6 Setup with the integrated indicating and adjustment
unit
6.1Adjustment system .....................
6.2Setup procedure .......................
6.3Application example.....................
7 Maintenance and fault rectification
7.1Maintenance ..........................
7.2Fault rectification .......................
7.3Instrument repair .......................
8 Dismounting
8.1Dismounting procedure ..................
8.2Disposal .............................
2SU 600 Ex - 4 ... 20 mA signal conditioning
11
11
13
15
16
20
23
23
24
25
25
30653-EN-050803
9 Supplement
9.1Technical data.........................
9.2Dimensions ...........................
9.3Certificate ............................
Contents
26
29
30
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning3
About this document
1 About this document
1.1 Function
This operating instructions manual has all the information you
need for quick setup and safe operation of SU 600 Ex. Please
read this manual before you start setup.
1.2 Target group
This operating instructions manual is directed to trained
personnel. The contents of this manual should be made
available to these personnel and put into practice by them.
1.3 Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could
occur. Ignoring this cautionary note can impair the person and/
or the instrument.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
For your safety
2 For your safety
2.1 Authorised personnel
All operations described in this operating instructions manual
must be carried out only by trained specialist personnel
authorised by the operator. For safety and warranty reasons,
any internal work on the instruments must be carried out only
by personnel authorised by the manufacturer.
2.2 Appropriate use
SU 600 Ex is a universal signal conditioning instrument and
power supply unit for connection of a 4 … 20 mA/HART
sensor.
2.3 Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to
system components through incorrect mounting or adjustment.
2.4 General safety instructions
SU 600 Ex is a high-tech instrument requiring the strict
observance of standard regulations and guidelines. The user
must take note of the safety instructions in this operating
instructions manual, the country-specific installation standards
(e.g. the VDE regulations in Germany) as well as all prevailing
safety regulations and accident prevention rules.
2.5 CE conformity
SU 600 ExisinCE conformity with EMC (89/336/EWG) and
NSR (73/23/EWG).
Conformity has been judged acc. to the following standards:
l EMC:
- Emission DIN/EN 61326: 2004
- Susceptibility DIN/EN 61326: 2004 incl. supplement A
l NSR: EN 61010-1: 2001
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning5
For your safety
2.6 Safety information for Ex areas
Please note the Ex-specific safety information for installation
and operation in Ex areas. These safety instructions are part of
the operating instructions manual and come with the Exapproved instruments.
6SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
3 Product description
3.1 Configuration
Product description
Scope of delivery
Overview
The scope of delivery encompasses:
l Indicating and signal conditioning instrument SU 600 Ex
l Mounting set
l Ex separating chamber
l Identification label
l Documentation
- this operating instructions manual
- Ex specific safety instructions and, if necessary, further
certificates.
1
2
1
8
2
3
7
+
0
C
1
B
2
A
3
9
4
8
5
7
6
6
-
4
5
Fig. 1: SU 600 Ex
1Status indications operating relay 1 and 2
2Status indication fail safe relay
3Status indication operation
4[+/-] adjustment keys
5Insertable tag for identification of the measurement loop
6Function switch
7Mode switch for sensor input (active/passive) on the rear of the instrument
8LC display
3.2 Principle of operation
Area of application
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning7
SU 600 Ex is a universal single signal conditioning instrument
with integrated level switches and display for continuously
measuring sensors. At the same time, it can serve as power
Product description
supply unit for connected sensors.SU 600 Ex is designed for
connection of an individual 4 … 20 mA sensor. The instrument
is suitable for carrier rail, panel and surface mounting.
Physical principle
Power supply
Packaging
SU 600 Ex signal conditioning instrument can power the
connected sensor and also evaluate its measurement signals.
The requested parameter is indicated in the display and, in
addition, outputted to the integrated current output for further
processing. Hence the measuring signal can be transmitted to
a remote display or a connected control system. In addition,
two level relays for control of pumps or other actuators are
integrated.
Wide-range power supply unit with 20 … 253 VAC/DC for
world-wide use.
You will find detailed information on the power supply in the
"Technical data" in the "Supplement".
3.3 Adjustment
The adjustment of SU 600 Ex is carried out via the integrated
keys and a 16-step function switch.
3.4 Storage and transport
Your instrument was protected by packaging during transport.
Its capacity to handle normal loads during transport is assuredby a test acc. to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions PE
foam or PE foil is also used. Dispose of the packaging material
via specialised recycling companies.
Storage and transport temperature
8SU 600 Ex - 4 ... 20 mA signal conditioning
l Storage and transport temperature see "Supplement –
Technical data – Ambient conditions"
l Relative humidity 20 … 85 %
30653-EN-050803
4 Mounting
4.1 General instructions
Mounting
Installation location
Carrier rail mounting
You can mount theSU 600 Ex signal conditioning instrument
onto a carrier rail 35x7.5 acc. to DIN EN 50022, or directly on
the wall by means of the three screws or in a front panel or
door of a switching cabinet.
Note:
Before mountingSU 600 Ex , set the requested mode of the
measuring data input. With a slide switch on the rear of the
instrument you can choose between active and passive
current input (see also chapter " Connecting to power supply
"). After mounting the instrument, the slide switch is no longer
accessible.
4.2 Mounting information
1 Place the adapter plate [1] to the rear of SU 600 Ex (spring
of the adapter plate downward) and fasten the plate with
screw [2](M4x6).
2 PlaceSU 600 Ex against the carrier rail [3] from below and
l Connect only in the complete absence of line voltage
l If overvoltages are expected, overvoltage arresters should
be installed.
In hazardous areas you should take note of the appropriate
regulations, conformity and type approval certificates of the
sensors and power supply units.
The power supply can be 20 … 253 VAC, 50/60 Hzor
20 … 253 VDC.
Power supply of SU 600 Ex is connected with standard cable
acc. to the national installation standards.
Standard two-wire cable without screening can be used to
connect sensors. If electromagnetic interference is expected,
screened cable must be used.
Connect the cable screen on both ends to ground potential. In
the sensor, the screen must be connected directly to the
internal ground terminal. The ground terminal outside on the
sensor housing must be connected to the potential equalisation.
If potential equalisation currents are expected, the screen
connection on SU 600 Ex must be made via a ceramic
capacitor (e.g. 1 nF, 1500 V). The low frequency potential
equalisation currents are thus suppressed, but the protective
effect against high frequency interference signals remains.
Select connection
cable for Ex applica-
tions
Take note of the corresponding installation regulations for Ex
applications. In particular, make sure that no potential equalisation currents flow over the cable screen. In case of
grounding on both sides this can be achieved by the use of a
capacitor or a separate potential equalisation.
5.2 Connection procedure
Proceed as follows:
1 Mount SU 600 Ex
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning11
Connecting to power supply
2 Connect sensor cable to terminal 1 and 2, and where
applicable, connect the screen
3 Connect power supply (switched off) to terminal 5 and 6
4 Where applicable, connect fail safe and operating relay as
well as current output
The electrical connection is finished.
After connection, it is absolutely necessary to plug the blue Ex
separating chamber to terminals 1 and 2 (sensor input). This
ensures the required distance of at least 50 mm (1.97 in) to
other instruments.
1 Place the Ex separating chamber as shown below on the
terminals of the sensor input
2 Lead the sensor cable towards the front and out of the Ex
separating chamber
3 Push the Ex separating chamber towards the front until you
hear it snap in
12SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
5.3 Wiring plan
Connecting to power supply
Overview
-
+
2
1
12
1
2
-
+
4
3
1
2
on
%
18 1716 15 1413 1211 10 9 876 5
3456
Fig. 5: Terminal assignment SU 600 Ex
1Measurement data input, optionally available with sensor power supply
2Current output
3Fail safe relay
4Relay 2
5Relay 1
6Power supply
N- L1+
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning13
Connecting to power supply
Information:
Via the slide switch on the rear of the instrument you can
switch over between active and passive operation of the
measuring data input:
l In active mode,SU 600 Ex provides the power for the
connected sensors. Power supply and measurement data
are transmitted over the same two-wire cable. This mode is
provided for connection of transmitters without separate
power supply (sensors in two-wire version).
l In passive mode, the sensors are not powered - only the
measured value is transmitted. This input is for transmitters
with their own separate power supply (sensors in four-wire
version). Furthermore,SU 600 Ex can be connected to an
existing circuit like a standard current meter.
The position of the slide switch also influences the preconditions for Ex implementation. Take note of the type approval
certificate or the conformity certificate ofSU 600 Ex.
14SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
Setup with the integrated indicating and adjustment unit
6 Setup with the integrated indicating and
adjustment unit
6.1 Adjustment system
The integrated indicating and adjustment unit is for measured
value display, adjustment and diagnosis ofSU 600 Ex.
Indication and adjustment is carried out in the front via a clear
LC-display and a function switch as well as two keys.
To open the cover, insert a screwdriver in the two slots on the
top and turn it slightly.
1
2
8
2
3
7
1
+
0
C
1
B
2
A
3
9
4
8
5
7
6
6
-
4
5
Fig. 6: Indicating and adjustment elements
1Status indications operating relay 1 and 2
2Status indication fail safe relay
3Status indication operation
4[+/-] adjustment keys
5Insertable tag for identification of the measurement loop
6Function switch
7Mode switch for sensor input (active/passive) on the rear of the instrument
8LC display
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning15
Setup with the integrated indicating and adjustment unit
Key functions
Set up
l [Function switch] for selection of:
- Adjustment
- Relay switching points
- Scaling
- Current output
- Integration time
- Offset correction
l [+/-] key:
- Change value of the parameter
By pushing the [+/-] key, you change the individual parameters
of the selected function. In this phase, the processed
parameter is flashing. By briefly pushing the two keys
simultaneously, you save your settings. "Save" is briefly
displayed.
6.2 Setup procedure
Setup encompasses mainly the adjustment of the measurement loop. A scaling of the measured value for the LC display
and the adaptation of the relay switching points are additional
settings. Additional setup steps might be, if necessary, setting
an integration time to smooth the measured value or modifying
the current output characteristics.
To clearly denote the measuring unit, the supplied labels can
be inserted in the cover. In case several SU 600 Ex are used,
each measurement loop should be clearly labelled.
Switch on phase
After being switched on, SU 600 Ex first of all carries out a
short self-check. The following steps are carried out:
l Internal check of the electronics
l indication of the firmware version
l the output signal jumps briefly to the set fault current
Then the actual measured value is displayed and the
corresponding current is transmitted to the current output.
Measured value indication
The measured value indication shows the digital indication
value and also an analogue bargraph. Here, it is absolutely
necessary that the function switch is set to position [ 0]
("OPERATE").
Function switch
16SU 600 Ex - 4 ... 20 mA signal conditioning
The following functions can be selected via the rotary switch:
l 0: Measured value display and simulation
l 1: Relay 1 switching point ON
l 2: Relay 1 switching point OFF
30653-EN-050803
Offset correction
Setup with the integrated indicating and adjustment unit
l 3: Relay 2 switching point ON
l 4: Relay 2 switching point OFF
l 5: Decimal point position of the scaling
l 6: Scaling for 100 %
l 7: Scaling for 0 %
l 8: Switch over current output 0/4 … 20 mA
l 9: Damping of the measured value (integration time)
l A: Offset correction
l B: Min. adjustment in % by modifying the level
l C: Max. adjustment in % by modifying the level
l D: Min. adjustment in mA without modifying the level
l E: Max. adjustment in mA without modifying the level
l F: No function
When a pressure transmitter is used, an offset correction
should be carried out first. These instruments are factory-set in
a certain position. If the pressure transmitter is now mounted in
adifferent position, its measuring range is shifted slightly. The
zero point is readjusted by carrying out the offset correction in
uncovered (unpressurised) condition. The complete measuring range will be shifted by the deviating amount.
à Make sure that the pressure transmitter is completely
unpressurised, uncovered (unimmersed) and mounted in
its final position.
à Set the function switch to position [ A ]. The display
indicates now the actual sensor current in mA. Save the
current status by pushing the [ +/- ] keys simultaneously.
Adjustment in mA without
changing the level
For this adjustment procedure, two sensor current values
(4 … 20 mA) must be entered corresponding to the levels 0 %and 100 %.
When using a pressure transmitter, an offset correction should
be carried out to reach maximum accuracy. Carry out this
offset correction before adjustment and with the sensor
uncovered (unimmersed).
à Select now position [D] or [E] on the function switch, enter
the current values in mA for min. or max. adjustment and
save your settings.
Adjustment in % by changing
the level
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning17
During this adjustment procedure, the current level is assigned
to a certain percentage value. For this reason, percentage
values that correspond to the actual filling levels must be
entered for the min. and max. adjustment. The ideal calibration
is at 0 % and 100 %. Because it is not always possible to
empty or fill a vessel completely, any value can of course be
Setup with the integrated indicating and adjustment unit
entered. The greater the difference between the two adjustment points, the more precise the measurement. It does not
matter which value is entered first.
à Select position [B] or [C] on the function switch, enter the
percentage values for the min. and max. adjustment and
save your settings.
Relay outputs
Two operating relays are integrated inSU 600 Ex for level
detection. First of all, determine at which switching points the
relays should switch on and off again. Furthermore you have to
distinguish between the relay modes overfill and dry run
protection. You switch over by exchanging the ON/OFF values
of the relay.
l Overfill protection: Relay is switched off when the max.
level is exceeded (safe currentless condition), relay is
switched on again when the level falls below the min. level
(switch on point < switch off point).
l Dry run protection: Relay is switched off when the level
falls below the min. level (safe currentless condition), relay
is switched on again when the max. level is exceeded
(switch on point > switch off point).
à To adjust the on and off switching points of relay 1, set the
function switch to position [1] or [2], enter the switching
points for ON or OFF and save your settings. If necessary,
proceed in the same way with relay 2 (position [3] or [4]).
18SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
Setup with the integrated indicating and adjustment unit
2
3
1Level
2Mode overfill protection
3Mode dry run protection
1
off (on)
on (off)
t
LED
on
off
on
off
Scaling
Scaling is the conversion of the measured value into a certain
parameter or measuring unit. Instead of the percentage value,
the volume can be displayed, e.g. in l. Indicating values
between max.-9999 and +9999 are possible.
à First of all, determine the max. indicating range and the
number of decimal places after the decimal point -- max.
four decimal places can be displayed. Select position [ 5 ]
of the function switch, place the decimal point in the
required position and save your settings.
à Now select position [6] or [7] on the function switch, enter
the requested values for 100 % or 0 % and save your
settings.
Damping
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning19
To suppress fluctuation in the measured value display, e.g.
caused by an agitated product surface, an integration time can
be set. This time can be between 0 and 250 seconds. Keep in
mind that this setting will increase the reaction time of the
measurement, and that the reaction to quick changes of the
measured value will be delayed. In general, a time of a few
seconds is sufficient to smooth the measured value display.
Setup with the integrated indicating and adjustment unit
à Now select position [9] on the function switch, enter the
requested value and save your settings.
Current output 0/4 … 20 mA
Simulation
Reset
The characteristics of the current output can be switched over
from 4 … 20 mA to 0 … 20 mA.
à Now select position [8] on the function switch, adjust the
requested characteristics curve and save your settings.
To check if the settings ofSU 600 Ex are correct, the simulation
mode can be used. Any individual measured value can be
simulated and e.g. the correct behaviour of the relays and the
connected instruments can be checked.
Switching over between the functions "OPERATE" and
"Simulation" is done by pushing the [+/-] keys for at least 3
seconds.In the simulation mode, the set value flashes on the
display. The simulation can be switched off by pushing both
keys again for approx. 3 seconds. If no key is pushed, the
display switches automatically over to "OPERATE" after
approx. 60 minutes and the simulation is terminated.
à To start simulation, push the [ +/-] keys simultaneously until
the displayed value starts flashing (approx. 3 seconds). By
pushing either of the [ +/-] keys, you can set the requested
simulation value and make your check.
With a reset, all values set by the user will be lost and are reset
to factory settings.
à Interrupt the power supply of SU 600 Ex. Push the [+/-]
keys simultaneously and hold them while you switch on the
power supply. The display shows "RES" and the default
settings will be restored. These are the following:
l Relay switch on points: 10 %
l Relay switch off points: 100 %
l Decimal point: 888.8
l Display min: 0
l Display max: 100.0
l Integration time: 0 s
l Offset correction: 0
l Current output: 4 … 20 mA
l Min. adjustment: 0 % or 4 mA
l Max. adjustment: 100 % or 20 mA
30653-EN-050803
6.3 Application example
l An upright cylindrical (linear) tank has a volume of 2700 l
20SU 600 Ex - 4 ... 20 mA signal conditioning
General procedure
Setup with the integrated indicating and adjustment unit
l The max. filling volume is 2650 l, the min. filling volume 50 l
l The level sensor in the vessel is a pressure transmitter
(passive), outputting a standardised 4 … 20 mA signal
l For further processing, an additional 4 … 20 mA output
signal is required
l The full and empty adjustment was carried out directly in
the sensor. The following values are outputted:
- max. volume (display max.) 20 mA = 2650 l
- min. volume (display min.) 4 mA = 50 l
l Relay 1 should switch on an emptying pump at a level of
90 % and switch off the pump at a level of 10 %
1 Select the following functions with the rotary switch.
2 Push one of the two [+/-] adjustment keys, the digital
indication flashes (if the rotary switch is set to "OPERATE",
the [+/-] keys are inoperable).
3 Adjust the requested value with the [+/-] keys. If you hold
the key pushed, the digital indication changes the value
more quickly.
4 Save your settings by pushing the [+/-] keys simultane-
ously.
Current output
à Set the function switch to position [8]. Select with the [+/-]
keys the measured value output 4 … 20 mA or 0 … 20 mA.
For this example, choose 4 – 20.
The displayed numbers have the following meanings:
l 0 – 20 = 0 … 20 mA
l 4 – 20 = 4 … 20 mA
à Save the value by pushing the [+/-] keys simultaneously.
To scale the indication of SU 600 Ex, the filling volumes for 0 %
and 100 %. The vessel does not have to be filled or emptied.
Scaled indication at 0 %
Scaled indication at 100 %
Decimal point
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning21
1 Set the function switch to position [7](display min.).
2 Set the value to 50 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.
1 Set the function switch to position [6](display max.).
2 Set the value to 2650 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.
Because the range of the example vessel is between 50 lto
2650 l, you will need all four positions of the digital indication.
Setup with the integrated indicating and adjustment unit
1 Set the function switch to position [5](Decimal Point).
2 By pushing the [+/-] keys, you move the decimal point.
3 Save the value by pushing both keys simultaneously.
Relay
l Set the function switch to position [ 1 ](relay 1 on). For the
given example, select the value 90.0 (90.0 %) with the [ +/-
] keys. The internal relay 1 then switches on when this
value is reached. Save the value by pushing the two keys
simultaneously.
l Set the function switch to position [ 2](relay 1 off). Select
the value 10.0 (10.0 %) with the [ +/-] keys. The internal
relay 1 then switches off when the value falls below this
value. The respective relay control lamp lights when the
relay is energized. If the switching points are too close
together (<0.1 %), the appropriate LED flashes. The relay
takes on the safe condition. In mode "OPERATE " an error
message is outputted on the display.
l If you want to control additional relays, proceed in the same
way, as with relay 1. The switch positions for setting the
respective relays are stated in the list of the function switch
under "Setup procedure".
Note:
If you want to change the mode (i.e. the switching function of
the relays), you have to exchange the On and Off values.
22SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
Maintenance and fault rectification
7 Maintenance and fault rectification
7.1 Maintenance
When used as directed in normal operation, SU 600 Exis
completely maintenance-free.
7.2 Fault rectification
Causes of malfunction
Fault rectification
Fault messages
SU 600 Exoffers maximum reliability. Nevertheless faults can
occur during operation. These may be caused by the following,
e.g.:
l Measured value of the sensor not correct
l Power supply
l Interference on the cables
The first measures to be taken are to check the input/output
signals as well as to evaluate the error messages via the
display. The procedure is described below. In many cases, the
causes can be determined in this way and faults can be
rectified.
? E003
l CRC-error
à Carry out a reset
à Return instrument for repair
? E014
l Short-circuit
à Eliminate short-circuit
à If necessary, exchange defective sensor
? E015
l Line break
à Repair sensor cable or replace it
à Check sensor connection
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning23
Maintenance and fault rectification
? E016
l Empty/full adjustment reversed
à Carry out a fresh adjustment
? E017
l Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E021
l Scaling span too small
à Carry out a fresh scaling, increase the distance
between min. and max. scaling.
? E110
l Relay switching points too close together
à Increase the difference between the two relay switching
points
7.3 Instrument repair
If a repair is necessary, please proceed as follows:
You can download a return form from our Internet homepagehttp://www.krohne-mar.com/fileadmin/media-lounge/PDF-
Download/Specimen_e.pdf.
By doing this you help us carry out the repair quickly and
without having to call back for needed information.
l Print and fill out one form per instrument
l Clean the instrument and pack it damage-proof
l Attach the completed form and possibly also a safety data
sheet to the instrument.
24SU 600 Ex - 4 ... 20 mA signal conditioning
30653-EN-050803
Dismounting
8 Dismounting
8.1 Dismounting procedure
Warning:
Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures,
corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power
supply" and carry out the listed steps in reverse order.
8.2 Disposal
SU 600 Ex consists of materials which can be recycled by
specialised recycling companies. We have purposely designed the electronic modules to be easily separable. Mark the
instrument as scrap and dispose of it according to government
regulations (electronic scrap ordinance, …).
Materials: see "Technical data"
If you cannot dispose of the instrument properly, please
contact us about disposal methods or return.
30653-EN-050803
SU 600 Ex - 4 ... 20 mA signal conditioning25
Supplement
9 Supplement
9.1 Technical data
General data
Seriesinstrument for panel or wall mounting or
mounting on carrier rail 35x7.5 acc. to
EN 50022
DimensionsW = 96 mm (3.78 in), H = 104 mm (4.09 in),
Power supply20 … 253 VAC, 50/60 Hz, 20 … 253 VDC
Power consumption12.4 VA, 4 W
S
ensor input
Number of sensors1x 4 … 20 mA
Kind of input (switch over)
- mode activesensor is powered by SU 600 Ex
- mode passivesensor has own power supply
Measured value transmission4 … 20 mA analogue
Terminal voltage mode active19.5 … 14.5 V at 4 … 20 mA
Current limitation mode activeapprox. 30 mA
Inner resistance mode passive< 250 Ohm
Detection line break<= 3.6 mA
Detection shortcircuit>= 21 mA
Adjustment range
- Empty adjustment3.8 … 20.2 mA
- Full adjustment4.1 … 20.5 mA
. adjustment delta300 µA
- min
Connection cable2-wire standard cable (screening recommen-