All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of KROHNE Messtechnik GmbH.
9.4 Inputs/outputs and HART® dynamic variables and device variables.......................... 139
10 Notes141
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
5
1 SAFETY INSTRUCTIONS
1.1 Software history
The "Electronic Revision" (ER) is consulted to document the revision status of electronic
equipment according to NE 53 for all GDC devices. It is easy to see from the ER whether
troubleshooting or larger changes in the electronic equipment have taken place and how that
has affected the compatibility.
Changes and effect on compatibility
1Downwards compatible changes and fault repair with no effect on operation (e.g. spelling
mistakes on display)
2-_Downwards compatible hardware and/or software change of interfaces:
HART
®
H
PPROFIBUS
FFoundation Fieldbus
MModbus
Xall interfaces
3-_Downwards compatible hardware and/or software change of inputs and outputs:
ICurrent output
F, PFrequency / pulse output
SStatus output
CControl input
CICurrent input
Xall inputs and outputs
4Downwards compatible changes with new functions
5Incompatible changes, i.e. electronic equipment must be changed.
MFC 400
INFORMATION!
In the table below, "x" is a placeholder for possible multi-digit alphanumeric combinations,
depending on the available version.
Release dateElectronic RevisionChanges and
Documentation
compatibility
2012-09-06ER 1.0.0x-MA MFC400 R01
2013-03-12ER 1.0.1x1MA MFC400 R02
2013-06-27ER 1.0.2x1; 2-M; 2-HMA MFC400 R02
2013-06-27ER 1.0.3x1; 2-F; 2-P; 2-XMA MFC400 R02
6
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
1.2 Intended use
The mass flowmeters are designed exclusively to directly measure mass flow rates, product
density and temperature as well to indirectly measure parameters such as the total volume and
concentration of dissolved substances as well as the volume flow rate.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
If the device is not used according to the operating conditions (refer to chapter Technical data),
the intended protection could be affected.
1.3 Certifications
CE marking
SAFETY INSTRUCTIONS 1
The device fulfils the statutory requirements of the following EC directives:
• Low Voltage Directive 2006/95/EC
• EMC Directive 2004/108/EC
as well as
• EN 61010
• EMC specification acc. to EN 61326/A1
• NAMUR recommendations NE 21 and NE 43
The manufacturer certifies successful testing of the product by applying the CE marking.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
7
1 SAFETY INSTRUCTIONS
1.4 Safety instructions from the manufacturer
1.4.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no
guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.
MFC 400
We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.
1.4.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.
8
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
1.4.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper
installation and operation of the devices (systems) will cause the warranty to be void. The
respective "Standard Terms and Conditions" which form the basis for the sales contract shall
also apply.
1.4.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the
information in this document and observe applicable national standards, safety requirements
and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of underneath icons.
SAFETY INSTRUCTIONS 1
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
9
1 SAFETY INSTRUCTIONS
1.4.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This information refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to
serious health problems and even death. There is also the risk of seriously damaging the device
or parts of the operator's plant.
MFC 400
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
• HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the
specified sequence.
iRESULT
RESULT
RESULTRESULT
This symbol refers to all important consequences of the previous actions.
1.5 Safety instructions for the operator
10
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and
maintained by properly trained and authorized personnel.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
2.1 Scope of delivery
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
DEVICE DESCRIPTION 2
Figure 2-1: Scope of delivery
1 Device in the version as ordered
2 Documentation (calibration protocol, factory and material certification if ordered, CD-ROM with product documenta-
tion for sensor and signal converter)
3 Signal cable (only for remote version)
Signal converter / measuring sensor combination possibilities
Measuring sensorSignal converter MFC 400
CompactRemote field housing
OPTIMASS 6000OPTIMASS 6400 COPTIMASS 6400 F
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
11
2 DEVICE DESCRIPTION
2.2 Device description
The mass flowmeters are designed exclusively to directly measure mass flow rates, product
density and temperature as well to indirectly measure parameters such as the total volume and
concentration of dissolved substances as well as the volume flow rate.
Your measuring device is supplied ready for operation. The factory settings for the operating
data have been made in accordance with your order specifications.
The following versions are available:
• Compact version (the signal converter is mounted directly on the measuring sensor)
• Remote version (electrical connection to the measuring sensor via field current and signal
cable)
MFC 400
Figure 2-2: Device versions
1 Compact version
2 Measuring sensor with connection box
3 Field housing
12
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
2.2.1 Field housing
Figure 2-3: Construction of the field housing
1 Cover for electronics and display
2 Cover for power supply and inputs/outputs terminal compartment
3 Cover for measuring sensor terminal compartment
4 Cable entry for measuring sensor signal cable
5 Cable entry for measuring sensor field current cable
6 Cable entry for power supply
7 Cable entry for inputs and outputs
8 Mounting plate for pipe and wall mounting
DEVICE DESCRIPTION 2
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
13
2 DEVICE DESCRIPTION
2.3 Nameplates
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
2.3.1 Example of a nameplate
MFC 400
Figure 2-4: Example of a nameplate
1 Approvals-related information: Ex approval, EC type test certificate, hygienic approvals, etc.
2 Approvals-related thresholds
3 Additional information on documentation, calibration and patents
4 Protection category
5 Electrical connection data
6 Software and hardware revision (Electronics Revision), CG number, order number for signal converter and measuring
sensor
7 Product description
8 Manufacturer and manufacturer logo
14
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
DEVICE DESCRIPTION 2
2.3.2 Electrical connection data of inputs/outputs (example of basic version)
Figure 2-5: Example of a nameplate for electrical connection data of inputs and outputs
1 Power supply (AC: L and N; DC: L+ and L-; PE for ≥ 24 VAC; FE for ≤ 24 VAC and DC)
2 Connection data of connection terminal D/D-
3 Connection data of connection terminal C/C-
4 Connection data of connection terminal B/B-
5 Connection data of connection terminal A/A-; A+ only operable in the basic version
• A = active mode; the signal converter supplies the power for connection of the subsequent
devices
• P = passive mode; external power supply required for operation of the subsequent devices
• N/C = connection terminals not connected
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
15
3 INSTALLATION
3.1 General notes on installation
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
3.2 Storage
• Store the device in a dry, dust-free location.
• Avoid continuous direct sunlight.
• Store the device in its original packing.
• Storage temperature: -50...+70°C / -58...+158°F
MFC 400
3.3 Transport
Signal converter
• No special requirements.
Compact version
• Do not lift the device by the signal converter housing.
• Do not use lifting chains.
• To transport flange devices, use lifting straps. Wrap these around both process connections.
3.4 Installation specifications
INFORMATION!
The following precautions must be taken to ensure reliable installation.
•
Make sure that there is adequate space to the sides.
•
Protect the signal converter from direct sunlight and install a sun shade if necessary.
•
Signal converters installed in control cabinets require adequate cooling, e.g. by fan or heat
exchanger.
•
Do not expose the signal converter to intense vibrations. The measuring devices are tested
for a vibration level in accordance with IEC 68-2-64.
16
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
3.5 Mounting of the compact version
INFORMATION!
The signal converter is mounted directly on the measuring sensor. For installation of the
flowmeter, please observe the instructions in the supplied product documentation for the
measuring sensor.
3.6 Mounting the field housing, remote version
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
3.6.1 Pipe mounting
INSTALLATION 3
Figure 3-1: Pipe mounting of the field housing
1 Fix the signal converter to the pipe.
2 Fasten the signal converter using standard U-bolts and washers.
3 Tighten the nuts.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
17
3 INSTALLATION
3.6.2 Wall mounting
Figure 3-2: Wall mounting of the field housing
MFC 400
1 Prepare the holes with the aid of the mounting plate. For further information refer to
plate, field housing
on page 133.
Mounting
2 Use the mounting material and tools in compliance with the applicable occupational health
and safety directives.
3 Fasten the housing securely to the wall.
Mounting multiple devices next to each other
a ≥ 600 mm / 23.6"
b ≥ 250 mm / 9.8"
18
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
3.6.3 Turning the display of the field housing version
INSTALLATION 3
Figure 3-3: Turning the display of the field housing version
The display of the field housing version can be turned in 90° increments.
1 Unscrew the cover from the display and operation control unit.
2 Using a suitable tool, pull out the two metal puller devices to the left and right of the display.
3 Pull out the display between the two metal puller devices and rotate it to the required position.
4 Slide the display and then the metal puller devices back into the housing.
5 Re-fit the cover and tighten it by hand.
CAUTION!
The ribbon cable of the display must not be folded or twisted repeatedly.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
19
4 ELECTRICAL CONNECTIONS
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
DANGER!
Observe the national regulations for electrical installations!
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
MFC 400
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
4.2 Important notes on electrical connection
DANGER!
Electrical connection is carried out in conformity with the VDE 0100 directive "Regulations for
electrical power installations with line voltages up to 1000 V" or equivalent national regulations.
CAUTION!
•
Use suitable cable entries for the various electrical cables.
•
The measuring sensor and signal converter have been configured together at the factory. For
this reason, please connect the devices in pairs.
20
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
4.3 Requirements for signal cables provided by the customer
INFORMATION!
If the signal cable was not ordered, it is to be provided by the customer. The following
requirements regarding the electrical values of the signal cable must be observed:
Specifications for standard signal cables
• 5 twisted pair circuits (24 AWG)
• Insulation thickness of cables: ≥ 0.2 mm / 0.008")
• Each cable pair shielded with foil and drain wire
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
21
4 ELECTRICAL CONNECTIONS
4.4 Connecting the signal cables
DANGER!
Cables may only be connected when the power is switched off.
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
MFC 400
22
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
4.4.1 Connection of signal cable - Field housing and connection box for sensor
Figure 4-1: Connection of signal cable - Field housing and connection box for sensor
1 Unscrew the terminal compartment cover.
2 Pass the prepared signal cable through the cable entry.
3 Secure the signal cable using the clip.
4 Connect the electrical conductors as shown. The shielding must also be connected to the
spring terminal.
5 Re-fit the cover and tighten it by hand.
CableCableConnection terminal
Cable pairColour
1yellowX1 SA+
1blackX1 SA-
2greenX1 SB+
2blackX1 SB-
3blueX2 T1
3blackX2 T2
4redX2 T3
4blackX2 T4
5whiteX3 DR+
5blackX3 DR-
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
23
4 ELECTRICAL CONNECTIONS
4.4.2 Connection diagram
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
MFC 400
Figure 4-2: Connection diagram
1 Terminal compartment for signal converter
2 Terminal compartment for measuring sensor
3 Connect shielding to spring terminal (drain wire and overall shield)
CableCableConnection terminal
Cable pairColour
1yellowX1 SA+
1blackX1 SA-
2greenX1 SB+
2blackX1 SB-
3blueX2 T1
3blackX2 T2
4redX2 T3
4blackX2 T4
5whiteX3 DR+
5blackX3 DR-
24
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.5 Grounding the measuring sensor
DANGER!
There should be no difference in potential between the measuring sensor and the housing or
protective earth of the signal converter!
• The measuring sensor must be properly grounded.
• The grounding cable should not transmit any interference voltages.
• Do not use the grounding cable to connect more than one device to ground.
• The measuring sensors are connected to ground by means of a functional grounding
conductor FE.
• In hazardous areas, grounding is used at the same time for equipotential bonding. Additional
grounding instructions are provided in the separate "Ex documentation", which are only
supplied together with hazardous area equipment.
ELECTRICAL CONNECTIONS 4
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
25
4 ELECTRICAL CONNECTIONS
4.6 Connecting power, all housing variants
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
• The protection category depends on the housing versions (IP65...67 to IEC 529 / EN 60529 or
NEMA4/4X/6).
• The housings of the devices, which are designed to protect the electronic equipment from
dust and moisture, should be kept well closed at all times. Creepage distances and
clearances are dimensioned to VDE 0110 and IEC 664 for pollution severity 2. Supply circuits
are designed for overvoltage category III and the output circuits for overvoltage category II.
• Fuse protection (I
breaker) to isolate the signal converter must be provided close to the device. The separator
must be marked as the separator for this device.
≤ 16 A) for the infeed power circuit, as well as a separator (switch, circuit
N
MFC 400
100...230 VAC (tolerance range: -15% / +10%)
• Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
• The protective ground terminal PE
clamp terminal in the terminal compartment of the signal converter
PE of the power supply must be connected to the separate U-
• For measurement process reasons, a functional ground FE
separate U-clamp terminal in the terminal compartment of the signal converter.
• When connecting to functional extra-low voltages, provide a facility for protective separation
(PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).
FE must be connected to the
FEFE
INFORMATION!
For 24 VDC, 12 VDC-10% is included in the tolerance range.
26
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
Power supply connection
1 100...230 VAC (-15% / +10%), 22 VA
2 24 VDC (-55% / +30%), 12 W
3 24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 22 VA or 12 W
4.7 Inputs and outputs, overview
4.7.1 Combinations of the inputs/outputs (I/Os)
This signal converter is available with various input/output combinations.
Basic version
• Has 1 current output, 1 pulse output and 2 status outputs / limit switches.
• The pulse output can be set as status output/limit switch and one of the status outputs as a
control input.
ELECTRICAL CONNECTIONS 4
Ex i version
• Depending on the task, the device can be configured with various output modules.
• Current outputs can be active or passive.
• Optionally available also with Foundation Fieldbus and Profibus PA
Modular version
• Depending on the task, the device can be configured with various output modules.
Bus systems
• The device allows intrinsically safe and non intrinsically safe bus interfaces in combination
with additional modules.
• For connection and operation of bus systems, please note the separate documentation.
Ex option
• For hazardous areas, all of the input/output variants for the housing designs C and F with
terminal compartment in the Ex d (pressure-resistant casing) or Ex e (increased safety)
versions can be delivered.
• Please refer to the separate instructions for connection and operation of the Ex-devices.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
27
4 ELECTRICAL CONNECTIONS
4.7.2 Description of the CG number
Figure 4-3: Marking (CG number) of the electronics module and input/output variants
1 ID number: 3
2 ID number: 0 = standard; 9 = special
3 Power supply option
4 Display (language versions)
5 Input/output version (I/O)
6 1st optional module for connection terminal A
7 2nd optional module for connection terminal B
The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal
connections. Please refer to the following examples.
Examples for CG number
MFC 400
CG 330 11 100100...230 VAC & standard display; basic I/O: Ia or Ip & Sp/Cp & Sp & Pp/S
p
CG 330 11 7FK100...230 VAC & standard display; modular I/O: Ia & PN/SN and optional module PN/SN & C
CG 330 81 4EB24 VDC & standard display; modular I/O: Ia & Pa/Sa and optional module Pp/Sp & I
p
Description of abbreviations and CG identifier for possible optional modules
on terminals A and B
AbbreviationIdentifier for CG No.Description
I
a
I
p
Pa / S
a
Pp / S
p
PN / S
N
C
a
C
p
C
N
-8No additional module installed
-0No further module possible
AActive current output
BPassive current output
CActive pulse output, frequency output, status output or limit switch
(changeable)
EPassive pulse output, frequency output, status output or limit switch
(changeable)
FPassive pulse output, frequency output, status output or limit switch acc.
to NAMUR (changeable)
GActive control input
KPassive control input
HActive control input to NAMUR
Signal converter monitors cable breaks and short circuits acc. to
EN 60947-5-6. Errors indicated on LC display. Error messages possible
via status output.
N
28
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.7.3 Fixed, non-alterable input/output versions
This signal converter is available with various input/output combinations.
• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Connection terminal A+ is only operable in the basic input/output version.
CG no.Connection terminals
A+AA-BB-CC-DD-
Basic I/Os (standard)
1 0 0
Ia + HART® active 1
Ip + HART® passive 1
Ex i IOs (option)
2 0 0
3 0 0
2 1 0Ia activePN / SNNAMUR
3 1 0Ia activePN / SNNAMUR
2 2 0Ip passivePN / SNNAMUR
3 2 0Ip passivePN / SNNAMUR
Sp / Cp passive 2Sp passivePp / Sp passive 2
passive 2
C
p
Cp passive 2
passive 2
C
p
Cp passive 2
ELECTRICAL CONNECTIONS 4
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SN NAMUR 2
PN / SNNAMUR 2
PN / SNNAMUR 2
PROFIBUS PA (Ex i) (option)
D 0 0PA+PA-PA+PA-
FISCO DeviceFISCO Device
D 1 0Ia activePN / SNNAMUR
passive 2
C
p
D 2 0Ip passivePN / SNNAMUR
passive 2
C
p
PA+PA-PA+PA-
FISCO DeviceFISCO Device
PA+PA-PA+PA-
FISCO DeviceFISCO Device
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
29
4 ELECTRICAL CONNECTIONS
FOUNDATION Fieldbus (Ex i) (option)
E 0 0V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
E 1 0Ia activePN / SNNAMUR
Cp passive 2
E 2 0Ip passivePN / SNNAMUR
Cp passive 2
1 function changed by reconnecting
2 changeable
V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
V/D+V/D-V/D+V/D-
FISCO DeviceFISCO Device
MFC 400
30
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.7.4 Alterable input/output versions
This signal converter is available with various input/output combinations.
• The grey boxes in the tables denote unassigned or unused connection terminals.
• In the table, only the final digits of the CG no. are depicted.
• Term. = (connection) terminal
CG no.Connection terminals
A+AA-BB-CC-DD-
Modular IOs (option)
4 _ _max. 2 optional modules for term. A + B
8 _ _max. 2 optional modules for term. A + B
6 _ _max. 2 optional modules for term. A + B
B _ _max. 2 optional modules for term. A + B
7 _ _max. 2 optional modules for term. A + B
C _ _max. 2 optional modules for term. A + B
ELECTRICAL CONNECTIONS 4
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Ia + HART® active
Ip + HART® passive
Pa / Sa active 1
Pa / Sa active 1
Pp / Sp passive 1
Pp / Sp passive 1
PN / SN NAMUR 1
PN / SN NAMUR 1
PROFIBUS PA (option)
D _ _max. 2 optional modules for term. A + BPA+ (2)PA- (2)PA+ (1)PA- (1)
FOUNDATION Fieldbus (option)
E _ _max. 2 optional modules for term. A + BV/D+ (2)V/D- (2)V/D+ (1)V/D- (1)
PROFIBUS DP (option)
F _ 01 optional module for
term. A
Termination P
RxD/TxDP(2)
RxD/TxDN(2)
Termination N
RxD/TxDP(1)
RxD/TxDN(1)
Modbus (option)
G _ _ 2max. 2 optional modules for term. A + BCommonSign. B
(D1)
H _ _ 3max. 2 optional modules for term. A + BCommonSign. B
(D1)
1 changeable
2 not activated bus terminator
3 activated bus terminator
Sign. A
(D0)
Sign. A
(D0)
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
31
4 ELECTRICAL CONNECTIONS
4.8 Description of the inputs and outputs
4.8.1 Current output
INFORMATION!
The current outputs must be connected depending on the version! Which I/O versions and
inputs/outputs are installed in your signal converter are indicated on the sticker in the cover of
the terminal compartment.
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power U
• Active mode: load impedance R
R
≤ 450 Ω at I ≤ 22 mA for Ex i outputs
L
• Self-monitoring: interruption or load impedance too high in the current output loop
• Error message possible via status output, error indication on LC display.
• Current value error detection can be adjusted. Default setting: 3.6 mA
• Automatic range conversion via threshold or control input. The setting range for the
threshold is between 5 and 80% of Q
smaller to larger range of 1:20 to 1:1.25).
Signaling of the active range possible via a status output (adjustable).
• Forward / reverse flow measurement (F/R mode) is possible.
≤ 32 VDC at I ≤ 22 mA
ext
≤ 1kΩ at I ≤ 22 mA;
L
100%
MFC 400
, ± 0...5% hysteresis (corresponding ratio from
INFORMATION!
For further information refer to Description of the inputs and outputs on page 38
Technical data on page 122
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
32
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.8.2 Pulse and frequency output
INFORMATION!
Depending on the version, the pulse and frequency outputs must be connected passively or
actively or according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are
installed in your signal converter are indicated on the sticker in the cover of the terminal
compartment.
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 100 mA at f ≤ 100 Hz
• Active mode:
Use of the internal power supply: U
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 20 mA at f ≤ 100 Hz
• NAMUR mode: passive in accordance with EN 60947-5-6, f ≤ 10 kHz,
over range up to f
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q
fixed (pulse width adjustable as required from 0.05 ms...2 s)
• Forward / reverse flow measurement (F/R mode) is possible.
• All pulse and frequency outputs can also be used as a status output / limit switch.
max
≤ 12 kHz
≤ 32 VDC
ext
=24VDC
nom
ELECTRICAL CONNECTIONS 4
≤ 12 kHz)
max
≤ 12 kHz)
max
);
100%
) or
100%
INFORMATION!
For further information refer to Description of the inputs and outputs on page 38
Technical data on page 122
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
33
4 ELECTRICAL CONNECTIONS
4.8.3 Status output and limit switch
INFORMATION!
Depending on the version, the status outputs and limit switches must be connected passively or
actively or according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are
installed in your signal converter are indicated on the sticker in the cover of the terminal
compartment.
• The status outputs / limit switches are electrically isolated from each other and from all
other circuits.
• The output stages of the status outputs/limit switches during simple active or passive
operation behave like relay contacts and can be connected with any polarity.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
≤ 32 VDC; I ≤ 100 mA
U
ext
• Active mode: use of the internal power supply:
=24VDC; I ≤ 20 mA
U
nom
• NAMUR mode: passive in accordance with EN 60947-5-6
• For information on the adjustable operating states refer to
Function tables
MFC 400
on page 68.
INFORMATION!
For further information refer to Description of the inputs and outputs on page 38
Technical data on page 122
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
34
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.8.4 Control Input
INFORMATION!
Depending on the version, the control inputs must be connected passively or actively or
according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are installed in your
signal converter are indicated on the sticker in the cover of the terminal compartment.
• All control inputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
≤ 32 VDC
U
ext
• Active mode: use of the internal power supply:
U
nom
• NAMUR mode: in accordance with EN 60947-5-6
(Active control input to NAMUR EN 60947-5-6: signal converter monitors cable breaks and
short circuits acc. to EN 60947-5-6. Errors indicated on LC display. Error messages possible
via status output.
• For information on the adjustable operating states refer to
=24VDC
ELECTRICAL CONNECTIONS 4
Function tables
on page 68.
INFORMATION!
For further information refer to Description of the inputs and outputs on page 38
Technical data on page 122
.
and refer to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
35
4 ELECTRICAL CONNECTIONS
4.9 Electrical connection of the inputs and outputs
INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.
4.9.1 Field housing, electrical connection of the inputs and outputs
DANGER!
All work on the electrical connections may only be carried out with the power disconnected. Take
note of the voltage data on the nameplate!
INFORMATION!
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).
MFC 400
Figure 4-4: Terminal compartment for inputs and outputs in field housing
1 Open the housing cover.
2 Push the prepared cable through the cable entry and connect the necessary conductors.
3 Connect the shield if necessary.
4 Close the touch guard.
5 Close the housing cover.
INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resinfree and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
36
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.9.2 Laying electrical cables correctly
Figure 4-5: Protect housing from dust and water
1 Lay the cable in a loop just before the housing.
2 Tighten the screw connection of the cable entry securely.
3 Never mount the housing with the cable entries facing upwards.
4 Seal cable entries that are not needed with a plug.
ELECTRICAL CONNECTIONS 4
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
37
4 ELECTRICAL CONNECTIONS
4.10 Description of the inputs and outputs
4.10.1 Important notes
INFORMATION!
Depending on the version, the inputs/outputs must be connected passively or actively or acc. to
NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are installed in your signal
converter are indicated on the sticker in the cover of the terminal compartment.
• All groups are electrically isolated from each other and from all other input and output
circuits.
• Passive mode: An external power supply is necessary to operate (activation) the subsequent
devices (U
• Active mode: The signal converter supplies the power for operation (activation) of the
subsequent devices, observe max. operating data.
• Terminals that are not used should not have any conductive connection to other electrically
conductive parts.
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
ext
).
MFC 400
Description of used abbreviations
I
I
a
P
a
P
N
S
a
S
N
C
a
C
N
Current output active or passive
p
P
Pulse/frequency output active or passive
p
Pulse/frequency output passive acc. to NAMUR EN 60947-5-6
S
Status output/limit switch active or passive
p
Status output/limit switch passive acc. to NAMUR EN 60947-5-6
C
Control input active or passive
p
Control input active acc. to NAMUR EN 60947-5-6:
Signal converter monitors cable breaks and short circuits acc. to EN 60947-5-6. Errors
indicated on LC display. Error messages possible via status output.
38
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.10.2 Description of the electrical symbols
mA meter
0...20 mA or 4...20 mA and other
RL is the internal resistance of the measuring point including the cable
resistance
DC voltage source (U
ELECTRICAL CONNECTIONS 4
), external power supply, any connection polarity
ext
Table 4-1: Description of symbols
DC voltage source (U
connection diagrams
Internal DC voltage source
Controlled internal power source in the device
Electronic or electromagnetic counter
At frequencies above 100 Hz, shielded cables must be used to connect the
counters.
Ri Internal resistance of the counter
Button, NO contact or similar
), observe connection polarity according to
ext
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
39
4 ELECTRICAL CONNECTIONS
4.10.3 Basic inputs/outputs
CAUTION!
Observe connection polarity.
Current output active (HART®), basic I/Os
• U
• I ≤ 22 mA
• R
= 24 VDC nominal
int, nom
≤ 1kΩ
L
MFC 400
Figure 4-6: Current output active I
a
Current output passive (HART®), basic I/Os
• U
• U
• I ≤ 22 mA
• U
• R
Figure 4-7: Current output passive I
= 24 VDC nominal
int, nom
≤ 32 VDC
ext
≥ 1.8 V
0
≤ (U
L
ext-U0
)/I
max
p
40
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
INFORMATION!
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
•
Any connection polarity.
Pulse/frequency output passive, basic I/Os
• U
• f
• f
• If the following maximum load impedance R
• The minimum load impedance R
• Can also be set as a status output; for the electrical connection refer to status output
≤ 32 VDC
ext
in the operating menu set to f
max
≤ 100 Hz:
max
I ≤ 100 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
= 0.2 V at I ≤ 10 mA
0, max
= 2 V at I ≤ 100 mA
0, max
in operating menu set to 100 Hz < f
max
≤ 10 kHz:
max
I ≤ 20 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
U
= 1.5 V at I ≤ 1 mA
0, max
= 2.5 V at I ≤ 10 mA
0, max
= 5.0 V at I ≤ 20 mA
0, max
L, max
be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
R
L, min
=(U
L, max
L, max
L, max
ext-U0
= 47 kΩ
= 10 kΩ
= 1 kΩ
)/I
max
is calculated as follows:
L, min
connection diagram.
is exceeded, the load impedance RL must
Figure 4-8: Pulse/frequency output passive P
p
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
41
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Any connection polarity.
Status output / limit switch passive, basic I/Os
• U
• I ≤ 100 mA
• R
• open:
• The output is open when the device is de-energized.
• X stands for the connection terminals B, C or D. The functions of the connection terminals
≤ 32 VDC
ext
= 47 kΩ
L, max
L, min
=(U
ext-U0
R
I ≤ 0.05 mA at U
)/I
= 32 VDC
ext
max
closed:
U
U
= 0.2 V at I ≤ 10 mA
0, max
= 2 V at I ≤ 100 mA
0, max
depend on the settings refer to
Function tables
MFC 400
on page 68.
Figure 4-9: Status output / limit switch passive S
p
Control input passive, basic I/Os
• 8V≤ U
• I
max
I
max
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• Can also be set as a status output; for the electrical connection refer to status output
connection diagram.
Figure 4-10: Control input passive C
1 Signal
≤ 32 VDC
ext
= 6.5 mA at U
= 8.2 mA at U
≤ 24 VDC
ext
≤ 32 VDC
ext
≤ 2.5 V with I
0
≥ 8 V with I
0
= 0.4 mA
nom
= 2.8 mA
nom
p
42
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.10.4 Modular inputs/outputs and bus systems
CAUTION!
Observe connection polarity.
INFORMATION!
•
For further information on electrical connection refer to Description of the inputs and outputs
on page 38
For the electrical connection of bus systems, please refer to the separate documentation for
•
the respective bus systems.
Current output active (only current output terminals C/C- have HART® capability),
modular I/Os
• U
int, nom
• I ≤ 22 mA
≤ 1kΩ
• R
L
• X designates the connection terminals A, B or C, depending on the version of the signal
converter.
.
= 24 VDC
ELECTRICAL CONNECTIONS 4
Figure 4-11: Current output active I
a
Current output passive (only current output terminals C/C- have HART® capability),
modular I/Os
• U
• I ≤ 22 mA
• U
• R
• X designates the connection terminals A, B or C, depending on the version of the signal
Figure 4-12: Current output passive I
≤ 32 VDC
ext
≥ 1.8 V
0
≤ (U
L
ext-U0
converter.
)/I
max
p
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
43
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
•
Any connection polarity.
Pulse/frequency output active, modular I/Os
• U
• f
• f
• If the following maximum load impedance R
• The minimum load impedance R
• X designates the connection terminals A, B or D, depending on the version of the signal
= 24 VDC
nom
in the operating menu set to f
max
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
= 24 V at I = 20 mA
0, nom
in operating menu set to 100 Hz < f
max
I ≤ 20 mA
open:
I ≤ 0.05 mA
closed:
U
U
U
= 22.5 V at I = 1 mA
0, nom
= 21.5 V at I = 10 mA
0, nom
= 19 V at I = 20 mA
0, nom
be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
R
L, min=U0/Imax
L, max
L, max
L, max
= 47 kΩ
= 10 kΩ
= 1 kΩ
L, min
converter.
≤ 100 Hz:
max
≤ 10 kHz:
max
is exceeded, the load impedance RL must
L, max
is calculated as follows:
MFC 400
44
Figure 4-13: Pulse / frequency output active P
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
a
MFC 400
ELECTRICAL CONNECTIONS 4
Pulse/frequency output passive, modular I/Os
• U
• f
• f
• If the following maximum load impedance R
• The minimum load impedance R
• Can also be set as status output; refer to status output connection diagram.
• X designates the connection terminals A, B or D, depending on the version of the signal
≤ 32 VDC
ext
in the operating menu set to f
max
≤ 100 Hz:
max
I ≤ 100 mA
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
=0.2V at I≤ 10 mA
0, max
=2V at I≤ 100 mA
0, max
in operating menu set to 100 Hz < f
max
≤ 10 kHz:
max
open:
I ≤ 0.05 mA at U
= 32 VDC
ext
closed:
U
U
U
=1.5V at I≤ 1mA
0, max
=2.5 V at I ≤ 10 mA
0, max
=5V at I≤ 20 mA
0, max
L, max
be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f ≤ 1 kHz: R
f ≤ 10 kHz: R
L, min
=(U
R
L, max
L, max
L, max
ext-U0
= 47 kΩ
= 10 kΩ
= 1 kΩ
)/I
max
is calculated as follows:
L, min
converter.
is exceeded, the load impedance RL must
Figure 4-14: Pulse frequency output passive P
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
p
45
4 ELECTRICAL CONNECTIONS
INFORMATION!
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
•
Any connection polarity.
Pulse and frequency output passive PN NAMUR, modular I/O
• Connection in conformity with EN 60947-5-6
• open:
= 0.6 mA
I
nom
closed:
= 3.8 mA
I
nom
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
MFC 400
Figure 4-15: Pulse and frequency output passive PN to NAMUR EN 60947-5-6
46
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
Status output / limit switch active, modular I/Os
• Observe connection polarity.
• U
• I ≤ 20 mA
• R
• open:
• X designates the connection terminals A, B or D, depending on the version of the signal
= 24 VDC
int
≤ 47 kΩ
L
I ≤ 0.05 mA
closed:
U
= 24 V at I = 20 mA
0, nom
converter.
Figure 4-16: Status output / limit switch active S
a
Status output / limit switch passive, modular I/Os
• Any connection polarity.
• U
• I ≤ 100 mA
• R
• open:
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
=32VDC
ext
= 47 kΩ
L, max
L, min
=(U
ext-U0
R
I ≤ 0.05 mA at U
closed:
U
U
=0.2V at I≤ 10 mA
0, max
=2V at I≤ 100 mA
0, max
converter.
)/I
= 32 VDC
ext
max
Figure 4-17: Status output / limit switch passive S
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
p
47
4 ELECTRICAL CONNECTIONS
Status output / limit switch SN NAMUR, modular I/Os
• Any connection polarity.
• Connection in conformity with EN 60947-5-6
• open:
= 0.6 mA
I
nom
closed:
= 3.8 mA
I
nom
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
MFC 400
Figure 4-18: Status output / limit switch SN to NAMUR EN 60947-5-6
48
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
CAUTION!
Observe connection polarity.
Control input active, modular I/Os
• U
• External contact open:
• Switching point for identifying "contact open or closed":
• X designates the connection terminals A or B, depending on the version of the signal
= 24 VDC
int
0, nom
=22V
U
External contact closed:
I
= 4 mA
nom
Contact closed (on): U
Contact open (off): U
≥ 12 V with I
0
converter.
≤ 10 V with I
0
nom
= 1.9 mA
nom
= 1.9 mA
Figure 4-19: Control input active C
1 Signal
a
Control input passive, modular I/Os
• 3V≤ U
• I
max
I
max
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• X designates the connection terminals A or B, depending on the version of the signal
converter.
≤ 32 VDC
ext
=9.5mA at U
=9.5mA at U
≤ 24 V
ext
≤ 32 V
ext
≤ 2.5 V with I
0
0
≥ 3V with I
nom
nom
=1.9mA
=1.9mA
Figure 4-20: Control input passive C
1 Signal
p
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
49
4 ELECTRICAL CONNECTIONS
CAUTION!
Observe connection polarity.
Control input active CN NAMUR, modular I/Os
• Connection acc. to EN 60947-5-6
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• Detection of cable break:
≥ 8.1 V with I ≤ 0.1 mA
U
0
• Detection of cable short circuit:
≤ 1.2 V with I ≥ 6.7 mA
U
0
• X designates the connection terminals A or B, depending on the version of the signal
converter.
= 6.3 V with I
0, nom
0, nom
= 6.3 V with I
< 1.9 mA
nom
nom
MFC 400
> 1.9 mA
Figure 4-21: Control input active CN to NAMUR EN 60947-5-6
50
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.10.5 Ex i inputs/outputs
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
For further information on electrical connection refer to Description of the inputs and outputs on
page 38
Current output active (only current output terminals C/C- have HART® capability), Ex i
I/Os
• Observe connection polarity.
• U
• I ≤ 22 mA
• R
• X designates the connection terminals A or C, depending on the version of the signal
.
= 20 VDC
int, nom
≤ 450 Ω
L
converter.
ELECTRICAL CONNECTIONS 4
Figure 4-22: Current output active Ia Exi
Current output passive (only current output terminals C/C- have HART® capability),
Ex i I/Os
• Any connection polarity.
• U
• I ≤ 22 mA
• U
• R
• X designates the connection terminals A or C, depending on the version of the signal
Figure 4-23: Current output passive Ip Exi
≤ 32 VDC
ext
≥ 4 V
0
≤ (U
L
ext-U0
converter.
)/I
max
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
51
4 ELECTRICAL CONNECTIONS
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
•
Compact and field housing versions:
Compact and field housing versions: Shield connected via the cable terminals in the terminal
Compact and field housing versions:Compact and field housing versions:
compartment.
•
Any connection polarity.
Pulse and frequency output passive PN NAMUR, Ex i I/Os
• Connection acc. to EN 60947-5-6
• open:
= 0.43 mA
I
nom
closed:
= 4.5 mA
I
nom
• X designates the connection terminals B or D, depending on the version of the signal
converter.
MFC 400
Figure 4-24: Pulse and frequency output passive PN as per NAMUR EN 60947-5-6 Exi
52
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
ELECTRICAL CONNECTIONS 4
INFORMATION!
•
Any connection polarity.
Status output/limit switch SN NAMUR, Ex i I/Os
• Connection acc. to EN 60947-5-6
• open:
= 0.43 mA
I
nom
closed:
I
= 4.5 mA
nom
• The output is closed when the device is de-energized.
• X designates the connection terminals B or D, depending on the version of the signal
converter.
Figure 4-25: Status output/limit switch SN to NAMUR EN 60947-5-6 Exi
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
53
4 ELECTRICAL CONNECTIONS
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
INFORMATION!
•
Any connection polarity.
Control input passive, Ex i I/Os
• 5.5 V ≤ U
• I
= 6 mA at U
max
I
= 6.5 mA at U
max
• Switching point for identifying "contact open or closed":
Contact open (off): U
Contact closed (on): U
• X designates the connection terminals B, if available.
≤ 32 VDC
ext
≤ 24 V
ext
≤ 32 V
ext
≤ 3.5 V with I ≤ 0.5 mA
0
≥ 5.5 V with I ≥ 4 mA
0
MFC 400
Figure 4-26: Control input passive Cp Exi
1 Signal
54
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
4.10.6 HART® connection
INFORMATION!
•
In the basic I/O the current output at connection terminals A+/A-/A always has HART®
capability.
•
For modular I/O and Ex i E/A, only the output module for the connection terminals C/C- has
®
HART
HART® connection active (point-to-point)
capability.
ELECTRICAL CONNECTIONS 4
Figure 4-27: HART® connection active (Ia)
1 Basic I/O: terminals A and A+
2 Modular I/O: terminals C- and C
3 HART
®
communicator
The parallel resistance to the HART® communicator must be R ≥ 230 Ω.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
55
4 ELECTRICAL CONNECTIONS
HART® connection passive (Multi-Drop mode)
• I: I0% ≥ 4mA
• Multi-Drop mode I: I
• U
≤ 32 VDC
ext
• R ≥ 230 Ω
≥ 4mA = I
fix
0%
MFC 400
Figure 4-28: HART® connection passive (Ip)
1 Basic I/O: terminals A- and A
2 Modular I/O: terminals C- and C
3 HART
4 Other devices with HART
®
communicator
®
capability
56
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
5.1 Switching on the power
Before connecting to power, please check that the system has been correctly installed.
This includes:
• The device must be mechanically safe and mounted in compliance with the regulations.
• The power connections must have been made in compliance with the regulations.
• The electrical terminal compartments must be secured and the covers have been screwed
on.
• Check that the electrical operating data of the power supply are correct.
• Switching on the power.
5.2 Starting the signal converter
The measuring device, consisting of the measuring sensor and the signal converter, is supplied
ready for operation. All operating data have been set at the factory in accordance with your order
specifications.
START-UP 5
When the power is switched on, a self test is carried out. After that the device immediately
begins measuring, and the current values are displayed.
Figure 5-1: Displays in measuring mode (examples for 2 or 3 measured values)
x, y and z denote the units of the measured values displayed
It is possible to change between the two measured value windows, the trend display and the list
with the status messages by pressing the keys ↑ and ↓. For possible status messages, their
meaning and cause refer to
Status messages and diagnostic information
on page 104.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
57
6 OPERATION
6.1 Display and operating elements
Figure 6-1: Display and operating elements (Example: flow indication with 2 measuring values)
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 Indicates when a key has been pressed
4 1st measured variable in large representation
5 Bargraph indication
6 Operating keys, optical and mechanical (see table below for function and representation in text)
7 Interface to the GDC bus (not present in all signal converter versions)
8 Infrared sensor (not present in all signal converter versions)
MFC 400
CAUTION!
The use of a jumper is only permitted for custody transfer devices to block access to parameters
relevant to custody transfer. When the jumper is set to or removed from the "protected" position,
the signal converter restarts to switch into the protected or unprotected operating mode.
INFORMATION!
•
The switching point for the 4 optical keys is located directly in front of the glass. It is
recommended to activate the keys at right angles to the front. Touching them from the side
can cause incorrect operation.
•
After 5 minutes of inactivity, there is an automatic return to measuring mode. Previously
changed data is not saved.
58
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
KeyMeasuring modeMenu modeSubmenu or function
mode
>Switch from measuring
mode to menu mode;
press key for 2.5 s,
"quick start" menu is
then displayed
^Reset display; "Quick
Access" function
↓ or ↑Switch between display
pages: measured
value 1 + 2, trend page
and status page
Esc (> + ↑)--Return to menu mode
Access to displayed
menu, then 1st
submenu is displayed
Return to measuring
mode but prompt
whether the data should
be saved
Select menuSelect submenu or
Access to displayed submenu or function
Press 1 to 3 times,
return to menu mode,
data saved
function
without acceptance of
data
Parameter and data
mode
For numerical values,
move cursor
(highlighted in blue) one
position to the right
Return to submenu or
function, data saved
Use cursor highlighted
in blue to change
number, unit, property
and to move the decimal
point
Return to submenu or
function without
acceptance of data
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
59
6 OPERATION
6.1.1 Display in measuring mode with 2 or 3 measured values
Figure 6-2: Example for display in measuring mode with 2 or 3 measured values
1 Indicates a possible status message in the status list
2 Tag number (is only indicated if this number was entered previously by the operator)
3 1st measured variable in large representation
4 Bargraph indication
5 Depiction with 3 measured values
6.1.2 Display for selection of submenu and functions, 3 lines
MFC 400
Figure 6-3: Display for selection of submenu and functions, 3 lines
1 Indicates a possible status message in the status list
2 Menu, submenu or function name
3 Number relating to 6
4 Indicates position within menu, submenu or function list
5 Next menu, submenu or function
(_ _ _ signalise in this line the end of the list)
6 Current menu, submenu or function
7 Previous menu, submenu or function
(_ _ _ signalise in this line the beginning of the list)
60
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.1.3 Display when setting parameters, 4 lines
Figure 6-4: Display when setting parameters, 4 lines
1 Current menu, submenu or function
2 Number relating to 7
3 Denotes factory setting
4 Denotes permissible value range
5 Permissible value range for numeric values
6 Currently set value, unit or function (when selected, appears with white text, blue background)
This is where the data is changed.
7 Current parameter
8 Factory setting of parameter
OPERATION 6
6.1.4 Display when previewing parameters, 4 lines
Figure 6-5: Display when previewing parameters, 4 lines
1 Current menu, submenu or function
2 Number relating to 6
3 Denotes a changed parameter (simple check of changed data when browsing through lists)
4 Next parameter
5 Currently set data from 6
6 Current parameter (for selection press key >; then see previous chapter)
7 Factory setting of parameter
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
61
6 OPERATION
6.1.5 Using an IR interface (option)
The optical IR interface serves as an adapter for PC-based communication with the signal
converter without opening the housing.
INFORMATION!
•
This device is not part of the scope of delivery.
•
For more information about activation with the functions A6 or C6.6.7.
MFC 400
Figure 6-6: IR interface
1 Glass panel in front of the control and display panel
2 IR interface
3 LED lights up when IR interface is activated.
4 Suction cups
Timeout function
Following activation of the IR interface in Fct. A6 or C6.6.7 the interface must be properly
positioned and attached to the housing with the suction cups within 60 seconds. If this does not
happen within the specified time period, the device can be operated using the optical keys again.
Upon activation, the LED 3 lights up and the optical keys no longer function.
62
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.2 Zero calibration (menu C1.1.1)
Following installation, perform zero calibration prior to commissioning the device. Finalise the
installation before performing zero calibration. Changes (pipe system or calibration factor) made
after the zero calibration may affect the accuracy, making it necessary to perform zero
calibration again.
Observe the following for reliable zero calibration:
• The measuring sensor should be completely filled with the product at the expected process
pressure and temperature.
• The product may contain no air or gas, especially when it comes to horizontal installations.
Prior to zero calibration, it is recommended that the product be flushed at a high flow rate
(>50%), for 2 minutes.
• After flushing, re-establish zero flow by closing off the corresponding valves.
Set zero calibration automatically or manually using the operating controls. The converter cover
must be installed on the display for automatic calibration.
A) Automatic calibration
OPERATION 6
ButtonScreenDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release the key.
2 x ↓CSetup
3 x >C1.1.1Zero Calibration
>Calibrate zero?
^Please Wait
^Zero Calibration
5 x ^Save Configuration?
^Display page
Automatic
Countdown from 40 s
Calibrate zero
Passed
Display of measured zero calibration in %.
+XX.XXX%
Yes
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
63
6 OPERATION
B) Manual calibration
ButtonScreenDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release the key.
2 x ↓CSetup
3 x >C1.1.1Zero Calibration
>Calibrate zero?
2 x ↓Calibrate zero?
5 x ^Save Configuration?
^Display page
Zero calibration log (C1.1.5)
Zero calibrations are recorded in the zero calibration log. Log information includes zero offset,
temperature, date and time. Navigate using the ↑ and ↓ keys. Exit the menu using the ^ key.
Automatic
Manual
Zero Calibration
+XX.XXX%
Yes
MFC 400
Display currently stored zero calibration in %.
(Warning, value can be changed!)
Possible manual entry of zero calibration.
Storing the displayed zero calibration.
Under certain conditions, zero calibration is not possible and will be cancelled:
• The product is still flowing. The shut-off valves are not closed tightly enough.
• There are still gas bubbles in the measuring sensor.
Remedy: Flush measuring sensor and repeat calibration
With some media, it may be difficult to perform zero calibration. In such cases, there are various
methods to still achieve good zero calibration:
MediumPossible solutions
Media that tend to evaporate or outgasIncrease pressure.
Two-phase media (slurries), that contain solids that
may fall out.
Two-phase media in which the solids or gasforming components cannot be separated.
Only fill the measuring sensor with the carrier
medium.
Fill measuring sensor with another liquid, e.g.
water.
64
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.3 Menu structure
INFORMATION!
Note the key function within and between the columns.
OPERATION 6
Measure modeSelect
menu↓ ↑
^Press
>2.5s
A Quick Setup> ^A1 Language>
↓↑↓↑↓↑↓↑ >
Select menu and/or submenu
↓↑
A2 Tag
A3 Reset> ^A3.1 Reset Errors
A3.2. All Totalisers
A3.3 Totaliser 1
A3.4 Totaliser 2
A3.5 Totaliser 3
A4 Analogue OutputsA4.1 Measurement
A4.2 Unit
A4.3 Range
A4.4 Low Flow Cutoff
A4.5 Time Constant
A5 Digital OutputsA5.1 Measurement
A5.2 Pulse Value Unit
A5.3 Value p. Pulse
A5.4 Low Flow Cutoff
A6 GDC IR interface
A7 Flow Direction
A8 Zero Calibration
A9 Operation Mode
Select
function
and set
data
↓↑ >
^
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
65
6 OPERATION
MFC 400
Measuring modeSelect
menu↓ ↑
^Press
>2.5s
B Test> ^B1 Simulation> ^B1.1 Mass Flow>
↓↑↓↑↓↑↓↑ >
Select menu and/or submenu
↓↑
B1.2 Volume Flow
B1.3 Density
B1.4 Temperature
B1._ Current Output X
B1._ Status Output X
B1._ Control Input X
B1._ Pulse Output X
B2 Actual Values> ^B2.1 Operating Hours
Date and Time
B2.3 Mass Flow
B2.4 Volume Flow
B2.5 Velocity
B2.6 Density
B2.7 Temperature
B2.8 Strain 1
B2.9 Strain 2
B2.10 Tube Frequency
B2.11 Drive Level
B2.12 Sensor A Level
B2.13 Sensor B Level
2.14 2 Phase Signal
B2.15 SE PCB
Temperature
B2.16 Act. Operat. Mode
B3 Information> ^B3.1 Status Log
B3.2 Status Details
B3.3 C Number
B3.4 Sensor Electronics
B3.6 Electronic Revision
B3.7 Sensor Revision
Change Log
Select
function
and set
data
↓↑ >
^
66
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
Measure modeSelect
menu↓ ↑
^Press
>2.5s
C Setup> ^C1 Process Input> ^C1.1 Zero and Offset>
^> ^C3 I/O (Inputs/Outputs) > ^C3.1 Hardware>
^> ^C4 I/O Totalisers> ^C4.1 Totaliser 1>
^> ^C5 I/O HART> ^C5.1 PV is>
^> ^C6 Device> ^C6.1 Device Info>
↓ ↑↓ ↑↓ ↑↓ ↑ >
Select menu and/or submenu
↓↑
C1.2 Density
C1.3 Filter
C1.4 System Control
C1.5 Diagnosis
C1.6 Information
C1.7 Flow Calibration
C1.8 Density Calib.
C1.9 Simulation
> ^C2 Concentration>
C3._ Current Output X
C3._ Frequency Output X
C3._ Pulse Output X
C3._ Status Output X
C3._ Limit Switch X
C3._ Control Input X
C4.2 Totaliser 2
C4.3 Totaliser 3
C5.2 SV is
C5.3 TV is
C5.4 4V is
C5.5 HART Units
C6.2 Display
C6.3 1st Meas. Page
C6.4 2nd Meas. Page
C6.5 Graphic Page
C6.6 Special Functions
C6.7 Units
C6.8 HART
C6.9 Quick Setup
Select
function
and set
data
↓↑ >
^
^
^
^
^
^
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
67
6 OPERATION
6.4 Function tables
INFORMATION!
•
The following tables describe the functions of the standard device with HART® connection.
The functions for Modbus, Foundation Fieldbus and Profibus are described in detail in the
corresponding supplementary instructions.
•
Depending on the device version, not all functions are available.
6.4.1 Menu A, Quick Setup
No.FunctionSetting / Description
A1 Language
A1LanguageLanguage selection depends on the device version.
A2 Tag
A2Tag
Measuring point identifier (Tag no.) (also for HART® operation) appears in
the LCD header (max. 8 digits).
MFC 400
A3 Reset
A3Reset
A3.1Reset ErrorsReset Errors? Select: No / Yes
A3.2All TotalisersReset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.3Totaliser 1Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.4Totaliser 2Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.5Totaliser 3Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A4 Analogue Outputs (only for HART®)
A4Analogue OutputsApplicable to all current outputs (terminals A, B and C), frequency outputs
A4.1MeasurementSelect:
A4.2UnitSelection of the unit from a list, depending on the "measurement"
A4.3RangeSetting for main current output (range: 0...100%)
A4.4Low Flow Cutoff1) Setting for main current output (sets output value to "0")
(terminals A, B and D), limit switch (terminals A, B, C, and / or D) and the 1st
display page / line 1.
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
Use for all outputs? (also use this setting for Fct. A4.2...A4.5!)
Setting: no (applies only to the main current output ) / yes (applies to all
analogue outputs)
Setting: 0…x.xx (format and unit, depending on measurement, see A4.1 and
A4.2 above)
Use for all outputs? Make setting, see Fct. A4.1 above!
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A4.1 above!
68
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
No.FunctionSetting / Description
OPERATION 6
A4.5Time Constant1) Setting for main current output (applicable to all flow measurements)
Setting: xxx.x s (range: 000.1…100 s)
2) Use for all outputs? Make setting, see Fct. A4.1 above!
2) Use for all outputs? (also use this setting for Fct. A5.2...A5.4!)
Setting: No (only for pulse output D) / Yes (for all digital outputs)
A5.2Pulse Value UnitSelection of the unit from a list, depending on the "measurement"
A5.3Value Per Pulse1) Setting for pulse output D (volume or mass value per pulse)
A5.4Low Flow Cutoff1) Setting for pulse output D (sets output value to "0")
Setting: xxx.xxx in l/s or kg/s
2) Use for all outputs? Make setting, see Fct. A5.1 above!
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A5.1 above!
A6 GDC IR interface
A6GDC IR InterfaceAfter this function has been activated an optical GDC adapter can be
connected to the LC display. After 60 seconds pass without a connection
being established or after the adapter is removed, the function is exited and
the optical keys are active again.
Break (exit function without connection)
Activate (the IR interface adapter and interrupt the optical keys)
A7 Flow Direction
A7Flow DirectionForwards (according to the arrow on the measuring sensor) or backwards
(in the opposite direction to the arrow)
A8 Zero Calibration
A8Zero CalibrationZero calibration; calibration sequence as described in Fct. C1.1.1...1.1.4
A9 Operation Mode
A9Operation ModeSet the operating mode.
Setting: Measure / Stop / Standby
For detailed information refer to
Operation Mode (menu A9)
on page 89.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
69
6 OPERATION
6.4.2 Menu B, test
No.FunctionSetting / Description
B1 Simulation
B1SimulationDisplayed values are simulated.
B1.1Mass FlowSimulation of mass flow
Set value (range and units depend on measurement)
Break (exit function without simulation)
Query: start simulation?
Settings: Yes (start simulation) / No (exit function without simulation)
B1.2Volume FlowSequence and settings similar to B1.1, see above!
B1.3Density
B1.4Temperature
B1._Current Output XSimulation X
B1._Pulse Output X
B1._Frequency Output X
B1._Control Input X
B1._Limit Switch X
B1._Status Output X
[X stands for one of the connection terminals A, B, C or D]
_ stands for Fct. B1.4...1.7
[X stands for one of the connection terminals A, B, C or D]
Sequence and settings similar to B1.1, see above!
For the pulse output the set number of pulses are displayed once in a
second!
MFC 400
B2 Actual Values
B2Actual ValuesDisplay of actual values;
B2.1Operating HoursDevice operating hours
B2.2Date and TimeDate and time of real time clock
B2.3Mass FlowCurrent unfiltered mass flow
B2.4Volume FlowCurrent unfiltered volume flow
B2.5VelocityCurrent unfiltered velocity
B2.6DensityCurrent unfiltered density
B2.7TemperatureCurrent unfiltered temperature
B2.8Strain 1Current value for the first strain
B2.9Strain 2Current value for the second strain
B2.10Tube FrequencyCurrent vibration frequency of the measuring tube
B2.11Drive LevelCurrent drive level to activate vibration
B2.12Sensor A LevelCurrent vibration amplitude
B2.13Sensor B Level
B2.142 Phase Signal2 phase indicator value
B2.15SE PCB TemperatureTemperature of measuring sensor electronics
B2.16Act. Operat. ModeCurrent operation mode
Exit the displayed function with the ^ key.
70
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
B3 Information
B3Information
B3.1Status LogLog with date and time of status messages that occurred
B3.2Status DetailsDetails about the status messages displayed
B3.3C NumberCG number, cannot be changed (input/output version)
B3.4Sensor ElectronicsDisplays the version of the measuring sensor electronics
B3.5"Bus interface"Only appears with Profibus, Modbus and FF
B3.6Electronic RevisionFor presentation of LC display see Fct. B3.3 and B3.4
B3.7Sensor RevisionRevision of measuring sensor
B3.8Change LogThe check sum across all settings is displayed directly below the menu item.
Shows the changes including date, time and check sum for all settings and
parameters in the converter, regardless of the interface (display, HART
PROFIBUS, ...) used.
®
6.4.3 Menu C, Setup
,
No.FunctionSettings / descriptions
C1 Process Input
C1.1 Zero and Offset
C1.1Zero and Offset-
C1.1.1Zero CalibrationStart zero calibration
Query: calibrate zero?
Setting:
Automatic / Factory Settings /
Manual (display last value; set new value, range: -10…+10%) /
Break (return with ^ key)
C1.1.2Zero Add. OffsetDirect setting of zero offset
C1.1.3Pipe DiameterSet the pipe diameter in mm to calculate flow velocity
C1.1.4Flow CorrectionDefines additional correction for mass flow;
C1.1.5Zero Calibration LogLog of last zero calibration including zero point, temperature, date and time
Range: -100...+100%
C1.2 Density
C1.2.1Density Calib.Start density calibration
For detailed information refer to
90.
C1.2.2Density ModeSelection of density mode:
Process (return with ^ key /
Fixed (a fixed value is used for the density (e.g. standard density)) /
Referred (calculates process density based on a reference temperature) /
Standard (calculates standard density based on a reference temperature
and the correction factors)
C1.2.3Fixed Density ValueSet the fixed value (e.g. standard density) for the density.
Appears only if density mode "Fixed" has been selected in Fct. C1.2.2.
C1.2.3Density Ref. Temp.Set the reference temperature for the reference density option
Appears only if density mode "Referred" has been selected in Fct. C1.2.2.
Density calibration (menu C1.2.1)
on page
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
71
6 OPERATION
MFC 400
No.FunctionSettings / descriptions
C1.2.4Ref. Density SlopeSet the slope for the reference density option
Appears only if density mode "Referred" has been selected in Fct. C1.2.2.
C1.2.5Standard Density Temp.Appears only if density mode "Standard" has been selected in Fct. C1.2.2.
C1.2.6Standard Density k0Appears only if density mode "Standard" has been selected in Fct. C1.2.2.
C1.2.7Standard Density k1Appears only if density mode "Standard" has been selected in Fct. C1.2.2.
C1.2.8Standard Density k2Appears only if density mode "Standard" has been selected in Fct. C1.2.2.
C1.2.9Last Density Cal.Date of last density calibration
Density reference temperature to calculate standard density
Coefficient k0 to calculate standard density
Coefficient k1 to calculate standard density
Coefficient k2 to calculate standard density
C1.3 Filter
C1.3Filter-
C1.3.1Flow DirectionDefine polarity of flow direction.
Forwards (according to the arrow on the measuring sensor) or backwards
(in the opposite direction to the arrow)
C1.3.2Press. Supp. TimeSet the pressure suppression time; range: 0.0...20.0 s
C1.3.3Press. Supp. CutoffLow flow cutoff settings for the pressure suppression; range: 0.0...10.0%
C1.3.4Low Flow CutoffSet the low flow cutoff; range: 00.0...10.0%
C1.4 System Control
C1.4System Control-
C1.4.1FunctionSet the system control.
C1.4.2Sys. Ctrl. ConditionSet the condition for activating the system control.
C1.4.3Sys. Ctrl. Max LimitDefines the upper limit for the condition selected in C1.4.2
C1.4.4Sys. Ctrl. Min LimitDefines the lower limit for the condition selected in C1.4.2
Select: Inactive (off) / Flow = 0 (flow to zero)
Selection: density or temperature
C1.5 Diagnosis
C1.5Diagnosis-
C1.5.1Max. Rec. Temp.Display of maximum recorded sensor temperature
C1.5.2Min. Rec. Temp.Display of minimum recorded sensor temperature
C1.5.32 Ph. ThresholdDefines the process-dependent sensitivity for 2 phase signal error message.
C1.5.4Defines the parameter for the respective diagnostic value.
C1.5.5
C1.5.6
C1.5.7Proc: Signal LowSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.8Proc: Signal SearchSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.9Proc: Current InputSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.10Proc: 2 Phase FlowSelection of status signal (Failure, Out of Specification, Function Check,
Select:
Off (goes to zero) / Sensor Average (sensor amplitude A+B) / Sensor
Deviation / Drive Level / MT Frequency / Strain 1 / Strain 2 /
2 Phase Signal
Maintenance Required and Information) for the group "Proc: Signal Low"
Maintenance Required and Information) for the group "Proc: Signal Search"
Maintenance Required and Information) for the group "Proc: Current Input"
Maintenance Required and Information) for the group "Proc: 2 Phase Flow"
72
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
No.FunctionSettings / descriptions
OPERATION 6
C1.5.11Proc: System ControlSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.12Config: TotaliserSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.13Electr: Power FailureSelection of status signal (Failure, Out of Specification, Function Check,
C1.5.14Electr: IO ConnectionSelection of status signal (Failure, Out of Specification, Function Check,
Maintenance Required and Information) for the group "Proc: System
Control"
Maintenance Required and Information) for the group "Config: Totaliser"
Maintenance Required and Information) for the group "Electr: Power
Failure"
Maintenance Required and Information) for the group "Electr: IO
Connection"
C1.6 Information
C1.6Information-
C1.6.1Sensor NameName of measuring sensor
C1.6.2Sensor IDID of measuring sensor
C1.6.3Nominal Mass FlowNominal mass flow of measuring sensor
C1.6.4Max. Allowed Temp.Displays the maximum permitted temperature for the measuring sensor
C1.6.5Min. Allowed Temp.Displays the minimum permitted temperature for the measuring sensor
C1.6.6Calibration DateDate of factory calibration
C1.6.7V No. SensorV number of the measuring sensor
C1.6.8Serial No. SensorSerial number of the measuring sensor
C1.6.9V No. ConverterV number of the signal converter
C1.6.10Sensor ElectronicsDisplays the version of the measuring sensor electronics
C1.7 Flow Calibration
C1.7Flow Calibration-
C1.7.1...
1.7.25
CF1...CF27Displays the measuring sensor calibration coefficients (not CF9 or CF10) for
the flow measurement
C1.8 Density Calib.
C1.8Density Calib.-
C1.8.1...
1.8.8
DCF1...DCF8Displays the measuring sensor calibration coefficients for density
measurement
C1.9 Simulation
C1.9Simulation-
C1.9.1Mass FlowAs in B1.1
C1.9.2Volume FlowAs in B1.2
C1.9.3DensityAs in B1.3
C1.9.4TemperatureAs in B1.4
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
C3.1HardwareConfiguration of connection terminals.
Selection depends on signal converter version.
C3.1.1Terminal ASelect:
Off (switched off) / Current Output / Frequency Output / Pulse Output / Status
Output / Limit Switch / Control Input
C3.1.2Terminal BSelect:
Off (switched off) / Current Output / Frequency Output / Pulse Output / Status
Output / Limit Switch / Control Input
C3.1.3Terminal CSelect:
Off (switched off) / Current Output / Status Output / Limit Switch
C3.1.4Terminal DSelect:
Off (switched off) / Frequency Output / Pulse Output / Status Output / Limit
Switch
MFC 400
C3._ Current Output X
C3._Current Output XX stands for one of the connection terminals A, B or C
C3._.1Range 0%…100%
C3._.2Extended RangeMin. and max. limits of current values. If the current range is exceeded, the
C3._.3Error CurrentSpecify error current (default setting: 3.6 mA)
C3._.4Error ConditionThe following error conditions can be selected:
C3._.5MeasurementMeasurements for activating the output
_ stands for Fct. C3.2 (A) / C3.3 (B) / C3.4 (C)
®
HART
current output: 4…20 mA
Current range for the selected measurement, e.g. 4...20 mA,
corresponds to 0…100%
Note: with a 0...20 mA current output, "HART" in Fct. C6.8.1 must be
switched off!
xx.x … xx.x mA; range: 0.00…20 mA
(condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 20 mA)
current is set to these limits.
xx.x … xx.x mA; range: 03.5…21.5 mA
(Condition: 0 mA ≤ 1st value ≤ 2nd value ≤ 21.5 mA and out of current range)
xx.x mA; range: 3…22 mA (condition: outside of extended range)
Select:
Failure / Maintenance Required / Out Of Specification (error category [S])
Select:
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
C3._.6Range0…100% of the measurement set in Fct. C3._.5
x.xx…xx.xx _ _ _ (format and unit depend on the "measurement", see above)
74
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
No.FunctionSettings / descriptions
C3._.7PolaritySet polarity; the flow direction in C1.3.2 must be noted!
Select:
Both Polarities (plus and minus values are displayed) /
Positive Polarity (display for negative values = 0) /
Negative Polarity (display for positive values = 0) /
Absolute Value (always displays positive, with both negative and positive
values)
C3._.8LimitationLimitation before applying the time constant
±xxx …±xxx%; range: -150…+150%
C3._.9Low Flow CutoffSets the measurement to "0" for low values
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C3._.10Time ConstantRange: 000.1…100 s
C3._.11Special FunctionAutomatic Range;
Select:
Off (switched off) /
Automatic Range (range is changed automatically, extended lower range,
only makes sense in combination with a status output) /
External Range (change by control input, extended lower range; control
input must also be activated)
C3._.12ThresholdAppears only when Fct. C3._.11 "Threshold" is activated between extended
C3._.13InformationSerial no. of the I/O board, software version no. and production date of the
C3._.14SimulationSequence see B1._ current output X
C3._.154mA TrimmingTrimming of the current at 4 mA
and normal range. The automatic range function always changes from the
extended to the normal range when the 100% current is reached.
The upper 100% value of the hysteresis is then = 0. The threshold is then the
hysteresis value, instead of "Threshold ± Hysteresis" as shown in the
display.
Range: 5.0…80%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
circuit board
Reset to 4 mA restores the factory calibration.
Used for HART® setting.
C3._.1620mA TrimmingTrimming of the current at 20 mA
Reset to 20 mA restores the factory calibration.
Used for HART® setting.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
75
6 OPERATION
C3._ Frequency Output X
C3._Frequency Output XX stands for one of the connection terminals A, B or D
C3._.1Pulse ShapeSpecify the pulse shape
C3._.2Pulse WidthOnly available if set to "Fixed" in Fct. C3._.1.
C3._.3100% Pulse RatePulse rate for 100% of the measuring range
C3._.4MeasurementMeasurements for activating the output
_ stands for Fct. C3.2 (A) / C3.3 (B) / C3.5 (D)
Select:
Symmetric (about 50% on and 50% off) /
Automatic (constant pulse with about 50% on and 50% off at 100% pulse
rate) /
Fixed (fixed pulse rate, setting see below Fct. C3._.3 100% pulse rate)
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
Range: 1…10000 Hz
Limitation 100% pulse rate ≤ 100/s: I
Limitation 100% pulse rate > 100/s: I
Select:
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
max
max
≤ 100 mA
≤ 20 mA
MFC 400
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
C3._.5Range0…100% of the measurement set in Fct. C3._.4
x.xx…xx.xx _ _ _ (format and unit depend on the "measurement", see above)
C3._.6PolaritySet polarity; the flow direction in C1.3.2 must be noted!
Select:
Both Polarities (plus and minus values are displayed) /
Positive Polarity (display for negative values = 0) /
Negative Polarity (display for positive values = 0) /
Absolute Value (always displays positive, with both negative and positive
values)
C3._.7LimitationLimitation before applying the time constant
±xxx …±xxx%; range: -150…+150%
C3._.8Low Flow CutoffSets the measurement to "0" for low values
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C3._.9Time ConstantRange: 000.1…100 s
C3._.10Invert SignalSelect:
C3._.11Phase Shift w.r.t. BOnly available when configuring the terminal A or D and only if output B is a
Off (activated output: switch closed) /
On (activated output: switch open)
pulse or frequency output. If setting in Fct. C2.5.6 is "Both Polarities", the
phase shift is prefixed by a symbol, e.g. -90° and +90°
Select:
Off (no phase shift) /
0° Phase Shift (between outputs A or D and B, inversion possible) /
90° Phase Shift (between outputs A or D and B, inversion possible) /
180° Phase Shift (between outputs A or D and B, inversion possible)
76
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
C3.3.11Special FunctionsThis function is only available at the terminal B frequency output. At the
C3._.12InformationSerial no. of the I/O board, software version no. and production date of the
C3._.13SimulationSequence see B1._ Frequency Output X
same time, 2 frequency outputs must be available:
1st output at terminal A or D / 2nd output at terminal B
The B output is operated as a slave output, controlled and set using master
output A or D
Select:
Off (no phase shift) /
Phase Shift w.r.t. D or A (slave output is B and master output is D or A)
circuit board
C3._ Pulse Output X
C3._Pulse Output XX stands for one of the connection terminals A, B or D
C3._.1Pulse ShapeSpecify the pulse shape
C3._.2Pulse WidthOnly available if set to "Fixed" in Fct. C3._.1.
C3._.3Max. Pulse RatePulse rate for 100% of the measuring range
C3._.4MeasurementMeasurements for activating the output
C3._.5Pulse Value UnitSelection of the unit from a list, depending on the "measurement"
C3._.6Value Per PulseSet value for volume or mass per pulse
C3._.7PolaritySet polarity; the flow direction in C1.3.2 must be noted!
C3._.8Low Flow CutoffSets the measurement to "0" for low values
C3._.9Time ConstantRange: 000.1…100 s
C3._.10Invert SignalSelect:
_ stands for Fct. C3.2 (A) / C3.3 (B) / C3.5 (D)
Select:
Symmetric (about 50% on and 50% off) /
Automatic (constant pulse with about 50% on and 50% off at 100% pulse
rate) /
Fixed (fixed pulse rate, setting see below Fct. C3._.3 100% pulse rate)
Range: 0.05…2000 ms
Note: max. setting value Tp [ms] ≤ 500 / max. pulse rate [1/s], gives the pulse
width = time where the output is activated
Range: 0.0…10000 1/s
Limitation 100% pulse rate ≤ 100/s: I
Limitation 100% pulse rate > 100/s: I
Select: Volume Flow / Mass Flow
xxx.xxx, measured value in [l] or [kg] depending on setting in C3._.6
At max. pulse rate see above 3._.3 "Pulse Output"
Select:
Both Polarities (plus and minus values are displayed) /
Positive Polarity (display for negative values = 0) /
Negative Polarity (display for positive values = 0) /
Absolute Value (always displays positive, with both negative and positive
values)
x.xxx ± x.xxx%; range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
Off (activated output: switch closed) /
On (activated output: switch open)
max
max
≤ 100 mA
≤ 20 mA
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
77
6 OPERATION
MFC 400
C3._.11Phase Shift w.r.t. BOnly available when configuring the terminal A or D and only if output B is a
C3.3.11Special FunctionsThis function is only available at the pulse output of terminal B. At the same
C3._.12InformationSerial no. of the I/O board, software version no. and production date of the
C3._.13SimulationSequence see B1._ Pulse Output X
pulse or frequency output. If setting in Fct. C2.5.6 is "Both Polarities", the
phase shift is prefixed by a symbol, e.g. -90° and +90°
Select:
Off (no phase shift) /
0° Phase Shift (between outputs A or D and B, inversion possible) /
90° Phase Shift (between outputs A or D and B, inversion possible) /
180° Phase Shift (between outputs A or D and B, inversion possible)
time, 2 pulse outputs must be available:
1st output at terminal A or D / 2nd output at terminal B
The B output is operated as a slave output, controlled and set using master
output A or D
Select:
Off (no phase shift) /
Phase Shift w.r.t. D or A (slave output is B and master output is D or A)
circuit board
78
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
C3._ Status Output X
C3._Status Output XX (Y) stands for one of the connection terminals A, B, C or D
C3._.1ModeThe output shows the following measuring conditions:
C3._.2Current Output YOnly appears if output A...C is set under "Mode" (see above), and this output
C3._.2Frequency Output Y and
Pulse Output Y
C3._.2Status Output YOnly appears if output A...D is set under "Mode" (see above), and this output
C3._.2Limit Switch Y and Control
Input Y
C3._.2Output YOnly appears if output A...D is set under "Mode" (see above) and this output
C3._.3Invert SignalSelect:
C3._.4InformationSerial no. of the I/O board, software version no. and production date of the
Failure (output set, signals status of the category "Failure" refer to
messages and diagnostic information
Out Of Specification (output set, signals status of category "Failure" or
"Maintenance Required" or "Out Of Specification" refer to
and diagnostic information
Maintenance Required (output set, signals status of category "Failure" or
"Maintenance Required" refer to
information
Flow Polarity (polarity of the current flow) /
Flow Over Range (over range of the flow)
Totaliser 1 Preset (activates when totaliser X preset value is reached) /
Totaliser 2 Preset (activates when totaliser X preset value is reached) /
Totaliser 3 Preset (activates when totaliser X preset value is reached) /
Output A (activated by the status of output Y, additional output data see
below) /
Output B (activated by the status of output Y, additional output data see
below) /
Output C (activated by the status of output Y, additional output data see
below) /
Output D (activated by the status of output Y, additional output data see
below) /
Off (switched off)
is a "Current Output".
Polarity (is signalled)
Over Range (is signalled)
Automatic Range signals lower range
Only appears if output A, B or D is set under "Mode" (see above), and this
output is a "Frequency/Pulse Output".
Polarity (is signalled)
Over Range (is signalled)
is a "Status Output".
Same Signal (like other connected status output, signal can be inverted, see
below)
Only appears if output A...D / input A or B is set under "Mode" (see above),
and this output / input is a "Limit Switch / Control Input".
Status Off (is always selected here if Status Output X is connected with a
Limit Switch / Control Input Y).
is switched off.
Off (activated output: switch closed) /
On (activated output: switch open)
circuit board
on page 104) /
on page 104) /
on page 104) /
Status messages
Status messages and diagnostic
Status
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
79
6 OPERATION
MFC 400
C3._ Limit Switch X
C3._Limit Switch XX stands for one of the connection terminals A, B, C or D
C3._.1MeasurementSelect:
C3._.2ThresholdSwitching level, set threshold with hysteresis
C3._.3PolaritySet polarity; the flow direction in C1.3.2 must be noted!
C3._.4Time ConstantRange: 000.1…100 s
C3._.5Invert SignalSelect:
C3._.6InformationSerial no. of the I/O board, software version no. and production date of the
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
xxx.x ±x.xxx (format and unit depend on the measurement, see above)
(1st value = threshold / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
Select:
both polarities (plus and minus values are displayed) /
Positive Polarity (display for negative values = 0) /
Negative Polarity (display for positive values = 0) /
Absolute Value (always displays positive, with both negative and positive
values)
Off (activated output: switch closed) /
On (activated output: switch open)
circuit board
C3._ Control Input X
C3._Control Input X
C3._.1ModeX stands for connection terminal A or B
C3._.2Invert SignalSelect:
C3._.3InformationSerial no. of the I/O board, software version no. and production date of the
C3._.4SimulationSequence see B1._ Control Input X
_ stands for Fct. C3.2 (A) / C3.3 (B)
Off (control input switched off) /
Hold All Outputs (hold actual values, not display and totalisers) /
Hold Output Y (hold actual values) /
All Outputs To Zero (actual values = 0%, not display and totalisers) /
Output Y To Zero (actual value = 0%) /
All Totalisers (reset all totalisers to "0") /
Totaliser "Z" Reset (set totaliser 1, 2 or 3 to "0") /
Stop All Totalisers /
Stop counter "Z" (stops counter 1, 2 or 3) /
Zero Outp.+Stop Tot. (all outputs 0%, stop all totalisers, not the display) /
External Range Y (control input for external range of current output Y) - also
make this setting on current output Y (no check if current output Y is
available) /
Error Reset (all resettable errors are deleted) /
Calibrate Zero
Off (activated output: switch closed) /
On (activated output: switch open)
circuit board
80
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
No.FunctionSettings / descriptions
C4 I/O Totalisers
C4.1Totaliser 1Set function of counter.
C4.2Totaliser 2
C4.3Totaliser 3
C4._.1Totaliser FunctionSelect:
C4._.2MeasurementSelection of the measurement for Totaliser _
C4._.3Low Flow CutoffSets the measurement to "0" for low values
C4._.4Time ConstantRange: 0.1…100 s
C4._.5Preset ValueIf this value is reached, positive or negative, a signal is generated that can be
C4._.6Reset TotaliserSequence see Fct. A3.2, A3.3 and A3.4
C4._.7Set TotaliserSet Totaliser _ to the desired value
C4._.8Stop TotaliserTotaliser _ is stopped and holds the actual value
C4._.9Start TotaliserStart Totaliser _ after that totaliser is stopped
C4._.10InformationSerial no. of the I/O board, software version no. and production date of the
_ stands for 1, 2, 3 (= Totaliser 1, 2, 3)
The basic version (standard) has only 2 totaliser!
Absolute Total (counts positive + negative values) /
+Totaliser (counts only the positive values) /
-counter (counts only the negative values) /
Off (Totaliser is switched off)
Select:
Volume Flow / Mass Flow /
(depends on the settings for the concentration measurement):
Conc. mass flow 1 / Conc. mass flow 2 / Conc. volume flow 1 / Conc. volume
flow 2
Range: 0.0…20%
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
used for a status output at which "Preset Totaliser X" has to be set.
Preset Value (max. 8 digits) x.xxxxx in selected unit, see C6.7.10 + 13
Select:
Break (exit function) / Set Value (opens the editor to make the entry)
Query: Set Totaliser?
Select:
Select: No (exit function without setting the value) / Yes (sets the totaliser
and exits the function)
Select:
No (exit the function without stopping the totaliser) / Yes (stop the totaliser
and exit the function)
Select:
No (exits the function without starting the totaliser) / Yes (starts the totaliser
and exits the function)
circuit board
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
81
6 OPERATION
No.FunctionSettings / descriptions
C5 I/O HART
C5I/O HART
C5.1PV isCurrent output (primary variable)
C5.2SV is(secondary variable)
C5.3TV is(tertiary variable)
C5.44V is(4th variable)
C5.5HART UnitsChanges units of DVs (dynamic variables) in the display
Selection or display of the 4 dynamic variables (DV) for HART
The HART® current output (terminal A basic I/Os or terminal C modular I/Os)
always has a fixed link to the primary variables (PV). Fixed links of the other
DVs (1-3) are only possible if additional analogue outputs (current and
frequency output) are available; if not, the measurement can be freely
selected from the following list: in Fct. A4.1 "Measurement"
_ stands for 1, 2, 3 or 4
X stands for connection terminals A...D
Break: return with ^ key
MFC 400
®
HART® display: copies the settings for the display units to the settings for
DVs
Standard: factory settings for DVs
C5._.1Current Output XShows the current analogue measured value of the linked current output.
C5._.1Frequency Output XShows the current analogue measured value of the linked frequency output,
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
No.FunctionSettings / descriptions
C6 Device
C6.1 Device Info
C6.1Device Info-
C6.1.1TagSettable characters (max. 8 digits):
C6.1.2V No. SensorV number of the measuring sensor, cannot be changed
C6.1.3Serial No. SensorSerial no. of the measuring sensor, cannot be changed
C6.1.4Sensor RevisionRevision of the measuring sensor, cannot be changed
C6.1.5V No. ConverterV number of the signal converter, cannot be changed
C6.1.6Converter Serial No.Serial no. of the signal converter, cannot be changed
C6.1.7C NumberCG number, cannot be changed; describes the signal converter version
C6.1.8Electronics Serial No.Serial no. of the electronic assembly, cannot be changed
C6.1.9Electronic RevisionShows ID no., electronic revision no. and production date;
A…Z; a…z; 0…9; / - + , .
Contains all hardware and software changes.
C6.2 Display
C6.2Display-
C6.2.1LanguageLanguage selection depends on the device version.
C6.2.2ContrastAdjust display contrast for extreme temperatures.
C6.2.3Default DisplaySpecification of the default display page that is returned to after a short
C6.2.4Optical KeysActivate or deactivate the optical keys
Setting: -9…0…+9
This change takes place immediately, not just when setting mode is exited!
delay period.
Select:
None (the current page is always active) / 1st Meas. Page (show this page) /
2nd Meas. Page (show this page) / Status Page (show only status
messages) / Graphic Page (trend display of the 1st measurement)
Select: On / Off
C6.3 & C6.4 1st Meas. Page & 2nd Meas. Page
C6.31st Meas. Page_ stands for 3 = 1st Meas. Page and 4 = 2nd Meas. Page
C6.42nd Meas. Page
C6._.1FunctionSpecify number of measured value lines (font size)
Select:
One Line / Two Lines / Three Lines
C6._.21st Line VariableSpecify measurement for 1st line
Select:
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
C6._.3Range0…100% of the measurement set in Fct. C5._.2
x.xx…xx.xx _ _ _ (format and unit depend on the "measurement")
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
83
6 OPERATION
No.FunctionSettings / descriptions
C6._.4LimitationLimitation before applying the time constant
±xxx ... ±xxx%; range: -150…+150%
C6._.5Low Flow CutoffSets low flow values to "0"
x.xxx ± x.xxx %; Range: 0.0…20 %
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
C6._.6Time ConstantRange: 0.1…100 s
C6._.71st Line FormatSpecify decimal places
Select:
Automatic (adaptation is carried out automatically) /
X°(=°none)°…X.XXXXXXXX°(max.°8°digits) depends on size of font
C6._.82nd Line VariableSpecify 2nd Line Variable (only available if this 2nd line is activated)
Select:
Bargraph (for the "measurement" selected in the 1st line) / Volume Flow /
Mass Flow / Temperature / Density / Velocity / Sensor Average / Sensor
Deviation / Drive Level / Tube Frequency / Strain 1 / Strain 2 / 2 Phase
Signal / Totaliser 1 / Totaliser 2 / Totaliser 3 / Operating Hours
MFC 400
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
C6._.92nd Line FormatSpecify decimal places
Select:
Automatic (adaptation is carried out automatically) /
X°(=°none)°…X.XXXXXXXX°(max.°8°digits) depends on size of font
C6._.103rd Line VariableSpecify 3rd Line Variable (only available if this 3rd line is activated)
Select:
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal / Totaliser 1 / Totaliser 2 / Totaliser 3 / Operating
Hours
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
C6._.113rd Line FormatSpecify decimal places
Select:
Automatic (adaptation is carried out automatically) /
X°(=°none)°…X.XXXXXXXX°(max.°8°digits) depends on size of font
C6.5 Graphic Page
C6.5Graphic Page-
C6.5.1Select RangeGraphic page always shows trend curve of the measurement of the 1st
C6.5.2RangeSet the scaling for the Y axis. Only available if "Manual" is set in C6.5.1.
page / 1st line, see Fct. C6.3.2
Select:
Manual (set range in Fct. C6.5.2) /
Automatic (automatic depiction based on the measured values)
Reset only after parameter change or after switching off and on.
±xxx ±xxx%; range: -100…+100%
(1st value = lower limit / 2nd value = upper limit),
condition: 1st value ≤ 2nd value
84
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
No.FunctionSettings / descriptions
C6.5.3Time ScaleSet the time scaling for the X axis, trend curve
xxx min; range: 0…100 min
C6.6 Special Functions
C6.6Special Functions-
C6.6.1Reset ErrorsReset Errors?
Select: No / Yes
C6.6.2Save SettingsSave current settings
C6.6.3Load SettingsLoad saved settings
C6.6.4Password Quick SetPassword required to change data in the menu "Quick Setup"
C6.6.5Password SetupPassword required to change data in the menu "Setup"
C6.6.6Date and TimeSet real time clock
C6.6.7Quick AccessSet "Quick Access" function;
C6.6.8GDC IR InterfaceAfter this function has been activated an optical GDC adapter can be
Select:
Break (exit function without saving) / Backup 1 (save in storage location 1) /
Backup 2 (save in storage location 2)
Query: Continue To Copy? (cannot be undone)
Select:
No (exit function without saving) / Yes (copy current settings to storage
backup 1 or backup 2)
Select:
Break (exit function without loading) / Factory Settings (restore factory
settings) / Backup 1 (load data from storage location 1) / Backup 2 (load data
from storage location 2)
Query: Continue To Copy? (cannot be undone)
Select:
No (exit the function without saving) / Yes (load data from the selected
storage location)
0000 (= to menu "Quick Setup" without password)
xxxx (password required); range 4 digits: 0001…9999
0000 (= to menu "Quick Setup" without password)
xxxx (password required); range 4 digits: 0001…9999
Select:
Off (deactivated) / Reset Totaliser 1, 2, 3 or All Totalisers
connected to the LC display. After 60 seconds pass without a connection
being established or after the adapter is removed, the function is exited and
the optical keys are active again.
Select:
Break (exit function without connection) /
Activate (the IR interface adapter and interrupt the optical keys)
After 60 seconds pass without a connection being established, the function is
exited and the optical keys are active again.
C6.7.11Text Free UnitFor text to be specified refer to
C6.7.12[m³]*FactorSpecification of the conversion factor, based on m³:
C6.7.13Masskg; t; mg; g; lb; ST; LT; oz;
C6.7.14Text Free UnitFor text to be specified refer to
C6.7.15[kg]*FactorSpecification of the conversion factor, based on kg:
C6.7.16Densitykg/L; kg/m³; lb/cf; lb/gal; SG
C6.7.17Text Free UnitFor text to be specified refer to
C6.7.18[kg/m³]*FactorSpecification of the conversion factor, based on kg/m³:
C6.7.19PressurePa; kPa; bar; mbar; psi (no free units possible);
lb/s; lb/min; lb/h; ST/min; ST/h (ST = Short Ton); LT/h (LT = Long Ton);
Free Unit (set factor and text in the next two functions, sequence see below)
Set free units
xxx.xxx refer to
Free Unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 87
Set free units
xxx.xxx refer to
Free Unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 87
Set free units
xxx.xxx refer to
Free Unit (set factor and text in the next two functions, sequence see below)
Set free units
on page 87
Set free units
xxx.xxx refer to
only if current input available
Set free units
on page 87
on page 87:
on page 87:
on page 87:
on page 87:
86
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
C6.8 HART
C6.8HART
C6.8.1HART
C6.8.2Address
C6.8.3MessageSet required text:
C6.8.4DescriptionSet required text:
C6.8.5HART Long tagSet the HART Long tags
Switch HART® communication on/off:
Select:
On (HART
Off (HART
0…20 mA
Set address for HART® operation:
Select:
00 (Point-to-Point operation,;current output has normal function;
current = 4…20 mA) / 01...15 (Multi-Drop operation; current output has a
constant setting of 4 mA)
A…Z ; a…z ; 0…9 ; / - + , . *
A…Z ; a…z ; 0…9 ; / - + , . *
®
activated) possible current range for current output 4…20 mA /
®
not activated) possible current range for current output
OPERATION 6
C6.9 Quick Setup
C6.9Quick SetupActivate quick access in the menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.1Reset Totaliser 1Reset Totaliser 1 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.2Reset Totaliser 2Reset Totaliser 2 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.3Reset Totaliser 3Reset Totaliser 3 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.4Reset All TotalisersReset all Totaliser in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
6.4.4 Set free units
Free unitsSequences to set texts and factors
Texts
Texts
TextsTexts
Volume flow, mass flow and density:3 digits before and after the slash
6.5.2 Deleting error messages in the menu "Quick Setup"
INFORMATION!
The detailed list of the possible error messages.
KeyDisplayDescription and setting
>Quick SetupPress and hold for 2.5 s, then release the key.
>Language2 x ↓Reset-
>Reset Errors-
>Reset?
No
↓ or ↑Reset?
Yes
^Reset ErrorsError has been reset.
3 x ^Measuring mode-
-
-
88
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.5.3 Operation Mode (menu A9)
The device can be switched to "Standby". In this mode, all flow values are set to zero and the
counter values are "frozen". The temperature and density values are displayed normally and
output via the outputs. The "Standby" indicator on the display shows either the "frozen" counter
value or simply "Standby". In this mode, the measuring tubes continue to vibrate and the device
can immediately return to "Measuring" mode if necessary.
There is also a "Stop" mode. In this mode, the measuring sensor is switched off and is no longer
vibrating. To return to measuring mode from this mode, the measuring device must
the complete "start-up" phase again before measurement continues.
The measuring device can be switched into "Standby" mode either using the operating keys on
the display or using the control input. You can only switch to "Stop" mode using the operating
keys.
Setting the operation mode (from measuring mode):
KeyDisplayDescription and setting
OPERATION 6
must go through
mustmust
>AQuick SetupPress and hold for 2.5 s, then release
> ↑A9Operation Mode
Measuring
>Operation Mode
Measuring
↑Operation Mode
Standby
↑Operation Mode
Stop
3 x ^Save Configuration?
Yes
^Display page
the key.
If "Standby" or "Stop" is selected, the device immediately switches to this operating state. To
return to the measuring mode, go to menu A9 and select "Measuring".
INFORMATION!
When changing from the "Stop" to "Standby" mode, the device goes through the entire start-up
phase.
In addition to the "Standby" mode, the system control function also allows you to switch to a
comparable "Standby" status completely automatically depending on the current operating
temperature or density.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
89
6 OPERATION
6.5.4 Density calibration (menu C1.2.1)
Mass flowmeters are calibrated for density in the factory. Density calibration is based on 2
calibration points. In the factory, air and water are used under reference conditions. The result
of this calibration is saved in the converter electronics and stored in the factory settings.
Regardless, various applications require maximum accuracy which can only be achieved with
on-site calibration.
Available options:
OptionExplanation
MFC 400
1 Point CalibrationOne of the 2 saved calibration points is replaced by customer calibration.
2nd Calibration PointCalibration of the 2nd point.
Factory Calib.The signal converter reactivates the factory settings for the density
The signal converter decides which of the 2 calibration points is modified.
calibration.
Example of 1 point calibration with town water
KeyDisplayDescription and setting
>AQuick SetupPress and hold for 2.5 s, then release
2 x ↓C1Setup↓C1.2Density
2 x >C1.2.1Density Calibration?
^C1.2.1Density Calib. Product
Press ↓
until
^C1.2.1Density Calibration?
^Please Wait
5 x ^Save Configuration?
^Display page
C1.2.1Density Calib. Product
1 Point Calibration
XXXXXXX
Town Water
OK
Countdown from 20 s
Density Calib.
Passed
Yes
the key.
90
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
On-site density calibration:
• Ensure that the device has been properly installed and functions smoothly.
• If air (empty) is used as the medium, the measuring tube must be completely dry and free of
liquids and solids. If possible, blow dry air into the measuring tube to empty it.
• If liquids are used, flush for a few minutes at a high flow rate to remove gas bubbles.
• Set the flow rate to a typical value (50% of the nominal flow is ideal).
• If the process temperature is higher than the ambient temperature, wait until the system has
stabilised.
• When it comes to 1 point and 2 point calibration, you can choose from the options "empty",
"pure water", "town water" and "other". The reference values for the specified products are
stored in the converter.
Density calibration has failed if "Density Calib. Error" is displayed. The reason for the error may
be indicated on the display. Possible reasons for failed density calibration:
• The device is not in "Measuring" mode.
• The calibration points are too close together.
• One or more calibration points did not pass the plausibility test.
• Flow, pressure, temperature or system are not stable?
• Please check your system and try again.
• If this results in another failed calibration, please contact the manufacturer.
1 Point Calibration
• See examples for "Calibration with town water and other".
• Select the function using ↓ and ↑ and then confirm with ^.
• If "Other" is selected, the product density must be entered.
• 1 point calibration is generally sufficient for most applications, such as adapting the density
measurement to a new installation.
• Make sure that prior to calibrating the 2nd point that 1 point calibration was carried out and
that the result was saved with the dialog "Save Configuration?".
2 Point Calibration
• In this case, both reference points are recalibrated (with the products of the system).
• With 2 point calibration, ensure that both calibration points entered by the user are accepted.
If the 2nd point cannot be calibrated immediately after the first one, because the 2nd product is
not yet available, the device continues to function normally as after the 1 point calibration. In
other words, there can be weeks or even months between the calibration of the two measuring
points.
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
91
6 OPERATION
6.5.5 Temperature/density tables
TemperatureDensityTemperatureDensity
MFC 400
°C°F
032999.839662.419990.532.9999.871262.42197
133.8999.898662.423671.534.7999.921362.42509
235.6999.939962.426252.536.5999.954262.42714
337.4999.964262.427773.538.3999.970162.42814
439.2999.97262.428254.540.1999.969962.42812
541999.963862.427745.541.9999.95462.42713
642.8999.940262.426276.543.7999.922762.42517
744.6999.901662.423867.545.5999.876662.4223
846.4999.848262.420538.547.3999.816262.4185
948.2999.780862.416329.549.1999.741962.41389
1050999.699762.4112510.550.9999.654162.40840
1151.8999.605162.4053511.552.7999.552962.40209
1253.6999.497562.3986312.554.5999.438962.39497
1355.4999.377262.3911213.556.3999.312462.38708
1457.2999.244662.3828414.558.1999.173662.37841
1559999.099862.373815.559.9999.022962.36901
1660.8998.943262.3640316.561.7998.860762.35887
1762.6998.775262.3535417.563.5998.68762.34803
1864.4998.59662.3423518.565.3998.502262.3365
1966.2998.405862.3304719.567.1998.306662.32428
2068998.204862.3179320.568.9998.100462.31141
2169.8997.993462.3047321.570.7997.883862.29788
2271.6997.771662.2908822.572.5997.656962.28372
2373.4997.539862.2764123.574.3997.420162.26894
2475.2997.298162.2613224.576.1997.173662.25355
2577997.046862.2456325.577.9996.917662.23757
2678.8996.786162.2293626.579.7996.652162.22099
2780.6996.515962.2124927.581.5996.377462.20384
2882.4996.236862.1950728.583.3996.093962.18614
2984.2995.948762.1770829.585.1995.801362.16788
3086995.651862.1585530.586.9995.500162.14907
3187.8995.346262.1394731.588.7995.190362.12973
3289.6995.032262.1198632.590.5994.872162.10987
kg/m
3
lb/ft
3
°C°F
kg/m
3
lb/ft
3
92
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
OPERATION 6
3391.4994.7162.0997533.592.3994.545862.08950
3493.2994.379662.0791234.594.1994.211362.06861
3595994.041162.0579935.595.9993.868962.04724
3698.6993.694862.0363736.597.7993.518762.02537
3798.6993.340662.0142637.599.5993.160662.00302
38100.4992.978961.9916838.5101.3992.795161.98020
39102.2992.609661.9686239.5103.1992.422161.95692
40104992.232961.945140.5104.9992.041861.93317
41105.8991.848961.9211341.5106.7991.654361.90898
42107.6991.457861.8967242.5108.5991.259761.88434
43109.4991.059761.8718643.5110.3990.858161.85927
44111.2990.654661.8465744.5112.1990.449461.83376
45113990.242761.8208545.5113.9990.034161.80783
46114.8989.823961.7947146.5115.7989.612161.78149
47116.6989.398661.7681647.5117.5989.183561.75473
48118.4988.966861.741248.5119.3988.748461.72756
49120.2988.528561.7138449.5121.1988.306961.70
50122988.083961.6860850.5122.9987.859261.67205
51123.8987.632961.6579351.5124.7987.405161.64371
52125.6987.175861.6293952.5126.5986.94561.61498
53127.4986.712761.6004853.5128.3986.478861.58588
54129.2986.243561.5711854.5130.1986.006661.5564
55131985.768461.5415355.5131.9985.528761.52656
56132.8985.287661.511556.5133.7985.045061.49636
57134.6984.800961.4811257.5135.5984.555561.4658
58136.4984.308661.4503958.5137.3984.060461.43489
59138.2983.810861.4193159.5139.1983.559761.40364
60140983.307261.3878760.5140.9983.053561.37203
61141.8982.798461.3561161.5142.7982.541961.34009
62143.6982.284161.32462.5144.5982.025061.30783
63145.4981.764661.2915763.5146.3981.502961.27523
64147.2981.239961.2588164.5148.1980.975661.24231
65149980.709961.2257365.5149.9980.443261.20907
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
93
6 OPERATION
66150.8980.175161.1923366.5151.7979.905761.17552
67152.6979.635161.1586267.5153.5979.363261.14165
68154.4979.090161.124668.5155.3978.815961.10748
69156.2978.540461.0902869.5157.1978.263661.07300
70158977.985861.0556670.5158.9977.706861.03823
71159.8977.426461.0207471.5160.7977.14561.00316
72161.6976.862460.9855272.5162.5976.578660.96781
73163.4976.293760.9500273.5164.3976.007660.93216
74165.2975.720460.9142374.5166.1975.432160.89623
75167975.142860.8781675.5167.9974.852260.86003
76168.8974.560660.8418276.5169.7974.267960.82355
77170.6973.974160.8052077.5171.5973.679260.7868
78172.4973.383260.7683278.5173.3973.086260.74977
79174.2972.788160.7311679.5175.1972.48960.71249
80176972.18860.69375
MFC 400
94
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.5.6 Density mode (menu C1.2.2)
There are 4 available operating modes for density that can be set here:
• Process:
The device measures and displays the current operating density of the product.
• Fixed:
The device displays a fixed density value. This value must be entered in menu C1.2.3.
• Referred:
The device calculates the density based on a set reference temperature.
• Standard:
The device calculates the standard density based on a set reference temperature and the
correction factors k
The following equation is used for the "Referred" mode:
The following equation is used for the "Referred" mode:
The following equation is used for the "Referred" mode:The following equation is used for the "Referred" mode:
ρ
= ρa + a (ta - tr)
r
ρ
= Density at reference temperature
r
= Current measured operating density at current operating temperature
ρ
a
a = Programmed temperature coefficient/density gradient
t
= Current measured operating temperature
a
= Reference temperature
t
r
...k2, so that a standard volume can be output.
0
OPERATION 6
The reference temperature must be entered in menu item C1.2.3. The density gradient is set in
C1.2.4.
Figure 6-7: Calculating the density gradient
1 Density
2 Temperature
The following equation is used to calculate the density gradient:
The following equation is used to calculate the density gradient:
The following equation is used to calculate the density gradient:The following equation is used to calculate the density gradient:
- ρC) / (TB - TA)
a = (ρ
D
The value for the density gradient is generally positive as an increase in temperature usually
reduces the measured density(exception: water anomaly).
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
95
6 OPERATION
Calculating the standard density
Calculating the standard density
Calculating the standard densityCalculating the standard density
The measuring device can display a density which has been corrected in terms of the standard
temperature in accordance with API 11.1. Standard 2540.
The corresponding reference temperature is entered in menu C1.2.5. The correction factors
...k2 are entered in menu C1.2.6...C1.2.8.
k
0
MFC 400
Standard factors for gasolines are: k
= 346.4228; k1 = 0.4388; k2 = 0
0
6.5.7 Pipe diameter (menu C1.1.3)
The converter can also provide the flow velocity based on a pipe diameter which the customer
can freely program. This value can either be the inner diameter of the measuring tube (factory
default) or the inner diameter of the process pipe.
6.5.8 Concentration measurement (menu C2)
This menu is used to enter the password to activate concentration measurement (in case the
concentration option is purchased) after the meter is delivered.
INFORMATION!
Please refer to the separate concentration manual for further details of concentration
measurement.
6.5.9 Flow direction (menu C1.3.1)
This function allows the operator to set the direction of flow in relation to the arrow on the
housing. If "Forwards" is selected, the flow direction corresponds to the "+" arrow and with
"Backwards" the flow direction corresponds to the "-" arrow on the housing.
96
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.5.10 Pressure suppression
The pressure suppression eliminates any disruption in the measurement in the event of an
abrupt flow switch-off e.g. when valves are suddenly closed. In such cases, surges may occur in
the pipe and in the measuring device which could lead to over-vibration. The flow then "swings"
back and forth before a stable zero flow is established, as shown in the figure below. This effect
occurs mainly in high pressure applications.
OPERATION 6
Figure 6-8: Vibration behaviour during pressure suppression
1 Flow switched off
2 Sinusoidal vibration ("over-vibration")
3 Stable zero flow
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
97
6 OPERATION
In most cases, the amplitude of this vibration is below the low flow cutoff and thus does not affect
the measurement. In very few cases, the amplitude is greater than the low flow cutoff (overvibration) and can cause errors with the counter values.
The pressure suppression function eliminates this effect by activating a larger low flow cutoff
level for a short period of time. The pressure suppression is activated when the flow falls below
the standard low flow cutoff level for the first time. For a programmable period of time, (can be
programmed in menu C1.3.2), the pressure suppression threshold is added to the standard low
flow threshold (can be set in menu C1.3.3).
The optimal setting values for pressure suppression depend on the current operating conditions
and can thus only be determined on-site through testing.
98
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
MFC 400
6.5.11 System control
Menu C1.4.1 - Function
This menu makes it possible to switch off certain measuring functions depending on a
programmable process state. When this system state occurs (as set in Fct. C1.4.2), the following
options can be activated:
• Inactive: system control is off
• Flow = 0: Flow set to zero
Menu C1.4.2 - Condition
Selecting the process measurement which activates the system control. Density and
temperature can be selected.
Menu C1.4.3 – Max Limit
Menu C1.4.4 – Min Limit
Setting the limit values to activate system control. Current measuring values outside of this
range activate this function.
OPERATION 6
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
99
6 OPERATION
6.5.12 2 Ph. Threshold (menu C1.5.3)
The threshold for the 2 phase signal can be set in this menu item. This makes it possible to
output a status signal indicating the presence of gas bubbles in the process. There are no default
values for this threshold. This means that the operator must adapt this value to suit his
application. This can be done, for example, by programming the 2 phase signal at the current
output and registering which threshold makes sense for the respective process for a certain
time period.
Example regarding the detection and notification of a two-phase disturbed flow (e.g.
gas bubbles in paints):
Fct.DisplayDescription and setting
MFC 400
B2.142 Phase SignalThe 2-phase signal value in % can be read
C1.5.32 Ph. ThresholdOnly input a value here if an error message
C1.5.4Diagnosis 1Set "2 Phase Signal".
C3.1.3Terminals CSet "Limit Switch".
C3.4.1MeasurementSet "Diagnosis 1".
C3.4.2Thresholde.g. set to "2.0 ± 0.2%".
C3.4.3Polaritye.g. set to "Absolute Value".
C3.4.4Time ConstantSet as needed.
C3.4.4Invert SignalSet as needed.
C6.4.12nd Meas. Page Set "Three Lines".
C6.4.103rd Line VariableSet "Diagnosis 1".
C6.4.113rd Line FormatSet "X.XX".
and transferred to Diagnosis 1.
is to be generated.
This error message can be displayed via the
status outputs.
The error message is then indicated on the
display as S: Out Of Specification
S: 2 Phase Flow
S: 2 Phase Flow indicated on the display.
S: 2 Phase FlowS: 2 Phase Flow
Caution: Take into account the setting of the
error conditions of the current output!
S: Out Of Specification and
S: Out Of SpecificationS: Out Of Specification
The 2 phase signal is displayed on the 2nd measuring page at the bottom with e.g.: 0.02%. If the
threshold is exceeded (C3.4.2), a message is sent via terminals C.
100
www.krohne.com08/2013 - 4002075802 - MA MFC 400 R02 en
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.