KROHNE IFS6000 User Manual

05/98
Electromagnetic
Installation instructions
flowmeters
• Primary heads
• Compact flowmeters
CONTENTS Installation in the pipeline Pages 4-5 and 7-8 Grounding Pages 8-9
IFS 6000 F
VARIFLUX IFS 6000 F
IFM 6010 K IFM 6020 K IFM 6080 K
IFM 1010 K IFM 1080 K
IFM 6010 K IFM 6080 K
3.1M54EA1 059821 Order No. DIN size 7.02143.31.00 US size 7.02143.71.00
0.73.00
Contents
System description 2 Product liability and warranty 2 Standards and approvals 2 Items included with supply 3
1 Important information for installation: PLEASE NOTE 4-5 2 Suggestions for installation 5 3 Instrument nameplate 6 4 Flowmeter versions 6 5 Installation in the pipeline and torques 7 6 Limits 8 7 Grounding 8-9 8 Service 10
9 Spares and order numbers 10 10 Technical data 11 11 Dimensions and weights 12-14
Printed form to accompany flowmeters returned to Krohne 15
System description
VARIFLUXelectromagnetic flowmeters are precision measuring instruments designed for the linear flow measurement of process liquids.
The process liquids must be electrically conductive: 05 µS/cm
20 µS/cm for demineralized cold water
The full-scale range Q DN 2.5 - 80 /
1
/10” - 3” Q
can be set as a function of the meter size:
100%
= 0.01 - 220 m3/hr = 0.03 - 960 US Gal/min
100%
This is equivalent to a flow velocity of 0.3 - 12 m/s, or 1 - 40 ft/s.
Product liability and warranty
VARIFLUX electromagnetic flowmeters are designed solely for measuring the volumetric flowrate of electrically conductive, liquid process products.
Special codes and regulations apply to their use in hazardous locations, and these are referred to in the special “Ex” installation and operating instructions (supplied only with hazardous-duty equipment).
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests solely with the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty. In addition, the “General conditions of sale” forming the basis of the purchase contract are
applicable. If VARIFLUX flowmeters need to be returned to Krohne, please note the information given on the
last-but-one page of this manual. Krohne regret that they cannot repair or check your flowmeter(s) unless accompanied by the completed form sheet.
Standards and approvals
Please refer to the installation and operating instructions for the signal converter.
2
Items included with supply
IFS 6000 F primary head
primary head
in the size as ordered
certificate of calibration data
installation instructions
Available meter sizes/types and connections
Aseptic weld-on connections
mm DN 02.5 DN 04 DN 06 DN 10 DN 15 DN 25 DN 40 DN 50 DN 65 DN 80
inch
1
/
10
1
/
8
1
/
4
3
/
8
1
/
2
1 1 1/ 2
1
2 3
for pipes to DIN 11 850
mm DN 10 DN 10 DN 10 DN 10 DN 15 DN 25 DN 40
2
DN 50
/
DN 65
2
DN 80
Aseptic weld-on connections
mm 12 12 12 12 18 25 38 51
63.5
76.1
for pipes to ISO 2037
inch – – – – – 1 1 1/ 2
1
2 3
Connection and pipe flanges
mm DN 10 DN 10 DN 10 DN 10 DN 15
*
– –
2
/
2
to DIN 2501 / PN 40
inch
1
/
1
/
1
/
1
/
1
/ – – – – –
IFM 6010 K, IFM 6020 K and IFM 6080 K compact flowmeters
compact flowmeter in the size as ordered
certificate of calibration data
installation instructions
installation and operating instructions for the signal converter
* not to ISO 2037
Dairy screw connections and
Connection and pipe flanges
to ANSI B 16.5 / 150, 300 lb
Connection and pipe flanges
mm DN 10
2
DN 10
2
DN 10
2
DN 10
2
DN 15
2
– – – – –
hose nozzles (option) to DIN 11851
to JIS 2210 / 20 K
mm DN 10 DN 10 DN 10 DN 10 DN 15 DN 25 DN 40 DN 50 DN 65 DN 80
Screwed pipe connections
to ISO 2853
inch – – – – – –
1
1 2
1
2 3
mm – – – – – 25
/
38
2
51
/
63.5
2
76
mm 12 12 12 12 18 25 38 51
63.5
76.1
Screwed pipe connections
to SMS 1145
mm 12 12 12 12 18 25 38 51
63.5
76.1
Clamp joints
to ISO 2852
inch – – – – – –
1
/
1
2
2
1
2
/
2
3
Items included with supply (Arrangement of gaskets and grounding rings see Sect. 7). Flanged units: with mounted grounding rings E and fitted gaskets D1.
Gaskets D2 not included, to be provided by customer.
Other connections: mounted adapter with fitted O-ring gaskets D1 and union nuts
(counterparts for the pipeline, such as tapered connectors, union nuts, hinged clamps and gaskets D2 not included, to be provided by customer).
Inside diameter of measuring tube and pipeline Size
Type
mm DN 02.5 DN 04 DN 06 DN 10 DN 15 DN 25 DN 40 DN 50 DN 65 DN 80
inch
1
/10
1
/8
1
/4
3
/8
1
/2 1 11/2 2 21/2 3
Inside diameter of measuring tube in mm (inch)
for connections to ... DIN
02.5 04 06
10 13 26 38 50 66 81
di
ISO, SMS, ect.
02.5 04 06
10 13 23 36 49 60 73
Pipe standard to
DIN 11850
Meter size
DN 25 DN 40 DN 50 DN 65 DN 80
26 38 50 66 81
di mm
Pipe standard to
ISO, SMS, RJT, JIS OD-Tube
Meter size
DN 25/1 DN 40/11/2 DN 50/2 DN 65/21/2 DN 80/3
23 36 49 60 73
di mm
3
1 Important information for installation: PLEASE NOTE
Handling
Do not lift flowmeter by the signal converter housing or
Do not set flowmeter down on signal converter housing or terminal box.
the terminal box.
Use only solventless detergents to clean the signal converter housing (polycarbonate).
Temperatures
For operating pressure and vacuum load based on connection standards, see Section 6 “Limits“.
Ambient temperature Product temperature
Compact systems -25 to +60 °C (-13 to +140 °F) -20 to +060 °C (-4 to +140 °F)
-25 to +40 °C (-13 to +104 °F) -20 to +140 °C (-4 to +284 °F)
- EEx version -25 to +40 °C (-13 to +104 °F) -20 to +140 °C (-4 to +284 °F)
IFS 6000 F -25 to +60 °C (-13 to +140 °F) -20 to +060 °C (-4 to +140 °F)
- flange connections -25 to +40 °C (-13 to +104 °F) -20 to +180 °C (-4 to +356 °F)
- other connections -25 to +40 °C (-13 to +104 °F) -20 to +140 °C (-4 to +284 °F)
- EEx version -25 to +40 °C (-13 to +104 °F) -20 to +140 °C (-4 to +284 °F)
Location and position as required,
but electrode axis X – • – • – • – X
Y
must be approximately horizontal in a horizontal pipe run.
Y terminal box or converter housing
X
X
Measuring tube must be completetly filled at all times.
Direction of flow is arbitrary. Arrow on flowmeter can normally be ignored.
For exceptions, refer to Section ”Factory settings” in the installation and operating instructions for the signal converter.
Stud bolts and nuts: to fit, make sure there is sufficient room next to the pipe flanges.
Vibration: support the pipeline on both sides of the compact flowmeter.
Level of vibration in conformity with IEC 068-2-34: 20-500 Hz, random / 2g runs / 30 minutes / x, y, z directions.
Do not expose to direct sunlight,
fit a sunshade if necessary, not included with flowmeter, to be provided by customer.
4
Strong electromagnetic fields, avoid in vicinity of flowmeter.
Straight inlet run minimum of 5 ××DN and outlet run minimum of 2 ××DN,
(DN = meter size), measured from the electrode axis.
Vortex and corkscrew flow: increase length of inlet and outlet runs or install flow conditioners.
Mixing different process liquids: install flowmeter upstream of mixing point or at an adequate distance downstream (minimum of 30 x DN), otherwise display may be unsteady.
Plastic pipes and internally coated metal pipelines: grounding rings required, see Section 7 ”Grounding”.
Insulated pipeline: do not insulate flowmeter.
Zero setting not necessary. To check, it should be possible to set ”zero” flow velocity
in the completely filled measuring tube. Shutoff valves should therefore be provided either downsteam of the flowmeter or upsteam and downstream of the flowmeter.
2 Suggestions for installation
To avoid measuring errors due to gas/air inclusion or to pipe runing empty please observe the following:
Highest point of pipe run
(Air bubbles collect in measuring tube - faulty measurements!)
Preferred locations
Downpipe
”Zero” flow velocity. Line drained. Faulty measurements!
Horizontal pipe run
Install in slightly ascending pipe section. If not possible, assure adequate velocity to prevent air, gas or vapor from collecting in upper part of flow tube.
Open feed or discharge
Install meter in low section of pipe.
Downpipe over 5 m (16 ft) length
Install air valve X downstream of flowmeter.
Long pipeline Always install control and shutoff valves
downstream of flowmeter.
Pumps Never install flowmeter on pump suction side.
> 5m
> 16 ft
open discharge
5