– 820X / 821X270 V ACBasic insulation
– 822X / 8200 vector270 V ACDouble insulation
– 93XX270 V ACDouble insulation
• Control terminals
– 820X / 8200 vector
(with internal supply)
– 8200 vector
(with external supply)
– 821X50 V ACMains isolation
– 822X270 V ACBasic insulation
– 93XX270 V ACBasic insulation
FieldValues
Maximum number of participants62
Process data words (PD)L-C1910 = 4: 2 words (32 bit)
Parameter data words (PCP)1(16bit)
Maximum number of data wordsThe maximum number of data words (PD + PCP) is 4.
INTERBUS ID (module ID)227
Maximum PDU length64 byte
Supported PCP servicesInitiate, abort, status, identify, Get-0V-long, read, write
0VACNo mains isolation
100 V ACBasic insulation
L-C1910 = 6: 3 words (48 bit)
=E3
dec
hex
à Lenze setting
PCP 1 word
L
EDSIBS-1.0-06/ 2003
5.3-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.3
5.3.4
5.3.4Communication times
5.3.4.1Cycle time
The cycle time of a communication system is the time needed to exchange all
process data
to the bus.
It depends on the communication system data and is calculated as follows
(example: baud rate of 500 kbit/s):
í
= Eå + QU + P × _hF × PKPR × NM−P+ MKOQ × i + MKO
ÅóÅä
Fig. 5.3-1 is shows the ratio between cycle time and number of connected
controllers.
The indicated values refer to the connection of Lenze controllers (e. g. 2XX) with
48 data bits (1 parameter data word + 2 process data words, see
Technical data
Communication times
(¶ 5.6-6) between the INTERBUSmaster and the devices connected
t
cycl
nSum of all data b it in the INTERBUS ring
BTNumber of b us terminals
LLength of remote bus cable in [km]
Cycletimein[ms]
(¶ 5.3-1).
Cycletime[ms]
NO
NM
U
S
Q
O
N
NM
Number of devices connected to the bus
Fig. 5.3-1INTERBUS cycle time for controllers
OM
PMQM
RMSM
5.3-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Technical data
Communication times
5.3.4.2Processing time in the controller
The processing time of the controller is added to the INTERBUS cycle time.
The processing time of the controller depends on the series and version:
Processing t ime 820X
For the 820X series several processing steps are required. These steps are
processed cyclically.
A processing cycle consists of:
l Writing of c ontrol word or setpoint, if the value has changed
l Alternating reading of status word and actual value
l Processing of PCP parameter access, if there is a service.
)
)Note!
))
A change of the setpoint signal results in writing the control word.
5.3
5.3.4
Processing t ime 821X /
8200 vector / 822X
If the time tolerances caused by cyclic reading of the status word/ actual value are
too large, the alternating reading of the status word and the actual value can be
suppressed. This is controlled by bit 15 (PE inhibit) of the DRIVECOM control
(¶ 5.6-35).
word:
A suppression of the processing of parameter access is not necessary, since this
is controlled by the user.
In the following table you will find a list of the processing times:
Processing stepMax. processing time
Parameter70-8Setpoint35-8180
Control word35-8180
Actual value35-8180
Status word35-8180
Setpoint + control word70-16180
Setpoint + control word + actual
value + status word
The parameter data (transmission via PCP channel) and process data are
independent of each other.
l Parameter data (PCP): approx. 30 ms + 20 ms tolerance
l Process data (PD): approx. 3 ms + 2 ms tolerance
[ms]
140-32180
Processing tolerance
[ms]
Additional parameter
[ms]
Processing t ime 9300 servo
inverter
Processing t ime Drive PLC / 9300
Servo PLC
L
The parameter data (transmission via PCP channel) and process data are
independent of each other.
l Parameter data (PCP): approx. 30 ms + 20 ms tolerance
l Process data (PD): approx. 2 ms + 1 ms tolerance
l Parameter data (PCP): 30 ms + 20 ms tolerance
l Process data (PD): depending on process image
EDSIBS-1.0-06/ 2003
5.3-3
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.3
5.3.5
5.3.5Dimensions
DRIVE
BUS
b
24V DC
+
a61mm
b75mm
e28mm
e118 mm
L
INTERBUS S
IN
OUT
_
2111
a
18
Technical data
Dimensions
e1
e
2111IBU005
5.3-4
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
0
1
Show/Hide Bookmarks
5
Installation
Components of the fieldbus module
5.4Installation
5.4.1Components of the fieldbus module
2
1
0
DRIVE
BUS
L
INTERBUS S
IN
3
4
5
24V DC
+
_
OUT
6
Fig. 5.4-1Components of the fieldb us module
5.4
5.4.1
7
2111
2111IBU004
PosLED statu sExplanation 3
0
1
2
3
4
5
6
7
Green bus LED (voltage supply)
ONThe fieldbus module is supplied with voltage and is connected to the drive controller.
OFFThe fieldbus module is not supplied with voltage. The drive controller or external
voltage supply is switched off.
BLINKINGThe fieldbus module is supplied with voltage, but it is not connected to the drive
controller, because
• the fieldbus module was not plugged on the drive controller correctly
• the data transfer of/to the drive controller is not possible (e. g. the drive controller
is in the initialisation phase).
Yellow bus LED (communication)
ONFieldbus module is initialised,
inactive INTERBUS communication of the master
OFFFieldbus module is not initialised yet
BLINKINGActive INTERBUS communication
• SLOW (1 Hz): process data and PCP communication.
• FAST (4 Hz): only process data
Red and green drive LED indicate the operating mode of the drive controller 82XX or 93XX (see the
Operating Instructions of the drive controller)
INTERBUS input (IN), Sub-D plug connector, 9-pole
INTERBUS output (OUT), Sub-D socket connector, 9-pole
Plug connector, connection for external voltage supply
PE connection
Fixing screw
^ 5.4-6
^ 5.4-7
^ 5.4-5
see note
L
)
)Note!
))
Only for 820X and 821X: If required use an additional PE screen
cable which avoids EMC-related communication interference in
surroundings with interferences.
EDSIBS-1.0-06/ 2003
5.4-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.4
5.4.2
5.4.2Mechanical installation
l Plug the fieldbus module onto the basic device (here: 8200 vector).
l Fasten the fieldbus module with the fixing screw onto the basic device to
ensure a good PE connection.
Installation
Mechanical installation
4 2102LEC014
)
)Note!
))
For the internal supply of the fieldbus module through the 8200
vector frequency inverter the interface of the jumper must be
adapted (see illustration above). Please observe the notes
^ 5.4-5.
5.4-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Installation
Electrical installation
5.4.3Electrical installation
Wiring to the INTERBUS master
)
)Note!
))
l The bus system must be designed as a ring.
l Go-and-return lines are both in the same bus cable.
l The ring connec ts the INTERBUS master with all devices connected to the
bus.
5.4
5.4.3
An additional mains isolation is required, if
l a 820X or 821X is connected to an INTERBUS master and
l a safe mains isolation (double basic insulation) is required
according to VDE 0160.
Use e.g. a bus terminal or an interface module for the INTERBUS
master with an additional mains isolation (see the corresponding
information of the manufacturer).
Only necessary if the mains which supply the corresponding controllers is to be switched
off but the communication must not be interrupted.
rigid: 1.5 mm2(AWG 16)
flexible:
without wire crimp cap
2
(AWG 16)
1.5 mm
with wire crimp cap, without plastic sleeve
2
(AWG 16)
1.5 mm
with wire crimp cap, with plastic sleeve
2
(AWG 16)
1.5 mm
5.4
Internal DC voltage supply 8
)
)Note!
))
Basic devices with extended AIF interface opening (8200 vector
front) can be internally supplied. The part of the drawing
highlighted in grey shows the jumper position.
l In the delivery state of the frequency inverter these are not
internally supplied.
l For internal voltage supply, put the jumper in the position
4. Then select „ Planning“. A list for field assignment (field names) is displayed.
Please enter the following values:
Field nameEntryExplanation
Module/PD
length
Module ID227Module identification
CR2 or higherCommunication reference for PCP communication
5. Select the menu „ File“ .
2
2
3
Process-data length in words (16 bit each)
for 82XX
for 93XX Lenze sett i ng (L-C1910 = 4)
for 93XX, when code L-C1910 = 6
L
6. Then select the menu point „ Save planning data“.
– Before saving the new settings, mark the options not to be executed:
( ) NO bus start
( ) NO communication initialization
()NOtransferstop
Mark the options not to be executed.
– Save your settings
7. Close the program „ SYSSWT“.
EDSIBS-1.0-06/ 2003
5.5-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.5
5.5.3
Different program
Commissioning
Start up of the 2111 fieldbus module
If you d o not use t he program ” SYSSWT” , the following settings must be mad e:
NameEntryExplanation
Module/PD length
2
2
3
Module ID227Module identification
Tab. 5.5-1Process-data communication
NameEntryExplanation
COM_REF2 or higherCommunication reference (CR)
CONN_TYPEAcyclic
master/slave
CONN_ATTRDefinedConnection attribute
Max PDU sending high prio0Sending history high priority
Max PDU sending low prio64Sending history low priority
Max PDU receiving high prio0Receiving history high priority
Max PDU receiving low prio64Receiving history low priority
Supported service request803000
Supported Services Response000000
Maximum SCC1
Maximum RCC0
Maximum SAC0
Maximum RAC0
Process-data length in words (16 bit each)
for 82XX
for 93XX Lenze sett i ng (L-C1910 = 4)
for 93XX, when code L-C1910 = 6
Connection type
hex
hex
Supported service, master request
Supported service, slave response
Tab. 5.5-2PCP communication
5.5.3Start up of the 2111 fieldbus module
1. The fieldbus module must be attached to the controller (¶ 5.4- 2).
2. Switch on the controller and, if required, the external voltage supply of the
2111 fieldbus module.
3. Check fieldbus module signals:
– The green bus LED indicates the operating status according to the
corresponding description
– The yellow bus LED indicates the communication status according to the
description
– If the signals are different in any way please see the chapter
“Troubleshooting and fault elimination” .
4. You can now communicate with the drive.
– With a PCP communication it is only possible to access the parameters of
the controller after having executed the PCP service ” Initiate“
5. It is then possible to access the parameters via the PCP services ”Read“
and ” Write“
(¶ 5.4-1) Pos. 1.
(¶ 5.6-49).
(¶ 5.4-1) Pos. 0.
(¶ 5.6-49).
5.5-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Commissioning
Prepare controller for INTERBUS oper ation
5.5.4Prepare controller for INTERBUS operation
82XX / 8200 vector
PreparationNotes
1. L-C0001 (operating mode):
Change value from “0” to “3”
.
2. Terminal 28 (controller
enable) must be HIGH during
INTERBUS operation.
Terminal 28 is always
active!
The controller is now ready to accept process and parameter data from the INTERBUS.
For this use
• the 8201BB for 82XX and
• the keypad for 8200 vector
Alternative
Direct access to the code via INTERBUS.
Example
Set code L-C0001 t o “3” (PCP write):
à For conversion formula and parameter value range see ^ 5.6-46
8200 vector (up to SW version 1.1)
à C0410/y (y = 1...16) must be assigned to the AIF control word (AIF-CTRL)
Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for the
controller).
821X, 8200vector und 822X
With these controllers the QSP function is always active. If QSP is assigned to an
input terminal (default setting: not assigned), this terminal must be at HIGH level
during INTERBUS operation (see the corresponding Operating Instructions).
:
– Index: 5FFE
– Subindex: 0
– Value: 30000
i.e. C0410/1 = 10, C0410/2 = 11 .... C0410/16 = 25 (see Operating
Instructions for 8200 vector).
hex
dec
(= 5FFF
− (L-C0001)
hex
hex
5.5
5.5.4
)
93XX controllers
PreparationNotes
1. L-C0005: Set “xxx3”.Use the 9371BB keypad
Alternative:
Direct access to the code via INTERBUS.
For the first commissioning you should select the signal configuration 1013 (speed
control).
Example
Set code L-C0005 to “1013” (PCP write):
– Index: 5FFA
– Subindex: 0
– Value: 10130000
à For conversion formula and parameter value range see ^ 5.6-46
2. L-C0142 (autostart lock):
Set “0”.
3. Terminal 28 (controller
enable) must be HIGH during
INTERBUS operation.
Terminal 28 is always
active!
The controller is now ready to accept process and parameter data from the INTERBUS.
Only necessary with DRIVECOM control
Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for 93XX).
à With the signal configuration L-C0005=1013, the function QSP (quick stop) and
the CW/CCW changeover are assigned to the digital input terminals E1 and E2
and thus they are always active. For INTERBUS operation E1 must be set to
HIGH level (see Operating Instructions 93XX).
à With the signal configuration L-C0005=xx13, terminal A1 is switched as
voltage output. Thus, only the following terminals can be connected via cables:
– X5.A1 with X5.28 (ctrl. enable)
– X5.A1 with X5.E1 (CW/QSP)
hex
(5FFF
dec
− (L-C0005)
hex
hex
)
L
EDSIBS-1.0-06/ 2003
5.5-3
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.5
5.5.5
5.5.5Controller enable via DRIVECOM
Controllers can be controlled with DRIVECOM proc ess data. The INTERBUS
master has direct access to the process data. In the INTERBUS master, data are
stored in the I/O area.
l Controller enable: DRIVECOM process data word ” Control word”
l Display of actual controller status: DRIVECOM process data word ” Status
word”.
The controller can be enabled by changing to OPERATION ENABLED by means
of the DRIVECOM control word.
Afterwards, the controller can be controlled as usual, e.g. via terminals.
)
)Note!
))
If DRIVECOM control is active and the fieldbus module
l in the controller
– 82XX / 8200 vector “ controller inhibit” will be activated if
L-C0001 = 3.
– 93XX “ Controller inhibit” will always be active.
l the fieldbus module sets SWITCH ON INHIBIT.
Commissioning
Controller enable via DRIVECOM
Enable the controller as follows:
1. Select speed setpoint (2nd process data word; PD2), value
2. Change to ” READY FOR SWITCH ON“
PD output word1 = 0000 0000 0111 1110
3. Wait for the status ” READY FOR SWITCH ON“.
PD input word1 = xxxx xxxx x01x 0001
The DRIVECOM profile 21 is a specification of important parameters and unit
performance of several manufacturers. The DRIVECOM profile 21 mainly
describes the unit control and a speed operating mode. In addition to the
DRIVECOM specifications there are further Lenze-specific functions, e.g.
digital-frequency connection or DCinjection-brake. These manufacturer-specific
specifications require minor changes in the settings to comply with the desired
DRIVECOM compatibility. In the following, you will find the changes required for
the Lenze controllers.
820XWith 820X controllers, parameters can only be set when the controller is inhibited.
821X,
8200 vector
and 822X
93XXSet the controller parameters for INTERBUS control, e.g. L-C0005=1013
9300 Servo
PLC
Drive PLCIt is necessar y to use the device control for the DRIVE PLC.
5.5
5.5.6
The controller is inhibited in DRIVECOM status.
• ”SWITCH-ON INHIBIT”
• ”READY FOR SWITCH ON”
• ”SWITCHED ON”
• ”TRIP”
The automatic DC-injection brake must be deactivated in all parameter sets, i. e.
• L-C0106=0
• L-C2106=0
• L-C4106=0 (only 8200 vector)
• L-C6106=0 (only 8200 vector)
If the automatic DC-injection brake is not deactivated (holding time o f the DC-injection brake L-C0106
not 0), the controller automatically switches from the status ”OPERATION ENABLED” to the status
”SWITCHED ON” when the speed is 0 and the holding time of the DC-injection brake is elapsed. If the
setpoint is higher than 0, the controller is automatically reset to the status ”OPERATION ENABLED”.
This configuration corresponds to t he signal configuration 1000 with the following changes:
• Setpoint selection with INTERBUS
• Unit control with INTERBUS
• Output X5.A1 is selected as voltage output for the internal supply of the digital inputs.
• Actual values and status signals for INTERBUS
For the detailed description of the signal configuration, see 93XX Manual.
The following links must be made in the PLC program.
• AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
• DCTRL_wStat W AIF1_wDctrlStat
L
EDSIBS-1.0-06/ 2003
5.5-5
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.5
5.5.7
Special features when using 82XX, 8200 vector and 93XX
5.5.7Special features when using 82XX, 8200 vector and 93XX
}
}Danger!
}}
Please note
l For safe operation it is absolutely necessary to observe the
notes for the controllers given in this chapter.
l Please observe the corresponding Operating Instructions of the
controllers.
820X• Parameter setting (codes except process data) is only possible when the controller is inhibited
8200 vector • Digital and analog input and output signals can be freely configured (see Operating Instructions for
93XX• Set the signal configuration L-C0005 = xxx3 instead of the operating mode L-C0001.
(DRIVECOM controller status unequal ”OPERATION ENABLED“). Parameters are accepted when the
controller is enabled, but they are not saved.
• A TRIP must only be reset through INTERBUS:
If the controller is set to the status TRIP while being operated with INTERBUS control
(L-C0001 = 3) and if the TRIP is reset through terminal 28, the drive can start for a short time.
When resetting a fault via INTERBUS, this does not occur.
• Aft er the command ”TRIP reset“ the 820X controller is basically initialized. During this time the
controller does not accept any services.
• Always send the direction of rotation with a low setpoint before the new setpoint:
If the setpoint and the direction of rotation are changed at the same time via the DRIVECOM speed
setpoint, the speed can change to the wrong direction or rotation for a short time. This is because
the setpoint is sent to the controller as unipolar value before and the information about the
direction of rotation is sent.
8200 vector; codes L-C0410, L-C0412, L-C0417 a nd L-C0421)
• A change of code L-C0001 to “3“ preconfigures the process data words in the controller.
• The change o f the code L-C0005 to xxx3 starts the preconfiguration of the process data words in
the controller
• Set the parameter L-C0142 = 0 (auto start lock), to avoid a short time start of the drive during the
initialization phase.
Commissioning
5.5-6
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
5.6Data transfer
5.6
INTERBUS master and slave communicate by sending data telegrams via the
INTERBUS.
The user data of the data telegram contains parameter data
Different communication channels are assigned to parameter and process data:
Telegram typeCommunication channel
Process data,
• Setpoints
• Actual values
Parameter data
• Operating parameters
• diagnostics information
• moto r data
Tab. 5.6-1Division of p arameter data and p rocess d ata into different c ommunication channels
The following describes the communication protocol only as much as needed for
networking Lenze controllers.
Process-data channel• Exchange between INTERBUS master and
Parameter data channel
or “PCP channel”
(PCP = Peripherials
Communication Protocol)
controller required as fast as possible. Small
amounts of data for cyclic data transfer.
• The INTERBUS master has direct access to the
process data.
• Process data can control the controller.
• Process data are
– not stored in the controller.
– exchanged between INTERBUS master and
controllers to ensure a constant update of
input and output data.
• In general, the parameter transfer is not as
time-critical as the tranfer of process data.
• Enables access to all Lenze codes and indexes.
or process data.
L
EDSIBS-1.0-06/ 2003
5.6-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.1
5.6.1Process data channel configuration
5.6.1.1Process data transfer
Process data telegrams between INTERBUS master and the controllers
connected to the INTERBUS are divided into:
l Process data telegrams from drive (PI)
l Process data telegrams to drive (PO)
)
)Note!
))
As agreed, the data flow is described from the INTERBUS
master’s view:
l PI data of the INTERBUS master are output data for the
controller.
l PO data of the INTERBUS master are input data for the
controller.
Data transfer
Process data channel configuration
Process data telegram from
drive
Process data telegram to
drive
For the cyclic process data telegram from
is called AIF-OUT. The status word included in the process data telegram (byte
1 and byte 2) is sent to the INTERBUS master via this function block.
For the cyclic process data telegram to
is called AIF-IN. The control word included in the process data telegram (byte 1
and byte 2) is sent to the INTERBUS master via this function block.
the drive, the func tion block to be used
the drive, the function block to be used
5.6-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data channel configuration
5.6.1.2Setpoint source selection
82XX controllers
Controller 8200 vector
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
is set to ”3” when the controller is operated together with the fieldbus module. The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
)
)Note!
))
The setpoint source selection for these controllers is determined under code
L-C0001 (5FFE
is set to ”3” when the controller is operated together with the fieldbus module. The
process data channel which describes the frequency setpoint (L-C0046) and the
control word (parameter channel, L-C0135) is the setpoint source
5.6.1
).An evaluation of process data is only possible if code L-C0001
hex
.
Please ensure that the setpoint source (L-C0001) is the same for
all parameter sets used.
).An evaluation of process data is only possible if code L-C0001
hex
.
5.6
93XX controllers
Servo PLC 9300 / Drive PLC
Check in L-C0412/ x whether the assignment of setpoint source and analog signal
is correct and change, if necessary.
)
)Note!
))
Please ensure that the setpoint source selection (L-C0001) is the
same for all parameter sets used.
The value in code C0005 must be set to ” xxx3” for bus operation (x = selected
preconfiguration).
Communication requires that AIF-IN 1 ... 3 or AIF-OUT 1 ... 3 and if available
AIF management are part of the control configuration of the IEC61131 project.
the
L
EDSIBS-1.0-06/ 2003
5.6-3
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.1
5.6.1.3Process data configuration
Some data important for the process must be transmitted as quickly as possible.
These data are called process data and stored in the I/O area of the controller for
access from the INTERBUS master.
The process data are cyclically exchanged between the controller and the
INTERBUS master.
Theprocess data of a Process-data configuration have a certain ”Process data
structure“.
The process-data structure is subdivided into
l Process input data (PI data, index = 6000
l Process output data (PO data, index = 6001
The controller receives control information from the INTERBUS master and sends
status information to the master.
The Lenze setting for the process-data length is 4 byte.
The PD length is set under code L-C1910.
Data transfer
Process data channel configuration
, (¶ 5.6-5))
hex
, (¶ 5.6-5))
hex
)
)Note!
))
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “0” under L-C1911.
Different controller signals can be assigned to the PI and PO data
words (see
(¶ 5.6-6)).
5.6-4
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
M
g
y
Show/Hide Bookmarks
5
Data transfer
Process data channel configuration
PI data description (6000
hex
)9
The parameter describes the process data which are sent from the controller to
the INTERBUS master (input data for the INTERBUS master). Parameters of the
described process data assignment of Lenze controllers can be assigned to the
subindex values (see
changed.
Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).
Parameter name (Index)SubindexData structureData type
PI data description (6000
)
)Note!
))
Subindex
1Number of process data [byte]04
2Index PI data word 16041
3Subindex PI data word 100
4/5No entry00
6Index PI data word 26044
7Subindex PI data word 200
8/9No entry00
10Index PI data word 35CA5
11Subindex PI data word 303
12/13No entry00
(¶ 5.6-6)). Exception: The value for subindex 1 cannot be
)1 ... 13RPBS(20
hex
hex
)
Only the valid subindex is displayed with the parameter 6000
It is determined by PD!
eaning
Value
Lenze settingNotes
hex
DRIVECOM status word
hex
DRIVECOM speed
hex
AIF-OUT.W2
hex
Of if code
L-C1910 = 6
5.6.1
hex
5.6
.
PO data description (6001
hex
)10
The parameter describes the process data which are sent to the controller from
theINTERBUSmaster (output data for the INTERBUS master).Parameters of the
described proc ess data of Lenze controllers can be assigned to subindex values
(¶ 5.6-6)). Exception: The value for subindex 1 cannot be changed.
(see
Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).
Parameter name (Index)Subindex Data structureData type
PO data description (6001
SubindexMeaning
1Number of process data
[byte]
2Index PO data word 16040
3Subindex PO data word 100
4/5No entry001
6Index PO data word 26042
7Subindex PO data word 200
8/9No entry003
10Index PO data word 35CA7
11Subindex PO data word 303
12/13No entry005
)1 ... 13RPBS(20
hex
Lenze setting
Value
04
hex
DRIVECOM control word0
hex
DRIVECOM speed setpoint2
hex
AIF-IN.W24
hex
hex
)
hex
index
6002 / Bit
Notes
Only if
L-C1910 = 6
L
EDSIBS-1.0-06/ 2003
5.6-5
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
5.6.2Process data signals of Lenze controllers
5.6.2.1Process data signals for frequency inverters 82XX
Process data telegram from
drive
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindex NameExplanationLenze setting:
60410DRIVECOM status wordPI data word 1^ 5.6-38
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 5.6-41
60540DRIVECOM actual
percentage value
5F690Device status word
(L-C0150)
5CA51AIF-OUT.W1AIF word 1
Data transfer
Process data signals of Lenze controllers
see
^ 5.6-42
Table below
Actual speed [%]
100% = 16383
Index 6000
hex
5.6-6
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Device status word AIF- STAT for 82XX (Lenze code C0150, index 5F69
Bit820X821x, 822x
0Actual parameter set0=Parameterset1or3active
1=Parameterset2or4active
1IMP (pulse inhibit)0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
2I
(current limit reached)0 = Current limit not reached
max
1 = Current limit reached
3not assignedfd=f
4fd=f
5Qmin (f
dset
≤ f
)0 = Qmin not active
d
dQmin
6fd+ 0 (act. frequency = 0)0=f
0=f
≠ f
d
dset
1=fd=f
dset
1=Qminactive
≠ 0
d
+0
1=f
d
7Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
1 = Controller inhibited
8...11 Controller status0 = Unit initialisation
8 = Error active
12Overtemperature warning0=Nowarning
1=Warning
13V
(DC-bus overvoltage)0 = No overvoltage
Gmax
1 = Overvoltage
14Direction of rotation0 = CW rotation
1 = CCW rotation
15Ready for operation0 = Not ready for operation
1 = Ready for operation
)
hex
Actual parameter set0=Parameterset1or3active
IMP (pulse inhibit)0 = Pulses for power stage enabled
I
(current limit reached)0 = Current limit not reached
max
dset
RFG on = RFG off0=RFGon≠ RFG off
Qmin (f
d
fd+ 0 (act. frequency = 0)0=f
Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
Controller status0 = Controller initialization
Overtemperature warning0=Nowarning
V
(DC-bus overvoltage)0 = No overvoltage
Gmax
Direction of rotation0 = CW rotation
Ready for operation0 = Not ready for operation
1=Parameterset2or4active
1 = Pulses for power stage inhibited
1 = Current limit reached
0=f
1=fd=f
1 = RFG on = RFG out
≤ f
)0 = Qmin not active
dQmin
1=Qminactive
1=f
1 = Controller inhibited
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
1=Warning
1 = Overvoltage
1 = CCW rotation
1 = Ready for operation
5.6
5.6.2
≠ f
d
dset
dset
≠ 0
d
+0
d
- / fd=fdset
fd=fdset / RFG
ctrl. inhibit
B11 B10 B9 B8
0
0
0
1
0
0
1
0
0
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
PAR
IMP
Imax
Qmin
fd>0
STAT
0
0
2
0
3
1
.
.
.
.
.
.
Vgmax
RDY
C0050
.
.
.
.
.
.
T
R/L
.B0
.B1
.B2
.B3
.B4
.B5
.B6
.B7
.B8
16 bits
.B9
.B10
.B11
ü
.B12
.B13
.B14
.B15
AIF
16 bits
2141LON012_en
Fig. 5.6-1Read access to status word and actual frequency in 82XX (fixed assignment)
L
EDSIBS-1.0-06/ 2003
5.6-7
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
Process data telegram to drive
Data transfer
Process data signals of Lenze controllers
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindex NameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 5.6-35
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
1AIF-IN.W1AIF word 1. See the
5CA7
)
)Note!
))
setpoint
setpoint
(L-C0135)
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “0” under L-C1911.
Speed setpoint [rpm] PO data word 2^ 5.6-41
Speed setpoint [%]
100% = 16383
following description.
Index 6001
hex
see
^ 5.6-42
Table below
5.6-8
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
0
0,0
1
01JOG1activeinC0037
R
d
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Control w ord AIF- CTRL for 82XX (Lenze code C0135, index 5F78
Bit820X821x, 822x
00 = C0046 active
01 = JOG1 active in C0037
10 = JOG2 active in C0038
11 = JOG3 active in C0039
02CW/CCW (CW rotation/
03QSP (quick stop)0 = QSP not active
04RFG stop (stop of the ramp function generator)0 = RFG stop not active
05RFG zero (deceleration along the Tiframp C0013)0 = RFG zero not active
06
07DOWN function for motor potentiometer0 = DOWN not active
08Reserved
09Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
10
11
12PAR1 (Parameter set changeover)0 -> 1 = Parameter set
13ReservedReserved
14DC brake (DC injection brake)0 = DC brake not active
15ReservedReserved
CCW rotation)
Reserved
eserve
0 = CW rotation
1 = CCW rotation
1=QSPactive
1 = Controller inhibited
1 -> 0 = Parameter set
1 = DC brake active
)
hex
00 = C0046 active
01 = JOG1 active in C0037
10 = JOG2 active in C0038
11 = JOG3 active in C0039
CW/CCW (CW rotation/CCW rotation)0 = CW rotation
QSP (quick stop)0 = QSP not active
UP function for motor potentiometer0=UPnotactive
Ctrl. inhibit (controller inhibit)0 = Controller not inhibited
Reserved
TRIP reset0 -> 1 = Edge from 0 to 1
PAR1 (Parameter set changeover)0 -> 1 = Parameter set
DC brake (DC injection brake)0 = DC brake not active
1 = CCW rotation
1=QSPactive
1=RFGstopactive
1=RFGzeroactive
1=UPactive
1 = DOWN active
1 = Controller inhibited
1 -> 0 = Parameter set
1 = DC brake active
5.6
5.6.2
AIF
16 bits
16 bits
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B12
.B13
.B14
.B15
0
011
JOG/
C046
0101
QSP
...
...
...
CINH
TRIP-SET
TRIP-RESET
C0046
Fig. 5.6-2Access to c ontrol word and actual frequency in 82XX (fixed assignment)
CW/
CCW
PAR
DC
brake
2141LON010_en
L
EDSIBS-1.0-06/ 2003
5.6-9
5
C
A
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
5.6.2.2Process data signals for 8200 vector frequency inverters
The function block AIF (AIF=automation interface) is the data interface between
the 8200 vector and the fieldbus module. The function block consists of AIF-OUT
and AIF-IN.
Process data telegram from
drive
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindex NameExplanationLenze setting:
60410DRIVECOM status wordPI data word 1^ 5.6-38
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 5.6-41
60540DRIVECOM actual
5F690Device status word
1AIF-OUT.W1AIF word 1
5
5
2AIF-OUT.W2AIF word 2PI data word 3
AIF-OUT.Wx is parameterised under code L-C0421.
percentage value
(L-C0150)
Process data signals of Lenze controllers
Actual speed [%]
100% = 16383
Index 6000
Data transfer
see
hex
^ 5.6-42
Table below
5.6-10
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Controller status word AIF-STAT for 8200 vector (Lenze code C0150, index 5F69
AIF-STAT.BxxLenze settingAdjustable in code L-0417/..
Fig. 5.6-3Function b loc k AIF-OUT in 8200 vector (freely p rogrammable assignment)
AIF
2141LON013_en
L
EDSIBS-1.0-06/ 2003
5.6-11
5
C
A
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
Process data telegram to drive
Data transfer
Process data signals of Lenze controllers
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindexNameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 5.6-35
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
1AIF-IN.W1AIF word 1
5
7
2AIF-IN.W2AIF word 2
AIF-IN.Wx is parameterised under code L-C0412.
setpoint
setpoint
(L-C0135)
Speed setpoint [rpm]PO data word 2^ 5.6-41
Speed setpoint [%]
100% = 16383
Frequency and speed
are normalised with
24000 ≡ 480 Hz.
Frequency and speed
are normalised with
24000 ≡ 480 Hz.
Index 60001
PO data word 3
hex
see
^ 5.6-42
Table below
)
)Note!
))
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “0” under L-C1911.
5.6-12
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
00,
01NSET1JOG1(C0037)activ
e
1
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Control w ord AIF- CTRL for 8200 vector (Lenze code C0135, index 5F78
AIF-CTRL.BxxDefault setting:
00,
01
02DCTRL1-CW/CCW0=notactive
03AIF-CTRL-QSP0=notactive
04NSET1-RFG1-STOP0=notactive
05NSET1-RFG1-00=notactive
06MPOT1-UP0=notactive
07MPOT1-DOWN0=notactive
08Freely configurable by user9
09AIF-CTRL-CINH0=notactive
10AIF-CTRL-TRIP-SET0=notactive
11AIF-CTRL-TRIP-RESET0 -> 1 = Edge from 0 to 1 AIF-CTRL-TRIP-RESET0 -> 1 = Edge from 0 to 1 12
12DCTRL1-PAR2/40=notactive
13DCTRL1-PAR3/40=notactive
14MCTRL1-DCB0=notactive
15Freely configurable by userFreely configurable by user16
00 = C0046 active
01 = NSET1-JOG1 (C0037) a ct ive
10 = NSET1-JOG2 (C0038) a ct ive
11 = NSET1-JOG3 (C0039) a ct ive
C0001=3 if C0007
≤ 51
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
1=active
)
hex
Default setting:
C0001=3 if C0007 > 51
Freely configurable by user
AIF-CTRL-QSP0=notactive
Freely configurable by user
AIF-CTRL-CINH0=notactive
AIF-CTRL-TRIP-SET0=notactive
Freely configurable by user
1=active
1=active
1=active
5.6
5.6.2
Adjustable in L-C0410/..
1
2
3
4
5
6
7
8
10
11
13
14
15
AIF
AIF-CTRL
16 bits
16 bits
16 bits
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B12
.B15
AIF-IN
DCTRL
QSP
...
...
...
...
...
...
Fig. 5.6-4Function b lock AIF-IN in 8200 vector (freely programmable assignment)
...
...
...
DCTRL
CINH
TRIP-SET
TRIP-RESET
...
...
...
AIF-IN.W1
AIF-IN.W2
2141LON011_en
L
EDSIBS-1.0-06/ 2003
5.6-13
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
5.6.2.3Process data signals for servo inverters 9300
The function block AIF (AIF = automation interface) is the data interface between
the 93XX controller and the fieldbus module. The function block consists of
AIF-OUT and AIF-IN.
With the 93XX controller the process data assignment can be changed by
reconfiguring the function blocks AIF-IN and AIF-OUT.
Data transfer
Process data signals of Lenze controllers
5.6-14
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Process data telegram from
drive
ThefollowingparameterscanbeassignedtothePI-data:
IndexSubindex Name (same in
60410DRIVECOM status wordPI data word 1^ 5.6-38
60440DRIVECOM speedActual speed [rpm]PI data word 2^ 5.6-41
60540DRIVECOM actual
5F690Device status word
5CA51AIF1-OUT.W1AIF word 1
5CA52AIF1-OUT.W2AIF word 2PI data word 3
5CA53AIF1-OUT.W3AIF word 3
5CA40AIF1-OUT.D1AIFdoubleword
The assignment of AIF-OUT depends on the signal configuration selected under
L-C0005:
Signal
configuration
(L-C0005)
Speed control
1003
1013
1113
Torque control
4003
4013
4113
DF master
5003
5013
5113
DF-slave bus
6003
6013
6113
DF-slave cascade
7003
7013
7113
Not equal to xxx3
(except self
configurations)
IEC1131)
percentage value
(AIF1_Stat)
AIF-OUT.W1AIF-OUT.W2AIF-OUT.W3AIF-
MCTRL-NACT
Actual speed
100%=16383
MCTRL-MSET2
Torque display
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
MCTRL-NACT
Actual speed
100%=16383
ExplanationLenze setting:
Actual speed [%]^ 5.6-42
MCTRL-MSET2
Torque display
100%=16383
MCTRL-NACT
Act. speed in %
100%=16383
MCTRL-MSET2
Torque display
100%=16383
MCTRL-PHI-ACT
Actual phase
MCTRL-PHI-ACT
Actual phase
MCTRL-MSET2
Torque display
100%=16383
Index 6000
hex
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-NSET2
Speed controller input
100%=16383
MCTRL-MSET2
Torque setpoint in %
100%=16383
MCTRL-MSET2
Torque setpoint in %
100%=16383
MCTRL-PHI-ACT
Actual phase
see
Table below
OUT.D1
not
assigned
not
assigned
not
assigned
not
assigned
not
assigned
not
assigned
5.6
5.6.2
L
For detailed description of the 93XX signal configuration see the Operating
Instructions for 93XX (only the main configurations: 1000, 4000, 5000, etc.) or the
Manual 93XX.
In the c ontroller, other signals can be assigned to AIF-OUT.W1 to AIF-OUT.W3.
For this, thefunction-block configuration - described in the Manual 93XX- is used.
The function block AIF-OUT determines the output data of the controller as data
interfac e for the 2133 fieldbus module.
For more detailed information about the function block AIF-OUT, see the Manual
93XX.
EDSIBS-1.0-06/ 2003
5.6-15
5
8...1
1
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
Process data signals of Lenze controllers
Data transfer
Controller status word AIF-STAT for 93XX
9300 Servo9300 POS9300 CRV9300 Vector
L-C0005:
1xxx, 2xxx,
Bit..
1xx34xx35xx36xx3,7xx32xxx3xxx3
3xxx, 5xxx,
4xx36xx3,7xx3
10xxx, 11xxx
0DCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0 not assignedCERR1-ERRDCTRL-PAR1-0 DCTRL-PAR1-0 DCTRL-PAR1-0
1DCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMPDCTRL-IMP
2MCTRL-IMAXMCTRL-IMAXREF-OKREF-OKPOS-REF-OKMCTRL-IMAXMCTRL-IMAXMCTRL-IMAXMCTRL-IMAX
3MCTRL-MMAX not assignedMCTRL-MMAX not assignednot assignedMCTRL-MMAX MCTRL-MMAX MCTRL-IMAX
Fig. 5.6-5Function b loc k AIF-OUT (function block extension on grey b ackground: available as
of software version 2.0 on)
5.6-16
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
notassignednotassigne
d
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Process data telegram to drive
ThefollowingparameterscanbeassignedtothePO-data:
IndexSubindex NameExplanationLenze setting:
60400DRIVECOM control wordPO data word 1^ 5.6-35
60420DRIVECOM speed
60520DRIVECOM percentage
5F780Device control word
5CA71AIF-IN.W1AIF word 1
5CA72AIF-IN.W2AIF word 2PO data word 3
5CA73AIF-IN.W3AIF word 3
5CA60AIF-IN.D1AIFdoubleword
)
)Note!
))
5.6.2
see
^ 5.6-42
Table below
setpoint
setpoint
(AIF1_CTRL)
Index 6001
Speed setpoint [rpm] PO data word 2^ 5.6-41
Speed setpoint [%]
100% = 16383
hex
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “0” under L-C1911.
5.6
The assignment of AIF-IN.W1 to AIF-IN.W3 depends on the signal configuration
selected under L- C0005:
Signal configuration
(L-C0005)
Speed control
1003 / 1013 / 1113
Torque control
4003 / 4013 / 4113
DF master
5003 / 5013 / 5113
DF-slave bus
6003 / 6013 / 6113
DF-slave cascade
7003 / 7013 / 7113
not equal to xxx3not assignednot assigned
AIF-IN.W1AIF-IN.W2AIF-IN.W3AIF-IN.D1
NSET-N
Speed setpoint
MCTRL-MADD
Torque setpoint
NSET-N
Speed setpoint
DFSET-A-TRIM
Phase trimming
DFSET-VP-DIV
DF factor
not assigned
not assigned
not assigned
not assignednot assigned
DFSET-N-TRIM
Speed trimming
DFSET-A-TRIM
Phase trimming
For detailed description of the 93XX signal configuration see the Operating
Instructions for 93XX (only the main configurations: 1000, 4000, 5000, etc.) or the
Manual 93XX.
In the controller, other signals can be assigned to AIF-IN.W1 to AIF-IN.W3. For
this, the function-block configuration - described in the Manual 93XX - is used.
The function block AIF-IN determines the input data of the controller as data
interfac e for the 2133 fieldbus module.
For more detailed information about the function block AIF-IN, see the Manual
93XX.
A I F - C T R L . B 6
A I F - C T R L . B 7
A I F - C T R L . B 1 2
A I F - C T R L . B 1 3
A I F - C T R L . B 1 4
A I F - C T R L . B 1 5
A I F - I N . W 1
A I F - I N . D 2
A I F - I N . W 2
A I F - I N . W 3
A I F - I N . B 0
A I F - I N . B 2
A I F - I N . B 1 4
A I F - I N . B 1 5
A I F - I N . B 1 6
A I F - I N . B 1 7
A I F - I N . B 3 0
A I F - I N . B 3 1
A I F - I N . D 1
A I F - C T R L . B 3
A I F - C T R L . B 8
A I F - C T R L . B 9
A I F - C T R L . B 1 0
1 6 b i t s
C 0 1 3 6 / 3
1 6 b i t s
1 6 b i t s
1 6 b i t s
C 0 8 5 5 / 1
1 6
b i n a r y
s i g n a l s
C 0 8 5 5 / 2
1 6
b i n a r y
s i g n a l s
1 6 b i t s
L o w W o r d
1 6 b i t s
H i g h W o r d
A I F - C T R L . B 1 1
1 6 b i t s
L o w W o r d
1 6 b i t s
H i g h W o r d
C 0 8 5 6 / 2
C 0 8 5 6 / 3
C 0 8 5 7
B i t 0
C o n t r o l w o r r d
B i t 1 5
B y t e 3 , 4B y t e 5 , 6
1
B y t e 7 , 8
5.6-18
2113IBU008_en
Fig. 5.6-6Function b loc k AIF-IN (grey: Extension available as of software version 2.0)
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
5.6.2.4Process data signals for 9300 servo PLC and Drive PLC
Process data telegram from
drive
The following data can be assigned to the PE data:
IndexSubindex Name/variable nameExplanationLenze setting: Ind ex 6000
6041 0DRIVECOM status wordPI data word 1
6044 0DRIVECOM speedActual speed [rpm]PI data word 2
6054 0DRIVECOM actual percentage
value
5F69 0Device status word
(AIF1_DctrlStat)
5CA5 1AIF_nOutW1_aAIF word 1
5CA5 2AIF_nOutW2_aAIF word 2PI data word 3
5CA5 3AIF_nOutW3_aAIF word 3
5CA5 4AIF2_nOutW1_aAIF word 4
5CA5 5AIF2_nOutW2_aAIF word 5
5CA5 6AIF2_nOutW3_aAIF word 6
5CA5 7AIF2_nOutW4_aAIF word 7
5CA5 8AIF3_nOutW1_aAIF word 8
5CA5 9AIF3_nOutW2_aAIF word 9
5CA5 10AIF3_nOutW3_aAIF word 10
5CA5 11AIF3_nOutW4_aAIF word 11
5CA4 0AIF1_dnOutD1_pAIFdoubleword1
5.6
5.6.2
hex
Actual speed [%]
)
)Note!
))
9300 Servo PLC
Please execute the following logic operations in the PLC program
of the controller:
AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
DCTRL_wStat W AIF1_wDctrlStat
Drive PLC
It is necessary to use the device control for the Drive PLC.
L
EDSIBS-1.0-06/ 2003
5.6-19
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
AIF1_wDctrlStat
AIF1_nOutW1_a
AIF1_nOutW2__a
AIF1_bFDO0_b
AIF1_bFDO15_b
AIF1_nOutW3_a
AIF1_bFDO16_b
AIF1_bFDO31_b
…
…
AIF1_dnOutD1_p
C0858/1
C0858/2
C0858/3
C0859
16 bits
16 bits
16 bits
C0151/4
16 binary
signals
16 bits
C0151/4
16 binary
signals
16 bits
Low Word
16 bits
High Word
Outputs_AIF1
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Data transfer
Process data signals of Lenze controllers
AIF2_nOutW1_a
1
2
3
4
5
6
7
8
Automation
Interface
AIF2_bFDO0_b
...
AIF2_bFDO15_b
AIF2_nOutW2_a
AIF2_bFDO16_b
...
AIF2_bFDO31_b
AIF2_dnOutD1_p
AIF2_nOutW3_a
AIF2_nOutW4_a
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
Outputs_AIF2
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
1
2
3
4
5
6
7
8
Automation
Interface
AIF3_nOutW1_a
AIF3_bFDO0_b
...
AIF3_bFDO15_b
AIF3_nOutW2_a
AIF3_bFDO16_b
...
AIF3_bFDO31_b
AIF3_dnOutD1_p
AIF3_nOutW3_a
AIF3_nOutW4_a
Fig. 5.6-7Function b locks AIF-OUT1, AIF-OUT2 and AIF-OUT3
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
Outputs_AIF3
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
1
2
3
4
5
6
7
8
Automation
Interface
5.6-20
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data signals of Lenze controllers
Process data telegram to drive
The following data can be assigned to the PA data:
Index Subindex Name/variable nameExplan ationLenze setting: Index 6001
6040 0DRIVECOM control wordPO data word 1
6042 0DRIVECOM speed setpointSpeed setpoint [rpm] PO data word 2
6052 0DRIVECOM percentage setpointSpeed setpoint [%]
5F78 0Device control word (AIF1_wDctrlCtrl)
5CA7 1AIF1_nInW1_aAIF word 1
5CA7 2AIF1_nInW2_aAIF word 2PO data word 3
5CA7 3AIF1_nInW3_aAIF word 3
5CA7 4AIF2_nInW1_aAIF word 4
5CA7 5AIF2_nInW2_aAIF word 5
5CA7 6AIF2_nInW3_aAIF word 6
5CA7 7AIF2_nInW4_aAIF word 7
5CA7 8AIF3_nInW1_aAIF word 8
5CA7 9AIF3_nInW2_aAIF word 9
5CA7 10AIF3_nInW3_aAIF word 10
5CA7 11AIF3_nInW4_aAIF word 11
5CA6 0AIF1_dnInD1_pAIFdoubleword1
5.6
5.6.2
hex
)
)Note!
))
9300 Servo PLC
Please execute the following logic operations in the PLC program
of the controller:
AIF1_wDctrlCtrl W DCTRL_wAIF1Ctrl
DCTRL_wStat W AIF1_wDctrlStat
Drive PLC
It is necessary to use the device control for the Drive PLC.
L
EDSIBS-1.0-06/ 2003
5.6-21
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.2
Automation
Interface
Inputs_AIF1
Byte
1
Controlword
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
16 bits
16 binary
signals
16 bits
16 bits
C0855/1
16 binary
signals
16 bits
C0855/2
16 binary
signals
16 bits
Low Word
16 bits
High Word
C0856/1
C0856/2
C0856/3
C0857
AIF1_wDctrlCtrl
AIF1_bCtrlB0_b
AIF1_bCtrlB1_b
AIF1_bCtrlB2_b
AIF1_bCtrlQuickstop_b
AIF1_bCtrlB4_b
AIF1_bCtrlB5_b
AIF1_bCtrlB6_b
AIF1_bCtrlB7_b
AIF1_bCtrlDisable_b
AIF1_bCtrlCInhibit_b
AIF1_bCtrlTripSet_b
AIF1_bCtrlTripReset_b
AIF1_bCtrlB12_b
AIF1_bCtrlB13_b
AIF1_bCtrlB14_b
AIF1_bCtrlB15_b
AIF1_nInW1_a
AIF1_nInW2_a
AIF1_bInB0_b
…
AIF1_bInB15_b
AIF1_nInW3_a
AIF1_bIn16_b
…
AIF1_bIn31_b
AIF1_dnInD1_p
Data transfer
Process data signals of Lenze controllers
Inputs_AIF2
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
16 bits
16 binary
signals
16 bits
16 binary
signals
16 bits
Low Word
16 bits
High Word
16 bits
16 bits
Automation
Interface
Automation
Interface
Byte
1
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
Inputs_AIF3
Byte
1
Byte
2
Byte
3
Byte
4
Byte
5
Byte
6
Byte
7
Byte
8
AIF2_nInW1_a
AIF2_bInB0_b
...
AIF2_bInB15_b
AIF2_nInW2_a
AIF2_bInB16_b
...
AIF2_bInB31_b
AIF2_dnInD1_p
AIF2_nInW3_a
AIF2_nInW4_a
AIF3_nInW1_a
AIF3_bInB0_b
...
AIF3_bInB15_b
AIF3_nInW2_a
AIF3_bInB16_b
...
AIF3_bInB31_b
AIF3_dnInD1_p
AIF3_nInW3_a
AIF3_nInW4_a
5.6-22
Fig. 5.6-8Function b locks AIF-IN1, AIF-IN2 and AIF-IN3
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Process data preconfiguration depending on L-C0009
5.6.3Process data preconfiguration depending on L-C0009
Use L-C0009 to assign predefined values to the process data words (see table
below).
This preconfiguration is meant to help you with applications whic h do not require
aPCP.
Presettings for the process data configuration can be made under code L-C0009
using the Drive PLC or any controller (82XX, 8200 vector, 93XX) even if the
INTERBUS is not connected.
It is also possible to configure the fieldbus module through the parameter channel
via index 6000
and 6001
hex
The process data configuration resulting from L-C0009 is automatically
l stored in the process data description structure when the device is
switched on.
WIndex 6000
l immediately active.
hex
(¶ 5.6-5)
.
hex
/ Index 6001
hex
(¶ 5.6-5)
5.6
5.6.3
.
l automatically writes the process data length (PD) in L-C1910 and
DRIVECOM in L-C1911 from the table. A change of the PD length will only
become active after mains switching.
The default setting of L- C0009 is “1” and influences the process data
configuration.
L-C0009PD length (L-C1910)DRIVECOM (L-C1911)PD word 1PD word 2PD word 3
Device control word/device status word
AIF-IN/OUT.Wx
DRIVECOM control word/DRIVECOM status word
DRIVECOM speed [rpm]
DRIVECOM speed [%]
L
EDSIBS-1.0-06/ 2003
5.6-23
5
2.Set
L-C0009=14(
d
)
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.3
Examples for process data
preconfiguration
Data transfer
Process data preconfiguration depending on L-C0009
Example 1: DRIVECOM control with 2 process data words (e.g. configuration L -C0009 = 14)
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
Acceptance of settingsThe fieldbus module must be switched on again to activate the process
Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures1. Remove the fieldbus module and disconnect it from the voltage
Result• The indexes 6000
Acceptance of settingsThe fieldbus module must be switched on again to activate the process
supply
3. Attach the fieldbus module again and connect it to the voltage
supply
and DCG.
• The process data length (PD) is set to 2 words by L-C1910 = 4.
• DRIVECOM is activated with L-C1911 = 1.
data word length.
supply
2. Set L-C0009 = 25 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage
supply
AIF-W1, AIF-W2.
• The process data length (PD) is set to 3 words by L-C1910 = 6.
• DRIVECOM is activated by L-C1911 = 0.
data word length.
e.g. viakeypa
and 6001
hex
and 6001
hex
accept the configurations DCSTW
hex
accept the configurations GSTW,
hex
5.6-24
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Examples for the configuration of PI/PO data
5.6.4Examples for the configuration of PI/PO data
PI data configuration
The PI data word 2 is to be assigned to the actual percentage (index = 6054
Procedure:
1. Data type derived from the code table ^ 5.6-42.
– The data type of the parameter actual percentage value is I16, i.e. it is a word parameter (16 bit). The code
table for the parameter ”Process input data description structure“ (index = 6000
word 2 is to be entered under subindex 6 and 7 (word parameters).
– The subindex of the paramet e r ”PI data description“ (index = 6000
”Write“ (see
2. Enter the index of the parameter ”Actual percentage“: Write (index = 6000
3. Enter the subindex of the parameter ”Actual percentage“: Write (index = 6000
)
)Note!
))
^ 5.6-49).
The index must be changed to zero to change a subindex.
You can then change the subindex before the index.
) shows that the PI data
hex
) can be written with the PCP service
hex
, subindex = 6
hex
subindex = 7
hex
, value = 6054
hex
,value=0
hex
5.6
5.6.4
hex
hex
)
hex
).
)
L
EDSIBS-1.0-06/ 2003
5.6-25
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.4
PO data configuration
Data transfer
Examples for the configuration of PI/PO data
ThePO data word 2is to be assigned to the percentage setpoint (index =6052
Procedure:
1. Data type derived from the code table ^ 5.6-42.
à The data type of the parameter ”Percentage setpoint“ is I16, i.e. it is a word parameter (16 bit). The code table
for the paramet er ”Process output data description structure“ (index = 6001
to be entered under subindex 6 and 7 (word parameters).
The subindex of the parameter ”PO data description“ (index = 6001
”Write“.
)
)Note!
))
The description of PO data results in inconsistent data, as the
data are exchanged between controller and INTERBUS master in
very short cycle times.
Therefore, the PO data are automatically inhibited when changing
the PO data configuration. After the adaptation of the PO data to
the new configuration, the data can be enabled via the parameter
”PO data enable” (index 6002
hex
hex
).
) shows that the PO data word 2 is
hex
) can be described with the PCP service
hex
).
2. Enter the index of the parameter ”Percentage setpoint“: Write
(index = 6001
3. Enter the subindex of the parameter ”Percentage setpoint“: Write
(index = 6001
)
)Note!
))
4. Enter the i ndex of the parameter ”PO data enable“ (6002
Write (index = 6002
Now the PO data can be read again from the controller.
)
)Note!
))
, subindex = 6
hex
, subindex = 7
hex
The index must be changed to zero to change a subindex.
You can then change the subindex before the index.
, subindex = 0
hex
If a parameter is configured for PO data (e.g. the parameter
”Control word“ (6040
write this parameter directly via its index (example: index =
6040
hex
)
, value = 6054
hex
,value=0
hex
,value=FF
hex
)
hex
)
hex
) to enable process data :
hex
)
hex
) in Lenze setting), it is not possible to
hex
5.6-26
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Device control
5.6.5Device control
5.6
5.6.5
)
)Note!
))
Deactivate the DRIVECOM control if you want to use the device
control (AIF-CTRL).
Use code L-C1911.
If you use the device control AIF-CTRL, the control information is determined by
the control inputs (terminal)
Explanation: Fig. 5.6-9
l Status word:
The controller status word AIF-STAT contains information about the current
controller status.
l Commands
– in the DRIVECOM parameter ”Control word“ are switched off and cannot
change the controller status.
– for changing the controller status are to be entered through the
Fig. 5.6-9Status d iagram for d evice control AIF-CTRL
qofm EÑ~ìäíF
pí~íìë ïçêÇ ññññ ññññ ñMññ NMMM
Fault
qofm кЙлЙнGG
kзнЙW
qЬЙ нЙкгл г~квЙЗ пбнЬ GG ~кЙ Езгг~еЗл
L
EDSIBS-1.0-06/ 2003
5.6-27
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.5
Data transfer
Device control
StatusMeaning
NOT READY TO SWITCH ON The controller is still in the initialisation phase and not ready for operation.
It then automatically switches to the status READY TO SWITCH ON.
READY TO SWITCH ONThe controller is inhibited and waits for the power stage to be charged. It then
automatically switches to the status ”SWITCHED ON“.
SWITCHED ONThe controller is inhibited and waits for controller enable.
OPERATION ENABLEDThe controller is enabled. In this status, a pulse inhibit can be set automatically.
FAULTThe controller is in the status ”FAULT“ (TRIP).
5.6-28
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM control
5.6.6DRIVECOM control
With INTERBUS control (for 82XX/8200vector: Lenze parameter L-C0001 = 3; for
93XX: always) and when using the fieldbus module, Lenze controllers have a
controller status according to the DRIVECOM profile 21.
Explanation: Fig. 5.6-10
l The DRIVECOM parameter “ Status word” contains information about the
l Commands in the DRIVECOM parameter ”Control word“ can change the
Explanation of the status
diagram for DRIVECOM control
Data transfer
DRIVECOM control
StatusMeaning
NOT READY TO SWITCH ONThe controller is being initialised and is not yet ready to operate. It then
SWITCH ON INHIBITThe controller is inhibited and waits for command 2 (shut down).
READY TO SWITCH ONThe controller is inhibited and waits for command 3 (switch on).
SWITCHED ONThe controller is inhibited and waits for command 4 (enable operation).
OPERATION ENABLEDThe controller is enabled. In this status, a pulse inhibit can be set
FAULT REACTION ACTIVEA fault (TRIP) was recognised and a fault response initiated.
FAULTThe controller is in the status ”FAULT“ (TRIP).
QUICK STOP ACTIVEWhile being in the status ”OPERATION ENABLED“ the command ”quick stop“
)
)Note!
))
automatically switches to the status READY TO SWITCH ON.
automatically.
was set. The controller is decelerated in a controlled way (quick-stop ramp).
After deceleration, the controller automatically changes to the controller
status ”SWITCH ON INHIBIT“.
The actual unit status can only be clarified by combining the
unit-status information bits (bit 0 to 6). This is shown in the
following:
Controller statusBits of the status word
Bit6543210
NOT READY TO SWITCH ON00000
SWITCH ON INHIBIT10000
READY TO SWITCH ON010001
SWITCHED ON010011
OPERATION ENABLED010111
FAULT01000
FAULT REACTION ACTIVE01111
QUICK STOP ACTIVE000111
Switch-on inhibit
Quick stop
Voltage inhibit
Fault
Operation enabled
Switched on
Ready to switch on
0= Bit status is 0
1= Bit status is 1
no entry = Any bit status, no influence
5.6-30
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM control
Explanation of the commands in
the status diagram for
DRIVECOM control
CommandMeaning
COMMAND 2, 6, 8 (standstill)
Control word: bit 0 = 0
COMMAND 3 (switch on)Command to change to the controller status ”SWITCHED ON“.
COMMAND 4 (enable operation)Command to change to the controller status ”OPERATION ENABLED“.
COMMAND 5 (inhibit operation)Command to change to the controller status ”SWITCHED ON“.
COMMAND 7, 9, 10, 12 (voltage
inhibit)
Control word: bit 1 = 0
COMMAND 7, 10, 11 (quick stop)
Control word: bit 2 = 0
COMMAND 13 (malfunction/TRIP))The controller has recognised a malfunction. For some malfunction a
COMMAND 14 (reset fault/TRIP)
Control word: bit 7 = 0
⇒ 1
Command to change from different states to the status ”READY TO SWITCH
ON“.
The controller inhibit is deactivated.
The controller inhibit is activated.
Command to change to the controller status ”SWITCH ON INHIBIT“.
The controller inhibit is activated.
Command to change to the controller status ”SWITCH ON INHIBIT“.
If the controller was enabled, it is decelerated in a controlled way along the
Lenze quick-stop ramp.
controlled deceleration may be necessary (depending on the controller).
Once completed, the controller changes to the status FAULT.
With t he series 821X, 8200 vector this command acknowledges a n error.
The controller changes to the status ”SWITCH ON INHIBIT“ when a fault is no
longer recognised.
5.6
5.6.6
)
)Note!
))
The single bit-control commands depend on other bit positions.
In the following you will find a description of the bits required to
effect the command.
Controller status commandsBits of the control word
Bit76543210
The parameter enables or inhibits the PO data (output data for INTERBUS
master). By this, the consistency of the PO data is guaranteed.
Inhibit output data: 00
Enable output data: FF
Every bit enables a process data byte!
If you change 6001
automatically. That means, that the controller does not receive new control data
until index 6002
Parameter name (Index)SubindexData structureData type
Enable PO data (6002
All process data are enabled when the device is switched on (6002
hex
)0SOS
hex
Data transfer
DRIVECOM profile parameters
(¶ 5.6-5).
(¶ 5.6-5).
hex
hex
, the changed process data bytes will be inhibited
hex
enables the communication again.
hex
≡ FF
hex
)
5.6-32
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
5.6.7.2Monitoring parameters
Process data monitoring time
(6003
Process data monitoring
selection code (6004
hex
)
)
hex
If the transmission of the process data is inactive for longer than the set monitoring
time (PCD watchdog), the action set in the parameter ” process-data monitoring
selection code” (6004
Parameter name (Index)SubindexData structureData typeValue range
Process data monitoring time
(6003
The parameter determines the reaction of the controller after the process data
monitoring time is over (6003
Parameter name (Index)SubindexData structureData typeValue range
Process data monitoring selection
code (6004
hex
5.6
5.6.7
) will be activated.
hex
)
)
hex
0SOS-1
).
hex
0SI160 (Lenze setting),
OS: Octet
string,
length: 4
0 - 65535
(Lenze setting: 65535,
monitoring is switched off)
0 = No action
2:
Unit control command
„Inhibit voltage“ (controller
inhibit with latching in the
status ”SWITCH ON INHIBIT“)
3:
Unit control command
”Quick stop“ (quick stop
(QSP)withlatchinginthe
status ”SWITCH ON
INHIBIT“).
L
EDSIBS-1.0-06/ 2003
5.6-33
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.7
5.6.7.3Error code (603F
Data transfer
DRIVECOM profile parameters
)
hex
If the drive sets TRIP, the error code transmits an error number which corresponds
to the DRIVECOM profile (see chapter 5.7.4 DRIVECOM error code).
A list of errors which occurred in Lenze controllers is stored under the Lenze
parameters:
l 82XX: L-C0162 - L-C0164
l 93XX: L-C0168 with subindex 1 to 8
Parameter name (Index)SubindexData structureData type
Error code (603F
)0SU16
hex
OS
5.6-34
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
5.6.7.4DRIVECOM control word (6040
The controller is controlled via this parameter. It contains comands for the
transition between different controller states (see chapter 5.6.6) and other
important control commands (see the following table).
Parameter name (Index)SubindexData structureData type
Control word (6040
)
)Note!
))
5.6.7
)
hex
)0SOS
hex
The bits contained in the control word are interdependent control
commands which are to be parameterised. Chapter 5.6.6
describes the bits required to make the the command become
effective.
820X:Not assigned
821X, 822X:Output of the RFG (speed setpoint integrator) is ”frozen”.
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B4 negated.
820X:Not assigned
821X, 822X:Ramp function generator input (speed setpoint integrator) = 0
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B5 negated.
For 82XX, the controller is initialised. During this time, the controller does not accept any
commands.
820X, 821X, 822X:Not assigned
:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B7.
820X, 821X, 822X:Parameter set changeover:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B12.
820X, 821X, 822X:DC-injection brake:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B13.
820X, 821X, 822X:Not assigned
:
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B14.
8201XPE inhibit
821X, 822X:Not assigned
8200 vector, 93XX:Free. Mapping to bit AIF-CTRL.B15.
1 = command 3 (controller inhibit)
1 = command ”voltage inhibit“ not active
1 = Command ”quick stop“ not active
1 = Command 4 (controller inhibit not active)
Quick stop is activated without the controller leaving its status.
0 = RFG inhibit (quick stop)
1 = RFG inhibit not active
0=RFGstop
1 = RFG stop not active
(controlled deceleration along the set ramp)
0=RFGzero
1 = RFG zero not active
® 1=Parameterset2
0
1
® 0=Parameterset1
0 = DCB not active
1=DCBactive
Inhibit the update of the PO data of the controller (input data for
the master).
Updates of status and current information of the process channel
can be inhibited in order to send control information more
precisely in time (see chapter 5.3.4.2).
0 = Read status and actual value
1 = Do not read status and actual value
Data transfer
5.6-36
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
Link between DRIVECOM control
word and AIF- CTRL control for
93XX and 9300 Servo PLC
Steuerwort
INTERBUS-Master
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
DRIVECOM State
Machine
1
1
C0136/3
AIF-CTRL.B3
AIF-CTRL.B8
AIF-CTRL.B9
AIF-CTRL.B10
AIF-CTRL.B11
AIF-IN
DCTRL
QSP
DISABLE
CINH
TRIP-SET
TRIP-RESET
AIF-CTRL.B0
AIF-CTRL.B1
AIF-CTRL.B2
AIF-CTRL.B4
AIF-CTRL.B5
AIF-CTRL.B6
AIF-CTRL.B7
AIF-CTRL.B12
AIF-CTRL.B13
AIF-CTRL.B14
AIF-CTRL.B15
5.6
5.6.7
2113IBU006
L
EDSIBS-1.0-06/ 2003
5.6-37
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.7
5.6.7.5DRIVECOM status word (6041
This parameter provides compact information about the controller. It contains
commands for the transition between the different controller states (see chapter
5.6.6) and other important information (see the following table).
)
)Note!
))
Parameter name (Index)SubindexData structureData type
Status word (6041
Data transfer
DRIVECOM profile parameters
)
hex
The current controller status can only be clarified by combining
the bits with the status information (bit 0, 1, 2, 3, 4, 5 and 6). This
isshowninchapter5.6.6.
)0SOS
hex
5.6-38
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
Struct ure of t he DRIVECOM
status word
5.6
5.6.7
BitNameMeaning
0Ready to switchonController status information
1Switched onController status information
2Operation
enabled
3FaultController status information
4Voltage inhibited Information about the command ”voltage inhibit“ (see chapter 5.6.7.4 ”control word“)
5Quick stopInformation about the command ”quick stop“ (see chapter 5.6.7.4 ”control word“)
6Switch-on
inhibit
7WarningCollective warning
8MeldungCollective message. Automatic setting and resetting of pulse inhibit in the controller status
9Remote82XX, 821X, 822X,
10FREE
DRIVECOM:
Setpoint
reached
11Limit valueStatus of the DRIVECOM speed limitation
12FREE
DRIVECOM:
Reserve
13FREE
DRIVECOM:
Reserve
14Manufacturer820X, 821X, 822X:
15Manufacturer820X, 821X, 822X:
0 = Status lower than ”READY TO SWITCH ON“
1 = Status at least ”READY TO SWITCH ON“
0 = Status lower than ”SWITCHED ON“
1 = Status at least ”SWITCHED ON“
Controller status information
0 = Status lower than ”OPERATION ENABLED“
1 = Status ”OPERATION ENABLED“
0 = No fault (TRIP))
1 = Fault (TRIP) occured
0 = Command active
1 = Command not active
0 = Command active
1 = Command not active
Controller status information
0 = Statu not ”SWITCH-ON INHIBIT“
1 = Status ”SWITCH-ON INHIBIT“
0=Nowarning
1 = Warning (overtemperature)
”OPERATION ENABLED”. Reasons for this can be under voltage or overvoltage as well as
overcurrent (clamp).
0 = No message
1 = Message (IMP)
8200 vector:
93XX:
Status of speed/frequency deviation
0=RFG
1=RFGon=RFG
0 = Limitation not addressed
1 = Limitation addressed
820X, 821X, 822X:
8200 vector, 93XX:
82XX:
8200 vector:
93XX:
8200 vector, 93XX:
8200 vector, 93XX:
<> RFG
on
Bus access, depends on Lenze parameter ”operating mode”
(L-C0001):
0 = L- C0001
1 = L- C0001
0 = L- C1911 = 0
1 = L- C1911 = 1
off
off
Not assigned
Free. Mapping to bit L-C0150.B14
Not assigned
Free. Mapping to bit L-C0150.B15
Free. Mapping to bit L-C0150.B3
I
max
0 = Current limit not reached
1 = Current limit exceeded
Free. Mapping to bit L-C0150.B2
Q
min(fd
0=Q
1=Q
Free. Mapping to bit L-C0150.B5
<> 3 or L-C1911 = 0
= 3 and L-C1911 = 1
(current limit reached)
≤ f
)
dQmin
not active
min
active
min
L
EDSIBS-1.0-06/ 2003
5.6-39
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.7
Link between DRIVECOM status
word and function block STAT
for 93XX and 9300 Servo PLC
The parameter sets the speed setpoint [rev/min]. If this parameter is changed,
also the nominal percentage will be changed.
Parameter name (Index)SubindexData structureData typeValue range
Speed setpoint
(6042
This parameter is the output valueof the speed ramp function generator [rev/min].
Parameter name (Index)SubindexData structureData typeValue range
Speed ref e rence variable (6043
The parameter indicates the actual speed (in rpm).
Parameter name (Index)SubindexData structureData typeValue range
Actual speed
(6044
hex
hex
5.6
5.6.7
)
)
0SI16−32768 to 32767
) 0SI16−32768 to 32767
hex
0SI16−32768 to 32767
Min/max speed value (6046
Setpoint factor (604B
hex
)
hex
)
This parameter indicates the minimum and the maximum speed (in rpm). It is
initialised with the Lenze parameter L-C0011. Changing this parameter does not
result in a change of L-C0011 (see ”Speed-reference value”).
Parameter name (Index)SubindexData structureData typeValue range
Min/max speed value (6046
hex
)
1AU320 to 32000
2AU320 to 32000
0: Minimum speed setpoint
[rev/min]
L-C0011: Maximum speed
setpoint [rev/min]
This parameter is used to change the resolution or the setting rangeof the setpoint
input. It consists of numerator and denominator. The setpoint is multiplied by the
setpoint factor; the actual values (reference variable, actual value) are multiplied
by the inverse setpoint factor.
Parameter name (Index)SubindexData structureData typeValue range
Setpoint factor (604B
hex
)
1AI16−32768 to 32767
Lenze setting: 1
(Numerator of the ”Setpoint
factor“)
2AI16−32768 to 32767
Lenze setting: 1
(Denominator of the
”Setpoint factor“)
L
EDSIBS-1.0-06/ 2003
5.6-41
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.7
Pole number (604D
Speed reference value (604E
Percentage setpoint (6052
hex
) 13
hex
hex
) 14
Data transfer
DRIVECOM profile parameters
The parameter indicates the pole number of asynchronous motors and is used to
convert frequency values into speed values. Only even values are possible.
Parameter name (Index)SubindexData structureData typeValue range
Pole number (604D
)
This parameter is the reference value for the relative speed parameters, e.g.
nominal percentage, actual percentage and acceleration time. The parameter is
mapped to the Lenze parameter L-C0011. A conversion to frequency values is
possible. The parameter determines the internal maximum speed, which is also
active with terminal control.
Parameter name (Index)SubindexData structureData typeMeaning
Speed re f e re nce value (604E
This parameter is the nominal speed in percent. It is scaled to the ” speed
reference value“ (= 100 % ). When changing this parameter, also the ”nominal
speed“ will be changed. If the ” nominal speed“ exceeds the limit value of the
”nominal percentage“ of 200 % during reading, it will be returned as a value
limited to 200 % .
)0SU82, 4, 6, ..., 254
hex
)0SU32
hex
Lenze setting: 4
L-C0011
2
in [rev∕min]
Percentage reference variable
(6053
Actual percentage (6054
hex
)
) 15
hex
Parameter name (Index)SubindexData structureData typeValue range
Percentage setpoint (6052
)0SI16−32768 to 32767
hex
(100 % = 16383)
This parameter is the ” speed reference variable“ in percent. It is scaled to the
”speed reference value“ (= 100 % ). The ”percentage reference variable“ is
multiplied by the inverse ” setpoint factor“ .
Parameter name (Index)SubindexData structureData typeValue range
Percentage reference variable
)
(6053
hex
0SI16−32768 to 32767
(100 % = 16383)
This parameter is the ”actual speed“ in percent. It is scaled to the ” speed
reference value“ .
Parameter name (Index)SubindexData structureData typeValue range
Actual percentage (6054
)0SI16−32768 to 32767
hex
(100 % = 16383)
Map of L-C0381
5.6-42
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
5.6.7.7Ramps
5.6
5.6.7
The DRIVECOM profile 21 provides two ramps for the speed setpoint:
l The absolute ramp is determined by the following ramp gradient:
dк~ЗбЙен =
The absolute ramps in the DRIVECOM profile 21 are ”acceleration” ,
”deceleration” and ”quick stop”.
l The relative ramp is determined by the following ramp gradient:
dк~ЗбЙен =
This definition corresponds to the Lenze ramp functions L-C0012 and L-C0013.
The relative ramps in the DRIVECOM profile 21 are ” acceleration time” ,
”deceleration time” and ”quick-stop time” .
aЙдн~|лйЙЙЗ
aÉäí~|íáãÉ
pйЙЙЗ кЙСЙкЙеЕЙ о~дмЙ
aÉäí~|íáãÉ
Speed ramps fro acceleration
(6048
hex
)
The ” ramp-min function” determines and activates the slower ramp. The absolute
ramps are deactivated in Lenze setting.
This parameter contains data of the absolute speed ramp for acceleration.
Ramp gradient:
Gradient =
The parameter is mapped to the Lenze acceleration ramp (L-C0012) via the
”ramp-min-function” .
”Delta_time“ = 0: Ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Speed a ccelerat io n (6048
The ” ramp-min function” determines and activates the slower ramp. The absolute
ramps are deactivated in Lenze setting.
Delta_speed
Delta_time
hex
)
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
L
EDSIBS-1.0-06/ 2003
5.6-43
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.7
Speed ramps for deceleration
(6049
Speed quick stop (604A
hex
)
)
hex
Data transfer
DRIVECOM profile parameters
This parameter contains data of the absolute speed ramp for deceleration.
Ramp gradient:
Gradient =
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
”ramp-min-function” . If the ”delta_time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Speed delay (6049
This parameter contains the data of the absolute speed ramp for deceleration in
the status ”QUICKSTOP“ or ”CTRL INHIBIT“ or the QSP terminal function.
Delta_speed
Delta_time
)
hex
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
Acceleration time (604F
hex
Ramp gradient:
Gradient =
Delta_speed
Delta_time
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
”ramp-min-function” . If the ”delta_time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Quick stop
)
(604A
hex
)
This parameter is for the acceleration of the relative speed ramp. The acceleration
1RS (21
2RS (21
)U320 to 4294967295
hex
)U160 to 65535
hex
0: Delta_speed [rev/min]
0 (ramp is switched off):
Delta_time [sec]
time refers to the parameter ” speed reference” with the following slope:
Ramp gradient:
Gradient =
Speed reference value (604E
Acceleration time (604F
)
hex
)
hex
The parameter is mapped to the Lenze acceleration ramp (L-C0012) via the
”ramp-min-function” . If the ”acceleration time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Acceleration time (604F
)0SU320 to 495000 [ms]
hex
(max. L-C0012 / 2)
5.6-44
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
DRIVECOM profile parameters
Deceleration time (6050
Quick-stop time (6051
hex
hex
)
)
5.6
5.6.7
Thisparameter is for the deceleration of the relative speed ramp. The deceleration
time refers to the parameter ” Speed reference value“.
Ramp gradient:
Gradient =
Speed reference value (604E
Deceleration time (6050
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
”ramp-min-function” . If the „deceleration time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Deceleration time (6050
)0SU320 to 495000 [ms]
hex
This parameter is assigned to the relative speed ramp for the unit-control
commands ” quick stop” and ” CTRL inhibit” or the QSP terminal function. The
quick stop time refers to the parameter ” Speed reference value“.
Ramp gradient:
)
hex
)
hex
(max. L-C0013 / 2)
Gradient =
Speed reference value (604E
Quich stop time (6051
)
hex
)
hex
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
”ramp-min-function”. If the ”quick stop time“ = 0, the ramp is switched off.
Parameter name (Index)SubindexData structureData typeValue range
Quick-stop time (6051
)0SU320 t o 495000 [ms]
hex
(max. L-C0105 / 2)
L
EDSIBS-1.0-06/ 2003
5.6-45
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.8
Configuration of the parameter data channel (PCP communication)
5.6.8Configuration of the parameter data channel (PCP communication)
5.6.8.1General information
Access to controller codes
The behaviour and features of a device connected to the INTERBUS can be
changed through the INTERBUS master. The device is connected via the
attached fieldbus module. All devices
Features and behaviour can be changed by changing the parameter data of the
basic unit. Parameter data are
l Lenze parameters (L- Cxxxx)
– Lenze parameters are implemented in Lenze controllers or fieldbus
modules.
– In these descriptions Lenze
the code as indicated in the corresponding controller description (“C” and
4-digit code number).
l DRIVECOM parameters
– For more all manufacturers
– Normalisation in DRIVECOM profile 21
– Every DRIVECOM parameter is addressed by the corresponding index
(overview in chapter 5.8.1.3).
Lenze controllers store the parameters to be changed incodes.
(¶ 5.2-1) can be connected to the bus.
parametersaremarkedbyanLfollowedby
Data transfer
Value range for Lenze parameters
)
)Note!
))
These Instructions use a ”L-Cxxxx“ in front of a code to indicate
that it is a Lenze code and not a DRIVECOM index.
Example: ’L-C0001’ stands for the Lenze code C0001.
Controller codes are addressed via the index when they are accessed through the
bus module.
The index for Lenze code numbers is between 16576 (40C0
Conversion formula:
Index[dec
Example for operating mode L-C0001:
Index = 24575 - LENZE CODENOIndex
Index = 24574 (= 24575 - 1)Index
The value range for Lenze codes can be found in the Operating Instructions for
the corresponding controller (see: Code table).
The data of the Lenze parameters are mainly represented in a fixed-point format
of the data type Integer32 with four decimal digits. This means, that the parameter
value listed in the Operating Instructions must be multiplied by 10000.
Example:
] = 24575 −
dechex
Lenze code
hex
hex
= 5FFF
= 5FFE
hex
hex
) and 24575 (5FFF
hex
- LENZE-CODENO
(= 5FFF
hex
-1)
hex
hex
).
5.6-46
dechex
L-C0039 (JOG) = 150.4 Hz150.4 x 10000 = 1504000= 0016F300
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
intheEEPROMofthecontroller.
Afterswitchonparameterset1i
s
à
Onlytheparametersetdirectlystoredin
Show/Hide Bookmarks
5
Data transfer
Configuration of the parameter data channel (PCP communication)
Lenze parameter sets
Parameter sets are for special code saving which is necessary because of
different configurations for different application processes.
The following table informs about number and addressing of parameter sets for
your controller:
82XX8200 vector93XX
The 82XX and 8200 vector have 2 and 4 parameter sets. The
parameters can be directly addressed via INTERBUS.
They are addressed by means of a code-digit offset:
• Offset 0 addresses parameter set 1 with the Le nze codes L-C0000
to L-C1999
• Offset 2000 addresses parameter set 2 with the Le nze codes
L-C2000 to L-C3999
No additional
parameter sets available.
If a parameter is available only once (see Operating Instructions for
82XX or 8200 vector), use the code digit offset 0.
Example for L-C0011 (maximum field frequency):
L-C0011 in parameter set 1: Lenze code = 11
L-C0011 in parameter set 2: Lenze code = 2011
-
Parameter changes
Automatic saving in the
controller
Process data changes
No automatic savingNo automatic savingNo automatic saving
• Offset 4000 addresses parameter set 3
with the Lenze codes L-C4000 to
L-C5999
• Offset 6000 addresses parameter set 4
with the Lenze codes L-C6000 to
L-C7999
L-C0011 in parameter set 3:
Lenze code = 4011
L-C0011 in parameter set 4:
Lenze code = 6011
Automatic saving is default setting
(changeable under L-C0003)
5.6
5.6.8
93XX controllers have 4 parameter sets
(depending on the variant). They are saved
in the EEPROM of the controller.
Another parameter set is in the user
memory of the controller. This parameter
set can be changed by the user.
• After switch-on parameter set 1 is
automatically loaded as current
parameter set.
• Parameter sets 2 - 4 must be loaded
à Only the parameter set directly stored in
Changes must be stored in code L - C0003.
All changes made without storing them will
be lost after the controller is switched off.
to the RAM.
manually
theRAMcanbeaddressedvia
INTERBUS.
(
(Stop!
((
l For 8200 vector
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.
– Please configure the code to C0003 = 0 after each mains
disconnection if you want to change the parameter data
cyclically.
l For 82XX
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.
L
EDSIBS-1.0-06/ 2003
5.6-47
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.8
5.6.8.2Initialisation of PCP communication
CRL entries
Configuration of the parameter data channel (PCP communication)
CRL (Communication ReferenceList) entries are requiredto ensure
communication between the INTERBUS master and the fieldbus module.
The following entries are to be set in the INTERBUS-master CRL:
Field nameEntry
Communication reference (CR)2
Connection typeAcyclic master/slave
Connection attributeDefined
Max PDU sending high prio0
Max PDU sending low prio64
Max PDU receiving high prio0
Max PDU receiving low prio64
Supported service request80 30 00
Supported Services Response00 00 00
Maximum SCC1
Maximum RCC1
Maximum SAC1
Maximum RAC1
Data transfer
hex
hex
5.6.8.3Available PCP services
In the following, you will find all the parameters and their contents which are
returned by Lenze controllers. All other transmission parameters of the stated
PCP services can be obtained from the corresponding INTERBUS master
description.
Parameters are transmitted via the PCP c hannel (PCP = Peripherials
Communication Protocol). This is carried out via PCP services.
The following PCP services are supported by Lenze controllers:
l Initiate: Build up connec tion between INTERBUS master and controller
l
l
l
l
l
l
(¶ 5.6-49)
Abort: Disconnect (¶ 5.6-49)
Read: Read parameters (¶ 5.6- 49)
Write: Write parameters (¶ 5.6- 49)
Get-OV: Read object directory (OV) (¶ 5.6-50)
Identify: Identification of controller (¶ 5.6- 50)
Status: Read controller status (¶ 5.6-51)
5.6-48
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Configuration of the parameter data channel (PCP communication)
Initiate16
Abort17
Read and write18
The PCP service ” Initiate“ creates a logic between the INTERBUS master and the
fieldbus module. The controller returns the following parameters:
NameValueMeaning
Profile number21
Password0Password function of INTERBUS not supported
Access groups0No access groups
Access protection supportedTRUEAccess protection is supported
Version OV0Version of the object directory
DRIVECOM profile of version 1
hex
The PCP service ” Abort“ interrupts a logic between the INTERBUS master and
the fieldbus module.
The PCP service ”Read“ reads parameters from the controller. The controller
transmits the required parameter or a fault message.
The PCP servic e ” Writ e“ writes controller parameters.The controller transmits a
positive or negative acknowledgement or a fault message.
5.6
5.6.8
The following fault messages can occur:
Error
clas s
6300
6510
6511
6512
6513
6600
6700
6800
8000
8020
8021
8022
8030
8031
8032
8033
8034
8035
8036
8041
8042
8043
Error
code
Additional codeMeaning
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
No access
Invalid service parameter
Invalid subindex
Data too long
Data too short
Object is not a parameter
Object does not exist
Data types are not identical
Servicecannotbeexecuted
Service cannot be executed currently
Cannot be executed because of local control
Cannot be executed because of unit status
Leave value range/parameter can o nly be changed while controller is
inhibited
Parameter value too high
Parameter value too small
Subparameter out of value range
Subparameter value too high
Subparameter value too small
Maximum value smaller than minimum value
Communication object cannot be mapped to process data
Process-data length exceeded
Collision with other values
L
EDSIBS-1.0-06/ 2003
5.6-49
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.6
5.6.8
Get-OV19
Identify20
Data transfer
Configuration of the parameter data channel (PCP communication)
The PCP service ”Get-OV“ reads the object desc ription for each parameter and
data type.
The PCP service ”Identify“ informs about the controller identification. The
controller returns the following parameters:
NameValueMeaning
Name of the manufacturer”Lenze“ (as visible string)Company name
Controller nameVisible string with 15
characters
Controller versionVisible string with 15
characters
Controller name
The visible string consists of the following characters:
l Characters 1 to 5: Name of the controller
(4 characters for the controller name plus 1 blank)
Unit name for controller and bus-interface module
Software version of the controller
l Characters 6 to 10: Name of the fieldbus module
(4 characters for the controller name plus 1 blank)
l Characters 11 to 15: No name
(5 blanks)
If a fieldbus module is not available, the corresponding area will be filled with
blanks.
Example:
8200 vector controller with 2113 fieldbus module: ”8212 2113“
sблбДдЙ лнкбеЦ
`зенкзддЙк е~гЙ
_~лбЕ мебн
`зенкзддЙк е~гЙ
cбЙдЗДмл гзЗмдЙ
_ä~åâ
NS
82122113
NNNR
Controller version
The visible string consists of the following characters:
l Characters 1 to 5: software version of the controller:
– 2 characters for the basic version
– 2 characters for the variant
– 1 character for the version of the variant
5.6-50
l Characters 6 to 10: software version of the fieldbus module
– 2 characters for the basic version
– 2 characters for the variant
– 1 character for the version of the variant
l Characters 11 to 15: No name
– 5 blanks
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Data transfer
Configuration of the parameter data channel (PCP communication)
Example:
For a 8200 controller 8201 (version V2.1; without variant and variant version) with
fieldbus module (version V1.0; without variant and variant version): ” 2100010000“
NS
2100100000
Controller status ”OPERATION
ENABLED“
• 1 = partly ready for operation
All other controller states
Status21
sблбДдЙ лнкбеЦ
`зенкзддЙк оЙклбзе
_~лбЕ мебн
`зенкзддЙк оЙклбзе
cбЙдЗДмл гзЗмдЙ
_ä~åâ
The PCP servic e ” Status“ informs about the controller status.
The controller returns the following parameters:
StatusValueMeaning
Logical status0 = ready to communicateInformation about the current operating mode
Physical status• 0 = ready for operation
Local detailParameter ”Status word“24-bit value comprising:
5.6
5.6.8
NNNR
(L-C0001) of t he controller concerning communication
Information about the current operating state of the
controller.
For the controller status see
• Bit 0 to 15: Profile parameter ”Status word“
(Index = 6041
• Bit 16 to 23: value 0
hex
^ 5.6-29.
)
L
EDSIBS-1.0-06/ 2003
5.6-51
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Troubleshooting
Controller is inhibited
5.7Troubleshooting
5.7.1Controller is inhibited
The controller cannot be enabled via INTERBUS process data, i.e. the status
”OPERATION ENABLED” will not be reached.
tбнЬ UONuLUOMMоЙЕнзкL
UOOu гбн iJ`MNMS Y[ M
лЙнйзбен об~ mltO
5.7-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Troubleshooting
Check INTERBUS
5.7.2Check INTERBUS
Short test of the INTERBUS system in the event of faulty initialisation. The
diagnostics information of the INTERBUS fieldbus modules must be considered
by the INTERBUS master.
For troubleshooting it can be useful to reduce the bus so that only one unit is
connected to the INTERBUS.
^кЙ ~дд мебнл
ЕзееЙЕнЙЗ нз нЬЙ
fkqbo_rp
лпбнЕЬЙЗ зе\
vÉë
aз езн ЕзееЙЕн ~еу гзкЙ
мебнл нз нЬЙ fkqbo_rp
менбд нЬЙ ЕзенкзддЙк бе
имЙлнбзе бл нЬЙ д~лн зеЙ
ЕзееЙЕнЙЗK
kç
pпбнЕЬ зе ~дд мебнл зк
ЗблЕзееЙЕн ~дд мебнл нЬ~н ~кЙ
лпбнЕЬЙЗ зСС Скзг нЬЙ
fkqbo_rp
5.7
5.7.2
fkqbo_rp
fåáíá~äáë~í áçå
çâ\
vÉë
`зееЙЕн нЬЙ еЙсн
ЕзенкзддЙк
kç
oÉéä~ÅÉ íÜÉ ìåáí
L
EDSIBS-1.0-06/ 2003
5.7-3
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.7
5.7.3
5.7.3Reset error (TRIP)
Error reset via INTERBUS process data.
mltN Z MMUM
лЙдЙЕнбзе
ññññ ññññ ñNMM MMMM
EлпбнЕЬJзе беЬбДбнF\
mкЙлЙдЙЕнбзеW
mltN Z MMMM
mltN Z MMUM
mftN Z
íÜÉå
ÜÉñ
kç
ÜÉñ
ÜÉñ
Troubleshooting
Reset error (TRIP)
Äáå
vÉë
kç
mftN Z
ññññ ññññ ñNMM MMMM
EлпбнЕЬJзе беЬбДбнF\
vÉë
lh
Äáå
5.7-4
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Troubleshooting
DRIVECOM error codes
5.7.4DRIVECOM error codes
DRIVECOM fault codes, which can be generated at present:
Lenze error
abbreviation
OC3132213Overcurrent during acceleration
OC4142214Overcurrent during deceleration
OC102300Overcurrent
OC5152311I*t monitoring
OC7172311I*t –monitoring limit 2
OC6162312I2t monitoring
OC1112320Short circuit, overload
OC2122330Earth fault
OU203000Overvoltage (operating status)
LP132/1823130Phase failure
US1403140Mains frequency error
US3423141Mains frequency too high
US2413142Mains frequency too low
OUE223212Overvoltage error
OH512034000PTC overtemperature
OH / OH2/450/52/544210Heatsink overtemperature
OH3/7/853/57/584310Motor overtemperature
OH1514410Supply module overtemperature
H081085000Hardware error
U15705111Vcc15 supply interrupted
H071075200Power stage detection
H101105210Heatsink temperature sensor error
H111115210Inside temperature sensor error
RST766000Auto-Trip-Reset error
H051056000Version error
CCr716010System error
Per/Pr574/796100Program error
P171676200TP control error
Pr0756300Gen. parameter set error
Pr1726301Parameter set 1 error
Pr2736302Parameter set 2 error
Pr3776303Parameter set 3 error
Pr4786304Parameter set 4 error
Id11406320Faulty parameter identification
Sd5-885-887300Setpoint encoder
PTs817301Analog encoder defective
Pr6807302Wrong encoder polarity
Sd2827303Open circuit at resolver
Sd3837305Incremental encoder 1
Sd4847306Incremental encoder 2
P091598000Error code monitoring
5.7
5.7.4
Lenze error no.DRIVECOM error code [hex]Meaning
00No error
201-2196200Overrun or float error
2306200No PLC program
2316200LenzeXXX.lib not supported
2206300No technology unit
L
EDSIBS-1.0-06/ 2003
5.7-5
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.7
5.7.4
Troubleshooting
DRIVECOM error codes
Lenze error
abbreviation
CE0618100AIF time monitoring
CE1.4
CE11-14
CE5668100CAN time OUT
P161668100Sync telegram transmission error
P181688200Internal limitation
NMAX2008400Nmax system speed
P041548500Negative position error
P051558500Positive position error
P061568500Home position not known
P071578500Absolute program set mode
P081588500Act. home position exceeding position
2408100Free CAN obj. send memory overflow
2418100Free CAN obj. too many telegrams
8100CAN time monitoring
MeaningDRIVECOM error code [hex]Lenze error no.
received
limits
)
)Note!
))
Only faults and errors caused by the controller can occur.
Please read the Operating Instructions for the controller.
5.7-6
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Appendix
Code table
5.8Appendix
5.8.1Code table
5.8.1.1Codes of the 2111 INTERBUS fieldbus module
Software codes
Process data length
These codes determine the software used.
Software version and date can be read.
CodeValuesLenze settingExplanation
L-C1810 33S2111I_xy000Software registration number of 2111
L-C1811Software creation date [mmm tt jjjj hh:mm:ss]
Here you can enter the number of transferred process data words in bytes.
The number of process data can have up to 6 bytes. L-C1910 can be written with
the values 4 and 6. The value issaved in the EEPROM of the 2113 fieldbus module.
A change of process data length only becomes effective after a basic initialisation
of the fieldbus module, i.e. after switching off the supply voltage.
5.8
5.8.1
Unit or DRIVECOM control
A value higher than 4 bytes should only be used for 93XX and 8200 vector since
only here the data can be passed on. However, a length of > 4 bytes is possible
wit h 82XX.
CodeValuesLenze settingExplanation
L-C1910 4, 64INTERBUS process data length in bytes
Here you can set the unit or DRIVECOM control if all DIP switches are “OFF”.The
setting is only active then.
CodeValuesLenze settingExplanation
L-C1911 0/11• 1:
The control word is transmitted from the INTERBUS master
to the controller via the DRIVECOM status machine.
• 0:
The AIF-CTRL control word is active.
L
EDSIBS-1.0-06/ 2003
5.8-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.8
5.8.1
5.8.1.2Controller codes
Appendix
Code table
CodeValuesLenze settingExplanation
L-C0001
0
1
2
3
L-C0009 Process data preconfiguration
) Please see the notes in chapter 5.6.3
L-C0142This parameter L-C0142 prevents the drive f ro m uncontrolled
Operating mode
Control source
Ter m ina l
Ter m ina l
Ter m ina l
INTERBUS
restarts after:
• Mains switching
• Internal fault
• Internal message (with pulse inhibit) > 0.5 s
If the controller sets the status ”message” because of a failure
(e.g. short mains failure) and the fault remains active for
longer than 0.5 s, controller inhibit will be set automatically.
The parameter L-C0142 has the fo llo wing function:
• L-C0142 = 1:
The drives will restart automatically as soon as the error
has been eliminated.
• L-C0142 = 0:
The controller remains inhibited and the drive cannot
restart even if the error has been eliminated.
– The drive restarts after a LOW-HIGH transition at one of
the inputs for ”controller inhibit” (CINH, e.g. at terminal
X5/28) wieder an
All codes are described in detail in the corresponding Operating Instructions.
5.8-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
y
p
Show/Hide Bookmarks
5
Appendix
Code table
5.8.1.3Code table for the DRIVECOM profile 21
Explanation of the following code tables:
NameMeaning
R/W
PD
SP
Data str.
Data type
Data numberDisplay of the parameter elements
Data lengthTotal length of the parameter in byte
Write/read authorization via LECOM
Ra =only read access permitted
Ra/W = Read access always permitted, write access permitted under certain conditions (e.g.
depending on Lenze paramet e r L-C0001 (operating mode) or controlle r status)
Mapping to INTERBUS process data (index 6010
PI =Process input data (from the controller to the host)
PO =Process output data (from the host to the controller)
POI =Process input and output data (see PO and PI)
-=Mapping of the process data not possible
Non-voltatile saving of the parameter
y=YesParameter will be saved
n=NoParameter will not be saved
-=Parameter depends on the process and will therefore not be saved
Data structure
S=S imple variable
The parameter consists of one value and can only be addressed via subindex 0.
A=Array variable (field parameter)
The parameter contains several values of the same data type. The individual elements can
be directly addressed by means of the subindex. Subindex = 0 addresses the whole
The parameter contains several values of different data types. Subindex = 0 addresses the
whole parameter contents.
Data type
BOL = BooleanFALSE = 00
I8 =Integer8−128 ≤ x ≤ 127
I16 =Integer16−32768 ≤ x ≤ 32767
I32 =Integer32−2147483648 ≤ x ≤ 2147483647
U8 =Unsigned80 ≤ x ≤ 255
U16 = Unsigned160 ≤ x ≤ 65535
U32 = Unsigned320 ≤ x ≤ 4294967295
OS =Octet string 8 bit/byte [= 1 byte or 8 bit per byte] binary coded
VS =Visible string; text coded to ISO 646
PDS = Process data description structure (index 20
RS =Ramp structure (index 21
Subindex 1: U32, numerator ”delta_speed“ in rev/min
Subindex 2: U16, denominator ”delta_time“ in seconds
hex
)
;TRUE=FF
hex
hex
, 6011
hex
hex
5.8
5.8.1
)
hex
)
L
EDSIBS-1.0-06/ 2003
5.8-3
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.8
5.8.1
Appendix
Code table
According to the standardization of controller parameters according to the
DRIVECOM profile 21 the following parameters are implemented:
Index
Index
hex
600024576 Process-input data descriptionRa/W-YCWPDS9
600124577 Process-output data descriptionRa/W-YCWPDS9
600224578 Process-output data - releaseRa/W-nSOS11
600324579 Process data - monitoring timeRa/W-YSU1612
600424580 Process-data - selection codeRa/W-YSI1612
603F24639 Error codeRa-nSOS12
604024640 Control wordRa/WPOI-SOS22
604124641 Status wordRaPE-SOS22
604224642 Speed setpointRa/WPOI-SI1612
604324643 Master speedRa--SI1612
604424644 Actual speedRaPE-SI1612
604624646 Speed - min./max. valueRa/W-nAU3228
604824648 AccelerationRa/W-nCWRS26
604924649 DecelerationRa/W-nCWRS26
604A24650 Quick stopRa/W-nCWRS26
604B24651 Setpoint factorRa/W-YAI1624
604D24653 Pole numberRa/W-YSU811
604E24654 Speed reference valueRa/W-nSU3214
604F24655 Acceleration timeRa/W-nSU3214
605024656 DecelerationRa/W-nSU3214
605124657 Quick stop time
605224658 Percentage setpointRa/WPOI-SI1612
605324659 Master percentageRa--SI1612
605424660 Actual percentageRaPE-SI1612
1)
only with 93XX / 8200 vector
Parameter nameR/WPDSP Data
dec
Ra/W-nSU3214
(not with 820X)
str.
Data
type
Data
number
1)
11
1)
11
Data
length
13
1)
19
13
1)
19
5.8-4
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Index
5.9Index
0 ... 9
2111 INTERBUS fieldbus module, 5.1-1
8200 vector, Status word, 5.6-12
82XX, Status word, 5.6-8
93XX
- Control word, 5.6-19
- Status w ord, 5.6-17
A
Abort, 5.6- 50
Appendix, 5.8-1
Application conditions, 5.3-1
Application range, 5.2-2
B
Basic insulation, 5.4- 3
Baud rate, 5.4-4
C
Code numbers, Access via the fieldbus module,
5.6-47
Code numbers / index, Conversion, 5.6-47
Code table, DRIVECOM , 5.8-3
Codes
- 2111 fieldbus module, 5.8-1
- Controller, 5.8-2
- Lenze, 5.6-47
Commissioning, 5.5-1
- of the fieldbus module, 5.5-2
Communication medium, 5.3- 1, 5.4-4
Components of the fieldbus module, 5.4-1
Configuration
- Process d ata c hannel, 5.6- 3
- Process d ata,, 5.6- 5
Configuration of host and fieldbus module, 5.5-1
Connection
- from the INTERBUS, 5.4-6
- to the INTERBUS, 5.4-7
Control, DRIVECOM, 5.6-30
Control w ord, 5.6-4, 5.6-36
- 8200 vector, 5.6-14
- 82XX, 5.6-10
- 93XX, 5.6-19
5.9
Controller, Process data signals, 5.6- 7
Conversion formula, Lenze codes, 5.6-47
CRL ent ries, 5.6-49
Cycle time, 5.3-2
D
Data transfer, 5.6-1
Default setting
- Subindex 6000, 5.6-6
- subind ex 6001, 5.6- 6
Device control, 5.6- 28
Dimensions, 5.3-4
DRIVECOM
- Control word, 5.6-36
- Enable controller, 5.5-4
-Errorcode,5.7-5
- Monitoring p arameter, 5.6-34
- Parameters of the DRVIECOM profile, 5.6-33
- Process d ata d esc ription, 5.6- 33
-Ramps,5.6-44
- Speed / velocity c hannel, 5.6-42
- Status word, 5.6-39
DRIVECOM control, Control, 5.6-30
DRIVECOM compatibility, 5.5-5
DRIVECOM control word, Assembly, 5.6-37
DRIVECOM status word, Assembly, 5.6-40
E
Electrical installation , 5.4-3
Error code, 5.6-35
- Index 603F, 5.6- 35
F
Features, 5.2-2
Frequency setpoint, 5.6-4
G
General data, 5.3-1
General information, 5.2- 1
Get-OV, 5.6-51
H
Hardware version, Type code, 5.2-1
L
EDSIBS-1.0-06/ 2003
5.9-1
5
Show/Hide Bookmarks
2111 INTERBUS fieldbus module
5.9
I
Identification, 5.2- 1, 5.6- 51
Identify, 5.6-51
Index, 5.9- 1
- Conversion, 5.6- 47
Initiate, 5.6-50
Installation, 5.4-1
- Wiring to the host, 5.4-3
INTERBUS cycle time, 5.3-2
INTERBUS process data length, 5.8-1
L
Lenze codes, 5.6- 47
- Conversion formula, 5.6-47
- Name, 5.6- 47
Lenze data types, 5.6-47
M
Mains isolat ion, 5.4- 3
Mechanical installation , 5.4-2
Monitoring parameter, 5.6-34
Monitoring time, Index 6003, 5.6- 34
N
Network topology, Point-to-point , 5.4-4
P
Parameter data, 5.6-1
Parameter data channel, configuration, 5.6-47
Parameter sets, 5.6-48
- Lenze, 5.6-48
Parameters
- Control word (C0135), 5.6-4
- DRIVECOM profile parameters, 5.6-33
- Frequency setpoint (C0046), 5.6-4
PCP communication, initialisation, 5.6-49
PCP services, 5.6-49
-Abort,5.6-50
- Get-OV, 5.6- 51
- Identify, 5.6-51
- initiate, 5.6- 50
- Read and write, 5.6- 50
- Status, 5.6-52
PI, 5.6-3
PI data, Index 6000, 5.6- 6, 5.6- 33
Index
PI/ PO data configuration, Examples, 5.6-26
PO, 5.6-3
PO data description, Index 6001, 5.6-6, 5.6-33
Preparations, for drive control using the INTERBUS,
5.5-3
Process data channel, configuration, 5.6-3
Process data description, 5.6-33
Process data monitoring time, 5.6-34
Process data signals, 5.6-7
- 8200 vector, 5.6-11
- 82XX, 5.6-7
- 9300 Servo PLC, 5.6- 20
- 93XX, 5.6-15
- Drive PLC, 5.6-20
Process data telegram
- from the controller, 5.6-7
- to the controller, 5.6-9
Process data transfer, 5.6-3
Process data,, 5.6-1
- configuration, 5.6-5
- Preconfiguration through L- C0009, 5.6- 24
Process-data configuration, 5.6-24
Process- data structure, 5.6-5, 5.6-24
Processing t ime
- in the controller, 5.3-3
- in Drive PLC, 5.3-3
Proconfiguration, of process data, 5.6- 24
Program
- Program different f rom SYSSWT, 5.5- 2
- SYSSWT, 5.5- 1
Protocol data, 5.3-1
R
Ramps, 5.6- 44
Rated data, 5.3-1
Read and write, 5.6-50
S
Services,PCP,5.6-49
Setpoint source, 5.6-4
Software version, Type code, 5.2-1
Speed / velocity channel, 5.6- 42
Status, 5.6- 52
Status w ord, 5.6- 39
- 93XX, 5.6-17
SYSSWT, 5.5- 1
System bus (CAN), Technical data, Communication
times, 5.3-2
5.9-2
EDSIBS-1.0-06/ 2003
L
2111 INTERBUS fieldbus module
Show/Hide Bookmarks
5
Index
T
Technical data, 5.3-1
TRIP, Error reset, 5.7- 4
Troubleshooting, 5.7-1
Type code, 5.2-1
5.9
V
Value range, 5.6-47
W
Wiring, to a host, 5.4-3
L
EDSIBS-1.0-06/ 2003
5.9-3
Show/Hide Bookmarks
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.