KROHNE IFM6080KEEx User Manual


$GGLWLRQWRWKH,QVWDOODWLRQDQG2SHUDWLQJ,QVWUXFWLRQV
Magnetic inductive flowmeters
ALTOFLUX
IFM 6080 K / i-EEx
with
7.30828.31
1 Contents
In this addition only the points which differ from the standard Installation and Operating Instructions are described. This addition is only valid for compact flowmeters with the IFC090 i-EEx signal converter with intrinsically safe signal in- and outputs.
1 CONTENTS........................................................................................................................2
2 DESCRIPTION OF THE SYSTEM.....................................................................................3
3 INSTALLATION IN THE PIPELINE....................................................................................3
4 ELECTRICAL CONNECTION............................................................................................3
5 CONNECTION DIAGRAMS OF THE SIGNAL IN/OUTPUTS ............................................6
6 OPERATION OF THE SIGNAL CONVERTER...................................................................6
7 SERVICE............................................................................................................................7
7.1 REPLACEMENT OF THE POWER SUPPLY FUSE................................................7
7.2 REPLACEMENT OF THE ELECTRONIC UNIT.......................................................8
8 PART NUMBERS...............................................................................................................8
9 TECHNICAL DATA.............................................................................................................9
10 MAINTENANCE .................................................................................................................9
11 CERTIFICATE OF CONFORMITY...................................................................................10
2
2 Description of the system
The explosion protected compact-flowmeters differ from the standard flowmeters mainly in their "internal assembly". Several types of protection are used in the compact flowmeter IFM 6080 K / i-EEx, depending on the ordered type of the connection compartment of the signal converter housing. See following overview:
Electronic compartment signal converter housing EEx d (Flameproof enclosure)
Connection compartment signal converter housing
- Housing and connection terminals for power supply:
standard: EEx e (Increased safety) optional: EEx d (Flameproof enclosure)
- Connection terminals of signal in/outputs (Current, Pulse/status/control and Fieldbus)
always EEx ia (Intrinsic safety, category ia)
Primary heads DN2.5 - DN15: EEx m (Encapsulation) and EEx e (Increased safety)
DN25 - DN80: EEx d (Flameproof enclosure) Internal electrode circuit
EEx ib (Intrinsic safety, category ib)
3 Installation in the pipeline
The installation of the compact flowmeter in the pipeline is equal to that of the standard compact flowmeters.
4 Electrical connection
For the electrical connection of the compact flowmeter the relevant national standard codes of practice for "Electrical installations of buildings" and "Electrical apparatus for use in potentially explosive atmospheres" have to be consulted.
In the connection compartment of the IFM 6080 K/ i-EEx the terminals for the intrinsically safe signal in/outputs and the non-intrinsically safe power supply circuits are placed. The location of the connection terminals is shown in the sketch on the next page.
The cable for the signal in/outputs leading into the IFM 6080 K / i-EEx is intrinsically safe. The connection of this cable must be carried out conform the requirements specified in the relevant national standard code of practice for the installation of electrically apparatus with type of protection "i".
3
g
Connection of signal-in/outputs (intrinsically safe)
Connection power supply (non-intrinsically safe)
With each in/output module a certain in/output function can be realised, see following overview: In/Output
Function Electrical data module P-SA passive current output Current: 4..20 mA
Working voltage: 8.. 30 V DC Voltage drop: 8 V at 4 mA
FA-ST passive pulse/status output or
control input (selectable through
software options)
Working voltage: 6..30 V DC Working current: < 110 mA Voltage drop in ON-state: < 2 V at 110 mA Leakage current in OFF-state: < 900 µA at 30 V Control input Input voltage LOW level: < 3 V Input voltage HIGH level: > 7 V Frequency range: 0.. 12 KHz
DC-I intrinsically safe voltage source,
to be used in combination with
modules P-SA and FA-ST
Voltage: 20 V DC Maximum current: 30 mA Internal resistance: 260
F-PA passive Fieldbus interface conform FISCO model The functionality of the terminals for signal in/outputs is depending on the version of the
IFC090 i-EEx electronic-unit installed. Each version is equipped with a different pair of in/output modules. Following versions are possible:
IFC090 i-EEx version Order no. MODIS module Terminal desi Ex-i1 2.11582.01 P-SA FA-ST Ex-i2 2.11582.03 P-SA F-PA
I I
IB1 ID
nation
B1
D Ex-i3 2.11582.02 P-SA DC-I I+ I Ex-i4 2.11582.04 FA-ST F-PA B1
B1
D
D Ex-i5 2.11582.05 FA-ST DC-I B1+ B1 Ex-i6 2.11582.06 FA-ST FA-ST B2
B2
B1
B1
The non-intrinsically safe terminals for the power supply 1L and 0L have to be wired conform the relevant standard code of practice for electrical apparatus for use in potentially explosive