
property may occur in the event of failure of the communication module.
3.3
l The drive system must only be operated when no faults occur.
l Retrofittings and modifications of the communication module are
prohibited. Lenze must be contacted in all cases.
l The communication module is electrical equipment intended for use in
industrial high-power plants. The communication module must be tightly
screwed to the corresponding controller during operation. In addition, all
measures described in the Operating Instructions of the controller used
must be taken. Example: Fasten covers to ensure protection against
contact.
L
EDSIBS-1.0-06/ 2003
3.3-1
Safety information
{
}
Show/Hide Bookmarks
3
Layout of safety notes
3.4Layout of safety notes
All safety information given in these Instructions have got the same layout:
}
}Signal word! (indicates the severity of danger)
}}
Pictograph
Dangerous electrical voltage
General danger
(
)
Pictograph (indicates the type of danger)
Note (describes the danger and explains how to avoid it)
Signal word
Signal wordMeaning
Danger!Impending danger for personsDeath or most severe injuries
Warning!Possible, very dangerous
situation for persons
Caution!Possible, dangerous situation for
persons
Stop!Possible material damag eDamage of the drive system
Note!Useful note or tip
If you observe it, handling of the
drive system will be easier.
Possible consequences if
the safety information are
disregarded
Death or most severe injuries
Injuries
or its surroundings
3.4
L
EDSIBS-1.0-06/ 2003
3.4-1
Show/Hide Bookmarks
Wiring according to EMC
Show/Hide Bookmarks
4Wiring according to EMC
)
)Note!
))
This topic has not been described yet.
You will be informed as soon as this chapter will be available.
Design:
Ex = Built-in unit IP20
Cx = Cold plate
I=ServoPLC
xK = Cam profiler
xP = Positioning controller
xR = Register controller
xS = Servo inverter
Features
Hardware version
Software version
Variant
Explanation
The fieldbus modle 2113 INTERBUS is
l an attachable intelligent additional module with a 16-bit micro-processor.
l compatible with the Lenze fieldbus module 2111 INTERBUS.
Benefits of the fieldbus module 2113 INTERBUS:
l Communication of 82XX, 8200 vector, 93XX controllers and 9300 servo PLC
via INTERBUS.
l Communication of Lenze Drive PLCs via INTERBUS.
l Bus connection via remote bus according to standard RS485.
l Access to all Lenze parameters.
l BecauseofitsDIPswitchonthefront:
– Choice between DRIVECOM drive profile 21 or device control AIF-CTRL.
– Change of baud rate.
– Change of number of process data words (PD)
– Change of number of parameter data words (PCD).
7.2-2
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Baudrate500kBit/s
Show/Hide Bookmarks
7
Technical data
General data and application conditions
7.3Technical data
7.3.1General data and application conditions
FieldValues
Order numberEMC 2113IB
Communication mediaRS485
Network topologyRing
INTERBUS participantSlave
Communication profilePCP 2.0
Drive profileDRIVECOM profile 21
Baud rate• 500 kBit/s
Ambient temperatureduring operation:
Permissible humidityClass 3K3 to EN 50178
Degree of pollutionVDE0110, part 2, pollution degree 2
EnclosureIP 20
Voltage supply (internal / external),
^ 7.4-5
see
• 2MBit/s
during transport:
during storage
(without condensation, average relative humidity 85%)
External supply via separate power supply unit
(+24 V DC
0 °C
°C
-25
-25
°C
±10 %, max. 120 mA)
7.3
7.3.1
to
to
to
55 °C
70 °C
60 °C
L
EDSIBS-1.0-06/ 2003
7.3-1
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.3
7.3.2
7.3.2Rated data
Technical data
Insulation voltages between incoming bus
and ...
• Reference earth / PE50 V ACMains isolation
• External supply (terminal 39/59)50 V ACMains isolation
• Power stage
– 820X / 821X270 V ACBasic insulation
– 822X / 8200 vector270 V ACDouble insulation
– 93XX270 V ACDouble insulation
• Control terminals
– 820X / 8200 vector
(with internal supply)
– 8200 vector
(with external supply)
– 821X50 V ACMains isolation
– 822X270 V ACBasic insulation
– 93XX270 V ACBasic insulation
– 820X / 821X270 V ACBasic insulation
– 822X / 8200 vector270 V ACDouble insulation
– 93XX270 V ACDouble insulation
• Control terminals
– 820X / 8200 vector
(with internal supply)
– 8200 vector
(with external supply)
– 821X50 V ACMains isolation
– 822X270 V ACBasic insulation
– 93XX270 V ACBasic insulation
• Input bus (IN)50 V ACMains isolation
Rated insulation voltageType of insulation
0VACNo mains isolation
100 V ACBasic insulation
7.3-2
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
(
)
Show/Hide Bookmarks
7
Technical data
Protocol data
7.3.3Protocol data
7.3.3
FieldValues
Maximum number of controllers
Process data words (PD)1 ... 10 (selectable)Default setting: 2 words
Parameter data words (PCP)0, 1, 2, 4Default setting: 1 word
Maximum number of data wordsAs a maximum the data word sum (PD + PCP) is to amount to 10 words.
INTERBUS ID (module ID)
Dependent on INTERBUS master (e.g. Phoenix Contact G4-Master).
For the following data, always the smaller value applies dependent on the
fact, whether PCP communication is available or not:
• With PCP communication:
• Without PCP communication:
Module ID for set length
3
227
224
225
dec
dec
dec
dec
=03
=E3
=E0
=E1
hex
hex
hex
hex
62or
256/number PD
PCP 0 words
PCP 1 word
PCP 2 words
PCP 4 words
7.3
L
EDSIBS-1.0-06/ 2003
7.3-3
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.3
7.3.4
7.3.4Communication times
7.3.4.1Cycle time
The cycle time of a communication system is the time needed to exchange all
process data
to the bus.
It depends on the communication system data and is calculated as follows
(example: baud rate of 500 kbit/s):
í
= Eå + QU + P × _hF × PKPR × NM−P+ MKOQ × i + MKO
ÅóÅä
Fig. 7.3-1 is shows the ratio between cycle time and number of connected
controllers.
The indicated values refer to the connection of Lenze controllers (e. g. 2XX) with
48 data bits (1 parameter data word + 2 process data words, see
Technical data
Communication times
(¶ 7.6-7) between the INTERBUS master and the devices connected
t
cycl
nSum of all data bit in the INTERBUS ring
BTNumber of bus terminals
LLength of remote bus cab le in [km]
Cycletimein[ms]
(¶ 7.3-3).
Cycletime[ms]
NO
NM
U
S
Q
O
N
NM
Number of devices connected to the bus
Fig. 7.3-1INTERBUS cycle time for controllers
OM
PMQM
RMSM
7.3-4
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Technical data
Communication times
7.3.4.2Processing time in the controller
The processing time of the controller is added to the INTERBUS cycle time.
The processing time of the controller depends on the series and version:
Processing t ime 820X
For the 820X series several processing steps are required. These steps are
processed cyclically.
A processing cycle consists of:
l Writing of control word or setpoint, if the value has changed
l Alternating reading of status word and actual value
l Processing of PCP parameter ac cess, if there is a service.
)
)Note!
))
A change of the setpoint signal results in writing the control word.
7.3
7.3.4
Processing t ime 821X /
8200 vector / 822X
If the time tolerances caused by cyclic reading of the status word/ac tual value are
too large, the alternating reading of the status word and the actual value can be
suppressed. This is controlled by bit 15 (PE inhibit) of the DRIVECOM control
(¶ 7.6-36).
word:
A suppression of the processing of parameter access is not necessary, since this
is controlled by the user.
In the following table you will find a list of the processing times:
Processing stepMax. processing time
Parameter70-8Setpoint35-8180
Control word35-8180
Actual value35-8180
Status word35-8180
Setpoint + control word70-16180
Setpoint + control word + actual
value + status word
The parameter data (transmission via PCP channel) and process data are
independent of each other.
l Parameter data (PCP): approx. 30 ms + 20 ms tolerance
l Process data (PD): approx. 3 ms + 2 ms tolerance
[ms]
140-32180
Processing tolerance
[ms]
Additional parameter
[ms]
Processing t ime 9300 servo
inverter
Processing t ime Drive PLC / 9300
Servo PLC
L
The parameter data (transmission via PCP channel) and process data are
independent of each other.
l Parameter data (PCP): approx. 30 ms + 20 ms tolerance
l Process data (PD): approx. 2 ms + 1 ms tolerance
l Parameter data (PCP): 30 ms + 20 ms tolerance
l Process data (PD): depending on process image
EDSIBS-1.0-06/ 2003
7.3-5
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.3
7.3.5
7.3.5Dimensions
Drivecom
Length
Baud
PCP
PD
OPEN
12345678
Bus
Drive
L
2113
a
INTERBUS
24V DC
_
+
b
OUT
IN
a61mm
b75mm
e28mm
e118 mm
18
Technical data
Dimensions
e1
e
2113IBU013
7.3-6
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
0
1
SLOW(1Hz)
dPC
P
S()oypocessdata
–indicatesinadmissiblesettings:
–
Show/Hide Bookmarks
7
Installation
Components of the fieldbus module
7.4Installation
7.4.1Components of the fieldbus module
Fig. 7.4-1Components of the fieldb us module
PosLED status Explanation 24
0
1
Green bus LED (voltage supply)
ONThe fieldbus module is supplied with voltage and is connected to the drive controller.
OFFThe fieldbus module is not supplied with voltage. The drive controller or external voltage
supply is switched off.
BLINKINGThe fieldbus module is supplied with voltage, but it is not connected to the drive
controller, because
• the fieldbus module was not plugged on the drive controller correctly
• the data transfer of/to the drive controller is not possible (e. g. the drive controller is
in the initialisation phase).
Yellow bus LED (communication)
ONFieldbus module is initialised,
inactive INTERBUS communication of the master
OFFFieldbus module is not initialised yet
BLINKINGActive INTERBUS communication
•
• FAST (4 Hz): only process data
• VERY FAST (8 Hz)
:processdata an
7.4
7.4.1
2113IBU001
communication.
L
2
4
5
6
7
8
)
)Note!
))
Red and green drive LED indicate the operating mode of the drive controller 82XX or 93XX (see the
Operating Instructions of the drive controller)
INTERBUS output (OUT), Sub-D socket connector, 9-pole
INTERBUS input (IN), Sub-D plug connector, 9-pole
PE connection
Fixing screw
Plug connector, connection for external voltage supply^ 7.4-4
Only for 820X and 821X: If required use an additional PE screen
cable which avoids EMC-related communication interference in
surroundings with interferences.
EDSIBS-1.0-06/ 2003
Datawordsum:PD+PCP>10ornumber of process data words: PD = 0.
The fieldbus module goes on working internally with the following values:
PD=2andPCP=1
^ 7.4-7
^ 7.4-6
see note
7.4-1
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.4
7.4.2
7.4.2Mechanical installation
l Plug the fieldbus module onto the basic device (here: 8200 vector).
l Fasten the fieldbus module with the fixing screw onto the basic device to
ensure a good PE connection.
Installation
Mechanical installation
25 2102LEC014
)
)Note!
))
For the internal supply of the fieldbus module through the 8200
vector frequency inverter the interface of the jumper must be
adapted (see illustration above). Please observe the notes
^ 7.4-5.
7.4-2
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Installation
Electrical installation
7.4.3Electrical installation
Wiring to the INTERBUS master
)
)Note!
))
l The bus system must be designed as a ring.
7.4
7.4.3
An additional mains isolation is required, if
l an 820X or 821X is connected to an INTERBUS master and
l a safe mains isolation (double basic insulation) is required
according to VDE 0160.
Use e.g. a bus terminal or an interface module for the INTERBUS
master with an additional mains isolation (see the corresponding
information of the manufacturer).
The incoming bus (IN) is isolated from the supply voltage and the
outgoing bus (OUT).
The supply voltage has the same potential as the outgoing data
bus (OUT).
Wiring example
l Go-and-return lines are both in the same bus cable.
l The ring connects the INTERBUS master with all devices connected to the
bus.
1
3.2
400 m
2
Fig. 7.4-2Wiring examp le, INTERBUS (baud rate 500 kbit/s)
4.2
3.2
3.1
8200 vector
+
2113
4.1
82XX
+
2112
4.24.24.2
20 m
INTERBUS-Loop 200 m
400 m
93XX
2112
3.1
93XX
+
2113
+
3.23.2
3.1
82XX
+
2111
4.14.1
8200 vector
2112
3
+
4
2131IBU003
L
EDSIBS-1.0-06/ 2003
7.4-3
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.4
7.4.3
Installation
Electrical installation
Pos.ElementExplanation
1INTERBUS master with
interface module
2INTERBUS loop bus
terminal
3Remote bus
Fig. 5.4-2 Pos. 3
3.1Long distance bus module Bus participant in the long distance bus; e.g. Lenze controller with INTERBUS
3.2Remote bus cableConnects the INTERBUS master interface module with the bus terminal and/or
4INTERBUS loop,
peripheral bus
Fig. 5.4-2 Pos. 4
4.1INTERBUS loop moduleBus participant in the INTERBUS loop; e.g. Lenze controller with INTERBUS loop
4.2INTERBUS loop cableConnection within the loop
Features:
Communication mediumRS485
Network topologyRing
Maximum number of
controllers
Baud rate / cable length
The bus system is a master-slave system, i.e. an INTERBUS master is connected
to several field devices (slaves).
The bus terminal connects a long distance bus to a peripheral bus.
The following connections are possible with remote buses:
• Connections between INTERBUS master interface module and first bus
terminal or first 2113 fieldbus module.
• Connection between bus terminal and 2113 fieldbus module
• Connection between two 2113 fieldbus modules
module (slave). Networking does not require bus terminals.
the long distance bus modules.
Connection in a peripheral-bus station
A peripheral-bus station consists of:
• a bus terminal (Fig. 5.4-2 pos. 2)
• up to eight peripheral bus modules (Fig. 5.4-2 pos. 3)
module 2112
Dependent on INTERBUS master (e.g. Phoenix Contact G4-Master).
For the following data, always the smaller value applies dependent on the fact, whether
PCP communication is available or not:
• With PCP communication:62or
• Without PCP communication:256/number PD
Baud rateMaximum cable length between
neighbouring participants
500 kBit/s400 m
2MBit/s150 m
External DC voltage supply 27
Specification of INTERBUS remote bus cable 26
Cable typeYard goods:
Number of conductors3 x 2, paired with common shielding
Conductor cross-section>0.2mm
DC cable resistance<96Ω/km
Impedance, characteristic120 Ω±20 % (f = 64 kHz)
Capacitance per unit length< 60 nF/km (f = 800 Hz)
Basic devices with extended AIF interface opening (8200 vector
front) can be internally supplied. The part of the drawing
highlighted in grey shows the jumper position.
l In the delivery state of the frequency inverter these are not
internally supplied.
l For internal voltage supply, put the jumper in the position
indicated below.
rigid: 1.5 mm2(AWG 16)
flexible:
without wire crimp cap
2
(AWG 16)
1.5 mm
with wire crimp cap, without plastic sleeve
Conditions for setting through the INTERBUS master:
Switch S1 ... S7 = OFF
l The configurations set for the codes L-1910, L- 1911 and
L-1912
l The settings can be changed.
l Switch off the voltage supply of the fieldbus module and
afterwards on again, in order to activate changed settings.
As a maximum the data word sum (PD + PCP) is to amount to 10
words.
Index detection: 24575 - Lenze code number (L-C xxxx )
Impermissible settings are indicated by the yellow bus LED
(communication)
get active with switching on.
(¶ 7.4-1).
Commissioning
Possible settings with INTERBUS master
Display codes
CodeValuesExplanation
L-C19102 ... 20 (1 ... 10 words)Number of process data bytes
L-C1911
L-C1912
CodeExplanation
L-C1915Display of the current switch positions S1 ... S4 for number of process data words
-L-
0: Device control AIF-CTRL
1: DRIVECOM control
Number of parameter
data words (PCP)
03
1E3
2E0
4E1
ay ofthe current position ofswitc
ID code
hex
hex
hex
hex
7.
(2 Process data bytes = 1 Process data word)
Operation with device control AIF-CTRL or
operation with DRIVECOM-Profil 21
Number of parameter data words (PCP)
.
7.5-4
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Commissioning
Ensure that the settings match the 2111 fieldbus module
7.5.4Ensure that the settings match the 2111 fieldbus module
Drivecom
Length
Length
PD
12345678
S1 ... S8Explanation
OFF
(Lenze setting)
OPEN
PCP
Baud
OFF
ON
The response is the same as of the Lenze fieldbus module “2111 INTERBUS”, if the
Lenze setting for the switches (S1 - S7 = OFF) and
L-C1912 = 1 remain unchanged.
7.5.5Commissioning of 2113 fieldbus module
1. The fieldbus module must be attached to the controller (¶ 7.4-2).
2. The controller and if available the separate voltage supply for the 2113
fieldbus module must be switched on.
7.5
7.5.4
2113IBU005
codes L-C1910 = 4, L-C1911 = 1 and
3. Check fieldbus module signals:
– The green bus LED indicates the operating status according to the
corresponding description
– The yellow bus LED indicates the communication status according to the
description
– Quick blinking (8 Hz) is the reaction of the yellow bus LED to
impermissible settings. Please see chapter 7.7, ”Troubleshooting and fault
elimination”.
4. You can now communicate with the drive.
– With a PCP communication it is only possible to acc ess the parameters of
the controller after having executed the PCP service ”Initiate“
5. It is then possible to access the parameters via the PCP services ” Read“
and ” Writ e“
(¶ 7.4-1) Pos. 1.
(¶ 7.6-50).
(¶ 7.4-1) Pos. 0.
(¶ 7.6-50).
L
EDSIBS-1.0-06/ 2003
7.5-5
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.5
7.5.6
Prepare controller for INTERBUS operation
7.5.6Prepare controller for INTERBUS operation
82XX / 8200 vect or
PreparationNotes
1. L-C0001 (operating mode):
Change value from “0” to “3”
.
2. Terminal 28 (controller
enable) must be HIGH during
INTERBUS operation.
Terminal 28 is always
active!
The controller is now ready to accept process and parameter data from the INTERBUS.
For this use
• the 8201BB for 82XX and
• the keypad for 8200 vector
Alternative
Direct access to the code via INTERBUS.
Example
Set code L-C0001 to “3” (PCP write):
à For conversion formula and parameter value range see ^ 7.6-47
8200 vector (up to SW version 1.1)
à C0410/y (y = 1...16) must be assigned to the AIF control word (AIF-CTRL)
Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for the
controller).
821X, 8200vector un d 822X
With these controllers the QSP function is always active. If QSP is assigned to an
input terminal (default setting: not assigned), this terminal must be at HIGH level
during INTERBUS operation (see the corresponding Operating Instructions).
:
– Index: 5FFE
– Subindex: 0
– Value: 30000
i.e. C0410/1 = 10, C0410/2 = 11 .... C0410/16 = 25 (see Operating
Instructions for 8200 vector).
hex
dec
(= 5FFF
− (L-C0001)
hex
hex
Commissioning
)
93XX controllers
PreparationNotes
1. L-C0005: Set “xxx3”.Use the 9371BB keypad
Alternative:
Direct access to the code via INTERBUS.
For the first commissioning you should select the signal configuration 1013 (speed
control).
Example
Set code L-C0005 to “1013” (PCP write):
– Index: 5FFA
– Subindex: 0
– Value: 10130000
à For conversion formula and parameter value range see ^ 7.6-47
2. L-C0142 (autostart lock):
Set “0”.
3. Terminal 28 (controller
enable) must be HIGH during
INTERBUS operation.
Terminal 28 is always
active!
The controller is now ready to accept process and parameter data from the INTERBUS.
Only necessary with DRIVECOM control
Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for 93XX).
à With the signal configuration L-C0005=1013, the function QSP (quick stop) and
the CW/CCW changeover are assigned to the digital input terminals E1 and E2
and thus they are always active. For INTERBUS operation E1 must be set to
HIGH level (see Operating Instructions 93XX).
à With the signal configuration L-C0005=xx13, terminal A1 is switched as
voltage output. Thus, only the following terminals can be connected via cables:
– X5.A1 with X5.28 (ctrl. enable)
– X5.A1 with X5.E1 (CW/QSP)
hex
(5FFF
dec
− (L-C0005)
hex
hex
)
7.5-6
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Commissioning
Controller enable via D RIVECOM
7.5.7Controller enable via DRIVECOM
Controllers can be c ontrolled with DRIVECOM process data. The INTERBUS
master has direct access to the process data. In the INTERBUS master, data are
stored in the I/O area.
l Controller enable: DRIVECOM process data word ” Control word”
l Display of actual controller status: DRIVECOM process data word ” Status
word”.
The controller can be enabled by changing to OPERATION ENABLED by means
of the DRIVECOM control word.
Afterwards, the controller can be controlled as usual, e.g. via terminals.
)
)Note!
))
If DRIVECOM control is active and the fieldbus module
l in the controller
– 82XX / 8200 vector “controller inhibit” will be activated if
L-C0001 = 3.
– 93XX “Controller inhibit” will always be active.
l the fieldbus module sets SWITCH ON INHIBIT.
7.5
7.5.7
Enable the controller as follows:
1. Select speed setpoint (2nd process data word; PD2), value
2. Change to ” READY FOR SWITCH ON“
PD output word1 = 0000 0000 0111 1110
3. Wait for the status ” READY FOR SWITCH ON“.
PD input word1 = xxxx xxxx x01x 0001
The DRIVECOM profile 21 is a specification of important parameters and unit
performance of several manufacturers. The DRIVECOM profile 21 mainly
describes the unit control and a speed operating mode. In addition to the
DRIVECOM specifications there are further Lenze-specific functions, e.g.
digital-frequency connection or DC injection-brake. Thesemanufacturer-specific
specifications require minor changes in the settings to comply with the desired
DRIVECOM compatibility. In the following, you will find the changes required for
the Lenze controllers.
820XWith 820X controllers, parameters can only be set when the controller is inhibited.
821X,
8200 vector
and 822X
93XXSet the controller parameters for INTERBUS control, e.g. L-C0005=1013
9300 Servo
PLC
Drive PLCIt is necessary to use the device control for the DRIVE PLC.
Commissioning
DRIVECOM compatibility
The controller is inhibited in DRIVECOM status.
• ”SWITCH-ON INHIBIT”
• ”READY FOR SWITCH ON”
• ”SWITCHED ON”
• ”TRIP”
The automatic DC-injection brake must be deactivated in all parameter sets, i. e.
• L-C0106=0
• L-C2106=0
• L-C4106=0 (only 8200 vector)
• L-C6106=0 (only 8200 vector)
If the automatic DC-injection brake is not deactivated (holding time of the DC-injection brake L-C0106
not 0), the controller automatically switches from the status ”OPERATION ENABLED” to the status
”SWITCHED ON” when the speed is 0 and the holding time of the DC-injection brake is elapsed. If the
setpoint is higher than 0, the controller is automatically reset to the status ”OPERATION ENABLED”.
This configuration corresponds to the signal configuration 1000 with the following changes:
• Setpoint selection with INTERBUS
• Unit control with INTERBUS
• Output X5.A1 is selected as voltage output for the internal supply of the digital inputs.
• Actual values and status signals for INTERBUS
For the detailed description of the signal configuration, see 93XX Manual.
The following links must be made in the PLC program.
• AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
• DCTRL_wStat W AIF1_wDctrlStat
7.5-8
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Commissioning
Special features when using 82XX, 8200 vector and 93XX
7.5.9Special features when using 82XX, 8200 vector and 93XX
}
}Danger!
}}
Please note
l For safe operation it is absolutely necessary to observe the
notes for the controllers given in this chapter.
l Please observe the corresponding Operating Instructions of the
controllers.
820X• Parameter setting (codes except process data) is only possible when the controller is inhibited
8200 vector • Digital and analog input and output signals can be freely configured (see Operating Instructions for
93XX• Set the signal configuration L-C0005 = xxx3 instead of the operating mode L-C0001.
(DRIVECOM controller status unequal ”OPERATION ENABLED“). Parameters are accepted when the
controller is enabled, but they are not saved.
• A TRIP must only be reset through INTERBUS:
If the controller is set to the status TRIP while being operated with INTERBUS control
(L-C0001 = 3) and if the TRIP is reset through terminal 28, t he drive can start for a short time.
When resetting a fault via INTERBUS, this does not occur.
• After the command ”TRIP reset“ the 820X controller is basically initialized. During this time the
controller does not accept any services.
• Always send the direction of rotation with a low setpoint before the new setpoint:
If the setpoint and the direction of rotation are changed at the same time via the DRIVECOM speed
setpoint, the speed can change to the wrong direction or rotation for a short time. This is because
the setpoint is sent to the controller as unipolar value before and the information about the
direction of rotation is sent.
8200 vector; codes L-C0410, L-C0412, L-C0417 and L-C0421)
• A change of code L-C0001 to “3“ preconfigures the process data words in the controller.
• The change of the code L-C0005 t o xxx3 starts the preconfiguration of the process data words in
the controller
• Set the parameter L-C0142 = 0 (auto start lock), to avoid a short time start of the drive during the
initialization phase.
7.5
7.5.9
L
EDSIBS-1.0-06/ 2003
7.5-9
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
7.6Data transfer
7.6
INTERBUS master and slave communicate by sending data telegrams via the
INTERBUS.
The user data of the data telegram contains parameter data
Different communication channels are assigned to parameter and process data:
Telegram typeCommunication channel
Process data,
• Setpoints
• Actual values
Parameter data
• Operating parameters
• diagnostics information
• motor data
Tab. 7.6-1Division of p arameter data and proc ess data into different communic ation channels
The following describes the communication protocol only as much as needed for
networking Lenze controllers.
Process-data channel• Exchange between INTERBUS master and
Parameter data channel
or “PCP channel”
(PCP = Peripherials
Communication Protocol)
controller required as fast as possible. Small
amounts of data for cyclic data transfer.
• The INTERBUS master has direct access to the
process data.
• Process data can control the controller.
• Process data are
– not stored in the controller.
– exchanged between INTERBUS master and
controllers to ensure a constant update of
input and output data.
• In general, the parameter transfer is not as
time-critical as the tranfer of process data.
• Enables access to all Lenze codes and indexes.
or process data.
L
EDSIBS-1.0-06/ 2003
7.6-1
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.1
7.6.1Process data channel configuration
7.6.1.1Process data transfer
Process data telegrams between INTERBUS master and the controllers
connected to the INTERBUS are divided into:
l Process data telegrams from drive (PI)
l Process data telegrams to drive (PO)
)
)Note!
))
As agreed, the data flow is described from the INTERBUS
master’sview:
l PI data of the INTERBUS master are output data for the
controller.
l PO data of the INTERBUS master are input data for the
controller.
Data transfer
Process data channel configuration
Process data telegram from
drive
Process data telegram to
drive
For the cyclic process data telegram from
is called AIF-OUT. The status word included in the process data telegram (byte
1 and byte 2) is sent to the INTERBUS master via this function block.
For the cyclic process data telegram to
is called AIF-IN. The control word included in the process data telegram (byte 1
and byte 2) is sent to the INTERBUS master via this function block.
the drive, the function block to be used
the drive, the function block to be used
7.6-2
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data channel configuration
7.6.1.2Setpoint source selection
82XX controllers
Controller 8200 vector
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
is set to ”3” whenthecontroller is operated togetherwiththefieldbusmodule.The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
)
)Note!
))
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
is set to ”3” whenthecontroller is operated togetherwiththefieldbusmodule.The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
7.6.1
).An evaluation of process data isonly possible if c ode L-C0001
hex
.
Please ensure that the setpoint source (L-C0001) is the same for
all parameter sets used.
).An evaluation of process data isonly possible if c ode L-C0001
hex
.
7.6
93XX controllers
Servo PLC 9300 / Drive PLC
Check in L-C0412/x whether the assignment of setpoint source and analog signal
is correct and change, if necessary.
)
)Note!
))
Please ensure that the setpoint source selection (L-C0001) is the
same for all parameter sets used.
The value in code C0005 must be set to ”xxx3” for bus operation (x = selected
preconfiguration).
Communication requires that AIF-IN 1 ... 3 or AIF-OUT 1 ... 3 and if available
AIF management are part of the control configuration of the IEC61131 project.
the
L
EDSIBS-1.0-06/ 2003
7.6-3
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.1
7.6.1.3Process data configuration
Some data important for the process must be transmitted as quickly as possible.
These data are called process data and stored in the I/O area of the controller for
access from the INTERBUS master.
The process data are cyclic ally exchanged between the controller and the
INTERBUS master.
Theprocess data of a Process-data configurationhave a certain ”Process data
structure“.
The process-data structure is subdivided into
l Process input data (PI data, index = 6000
l Process output data (PO data, index = 6001
The controller receives control information from the INTERBUS master and sends
status information to the master.
The Lenze setting for the process-data length is 4 byte.
The PD length settings are made by means of
Data transfer
Process data channel configuration
, (¶ 7.6-5))
hex
, (¶ 7.6-6))
hex
– DIP switch
– Code L-C1910
The contents of code L-C1910 is overwritten when the DIP switch is used
because the DIP switch settings have higher priority.
)
)Note!
))
(¶ 7.5-2) or
(¶ 7.5-4).
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering 0 under L-C1911 or
the front.
Different controller signals can be assigned to the PI and PO data
words (see
(¶ 7.6-7)).
using the switch S7 at
7.6-4
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data channel configuration
PI data description (6000
hex
)34
The parameter describes the process data which are sent from the controller to
the INTERBUS master (input data for the INTERBUS master). Paramters of the
described process data assignment of Lenze controllers can be assigned to the
sub-index values (see
changed.
Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).
Parameter name (Index)SubindexData structureData type
PI data description (6000
)
)Note!
))
(¶ 7.6-7)). Exception: The value for subindex 1 cannot be
)1 ... 41RPBS(20
hex
hex
)
Only the valid subindex is displayed with the parameter 6000
It is determined by PD!
7.6.1
hex
7.6
.
SubindexMeaningValueLenze setting
1Number of process data [byte]PD S 2
2Index PI data word 16041
3Subindex PI data word 100
4/5No entry00
6Index PI data word 26044
7Subindex PI data word 200
8/9No entry00
10Index PI data word 35CA5
11Subindex PI data word 302
12/13No entry00
14Index PI data word 45CA5
15Subindex PI data word 403
16/17No entry
18Index PI data word 55CA5
19Subindex PI data word 504
20/21No entry
22Index PI data word 65CA5
23Subindex PI data word 605
24/25No entry
26Index PI data word 75CA5
27Subindex PI data word 706
28/29No entry
30Index PI data word 85CA5
31Subindex PI data word 807
32/33No entry
34Index PI data word 95CA5
35Subindex PI data word 908
36/37No entry
38Index PI data word 105CA5
39Subindex PI data word 1009
40/41No entry
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
DRIVECOM status word
DRIVECOM speed
AIF-OUT.W2
AIF-OUT.W3
AIF-OUT.W4
AIF-OUT.W5
AIF-OUT.W6
AIF-OUT.W7
AIF-OUT.W8
AIF-OUT.W9
L
EDSIBS-1.0-06/ 2003
7.6-5
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.1
PO data description (6001
hex
)35
Data transfer
Process data channel configuration
The parameter describes the process data which are sent to the controller from
theINTERBUSmaster(output data for the INTERBUS master). Parameters of the
described proc ess data of Lenze controllers can be assigned to subindex values
(¶ 7.6-7)). Exception: The value for subindex 1 cannot be changed.
(see
Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).
Parameter name (Index)Subindex Data s tructureData type
PO data description (6001
SubindexMeaningValueLenze settingIndex 6002/
1Number of process data [byte]PD S 2
2Index PO data word 16040
3Subindex PO data word 100
4/5No entry001
6Index PO data word 26042
7Subindex PO data word 200
8/9No entry003
10Index PO data word 35CA7
11Subindex PO data word 302
12/13No entry005
14Index PO data word 45CA7
15Subindex PO data word 403
16/17No entry7
18Index PO data word 55CA7
19Subindex PO data word 504
20/21No entry9
22Index PO data word 65CA7
23Subindex PO data word 605
24/25No entry11
26Index PO data word 75CA7
27Subindex PO data word 706
28/29No entry13
30Index PO data word 85CA7
31Subindex PO data word 807
32/33No entry15
34Index PO data word 95CA7
35Subindex PO data word 908
36/37No entry17
38Index PO data word 105CA7
39Subindex PO data word 1009
40/41No entry19
)1 ... 41RPBS(20
hex
DRIVECOM control word0
hex
DRIVECOM speed setpoint2
hex
AIF-IN.W24
hex
hex
AIF-IN.W36
hex
hex
AIF-IN.W48
hex
hex
AIF-IN.W510
hex
hex
AIF-IN.W612
hex
hex
AIF-IN.W714
hex
hex
AIF-IN.W816
hex
hex
AIF-IN.W918
hex
hex
hex
)
Bit
7.6-6
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
7.6.2Process data signals of Lenze controllers
7.6.2.1Process data signals for frequency inverters 82XX
Process data telegram from
drive
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindex NameExplanationLenze setting:
60410DRIVECOM status wordPI data word 1^ 7.6-39
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 7.6-42
60540DRIVECOM actual
percentage value
5F690Device status word
(L-C0150)
5CA51AIF-OUT.W1AIF word 1
Actual speed [%]
100% = 16383
Index 6000
7.6
7.6.2
see
hex
^ 7.6-43
Table below
L
EDSIBS-1.0-06/ 2003
7.6-7
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Device status word AIF-STAT for 82XX (Lenze code C0150, index 5F69
Bit820X821x, 822x
0Actual parameter set0=Parameterset1or3active
1=Parameterset2or4active
1IMP (pulse inhibit)0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
2I
(current limit reached)0 = Current limit not reached
max
1 = Current limit reached
3not assignedfd=f
4fd=f
5Qmin (f
dset
≤ f
)0 = Qmin not active
d
dQmin
6fd+ 0 (act. frequency = 0)0=f
0=f
≠ f
d
dset
1=fd=f
dset
1=Qminactive
≠ 0
d
+0
1=f
d
7Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
1 = Controller inhibited
8...11 Controller status0 = Unit initialisation
8=Erroractive
12Overtemperature warning0=Nowarning
1=Warning
13V
(DC-bus overvoltage)0 = No overvoltage
Gmax
1 = Overvoltage
14Direction of rotation0 = CW rotation
1 = CCW rotation
15Ready for operation0 = Not ready for operation
1 = Ready for operation
hex
Process data signals of Lenze controllers
)
Actual parameter set0=Parameterset1or3active
IMP (pulse inhibit)0 = Pulses for power stage enabled
I
(current limit reached)0 = Current limit not reached
max
dset
RFG on = RFG off0=RFGon≠ RFG off
Qmin (f
d
fd+ 0 (act. frequency = 0)0=f
Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
Controller status0 = Controller initialization
Overtemperature warning0=Nowarning
V
(DC-bus overvoltage)0 = No overvoltage
Gmax
Direction of rotation0 = CW rotation
Ready for operation0 = Not ready for operation
1=Parameterset2or4active
1 = Pulses for power stage inhibited
1 = Current limit reached
0=f
1=fd=f
1 = RFG on = RFG out
≤ f
)0 = Qmin not active
dQmin
1=Qminactive
1=f
1 = Controller inhibited
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
1=Warning
1 = Overvoltage
1 = CCW rotation
1 = Ready for operation
Data transfer
≠ f
d
dset
dset
≠ 0
d
+0
d
- / fd=fdset
fd=fdset / RFG
ctrl. inhibit
B11 B10 B9 B8
0
0
0
1
0
0
1
0
0
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
PAR
IMP
Imax
Qmin
fd>0
STAT
0
0
2
0
3
1
.
.
.
.
.
.
Vgmax
RDY
C0050
.
.
.
.
.
.
T
R/L
.B0
.B1
.B2
.B3
.B4
.B5
.B6
.B7
.B8
16 bits
.B9
.B10
.B11
ü
.B12
.B13
.B14
.B15
AIF
16 bits
2141LON012_en
Fig. 7.6-1Read access to status word and actual frequency in 82XX (fixed assignment)
7.6-8
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Process data telegram to drive
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindex NameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 7.6-36
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
1AIF-IN.W1AIF word 1. See the
5CA7
)
)Note!
))
7.6.2
Index 6001
setpoint
setpoint
(L-C0135)
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering 0 under L-C1911 or
the front.
Speed setpoint [rpm] PO data word 2^ 7.6-42
Speed setpoint [%]
100% = 16383
following description.
hex
using the switch S7 at
see
^ 7.6-43
Table below
7.6
L
EDSIBS-1.0-06/ 2003
7.6-9
7
0
0,0
1
01JOG1activeinC0037
R
d
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Control w ord AIF- CTRL for 82XX (Lenze code C0135, index 5F78
Bit820X821x, 822x
00 = C0046 active
01 = JOG1 active in C0037
10 = JOG2 active in C0038
11 = JOG3 active in C0039
02CW/CCW (CW rotation/
03QSP (quick stop)0 = QSP not active
04RFG stop (stop of the ramp function generator)0 = RFG stop not active
05RFG zero (deceleration along the Tiframp C0013)0 = RFG zero not active
06
07DOWN function for motor potentiometer0 = DOWN not active
08Reserved
09Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
10
11
12PAR1 (Parameter set changeover)0 -> 1 = Parameter set
13ReservedReserved
14DC brake (DC injection brake)0 = DC brake not active
15ReservedReserved
CCW rotation)
Reserved
eserve
0 = CW rotation
1 = CCW rotation
1=QSPactive
1 = Controller inhibited
1 -> 0 = Parameter set
1 = DC brake active
)
hex
00 = C0046 active
01 = JOG1 active in C0037
10 = JOG2 active in C0038
11 = JOG3 active in C0039
CW/CCW (CW rotation/CCW rotation)0 = CW rotation
QSP (quick stop)0 = QSP not active
UP function for motor potentiometer0=UPnotactive
Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
Reserved
TRIP reset0 -> 1 = Edge from 0 to 1
PAR1 (Parameter set changeover)0 -> 1 = Parameter set
DC brake (DC injection brake)0 = DC brake not active
Process data signals of Lenze controllers
Data transfer
1 = CCW rotation
1=QSPactive
1=RFGstopactive
1=RFGzeroactive
1=UPactive
1 = DOWN active
1 = Controller inhibited
1 -> 0 = Parameter set
1 = DC brake active
AIF
16 bits
16 bits
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B12
.B13
.B14
.B15
0
011
JOG/
C046
0101
QSP
...
...
...
CINH
TRIP-SET
TRIP-RESET
C0046
Fig. 7.6-2Access to control word and ac tual frequency in 82XX (fixed assignment)
CW/
CCW
PAR
DC
brake
2141LON010_en
7.6-10
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
C
A
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
7.6.2.2Process data signals for 8200 vector frequency inverters
The function block AIF (AIF=automation interface) is the data interface between
the 8200 vector and the fieldbus module. The function block consists of AIF-OUT
and AIF-IN.
Process data telegram from
drive
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindexNameExplanationLenze setting:
60410DRIVECOM status wordPI data word 1^ 7.6-39
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 7.6-42
60540DRIVECOM actual
5F690Device status word
1AIF-OUT.W1AIF word 1
5
5
2AIF-OUT.W2AIF word 2PI data word 3
AIF-OUT.Wx is parameterised under code L-C0421.
percentage value
(L-C0150)
Actual speed [%]
100% = 16383
Index 6000
7.6
7.6.2
see
hex
^ 7.6-43
Table below
L
EDSIBS-1.0-06/ 2003
7.6-11
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Controller status word AIF-STAT for 8200 vector (Lenze code C0150, index 5F69
AIF-STAT.BxxLenze settingAdjustable in code L -0417/..
0 = Controller initialization
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
12DCTRL1-OH-WARN13
13DCTRL1-OV14
14DCTRL1-CCW15
15DCTRL1-RDY16
Process data signals of Lenze controllers
)
hex
Reserved
Data transfer
C0417/1
DCTRL1-IMP
C0417/3
C0417/4
C0417/5
C0417/6
DCTRL1-NOUT=0
DCTRL1-CINH
DCTRL1-STAT*1
DCTRL1-STAT*2
DCTRL1-STAT*4
DCTRL1-STAT*8
DCTRL1-OH-WARN
DCTRL1-OV
C0417/15
C0417/16
C0421/1
C0421/2
STAT1
AIF-OUT.W1
AIF-OUT.W2
.B0
.B1
.B2
.B3
.B4
.B5
.B6
.B7
.B8
.B9
.B10
.B11
.B12
.B13
.B14
.B15
AIF-OUT
.B0
.B1
.B2
.B3
.B4
.B5
.B6
.B7
.B8
AIF-STAT
.B9
16 bits
.B10
.B11
.B12
.B13
.B14
.B15
16 bits
16 bits
Fig. 7.6-3Function block AIF-OUT in 8200 vector (freely p rogrammable assignment)
AIF
2141LON013_en
7.6-12
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
C
A
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Process data telegram to drive
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindexNameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 7.6-36
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
1AIF-IN.W1AIF word 1
5
7
2AIF-IN.W2AIF word 2
AIF-IN.Wx is parameterised under code L-C0412.
setpoint
setpoint
(L-C0135)
Index 60001
Speed setpoint [rpm]PO data word 2^ 7.6-42
Speed setpoint [%]
100% = 16383
Frequency and speed
are normalised with
24000 ≡ 480 Hz.
PO data word 3
Frequency and speed
are normalised with
24000 ≡ 480 Hz.
hex
see
^ 7.6-43
Table below
7.6
7.6.2
)
)Note!
))
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering 0 under L-C1911 or
the front.
using the switch S7 at
L
EDSIBS-1.0-06/ 2003
7.6-13
7
00,
01NSET1JOG1(C0037)activ
e
1
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Control w ord AIF- CTRL for 8200 vector (Lenze code C0135, index 5F78
AIF-CTRL.BxxDefault setting:
00,
01
02DCTRL1-CW/CCW0=notactive
03AIF-CTRL-QSP0=notactive
04NSET1-RFG1-STOP0=notactive
05NSET1-RFG1-00=notactive
06MPOT1-UP0=notactive
07MPOT1-DOWN0=notactive
08Freely configurable by user9
09AIF-CTRL-CINH0=notactive
10AIF-CTRL-TRIP-SET0=notactive
11AIF-CTRL-TRIP-RESET0 -> 1 = Edge from 0 to 1 AIF-CTRL-TRIP-RESET0 -> 1 = Edge from 0 to 1 12
12DCTRL1-PAR2/40=notactive
13DCTRL1-PAR3/40=notactive
14MCTRL1-DCB0=notactive
15Freely configurable by userFreely configurable by user16
00 = C0046 active
01 = NSET1-JOG1 (C0037) active
10 = NSET1-JOG2 (C0038) active
11 = NSET1-JOG3 (C0039) active
C0001=3 if C0007
≤ 51
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
Freely configurable by user
AIF-CTRL-QSP0=notactive
Freely configurable by user
AIF-CTRL-CINH0=notactive
AIF-CTRL-TRIP-SET0=notactive
Freely configurable by user
Process data signals of Lenze controllers
)
hex
Default setting:
C0001=3 if C0007 > 51
1=active
1=active
1=active
Data transfer
Adjustable in L-C0410/..
1
2
3
4
5
6
7
8
10
11
13
14
15
AIF
AIF-CTRL
16 bits
16 bits
16 bits
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B12
.B15
AIF-IN
DCTRL
QSP
...
...
...
...
...
...
Fig. 7.6-4Function block AIF-IN in 8200 vector (freely programmable assignment)
...
...
...
DCTRL
CINH
TRIP-SET
TRIP-RESET
...
...
...
AIF-IN.W1
AIF-IN.W2
2141LON011_en
7.6-14
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
7.6.2.3Process data signals for servo inverters 9300
The function block AIF (AIF=automation interface) is the data interface between
the 93XX controller and the fieldbus module. The function block consists of
AIF-OUT and AIF-IN.
With the 93XX controller the process data assignment can be changed by
reconfiguring the function blocks AIF-IN and AIF-OUT.
7.6
7.6.2
L
EDSIBS-1.0-06/ 2003
7.6-15
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Process data telegram from
drive
Data transfer
Process data signals of Lenze controllers
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindexName
60410DRIVECOM status wordPI data word 1^ 7.6-39
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 7.6-42
60540DRIVECOM actual
5F690Device status word
5CA51AIF1-OUT.W1AIF word 1
5CA52AIF1-OUT.W2AIF word 2PI data word 3
5CA53AIF1-OUT.W3AIF word 3PI data word 4
5CA40AIF1-OUT.D1AIFdoubleword
(same in IEC1131)
percentage value
(AIF1_Stat)
The assignment of AIF-OUT depends on the signal configuration selected under
L-C0005:
Signal
configuration
(L-C0005)
Speed control
1003
1013
1113
Torque control
4003
4013
4113
DF master
5003
5013
5113
DF-slave bus
6003
6013
6113
DF-slave cascade
7003
7013
7113
Not equal to xxx3
(except self
configurations)
AIF-OUT.W1AIF-OUT.W2AIF-OUT.W3AIF-
MCTRL-NACT
Actual speed
100%=16383
MCTRL-MSET2
Torque display
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
ExplanationLenze setting:
Actual speed [%]^ 7.6-43
MCTRL-MSET2
Torque display
100%=16383
MCTRL-NACT
Act. speed in %
100%=16383
MCTRL-MSET2
Torque display
100%=16383
MCTRL-PHI-ACT
Actual phase
MCTRL-PHI-ACT
Actual phase
MCTRL-MSET2
Torque display
100%=16383
Index 6000
hex
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-MSET2
Torque setpoint in %
100%=16383
MCTRL-MSET2
Torque setpoint in %
100%=16383
MCTRL-PHI-ACT
Actual phase
see
Table below
OUT.D1
not
assigned
not
assigned
not
assigned
not
assigned
not
assigned
not
assigned
7.6-16
For detailed description of the 93XX signal configuration see the Operating
Instructions for 93XX (only the main configurations: 1000, 4000, 5000, etc.) or the
Manual 93XX.
In the c ontroller, other signals can be assigned to AIF-OUT.W1 to AIF-OUT.W3.
For this, the function-block configuration - described in the Manual 93XX- is used.
The function block AIF-OUT determines the output data of the controller as data
interfac e for the 2133 fieldbus module.
For more detailed information about the function block AIF-OUT, see the Manual
93XX.
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
8...1
1
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Controller status word AIF-STAT for 93XX
9300 Servo9300 POS9300 CRV9300 Vector
Bit..
1xx34xx35xx36xx3,7xx32xxx3xxx3
0DCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0 not assignedCERR1-ERRDCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0
1DCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMP
2MCTRL-IMAXMCTRL-IMAXREF-OKREF-OKPOS-REF-OKMCTRL-IMAXMCTRL-IMAXMCTRL-IMAXMCTRL-IMAX
3MCTRL-MMAX not assignedMCTRL-MMAX not assignednot assignedMCTRL-MMAXMCTRL-MMAX MCTRL-IMAX
Fig. 7.6-5Function block AIF-OUT (function block extension on grey bac kground: available as
of software version 2.0 on)
L
EDSIBS-1.0-06/ 2003
7.6-17
7
notassignednotassigne
d
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Process data telegram to drive
Data transfer
Process data signals of Lenze controllers
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindexNameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 7.6-36
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
5CA71AIF-IN.W1AIF word 1
5CA72AIF-IN.W2AIF word 2PO data word 3
5CA73AIF-IN.W3AIF word 3PO data word 4
5CA60AIF-IN.D1AIFdoubleword
)
)Note!
))
setpoint
setpoint
(AIF1_CTRL)
Speed setpoint [rpm] PO data word 2^ 7.6-42
Speed setpoint [%]
100% = 16383
Index 6001
hex
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering 0 under L-C1911 or
using the switch S7 at
the front.
see
^ 7.6-43
Table below
The assignment of AIF-IN.W1 to AIF-IN.W3 depends on the signal configuration
selected under L-C0005:
Signal configuration
(L-C0005)
Speed control
1003 / 1013 / 1113
Torque control
4003 / 4013 / 4113
DF master
5003 / 5013 / 5113
DF-slave bus
6003 / 6013 / 6113
DF-slave cascade
7003 / 7013 / 7113
not equal to xxx3not assignednot assigned
AIF-IN.W1AIF-IN.W2AIF-IN.W3AIF-IN.D1
NSET-N
Speed setpoint
MCTRL-MADD
Torque setpoint
NSET-N
Speed setpoint
DFSET-A-TRIM
Phase trimming
DFSET-VP-DIV
DF factor
not assigned
not assigned
not assigned
not assignednot assigned
DFSET-N-TRIM
Speed trimming
DFSET-A-TRIM
Phase trimming
For detailed description of the 93XX signal configuration see the Operating
Instructions for 93XX (only the main configurations: 1000, 4000, 5000, etc.) or the
Manual 93XX.
In the controller, other signals can be assigned to AIF-IN.W1 to AIF-IN.W3. For
this, the function-block configuration - described in the M anual 93XX - is used.
The function block AIF-IN determines the input data of the controller as data
interfac e for the 2133 fieldbus module.
For more detailed information about the function block AIF-IN, see the Manual
93XX.
7.6-18
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
X
. . .. . .
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Fig. 7.6-6Function block AIF-IN (grey: Extension available as of software version 2.0)
EDSIBS-1.0-06/ 2003
7.6-19
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
7.6.2.4Process data signals for 9300 servo PLC and Drive PLC
Process data telegram from drive
The following data can be assigned to the PE data:
IndexSubindexName/variable nameExplanationLenze setting: Index 6000
6041 0DRIVECOM status wordPI data word 1
6044 0DRIVECOM speedActual speed [rpm]PI data word 2
6054 0DRIVECOM actual percentage
value
5F69 0Device status word
(AIF1_DctrlStat)
5CA5 1AIF_nOutW1_aAIF word 1
5CA5 2AIF_nOutW2_aAIF word 2PI data word 3
5CA5 3AIF_nOutW3_aAIF word 3PI data word 4
5CA5 4AIF2_nOutW1_aAIF word 4PO data word 5
5CA5 5AIF2_nOutW2_aAIF word 5PO data word 6
5CA5 6AIF2_nOutW3_aAIF word 6PO data word 7
5CA5 7AIF2_nOutW4_aAIF word 7PO data word 8
5CA5 8AIF3_nOutW1_aAIF word 8PO data word 9
5CA5 9AIF3_nOu tW 2_aAIF word 9PO data word 10
5CA5 10AIF3_nOutW3_aAIF word 10
5CA5 11AIF3_nOutW4_aAIF word 11
5CA4 0AIF1_dnOutD1_pAIFdoubleword1
Process data signals of Lenze controllers
Data transfer
hex
Actual speed [%]
)
)Note!
))
9300 Servo PLC
Please execute the following logic operations in the PLC program
of the controller:
AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
DCTRL_wStat W AIF1_wDctrlStat
Drive PLC
It is necessary to use the device control for the Drive PLC.
7.6-20
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Outputs_AIF1
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
1
2
3
4
5
6
7
8
AIF1_wDctrlStat
AIF1_nOutW1_a
AIF1_nOutW2__a
AIF1_bFDO0_b
…
AIF1_bFDO15_b
AIF1_nOutW3_a
AIF1_bFDO16_b
…
AIF1_bFDO31_b
AIF1_dnOutD1_p
C0858/1
C0858/2
C0858/3
C0859
16 bits
16 bits
16 bits
C0151/4
16 binary
signals
16 bits
C0151/4
16 binary
signals
16 bits
Low Word
16 bits
High Word
Automation
Interface
AIF2_nOutW1_a
AIF2_bFDO0_b
...
AIF2_bFDO15_b
AIF2_nOutW2_a
AIF2_bFDO16_b
...
AIF2_bFDO31_b
AIF2_dnOutD1_p
AIF2_nOutW3_a
AIF2_nOutW4_a
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
Outputs_AIF2
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
7.6
7.6.2
1
2
3
4
5
6
7
8
Automation
Interface
AIF3_nOutW1_a
AIF3_bFDO0_b
...
AIF3_bFDO15_b
AIF3_nOutW2_a
AIF3_bFDO16_b
...
AIF3_bFDO31_b
AIF3_dnOutD1_p
AIF3_nOutW3_a
AIF3_nOutW4_a
Fig. 7.6-7Function blocks AIF-OUT1, AIF-OUT2 and AIF-OUT3
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
Outputs_AIF3
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
1
2
3
4
5
6
7
8
Automation
Interface
L
EDSIBS-1.0-06/ 2003
7.6-21
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
Process data telegram to drive
Data transfer
Process data signals of Lenze controllers
The following data can be assigned to the PA data:
Index Subindex Name/variable nameExplanationLenze s etting : Index 6001
6040 0DRIVECOM control wordPO data word 1
6042 0DRIVECOM speed setpointSpeed setpoint [rpm] PO data word 2
6052 0DRIVECOM percentage setpointSpeed setpoint [%]
5F78 0Device control word (AIF1_wDctrlCtrl)
5CA7 1AIF1_n InW1_aAIF word 1
5CA7 2AIF1_nInW2_aAIF word 2PO data word 3
5CA7 3AIF1_nInW3_aAIF word 3PO data word 4
5CA7 4AIF2_nInW1_aAIF word 4PO data word 5
5CA7 5AIF2_nInW2_aAIF word 5PO data word 6
5CA7 6AIF2_nInW3_aAIF word 6PO data word 7
5CA7 7AIF2_nInW4_aAIF word 7PO data word 8
5CA7 8AIF3_nInW1_aAIF word 8PO data word 9
5CA7 9AIF3_n InW2_aAIF word 9PO data word 10
5CA7 10AIF3_nInW3_aAIF word 10
5CA7 11AIF3_nInW4_aAIF word 11
5CA6 0AIF1_dnInD1_pAIFdoubleword1
hex
)
)Note!
))
9300 Servo PLC
Please execute the following logic operations in the PLC program
of the controller:
AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
DCTRL_wStat W AIF1_wDctrlStat
Drive PLC
It is necessary to use the device control for the Drive PLC.
7.6-22
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Process data signals of Lenze controllers
Automation
Interface
Inputs_AIF1
Byte
1
Controlword
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
16 bits
16 binary
signals
16 bits
16 bits
C0855/1
16 binary
signals
16 bits
C0855/2
16 binary
signals
16 bits
Low Word
16 bits
High Word
C0856/1
C0856/2
C0856/3
AIF1_bCtrlQuickstop_b
C0857
AIF1_wDctrlCtrl
AIF1_bCtrlB0_b
AIF1_bCtrlB1_b
AIF1_bCtrlB2_b
AIF1_bCtrlB4_b
AIF1_bCtrlB5_b
AIF1_bCtrlB6_b
AIF1_bCtrlB7_b
AIF1_bCtrlDisable_b
AIF1_bCtrlCInhibit_b
AIF1_bCtrlTripSet_b
AIF1_bCtrlTripReset_b
AIF1_bCtrlB12_b
AIF1_bCtrlB13_b
AIF1_bCtrlB14_b
AIF1_bCtrlB15_b
AIF1_nInW1_a
AIF1_nInW2_a
AIF1_bInB0_b
AIF1_bInB15_b
AIF1_nInW3_a
AIF1_bIn16_b
AIF1_bIn31_b
AIF1_dnInD1_p
7.6
7.6.2
Inputs_AIF2
Byte
1
Byte
2
Byte
3
Byte
Automation
Interface
…
…
Automation
Interface
4
Byte
5
Byte
6
Byte
7
Byte
8
Inputs_AIF3
Byte
1
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
AIF2_nInW1_a
AIF2_bInB0_b
...
AIF2_bInB15_b
AIF2_nInW2_a
AIF2_bInB16_b
...
AIF2_bInB31_b
AIF2_dnInD1_p
AIF2_nInW3_a
AIF2_nInW4_a
AIF3_nInW1_a
AIF3_bInB0_b
...
AIF3_bInB15_b
AIF3_nInW2_a
AIF3_bInB16_b
...
AIF3_bInB31_b
AIF3_dnInD1_p
AIF3_nInW3_a
AIF3_nInW4_a
L
Fig. 7.6-8Function blocks AIF-IN1, AIF-IN2 and AIF-IN3
EDSIBS-1.0-06/ 2003
7.6-23
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.3
Process data preconfiguration depending on L-C0009
7.6.3Process data preconfiguration depending on L-C0009
Use L-C0009 to assign predefined values to the process data words (see table
below).
This preconfiguration is meant to help you with applications which do not require
aPCP.
Presettings for the process data configuration can be made under code L-C0009
using the Drive PLC or any controller (82XX, 8200 vector, 93XX) even if the
INTERBUS is not connected.
It is also possible to configure the fieldbus module through the parameter channel
via index 6000
The process data configuration resulting from L-C0009 is automatically
l stored in the process data description structure when the device is
switched on.
WIndex 6000
and 6001
hex
hex
(¶ 7.6-5)
.
hex
/ Index 6001
hex
(¶ 7.6-6)
Data transfer
.
l immediately active.
l automatically writes the process data length (PD) in L-C1910 and
DRIVECOM in L-C1911 from the table. A change of the PD length will only
become active if the mains is switched on again and all DIP switches S1 S7 are OFF.
The default setting of L-C0009 is “1” and influences the process data
configuration.
Data transfer
Process data preconfiguration depending on L-C0009
Examples for process data
preconfiguration
Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
Acceptance of settingsThe fieldbus module must be switched on again to activate the process
Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
Acceptance of settingsThe fieldbus module must be switched on again to activate the process
supply
2. Set L - C0009 = 14 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
and DCG.
hex
and 6001
accept the configurations DCSTW
hex
• The process data length (PD) is set to 2 words by L-C1910 = 4.
• DRIVECOM is activated with L-C1911 = 1.
data word length.
supply
2. Set L - C0009 = 25 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
AIF-W1, AIF-W2.
hex
and 6001
accept the configurations GSTW,
hex
• The process data length (PD) is set to 3 words by L-C1910 = 6.
• DRIVECOM is activated by L-C1911 = 0.
data word length.
7.6
7.6.3
Example 3: DRIVECOM control with 5 process data words (e.g. configuration L-C0009 = 21)
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
supply
2. Set L - C0009 = 21 (e.g. via keypad)
3. DIP switch
– S1 = OFF, S2 = ON, S3 = OFF, S4 = ON (PD = 5 words)
– S5/S6: Set required PCP data word length
– S7 = ON (DRIVECOM activated)
4. Attach the fieldbus module again and connect it to the voltage
supply
and 6001
DCG, AIF-W2, AIF-W3, AIF-W4.
hex
accept the configurations DCSTW,
hex
• Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active
(DIP switch in position “ON”).
Acceptance of settingsA process data word length of 5 words and DRIVECOM are immediately
Example 4: Configuration of 10 PD words to AIF interface (configuration L-C0009 = 27).
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
active through switches.
supply
2. Set L - C0009 = 27 (e.g. via keypad)
3. DIP switch
– S1 = ON, S2 = OFF, S3 = ON, S4 = OFF (PD = 10 words)
– S5 = OFF, S6 = OFF: no PCP
– S7 = OFF (DRIVECOM deactivated)
4. Attach the fieldbus module again and connect it to the voltage
supply
AIF-W1 .... AIF-W10.
hex
and 6001
accept the configurations
hex
• Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active
(DIP switch in position “ON”).
Acceptance of settingsAll switch settings become active immediately.
L
EDSIBS-1.0-06/ 2003
7.6-25
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.4
Examples for the configuration of PI/PO data
7.6.4Examples for the configuration of PI/PO data
PI data configuration
The PI data word 2 is to be assigned to the actual percentage (index = 6054
Procedure:
1. Data type derived from the code table ^ 7.6-43.
– The data type of the parameter actual percentage value is I16, i.e. it is a word parameter (16 bit). The code
table for the parameter ”Process input data description structure“ (index = 6000
word 2 is to be entered under subindex 6 and 7 (word parameters).
– The subindex of the parameter ”PI data description“ (index = 6000
”Write“ (see
2. Enter the index of the parameter ”Actual percentage“: Write (index = 6000
3. Enter the subindex of the parameter ”Actual percentage“: Write (index = 6000
)
)Note!
))
^ 7.6-50).
The index must be changed to zero to change a subindex.
You can then change the subindex before the index.
Data transfer
) shows that the PI data
hex
)canbewrittenwiththePCPservice
hex
, subindex = 6
hex
subindex = 7
hex
, value = 6054
hex
,value=0
hex
hex
hex
hex
).
)
)
7.6-26
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Examples for the configuration of PI/PO data
PO data configuration
ThePO data word 2 is to be assigned to the percentage setpoint (index = 6052
Procedure:
1. Data type derived from the code table ^ 7.6-43.
à The data type of the parameter ”Percentage setpoint“ is I16, i.e. it is a word parameter (16 bit). The code table
for the parameter ”Process output data description structure“ (index = 6001
to be entered under subindex 6 and 7 (word parameters).
The subindex o f the parameter ”PO data description“ (index = 6001
”Write“.
)
)Note!
))
The description of PO data results in inconsistent data, as the
data are exchanged between controller and INTERBUS master in
very short cycle times.
Therefore, the PO data are automatically inhibited when changing
the PO data configuration. After the adaptation of the PO data to
the new configuration, the data can be enabled via the parameter
”PO data enable” (index 6002
hex
) shows that the PO data word 2 is
hex
) can be described with the PCP service
hex
).
7.6
7.6.4
hex
).
2. Enter the index of the parameter ”Percentage setpoint“: Write
(index = 6001
3. Enter the subindex of the parameter ”Percentage setpoint“: Write
(index = 6001
)
)Note!
))
4. Enter the index of the paramet e r ”PO data enable“ (6002
(index = 6002
Now the PO data can be read again from the controller.
)
)Note!
))
, subindex = 6
hex
, subindex = 7
hex
The index must be changed to zero to change a subindex.
You can then change the subindex before the index.
, subindex = 0
hex
If a parameter is configured for PO data (e.g. the parameter
”Control word“ (6040hex) in Lenze setting), it is not possible to
write this parameter directly via its index (example: index =
6040hex)
, value = 6054
hex
,value=0
hex
, value = FFFFFF
hex
hex
)
hex
)
) to enable process data : Write
hex
)
hex
L
EDSIBS-1.0-06/ 2003
7.6-27
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.5
7.6.5Device control
Data transfer
Device control
)
)Note!
))
Deactivate the DRIVECOM control if you want to use the device
control (AIF-CTRL). For this use either code L-C1911 or the DIP
switch S7 (
If you use the device control AIF-CTRL, the control information is determined by
the control inputs (terminal)
Explanation: Fig. 7.6-9
l Status word:
The controller status word AIF-STAT contains information about the current
controller status.
l Commands
– in the DRIVECOM parameter ”Control word“ are switched off and cannot
change the controller status.
– for changing the controller status are to be entered through the
Fig. 7.6-9Status d iagram for device c ontrol AIF-CTRL
qofm EÑ~ìäíF
pí~íìë ïçêÇ ññññ ññññ ñMññ NMMM
Fault
qofm кЙлЙнGG
kзнЙW
qЬЙ нЙкгл г~квЙЗ пбнЬ GG ~кЙ Езгг~еЗл
7.6-28
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Device control
7.6
7.6.5
StatusMeaning
NOT READY TO SWITCH ON The controller is still in the initialisation phase and not ready for operation.
It then automatically switches to the status READY TO SWITCH ON.
READY TO SWITCH ONThe controller is inhibited and waits for the power stage to be charged. It then
automatically switches to the status ”SWITCHED ON“.
SWITCHED ONThe controller is inhibited and waits for controller enable.
OPERATION ENABLEDThe controller is enabled. In this status, a pulse inhibit can be set automatically.
FAULTThe controller is in the status ”FAULT“ (TRIP).
L
EDSIBS-1.0-06/ 2003
7.6-29
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.6
7.6.6DRIVECOM control
With INTERBUS control (for 82XX/8200vector: Lenze parameter L-C0001 = 3; for
93XX: always) and when using the fieldbus module, Lenze controllers have a
controller status according to the DRIVECOM profile 21.
Explanation: Fig. 7.6-10
l The DRIVECOM param eter “Status word” contains information about the
l Commands in the DRIVECOM parameter ” Control word“ can change the
Explanation of the status
diagram for DRIVECOM control
7.6.6
StatusMeaning
NOT READY TO SWITCH ONThe controller is being initialised and is not yet ready to operate. It then
SWITCH ON INHIBITThe controller is inhibited and waits for command 2 (shut down).
READY TO SWITCH ONThe controller is inhibited and waits for command 3 (switch on).
SWITCHED ONThe controller is inhibited and waits for command 4 (enable operation).
OPERATION ENABLEDThe controller is enabled. In this status, a pulse inhibit can be set
FAULT REACTION ACTIVEA fault (TRIP) was recognised and a fault response initiated.
FAULTThe controller is in the status ”FAULT“ (TRIP).
QUICK STOP ACTIVEWhile being in the status ”OPERATION ENABLED“ the command ”quick stop“
)
)Note!
))
automatically switches to the status READY TO SWITCH ON.
automatically.
was set. The controller is decelerated in a controlled way (quick-stop ramp).
After deceleration, the controller automatically changes to the controller
status ”SWITCH ON INHIBIT“.
7.6
The actual unit status can only be clarified by combining the
unit-status information bits (bit 0 to 6). This is shown in the
following:
Controller statusBits of the status word
Bit6543210
NOT READY TO SWITCH ON00000
SWITCH ON INHIBIT10000
READY TO SWITCH ON010001
SWITCHED ON010011
OPERATION ENABLED010111
FAULT01000
FAULT REACTION ACTIVE01111
QUICK STOP ACTIVE000111
Switch-on inhibit
Quick stop
Voltage inhibit
Fault
Operation enabled
Switched on
Ready to switch on
0= Bit status is 0
1= Bit status is 1
no entr y = Any bit status, no influence
L
EDSIBS-1.0-06/ 2003
7.6-31
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.6
Explanation of the commands in
the status diagram for
DRIVECOM control
Data transfer
DRIVECOM control
CommandMeaning
COMMAND 2, 6, 8 (standstill)
Control word: bit 0 = 0
COMMAND 3 (switch on)Command to change to the controller status ”SWITCHED ON“.
COMMAND 4 (enable operation)Command to change to the controller status ”OPERATION ENABLED“.
COMMAND 5 (inhibit operation)Command to change to the controller status ”SWITCHED ON“.
COMMAND 7, 9, 10, 12 (voltage
inhibit)
Control word: bit 1 = 0
COMMAND 7, 10, 11 (quick stop)
Control word: bit 2 = 0
COMMAND 13 (malfunction/TRIP))The controller has recognised a malfunction. For some malfunction a
COMMAND 14 (reset fault/TRIP)
Control word: bit 7 = 0
⇒ 1
Command to change from different states to the status ”READY TO SWITCH
ON“.
The controller inhibit is deactivated.
The controller inhibit is activated.
Command to change to the controller status ”SWITCH ON INHIBIT“.
The controller inhibit is activated.
Command to change to the controller status ”SWITCH ON INHIBIT“.
If the controller was enabled, it is decelerated in a controlled way along the
Lenze quick-stop ramp.
controlled deceleration may be necessary (depending on the controller).
Once completed, the controller changes to the status FAULT.
With the series 821X, 8200 vector this command acknowledges an error.
The controller changes to the status ”SWITCH ON INHIBIT“ when a fault is no
longer recognised.
)
)Note!
))
The single bit-control commands depend on other bit positions.
In the following you will find a description of the bits required to
effect the command.
Controller status commandsBits of the control word
Bit76543210
The parameter enables or inhibits the PO data (output data for INTERBUS
master). By this, the consistency of the PO data is guaranteed.
Output data inhibit: 00000000
Output data enable: FFFFF
Every bit enables a process data byte!
If you change 6001
automatically. That means, that the controller does not receive new control data
until index 6002
Parameter name (Index)SubindexData structureData type
PO data description (6002
All process data areenabled when the device is switched on (6002
hex
(¶ 7.6-5).
(¶ 7.6-6).
hex
hex
, the changed process data bytes will be inhibited
hex
enables the communication again.
)0RPBS(20
hex
hex
)
hex
7.6.7
≡ FFFFF
7.6
hex
)
L
EDSIBS-1.0-06/ 2003
7.6-33
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
7.6.7.2Monitoring parameters
Process data monitoring time
(6003
Process data monitoring
selection code (6004
hex
)
)
hex
If the transmission of the process data isinactive for longer than the set monitoring
time (PCD watchdog), the action set in the parameter ” process-data monitoring
selection code” (6004
Parameter name (Index)SubindexData structureData typ eValue range
Process data monitoring time
(6003
The parameter determines the reaction of the controller after the process data
monitoring time is over (6003
Parameter name (Index)SubindexData structureData typ eValue range
Process data monitoring selection
code (6004
hex
Data transfer
DRIVECOM profile parameters
) will be activated.
hex
)
)
hex
0SOS-1
).
hex
0SI160 (Lenze setting),
OS: Octet
string,
length: 4
0 - 65535
(Lenze setting: 65535,
monitoring is switched off)
0 = No action
2:
Unit control command
„Inhibit voltage“ (controller
inhibit with latching in the
status ”SWITCH ON INHIBIT“)
3:
Unit control command
”Quick stop“ (quick stop
(QSP)withlatchinginthe
status ”SWITCH ON
INHIBIT“).
7.6-34
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
DRIVECOM profile parameters
7.6.7.3Error code (603F
hex
7.6
7.6.7
)
If the drive sets TRIP, the error code transmits an error number which corresponds
to the DRIVECOM profile (see chapter 7.7.4 DRIVECOM error code).
A list of errors which occurred in Lenze controllers is stored under the Lenze
parameters:
l 82XX: L-C0162 - L-C0164
l 93XX: L-C0168 with subindex 1 to 8
Parameter name (Index)SubindexData structureData type
Error code (603F
)0SU16
hex
OS
L
EDSIBS-1.0-06/ 2003
7.6-35
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
7.6.7.4DRIVECOM control word (6040
The controller is controlled via this parameter. It contains comands for the
transition between different controller states (see chapter 7.6.6) and other
important control commands (see the following table).
Parameter name (Index)SubindexData structureData type
Control word (6040
)
)Note!
))
Data transfer
DRIVECOM profile parameters
)
hex
)0SOS
hex
The bits contained in the control word are interdependent control
commands which are to be parameterised. Chapter 7.6.6
describes the bits required to make the the command become
effective.
820X:Not assigned
821X, 822X:Output of the RFG (speed setpoint integrator) is ”frozen”.
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B4 negated.
820X:Not assigned
821X, 822X:Ramp function generator input (speed setpoint integrator) = 0
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B5 negated.
For 82XX, the controller is initialised. During this time, the controller does not accept any
commands.
820X, 821X, 822X:Not assigned
:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B7.
820X, 821X, 822X:Parameter set changeover:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B12.
820X, 821X, 822X:DC-injection brake:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B131).
820X, 821X, 822X:Not assigned
:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B14.
8201XPE inhibit
821X, 822X:Not assigned
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B15.
1 = command 3 (controller inhibit)
1 = command ”voltage inhibit“ not active
1 = Command ”quick stop“ not active
1 = Command 4 (controller inhibit not active)
Quick stop is activated without the controller leaving its status.
0 = RFG inhibit (quick stop)
1 = RFG inhibit not active
0=RFGstop
1 = RFG stop not active
(controlled deceleration along the set ramp)
0=RFGzero
1 = RFG zero not active
® 1=Parameterset2
0
1
® 0=Parameterset1
0 = DCB not active
1=DCBactive
Inhibit the update of the PO data of the controller (input data for
the master).
Updates of status and current information of the process channel
can be inhibited in order to send control information more
precisely in time (see chapter 7.3.4.2).
0 = Read status and actual value
1 = Do not read status and actual value
7.6
7.6.7
L
EDSIBS-1.0-06/ 2003
7.6-37
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
Link between DRIVECOM control
word and AIF- CTRL control for
93XX and 9300 Servo PLC
Steuerwort
INTERBUS-Master
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
DRIVECOM State
Machine
1
1
C0136/3
AIF-CTRL.B3
AIF-CTRL.B8
AIF-CTRL.B9
AIF-CTRL.B10
AIF-CTRL.B11
Data transfer
DRIVECOM profile parameters
AIF-IN
DCTRL
QSP
DISABLE
CINH
TRIP-SET
TRIP-RESET
AIF-CTRL.B0
AIF-CTRL.B1
AIF-CTRL.B2
AIF-CTRL.B4
AIF-CTRL.B5
AIF-CTRL.B6
AIF-CTRL.B7
AIF-CTRL.B12
AIF-CTRL.B13
AIF-CTRL.B14
AIF-CTRL.B15
2113IBU006
7.6-38
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
DRIVECOM profile parameters
7.6.7.5DRIVECOM status word (6041
This parameter provides compact information about the controller. It contains
commands for the transition between the different controller states (see chapter
7.6.6) and other important information (see the following table).
)
)Note!
))
Parameter name (Index)SubindexData structureData type
Status word (6041
)
hex
The current controller status can only be clarified by combining
the bits with the status information (bit 0, 1, 2, 3, 4, 5 and 6). This
isshowninchapter7.6.6.
)0SOS
hex
7.6
7.6.7
L
EDSIBS-1.0-06/ 2003
7.6-39
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
Struct ure of the DRIVECOM
status word
Data transfer
DRIVECOM profile parameters
BitNameMeaning
0Ready to switchonController status information
1Switched onController status information
2Operation
enabled
3FaultController status information
4Voltage inhibited Information about the command ”voltage inhibit“ (see chapter 7.6.7.4 ”control word“)
5Quick stopInformation about the command ”quick stop“ (see chapter 7.6.7.4 ”control word“)
6Switch-on
inhibit
7WarningCollective warning
8MeldungCollective message. Automatic setting and resetting of pulse inhibit in the controller status
9Remote82XX, 821X, 822X,
10FREE
DRIVECOM:
Setpoint
reached
11Limit valueStatus of the DRIVECOM speed limitation
12FREE
DRIVECOM:
Reserve
13FREE
DRIVECOM:
Reserve
14Manufacturer820X, 821X, 822X:
15Manufacturer820X, 821X, 822X:
0 = Status lower than ”READY TO SWITCH ON“
1 = Status at least ”READY TO SWITCH ON“
0 = Status lower than ”SWITCHED ON“
1 = Status at least ”SWITCHED ON“
Controller status information
0 = Status lower than ”OPERATION ENABLED“
1 = Status ”OPERATION ENABLED“
0 = No fault (TRIP))
1 = Fault (TRIP) occured
0 = Command active
1 = Command not active
0 = Command active
1 = Command not active
Controller status information
0 = Statu not ”SWITCH-ON INHIBIT“
1 = Status ”SWITCH-ON INHIBIT“
0=Nowarning
1 = Warning (overtemperature)
”OPERATION ENABLED”. Reasons for this can be undervoltage or overvoltage as well as
overcurrent (clamp).
0 = No message
1 = Message (IMP)
8200 vector:
93XX:
Status of speed/frequency deviation
0=RFG
1=RFGon=RFG
0 = Limitation not addressed
1 = Limitation addressed
820X, 821X, 822X:
8200 vector, 93XX:
82XX:
8200 vector:
93XX:
8200 vector, 93XX:
8200 vector, 93XX:
<> RFG
on
Bus access, depends on Lenze parameter ”operating mode”
(L-C0001):
0 = L-C0001
1 = L-C0001
0 = L-C1911 = 0
1 = L-C1911 = 1
off
off
Not assigned
Free. Mapping to bit L-C0150.B14
Not assigned
Free. Mapping to bit L-C0150.B15
Free. Mapping to bit L-C0150.B3
I
max
0 = Current limit not reached
1 = Current limit exceeded
Free. Mapping to bit L-C0150.B2
Q
min(fd
0=Q
1=Q
Free. Mapping to bit L-C0150.B5
<> 3 or L-C1911 = 0
= 3 and L-C1911 = 1
(current limit reached)
≤ f
)
dQmin
not active
min
active
min
7.6-40
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
DRIVECOM profile parameters
Link between DRIVECOM status
word and function block STAT
for 93XX and 9300 Servo PLC
The parameter sets the speed setpoint [rev/min]. If this parameter is changed,
also the nominal percentage will be changed.
Parameter name (Index)SubindexData structureData typ eValue range
Speed setpoint
(6042
This parameter is the output value of the speed ramp function generator [rev/min].
Parameter name (Index)SubindexData structureData typ eValue range
Speed reference variable (6043
The parameter indicates the actual speed (in rpm).
Parameter name (Index)SubindexData structureData typ eValue range
Actual speed
(6044
hex
hex
Data transfer
DRIVECOM profile parameters
)
)
0SI16−32768 to 32767
)0SI16−32768 t o 32767
hex
0SI16−32768 to 32767
Min/max speed value (6046
Setpoint factor (604B
hex
)
hex
)
This parameter indicates the minimum and the maximum speed (in rpm). It is
initialised with the Lenze parameter L-C0011. Changing this parameter does not
result in a change of L-C0011 (see ”Speed-reference value”).
Parameter name (Index)SubindexData structureData typ eValue range
Min/max speed value (6046
hex
)
1AU320 to 32000
2AU320 to 32000
0: Minimum speed setpoint
[rev/min]
L-C0011: Maximum speed
setpoint [rev/min]
This parameter is used to change the resolution or the setting range of the setpoint
input. It consists of numerator and denominator. The setpoint is multiplied by the
setpoint factor; the actual values (reference variable, actual value) are multiplied
by the inverse setpoint factor.
Parameter name (Index)SubindexData structureData typ eValue range
Setpoint factor (604B
hex
)
1AI16−32768 to 32767
Lenze setting: 1
(Numerator of the ”Setpoint
factor“)
2AI16−32768 to 32767
Lenze setting: 1
(Denominator of the
”Setpoint factor“)
7.6-42
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
DRIVECOM profile parameters
Pole number (604D
Speed reference value (604E
Percentage setpoint (6052
hex
) 38
hex
hex
) 39
)
7.6
7.6.7
The parameter indicates the pole number of asynchronous motors and is used to
convert frequency values into speed values. Only even values are possible.
Parameter name (Index)SubindexData structureData typeValue range
Pole number (604D
This parameter is the reference value for the relative speed parameters, e.g.
nominal percentage, actual percentage and acceleration time. The parameter is
mapped to the Lenze parameter L-C0011. A conversion to frequency values is
possible. The parameter determines the internal maximum speed, which is also
active with terminal control.
Parameter name (Index)SubindexData structureData typeMeaning
Speed reference value (604E
This parameter is the nominal speed in percent. It is scaled to the ”speed
reference value“ (= 100 % ). When changing this parameter, also the ”nominal
speed“ will be changed. If the ” nominal speed“ exceeds the limit value of the
”nominal percentage“ of 200 % during reading, it will be returned as a value
limited to 200 % .
)0SU82, 4, 6, ..., 254
hex
)0SU32
hex
Lenze setting: 4
L-C0011
2
in [rev∕min]
Percentage reference variable
(6053
Actual percentage (6054
hex
)
) 40
hex
Parameter name (Index)SubindexData structureData typeValue range
Percentage setpoint (6052
)0SI16−32768 t o 32767
hex
(100 % = 16383)
This p aramet er is t he ”speed reference variable“ in percent. It is scaled to the
”speed reference value“ (= 100 % ). The ”percentage reference variable“ ismultiplied by the inverse ”setpoint factor“ .
Parameter name (Index)SubindexData structureData typeValue range
Percentage reference variable
)
(6053
hex
0SI16−32768 to 32767
(100 % = 16383)
This paramet er is the ” actual speed“ in percent. It is scaled to the ”speed
reference value“ .
Parameter name (Index)SubindexData structureData typeValue range
Actual percentage (6054
)0SI16−32768 to 32767
hex
(100 % = 16383)
Map of L-C0381
L
EDSIBS-1.0-06/ 2003
7.6-43
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
7.6.7.7Ramps
Data transfer
DRIVECOM profile parameters
The DRIVECOM profile 21 provides two ramps for the speed setpoint:
l The absolute ramp is determined by the following ramp gradient:
dк~ЗбЙен =
The absolute ramps in the DRIVECOM profile 21 are ”acceleration”,
”deceleration” and ”quick stop”.
l The relative ramp is determined by the following ramp gradient:
dк~ЗбЙен =
This definition corresponds to the Lenze ramp functions L-C0012 and L-C0013.
The relative ramps in the DRIVECOM profile 21 are ” acceleration time”,”deceleration time” and ”quick-stop time”.
aЙдн~|лйЙЙЗ
aÉäí~|íáãÉ
pйЙЙЗ кЙСЙкЙеЕЙ о~дмЙ
aÉäí~|íáãÉ
Speed ramps fro acceleration
(6048
hex
)
The ”ramp-min function” determines and activates the slower ramp. Theabsolute
ramps are deactivated in Lenze setting.
This parameter contains data of the absolute speed ramp for acceleration.
Ramp gradient:
Gradient =
The parameter is mapped to the Lenze acceleration ramp (L-C0012) via the
”ramp-min-function”.
”Delta_time“ = 0: Ramp is switched off.
Parameter name (Index)SubindexData structureData typ eValue range
Speed acceleration (6048
The ”ramp-min function” determines and activates the slower ramp. Theabsolute
ramps are deactivated in Lenze setting.
Delta_speed
Delta_time
hex
)
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
7.6-44
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
DRIVECOM profile parameters
Speed ramps for deceleration
(6049
Speed quick stop (604A
hex
)
)
hex
7.6
7.6.7
This parameter contains data of the absolute speed ramp for deceleration.
Ramp gradient:
Gradient =
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
”ramp-min-function”.Ifthe” delta_time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Speed delay (6049
This parameter contains the data of the absolute speed ramp for deceleration in
the status ” QUICKSTOP“ or ”CTRL INHIBIT“ or the QSP terminal function.
Delta_speed
Delta_time
)
hex
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
Acceleration time (604F
hex
Ramp gradient:
Gradient =
Delta_speed
Delta_time
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
”ramp-min-function”.Ifthe” delta_time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Quick stop
)
(604A
hex
)
This parameter is for the acceleration of the relative speed ramp. Theacceleration
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
time refers to the parameter ” speed reference” with the following slope:
Ramp gradient:
Gradient =
Speed reference value (604E
Acceleration time (604F
)
hex
)
hex
The parameter is mapped to the Lenze acceleration ramp (L-C0012) via the
”ramp-min-function”.Ifthe” acceleration time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Acceleration time (604F
)0SU320 to 495000 [ms]
hex
(max. L-C0012 / 2)
L
EDSIBS-1.0-06/ 2003
7.6-45
7
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
Deceleration time (6050
Quick-stop time (6051
hex
hex
Data transfer
DRIVECOM profile parameters
)
)
Thisparameter isfor the deceleration of therelative speed ramp. Thedeceleration
time refers to the parameter ” Speed reference value“.
Ramp gradient:
Gradient =
Speed reference value (604E
Deceleration time (6050
)
hex
)
hex
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
”ramp-min-function”.Ifthe„ deceleration time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typ eValue range
Deceleration time (6050
)0SU320 to 495000 [ms]
hex
(max. L-C0013 / 2)
This parameter is assigned to the relative speed ramp for the unit-control
commands ”quick stop” and ”CTRL inhibit” or the QSP terminal function. The
quick stop time refers to the parameter ” Speed reference value“.
Ramp gradient:
Gradient =
Speed reference value (604E
Quich stop time (6051
)
hex
)
hex
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
”ramp-min-function”.Ifthe” quick stop time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typ eValue range
Quick-stop time (6051
)0SU320 t o 495000 [ms]
hex
(max. L-C0105 / 2)
7.6-46
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Configuration of the parameter data channel (PCP communication)
7.6.8Configuration of the parameter data channel (PCP communication)
7.6.8.1General information
Access to controller codes
The behaviour and features of a devic e connected to the INTERBUS can be
changed through the INTERBUS master. The device is connected via the
attached fieldbus module. All devices
Features and behaviour can be changed by changing the parameter data of the
basic unit. Parameter data are
l Lenze parameters (L- Cxxxx)
– Lenze parameters are implemented in Lenze controllers or fieldbus
modules.
– In these descriptions Lenze
the code as indicated in the corresponding controller description (“C” and
4-digit code number).
l DRIVECOM parameters
– For more all manufac turers
– Normalisation in DRIVECOM profile 21
– Every DRIVECOM parameter is addressed by the corresponding index
(overview in chapter 7.8.1.3).
Lenze controllers store the parameters to be changed inc odes.
(¶ 7.2-1) can be connected to the bus.
parametersaremarkedbyanLfollowedby
7.6
7.6.8
Value range for Lenze parameters
)
)Note!
))
These Instructions use a ”L-Cxxxx“ in front of a code to indicate
that it is a Lenze code and not a DRIVECOM index.
Example: ’L-C0001’ stands for the Lenze code C0001.
Controller codes are addressed via the index when they areaccessed through the
bus module.
The index for Lenze code numbers is between 16576 (40C0
Conversion formula:
Index[dec
Example for operating mode L-C0001:
Index = 24575 - LENZE CODENOIndex
Index = 24574 (= 24575 - 1)Index
The value range for Lenze codes can be found in the Operating Instructions for
the corresponding controller (see: Code table).
The data of the Lenze parameters are mainly represented in a fixed-point format
of the data type Integer32 with four decimal digits. This means, that the parameter
value listed in the Operating Instructions must be multiplied by 10000.
Example:
] = 24575 −
dechex
Lenze code
hex
hex
= 5FFF
= 5FFE
hex
hex
) and 24575 (5FFF
hex
- LENZE-CODENO
(= 5FFF
hex
-1)
hex
hex
).
L
dechex
L-C0039 (JOG) = 150.4 Hz150.4 x 10000 = 1504000= 0016F300
EDSIBS-1.0-06/ 2003
7.6-47
7
intheEEPROMofthecontroller.
Afterswitchonparameterset1i
s
à
Onlytheparametersetdirectlystoredin
Show/Hide Bookmarks
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.8
Lenze parameter sets
Data transfer
Configuration of the parameter data channel (PCP communication)
Parameter sets are for special code saving which is necessary because of
different configurations for different application processes.
The following table informs about number and addressing of parameter sets for
your controller:
82XX8200 vector93XX
The 82XX and 8200 vector have 2 and 4 parameter sets. The
parameters can be directly addressed via INTERBUS.
They are addressed by means of a code-digit offset:
• Offset 0 addresses parameter set 1 with t he Lenze codes L-C0000
to L-C1999
• Offset 2000 addresses parameter set 2 with t he Lenze codes
L-C2000 to L-C3999
No additional
parameter sets available.
If a parameter is available only once (see Operating Instructions for
82XX or 8200 vector), use the code digit offset 0.
Example for L-C0011 (maximum field frequency):
L-C0011 in parameter set 1: Lenze code = 11
L-C0011 in parameter set 2: Lenze code = 2011
-
Parameter changes
Automatic saving in the
controller
Process data changes
No automatic savingNo automatic savingNo automatic saving
• Offset 4000 addresses parameter set 3
with the Lenze codes L-C4000 to
L-C5999
• Offset 6000 addresses parameter set 4
with the Lenze codes L-C6000 to
L-C7999
L-C0011 in parameter set 3:
Lenze code = 4011
L-C0011 in parameter set 4:
Lenze code = 6011
Automatic saving is default setting
(changeable under L-C0003)
93XX controllers have 4 parameter sets
(depending on the variant). They are saved
in the EEPROM of the controller.
Another parameter set is in the user
memory of the controller. This parameter
set can be changed by the user.
• After switch-on parameter set 1 is
automatically loaded as current
parameter set.
• Parameter sets 2 - 4 must be loaded
à Only the parameter set directly stored in
Changes must be stored in code L-C0003.
All changes made without storing them will
be lost after the controller is switched off.
to the RAM.
manually
theRAMcanbeaddressedvia
INTERBUS.
(
(Stop!
((
l For 8200 vector
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.
– Please configure the code to C0003 = 0 after each mains
disconnection if you want to change the parameter data
cyclically.
l For 82XX
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.
7.6-48
EDSIBS-1.0-06/ 2003
L
Feldbus-Baugruppe 2113 INTERBUS
Show/Hide Bookmarks
7
Data transfer
Configuration of the parameter data channel (PCP communication)
7.6.8.2Initialisation of PCP communication
CRL entries
CRL (CommunicationReferenceList) entriesare requiredtoensure
communication between the INTERBUS master and the fieldbus module.
The following entries are to be set in the INTERBUS-master CRL:
Field nameEntry
Communication reference (CR)2
Connection typeAcyclic master/slave
Connection attributeDefined
Max PDU sending high prio0
Max PDU sending low prio64
Max PDU receiving high prio0
Max PDU receiving low prio64
Supported service request80 30 00
Supported Services Response00 00 00
Maximum SCC1
Maximum RCC1
Maximum SAC1
Maximum RAC1
hex
hex
7.6
7.6.8
7.6.8.3Available PCP services
In the following, you will find all the parameters and their contents which are
returned by Lenze controllers. All other transmission parameters of the stated
PCP services can be obtained from the corresponding INTERBUS master
description.
Parameters are transmitted via the PCP channel (PCP = Peripherials
Communication Protocol). This is carried out via PCP services.
The following PCP services are supported by Lenze controllers:
l Initiate: Build up connection between INTERBUS master and c ontroller
l
l
l
l
l
l
(¶ 7.6-50)
Abort: Disconnect (¶ 7.6-50)
Read: Read parameters (¶ 7.6-50)
Write: Write parameters (¶ 7.6-50)
Get-OV: Read object direc tory (OV) (¶ 7.6-51)
Identify: Identification of controller (¶ 7.6-51)
Status: Read controller status (¶ 7.6-52)
L
EDSIBS-1.0-06/ 2003
7.6-49
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.