The flow sensor must be installed in the pipeline as described in the instructions for
installation inside the packing of the flow sensor.
– Connection of power supply (Sect. 1.1-1.2)Pages 6- 7
– Electrical connection between IFC 110 F and primary head (Sect. 1.3)Pages 8-15
– Electrical connection of outputs and inputs (Sect. 2)Pages 16-24
–Factory settings (Sect. 2.7) and start-up (Sect. 3)Pages 25-27
Power the flowmeter. THAT’S ALL. The system is operative.
Operator control of the IFC 110 F signal converter is described in Sect. 4 and 5.
● Display & control unit
No. 3.19937.02.00
● A/D converter
No. 8.13393.02.00
● Outputs/inputs (I/O)
No. 3.16230.01.00
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications technology
Engineering systems & solutions
Switches, counters, displays and recorders
Heat metering
Pressure and temperature
Contents
1 Electrical connection: power supply ....................................................................................................6
1.1 Location and important installation notes ……………………. PLEASE NOTE ! ......................................6
1.2 Power supply - connection .......................................................................................................................7
1.3 Electrical connection of flow sensors .......................................................................................................8
1.3.1 General remarks on signal lines A and B and field current line C ............................................................8
1.3.2 Stripping (preparation) of signal cables....................................................................................................9
1.3.3 Grounding of flow sensor .......................................................................................................................10
1.3.4 Cable lengths (max. distance between signal converter and flow sensor).............................................11
1.3.5 Connection diagrams for power supply and flow sensors ......................................................................12
1.3.6 EEx-Connection diagrams for power supply and flow sensors ..............................................................14
2 Electrical connection: outputs and inputs.........................................................................................16
2.1 Important information for outputs and inputs …….…………. PLEASE NOTE ! .....................................16
2.2 Current output I.......................................................................................................................................17
2.3 Pulse outputs P and A1..........................................................................................................................18
2.3.1 Pulse output P for electronic totalizers (EC)...........................................................................................18
2.3.2 Pulse output A1 for electromechanical totalizers (EMC) ........................................................................19
2.4 Status outputs A1 / A2 / D1 / D2.............................................................................................................20
2.5 Control inputs C1 and C2 .......................................................................................................................20
2.6 Connection diagrams of outputs and inputs ...........................................................................................21
2.7 Standard factory settings........................................................................................................................25
4.4 Table of settable functions .....................................................................................................................32
4.5 Error messages in measuring mode ......................................................................................................38
4.6 Resetting the totalizer and deleting error messages, RESET/QUIT menu ............................................39
4.7 Examples of signal converter settings....................................................................................................39
5 Description of functions ......................................................................................................................40
5.1 Full-scale range Q
5.2 Time constant.........................................................................................................................................40
5.6 Internal power supply (E+/E-) for connected loads ................................................................................43
5.7 Current output I.......................................................................................................................................43
5.8 Pulse outputs P and A1..........................................................................................................................44
5.9 Status outputs A1 / A2 and D1 / D2 .......................................................................................................46
5.10 Control inputs C1 and C2 .......................................................................................................................47
5.14 User-defined units ..................................................................................................................................50
5.20 Range change ........................................................................................................................................54
6.1.2 Main safety features .............................................................................................................................. 55
6.1.3 Installation and electrical connection..................................................................................................... 56
6.2 Magnetic sensors MP (optional) ............................................................................................................ 57
6.3 Changing the load capacity of the output A1 for polarized DC operation.............................................. 58
9 Order numbers..................................................................................................................................... 87
10.1 Signal converter..................................................................................................................................... 88
13.1 EC-type examination certificate English translation ............................................................................. 94
13.2 EC-type examination certificate German original ................................................................................. 97
14 Index ................................................................................................................................................... 100
If you need to return flowmeters for testing or repair to KROHNE ........................................................... 103
IFC 110 F3
05/2003
A
The operating data are factory-set to your ordered specifications.
Signal converter versions
IFC 110 F / D Standard version, with local display and control elements
(Standard)
IFC 110 F / D / MP Same as display version, additional with magnetic sensors (MP)
(Option)
IFC 110 F / D / MP / EEx Same as display version (D + MP),
(Option) for operation with flow sensors installed in hazardous areas
IFC 110 F / RS 485 Same as standard version,
but additionally with different interfaces
• Signal converter in the version as ordered, see above.
Items included with supply
• Signal cable in the version and length as ordered (standard: signal cable A,
length 10 m / 30 ft)
• Condensed installation and operating manual in the ordered language for installation,
electrical connection, start-up and operator control of the signal converter.
• Service Manual in english language.
Please note!
In the Installation and Operating Manual there are hints with Sect. Numbers which you can find
in the Handbook / Service Manual only!
Instrument nameplates
Signal converter (example)
IFC 110 F
Signal converter IFC 110F-EEx (example)
Flow sensor (example)
LTOFLUX 4000 F
4 IFC 110 F
05/2003
System description
Electromagnetic flowmeters are precision instruments designed for linear flow measurement of
liquid products
The process liquids must be electrically conductive:, ≥ 5 µS/cm
(for cold demineralized water ≥ 20 µS/cm).
The full-scale range Q
can be set as a function of the meter size: flow velocity of 0.3 - 12 m/s
100%
or 1 - 40 ft/s (s. Section 10.4.).
Product liability and warranty
The electromagnetic flowmeters are designed solely for measuring the volumetric flowrate of
electrically conductive, liquid process products.
These flowmeters are available for use in hazardous areas.
Special regulations apply in this case, which are given in the special EEx directions.
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests
solelywith the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty.
In addition, the “General conditions of sale” forming the basis of the purchase contract are
applicable.
If flowmeters need to be returned to KROHNE, please note the information given on the last-butone page of these Instructions. KROHNE regrets that it cannot repair or check your flowmeter(s)
unless accompanied by the completed form sheet.
CE / EMC / Standards / Approvals
The here described Electromagnetic flowmeters meet the NAMUR Directive NE21,
the protection requirements of Directive 89/336/EEC in conjunction with EN61326-1 (1997) and A1 (1998), as well as Directives 73/23/EEC and 93/68/EEC
in conjunction with EN 61010-1, and bear the CE marking.
Software history
Display & control unit Amplifier (ADC) Inputs and outputs (I/O)
Software Status Software Status Software Status
3.19937.02.00
current
IMPORTANT!
In respect of EEx versions, pay regard to all directions marked with the symbol,
and also the information given in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
8.13393.02.00
current
3.16230.01.00
current
IFC 110 F5
05/2003
Sect. 1.1 Part A System installation and start-up
1 Electrical connection: power supply
1.1 Location and important installation notes ……………………. PLEASE NOTE !
• Electrical connection in accordance with VDE 0100 ”Regulations for the erection of power
installations with nominal voltages up to 1000 V” or equivalent national regulations.
• Do not cross or loop cables inside the terminal compartment.
• Use separate wiring (PG screwed cable entries) for power supply, field current lines, signal
lines, outputs and inputs.
• Hazardous areas are subject to special regulations, see Section 6.1 and special installation
instructions for hazardous-duty versions.
• Do not expose signal converter and switchgear cabinets with built-in converters to direct
sunlight. Install a sunshade if necessary.
• Signal converters installed in switchgear cabinets require adequate cooling (e.g. by fans
or heat exchangers).
• Do not expose signal converters to intense vibration.
• Keep the distance between the flow sensor and signal converter as small as possible, for
empty pipe detection (EPD) ≤ 20 m / ≤ 66 ft. Observe maximum lengths of signal and field
current lines (see Section 1.3.4).
• Use KROHNE signal line A (type DS, standard) or signal line B (type BTS, bootstrap,
optional), standard length 10 m (33 ft).
• Generally use bootstrap signal lines B (type BTS) for PROFIFLUX 5000 F and VARIFLUX
6000 F flow sensors sized at DN 2.5-15 and 1/10’’-1/2’’ and for contaminated liquids which
tend to form electrically insulating deposits.
• Always calibrate flow sensor and signal converter together. During installation particular care
should therefore be given to identical settings of flow sensor constant GK (see instrument
nameplate of flow sensor). In case GK constants are not identical, the signal converter must
be adjusted to the flow sensor GK (see Sections 4 and 8.5).
• Dimensions of signal converter see Section 10.3.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
6 IFC 110 F
05/2003
Part A System installation and start-up Sect. 1.2
1.2 Power supply - connection
PLEASE NOTE !
• Type of enclosure
• Dimensioning:
moisture must always be kept closed. The selected clearances and creeping distances comply
with VDE 0110 and/or IEC 664 regulations for contamination grade 2. Supply circuits and
output circuits are designed to meet standards of overvoltage classes III and II, respectively.
• Fuse protection, disconnecting device: fuse protection for the feeding power circuit, and also a
disconnecting device (switch, circuit breaker) for isolating the signal converters must be
provided (see also Sect. 1.3.5 and 1.3.6).
100-230 V AC (tolerance range 85-255 V AC)
• Observe information on the instrument nameplate, power supply voltage and frequency.
• The protective conductor PE of the power supply must be connected to the separate
U-clamp terminal inside the terminal compartment of the signal converter.
• CAUTION: do not remove the internal connection (line) inside the terminal compartment of the
signal converter (yellow/green wire) between the U-clamp terminal and terminal 10 protective conductor (protection class I instrument).
• Connection diagrams I - IV for the power supply and for the electrical connection between
flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
24 V AC / DC (tolerance ranges: AC 20.4 - 26.4 V / DC 18 - 31.2 V)
• Observe information on the instrument nameplate, power supply voltage and frequency.
• For technical reasons concerning the measuring process, a functional grounding conductor
FE has to be connected to the separate U-clamp terminal inside the terminal compartment of
the signal converter.
• A facility providing a reliable electrical separation (PELV) has to be provided for connections
to functional extra-low voltages (24 V AC / DC) - (VDE 0100 / VDE 0106 and/or IEC 364 /
IEC 536 or equivalent national regulations).
• Connection diagrams I - IV for the power supply and for the electrical connection between
flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
IP 65 to IEC 529 / EN 60529 equivalent to NEMA 4/4X.
the flowmeter housing protecting the electronic equipment against dust and
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
IFC 110 F7
05/2003
Sect. 1.3.1 Part A System installation and start-up
1.3 Electrical connection of flow sensors
1.3.1 General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when KROHNE signal lines A and B are used with
foil screen and magnetic shield.
• Signal lines must be firmly installed.
• Shields are connected via stranded drain wires.
• Underwater or underground routing is possible.
• Insulating material flame-retardant to IEC 332.1 / VDE 0742.
• Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Signal line B (type BTS) with triple shielding (bootstrap line)
8 Outer sheath
The bootstrap technology always controls the individual shields (3) of the signal converter exactly
to the voltage which is supplied to the signal conductors (5). As this prevents voltage differences
between the individual shields (3) and signal conductors (5), no current flows via the line
capacitances between 3 and 5. The line capacitance seems to become ”zero”.
This allows greater cable lengths in case the electric conductivity of the liquid to be measured is
low.
1
Dummy glider wire
2
Insulation (2.1 red/2.2 white)
3
Special foil, 1st shield (3.1/3.2)
4
Insulation (4.1/4.2)
5
Stranded wire 0.5 mm² or AWG 20
(5.1 red/5.2 white)
Stranded drain wire, 2nd shield, 1.5 mm² or AWG 14
9
Insulation
10
Mu-metal foil, 3rd shield
11
Stranded drain wire, 3rd shield, 0.5 mm² or AWG 20
12
Outer sheath
Field current line C1
Line 2 x 0.75 mm² (18 AWG) Cu or 2 x (4 x) 1.5 mm² (14 AWG) Cu (Cu = copper cross section)
The cross section depends on the required cable length.
For max. permissible cable lengths please refer to Section 1.3.4
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
8 IFC 110 F
05/2003
Part A System installation and start-up Sect. 1.3.2
1.3.2 Stripping (preparation) of signal cables
Please note: The numbers in the drawings designate the stranded drain wires of signalling cables
A and B, see sectional drawings in Sect. 1.3.1.
Flow sensor Converter
Length flow sensor Length Converter
mm inch mm inch
a 90 3.60 a 50 2.00
b 8 0.30 b 8 0.40
c 25 1.00 d 8 0.40
d 8 0.30 e 20 0.80
e 70 2.80
Signal cable A (type DS),
double shielding
for flow sensor
Signal cable A (type DS),
double shielding
for IFC 110 F Converter
Signal cable A
bending radius
≥ 50 mm (≥ 2”)
Signal cable B (type BTS),
with triple shielding (bootstrap)
for flow sensor
Signal cable B
bending radius
≥ 50 mm (≥ 2”)
Customer-supplied materials
W
Insulation tubing (PVC), Ø 2.0-2.5 mm (Ø 1”)
X
Heat-shrinkable tubing or cable sleeve
Y
Wire end sleeve to DIN 41 228: E 1.5-8
Z
Wire end sleeve to DIN 41 228: E 0.5-8
Signal cable A
bending radius
≥ 50 mm (≥ 2”)
Signal cable B (type BTS),
with triple shielding (bootstrap)
for IFC 110 F Converter
Signal cable B
bending radius
≥ 50 mm (≥ 2”)
IFC 110 F9
05/2003
Sect. 1.3.3 Part A System installation and start-up
1.3.3 Grounding of flow sensor
• The flow sensor must be correctly connected to ground.
• The grounding cable may not transfer interference voltages.
• Do not use the grounding cable to connect more than one device to ground.
• In hazardous areas the grounding line is also used for potential equalizing purposes. Special
grounding instructions are contained in the installation instructions for hazardous-duty
instruments (only supplied together with such instruments).
• The flow sensor is connected to ground by means of a functional grounding conductor FE.
• Special grounding instructions for the connection of several flow sensors are contained in the
separate installation instructions of the flow sensors.
• These instructions also contain detailed descriptions on how to use grounding rings and how
to install flow sensors in metal or plastic pipes or in pipes which are coated on the inside.
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
10 IFC 110 F
05/2003
Part A System installation and start-up Sect. 1.3.4
1.3.4 Cable lengths (max. distance between signal converter and flow sensor)
Abbreviations and explanations
The abbreviations used in the following tables, diagrams and connection diagrams stand for:
A Signal line A (type DS) with double shielding, max. length see diagram
B Signal line B (type BTS) with triple shielding, max. length see diagram
C Field current line, minimum cross section (A
) and max. length see table
F
D High-temperature silicone line, 3x1.5 mm² (14 AWG) Cu, with single shield,
max. length 5 m (16 ft)
E High-temperature silicone line, 2 x 1.5 mm² (14 AWG) Cu, max. length 5 m (16 ft)
Cross section of field current line C in Cu, see table
A
F
L Cable length in m or ft
Electrical conductivity of the process liquid
Κ
ZD Intermediate connection box required in connection with lines D and E for flow sensors
ALTOFLUX 4000 F, PROFIFLUX 5000 F and VARIFLUX 6000 F for process temperatures
exceeding 150°C (302°F).
Recommended length of signal line
for magnetic field frequencies ≤ 1/6 x power frequency
Flow Meter size Signal Please note!
sensor DN mm Inch line
Max. length and minimum cross section of field current line
Length L Cross section AF (Cu), minimum
0 to 150 m 5 to 500 ft 2 x 0.75 mm² Cu 2 x 18 AWG
150 to 300 m 500 to 1000 ft 2 x 1.50 mm² Cu 2 x 14 AWG
300 to 600 m 1000 to 1900 ft 4 x 1.50 mm² Cu 4 x 14 AWG
IFC 110 F11
05/2003
Sect. 1.3.5 Part A System installation and start-up
1.3.5 Connection diagrams for power supply and flow sensors
Important remarks for circuit diagrams PLEASE NOTE !
• The figures in brackets indicate the stranded drain wires of the shields (see cross-sectional
drawings of signal lines in Section 1.3.1).
• Electrical connection to VDE 0100 ”Regulations for the erection of power installations with
nominal voltages up to 1000 V”
• Power supply 24 V AC / DC:
• Systems to be used in hazardous areas are subject to special regulations applying to
electrical connections (see Section 1.3.6) for hazardous-duty instruments.
• PE = protective conductor
Do not remove the internal connection (cable) inside the terminal compartment of the signal
converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective
*
conductor for protection class I instruments).
IMPORTANT!
Electrical connection of EEx flow sensors and EEx signal converters to be carried
out as described in Sect. 1.3.6.
protective extra-low voltages (PELV) acc. to VDE 0100/
VDE 0106 and/or IEC 364/IEC 365, or corresponding
national regulations.
FE = functional ground conductor
12 IFC 110 F
05/2003
Part A System installation and start-up Sect. 1.3.5
Process temperature below 150°C (302°F)
I Signal cable A (type DS) II Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Flow sensor Flow sensor
III Signal cable A (type DS) IV Signal cable B (type BTS)
Process temperature above 150°C (302°F)
IFC 110 F V 2.0 IFC 110 F V 2.0
Flow sensor Flow sensor
IFC 110 F13
05/2003
Sect. 1.3.6 Part A System installation and start-up
1.3.6 EEx-Connection diagrams for power supply and flow sensors
PLEASE NOTE!
• The figures in brackets indicate the stranded drain wires for the shields (see cross-sectional
drawing of signal cable in Section 1.3.1).
• The connections for the intrinsically safe electrode circuit including the shield terminals
are safety-separated up to a peak value of 375 V from the terminals for thepower supply,
for the inputs/outputs and for the field circuit. They are galvanically isolated from the housing
(PE/PA).
• For connection of the intrinsically safe electrode circuit including shield terminals to the
primary head, please refer to Item 12 in EN 60079-14.
The non-intrinsically safe field circuit to be connected to the primary head in keeping with the
requirements of Item 9 in EN 60079-14 .
• The non-intrinsically safe input and output circuits may only be routed into the hazardous
area in compliance with appropriate measures as specified in EN 60079-14.
• Supply power (terminals 11,12)
In conformity with current regulations for electrical installations, an isolating facility is required
to be provided for the signal converter. The housing of the IFC 110 F – EEx signal converter
must be incorporated in the equipotential bonding system (via external PA connection).
Note!
A PE safety conductor is not connected if a functional extra-low voltage with safety
separation (PELV) is used. Grounding is then carried out by way of the equipotential
In conformity with the requirements for separation of intrinsically safe circuits, Category ib to
EN 50 020, the cable for the intrinsically safe electrode circuit must, up to the terminals, be
separated from all non-intrinsically safe circuits.
Terminals 20 and 30 are optionally provided for connecting cables with single shielding. The
terminal for the outer shield (S) is capacitance grounded in the signal converter. The outer
overall shield to be connected by the shortest possible wire to the shield terminal. Shields to
be carefully insulated from ground and from each other.
• Field circuit FSV (terminals 7, 8)
The field circuit is all-pole protected on the FSV circuit board with an internal fusible link 160mA / 250V.
• Input/output circuits
The connection is made to functional extra-low voltage circuits with safety separation (PELV).
The I/O functions and technical data are described in the Standard Installation and Operating
Instructions.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
Do not remove the internal connection (cable) inside the terminal compartment of the signal
converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective
*
conductor for protection class I instruments).
14 IFC 110 F
05/2003
Part A System installation and start-up Sect. 1.3.6
Process temperature below 150°C (302°F)
I Signal cable A (type DS) II Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Hazardous area
Hazardous area
Flow sensor Flow sensor
III Signal cable A (type DS) IV Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Process temperature above 150°C (302°F)
Hazardous area
Hazardous area
Flow sensor Flow sensor
IFC 110 F15
05/2003
Sect. 2.1 Part A System installation and start-up
2 Electrical connection: outputs and inputs
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
2.1 Important information for outputs and inputs …….…………. PLEASE NOTE !
• The signal converter has the following outputs and inputs:
Output and Symbol Terminals Remarks
input group
Power output I IS / I active / passive selectable
Current output P P / P for electronic totalizers
Pulse output A1* (P2)
Status outputs A1* and A2
Status outputs D1 and D2
Control inputs C1 and C2
A1* / A⊥
A1* / A⊥ / A2 A⊥ common centre grounding contact
D1 / D⊥ / D2 D⊥ common centre grounding contact
C1 / C⊥ / C2 C⊥ common centre grounding contact
Internal power supply E E+ / E- for active mode of outputs and inputs
* Output A1 can be used as a 2nd pulse output P2 for electromechanical totalizers or as a
4th status output, see Section 4.4, Fct. 3.07 HARDWARE.
• The output and input groups are electrically isolated from each other and from all other input
and output circuits.
• Please note:
A⊥ common centre grounding contact for outputs A1 and A2
D⊥ common centre grounding contact for outputs D1 and D2
C⊥ common centre grounding contact for control inputs C1 and C2
• Active mode:
the signal converter supplies the power for the operation (selection) of
receiver instruments, observe max. operating data (terminals E+ and E-).
• Passive mode:
the operation (selection) of receiver instruments requires an external
power supply (U
), observe max. operating data.
ext
• Connection diagrams of outputs and inputs are shown in Section 2.6.
• For operating data of outputs and inputs please refer to Sections 2.6 and 10.1.
for electromechanical totalizers
16 IFC 110 F
05/2003
Part A System installation and start-up Sect. 2.2
2.2 Current output I
• The current output is electrically isolated from all other circuits.
• Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
• All operating data and functions are adjustable (see Sections 4.4 and 5.6, Fct. 1.05).
• Max. load :
• Selfcheck :
- short-circuit of mA loop via test function, see Fct. 2.03
or when power supply is switched on in Fct. 3.07
Error message on display (see Fct. 1.04, Section 5.4) and/or
status output (see Fct. 1.07-1.10, Section 5.8).
• Current value for error identification is adjustable, see Fct. 1.05 and Section 5.6.
• Range change-over, automatically or externally by control input,
see Sections 4.4 and 5.19, Fct. 1.07-1.10 and 1.11-12.
Setting range from 5-80% of Q
(corresponding low to high range ratio from 1:20 to 1:1.25).
Change-over from high to low range at approx. 85% of low range and vice versa at approx.
98% of low range.
The active range is signalled via one of the four status outputs.
• Forward/reverse flow measurement (F/R mode) is possible (see Section 5.15).
• Connection diagrams see Section 2.6.
active operation 15-500 Ω
passive operation
≤ 800 Ω
- interrupting the mA loop, and
100%
IFC 110 F17
05/2003
Sect. 2.3.1 Part A System installation and start-up
2.3 Pulse outputs P and A1
2.3.1 Pulse output P for electronic totalizers (EC)
• Pulse output P is electrically isolated from all other circuits.
• Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
• All operating data and functions are adjustable, see Sections 4.4 and 5.7, Fct. 1.05.
• Active mode:
Passive mode:
• Max. adjustable frequency 10 kHz
• Scaling
in pulses per unit volume
• Pulse width
automatic
pulse duty factor approx. 1:1 at Q
pulse width range from 0.01 to 1 s
correspondingly lower output frequency.
• Forward/reverse flow measurement (F/R mode) is possible, see Section 5.15.
• Connection diagrams see Section 2.6
• Schematic wiring diagram for pulse output P for electronic totalizers EC
Similar to a relay contact, this pulse output switches direct and alternating voltages.
uses the internal power supply, terminals E+/Erequires external power supply, U
in pulses per unit time
(e.g. 1000 pulses/s at Q
≤ 32V DC/24V AC, I ≤ 30mA
ext
(e.g. 100 pulses/m³ or US Gal).
symmetric
, pulse duty factor 1:1, independent of output frequency,
, with optimum pulse width,
, or
100%
adjustable as required for
100%
flow) or
18 IFC 110 F
05/2003
Part A System installation and start-up Sect. 2.3.2
2.3.2 Pulse output A1 for electromechanical totalizers (EMC)
PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1 for
electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE, see Sections 4.4 and 5.18.
• Pulse output A1 is electrically connected to status output A2 (common centre grounding
contact A⊥) but electrically isolated from all other circuits.
• Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
• All operating data and functions are adjustable, see Sections 4.4 and 5.7, Fct. 1.07.
• Active mode:
• Passive mode:
uses the internal power supply, terminals E+/Erequires external power supply, U
≤ 32V DC/24V AC, I ≤ 100mA
ext
(I ≤ 200mA for polarized DC operation, see Section 6.3)
• Max. adjustable frequency 50 kHz
• Scaling
in pulses per unit of time
(e.g. 10 pulses/s at Q
100%
flow) or
in pulses per unit of volume (e.g. 10 pulses/m³ or US Gal).
• Pulse width
symmetric
, pulse duty factor 1:1, independent of output frequency,
automatic, with optimum pulse width,
pulse duty factor approx. 1:1 at Q
pulse width range from 0.01 to 1 s
, or
100%
adjustable as required for
correspondingly lower output frequency.
• Forward/reverse flow measurement (F/R mode) is possible, see Section 5.15.
• Connection diagrams see Section 2.6
• Schematic wiring diagram for pulse output A1 for electromechanical totalizers EMC.
This pulse output has a MOSFET switch as output which switches direct and alternating
voltages similar to a relay contact.
IFC 110 F19
05/2003
Sect. 2.4 Part A System installation and start-up
2.4 Status outputs A1 / A2 / D1 / D2
PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1 for
electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE, see Sections 4.4 and 5.18.
• Status outputs A1/A2 and D1/D2 with the common centre grounding contacts A⊥ and B⊥ are
electrically isolated from each other and from all other circuits.
• Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
• All operating data and functions are adjustable, see Sections 4.4 and 5.8, Fct. 1.07-1.10.
• Active mode:
Passive mode:
uses the internal power supply, terminals E+/Erequires external power supply, U
≤ 32V DC/24V AC, I ≤ 100mA
ext
(I ≤ 200mA for A1 in case of polarized DC operation, see Section 6.3)
• The following operating conditions can be signalled using the status outputs:
- flow direction (F/R mode)
- limits
- error messages
- active range in case of range change-over
- inverse operation of A1 and A2 or D1 and D2,
i.e. used as change-over switch with common centre grounding contact A⊥ or D⊥.
• Connection diagrams see Section 2.6
• Schematic wiring diagram for status outputs A1/A2 and D1/D2.
This status outputs have MOSFET switches as outputs which switch direct and alternating
voltages similar to relay contacts.
2.5 Control inputs C1 and C2
• Control inputs C1 and C2 are electrically connected (common centre grounding
contact C⊥) but electrically isolated from all other circuits.
• Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
• All operating data and functions are adjustable, see Sections 4.4 and 5.9, Fct. 1.11-1.12.
• Active mode:
Passive mode:
uses the internal power supply, terminals E+/Erequires external power supply, U
≤ 32V DC/24V AC, I ≤ 10mA
ext
• The following operating conditions can be initiated using the control inputs:
- external range change
- holding of output values
- zeroing the outputs
- resetting the internal totalizer
- resetting (deleting) the error messages
• Connection diagrams see Section 2.6
20 IFC 110 F
05/2003
Part A System installation and start-up Sect. 2.6
2.6 Connection diagrams of outputs and inputs
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
I
P, A1*
A1*, A2,
D1, D2
C1, C2
Current output (included HART
Pulse output
Status outputs
Control inputs
Totalizer
-electromechanical (EMC)
- electronic (EC)
milliampmeter
0-20 mA or 4-20 mA and other
Key, N/O contact
External voltage source (U
connection polarity arbitrary
DC voltage,
external power source (U
Active mode: the IFC 110 F supplies the power required for operating (driving) the receiver
instruments. Observe the max. operating data (terminals E+ and E-).
Passive mode: an external power supply source (Uext) is required for operating (driving) the
receiver instruments.
Groups A / C / D / E / I / P are electrically isolated from each other and from all other input and
output circuits.
Please note:
common reference potential
A⊥ for A1 and A2
C⊥ for C1 and C2
D⊥ for D1 and D2
®
)
), DC or AC voltage,
ext
), note connection polarity
ext
Please note ! Unwired
contacts or terminals may not
have any conductive
connection with other
electrically conducting parts.
Interface operation with
HART® or RS 485 (Option)
see Sect. 6.4.
*
selectable as
status output A1 or
pulse output A1
IFC 110 F21
05/2003
Sect. 2.6 Part A System installation and start-up
Current output I
{
active
Current output I
|
range change BA
with automatic
active
without external change-over relay
low range
high range
Ri 15 - 500 Ω
Ri 15 - 500 Ω
Current output I
}
(see Sect. 6.8 passive/active for pulse and current outputs (P and I
passive
Forward/reverse flow meausrement (F/R mode)
~
active
)
operation without external change-over relay
reverse
flow
forward
flow
reverse
flow
forward
flow
Ri 15 - 500 Ω
selectable with internal power supply
E or external power supply U
the connection diagrams for pulse output P on the
ext.
Electronic totalizers must be connected as shown in
following page.
U
15 - 22 V DC 22 - 32 V DC
ext.
R
0 - 500 Ω0 - 800 Ω
i
Pulse output A1 active
Pulse output A1 passive
for electromechanical totalizers (EMC) for electromechanical totalizers (EMC)
≤ 32 V DC / ≤ 24 V AC I ≤ 10 mA
Ri ≥ 160 Ω
I ≤ 100 mA
22 IFC 110 F
U
ext.
oder umschaltbar auf
≤ 32 V DC I ≤ 200 mA
U
ext.2
05/2003
Part A System installation and start-up Sect. 2.6
Pulse output P
active
for electronic totalizers (EC)
for frequencies ≤ 1 kHz
Pulse output P
for electronic totalizers (EC)
for frequencies > 1 kHz
active
R1 = 1 kΩ/0.5 W I ≤ 20 mA R
> 100 kΩ R = 1 kΩ/0.35 W I ≤ 30 mA
i EC
R2 / 0.2 W
U
EC max
10 kΩ 1 kΩ 270 Ω
22 V 12 V 5 V
Pulse output P
passive
for electronic totalizers (EC)
for frequencies ≤ 1 kHz
U
≤ ≤ 32 V DC / ≤ 24 V AC
ext
I
≤ ≤ 30 mA
R
=
1 - 10 kΩ
P
≥
R
2
U
ext
R
for frequences > 1 kHz
U
=
ext
R
i EC
I ~ 30 mA ~ 18 mA
R
P
R
U
EC
≤ 24 V DC / AC
≥ 100 kΩ
560 Ω 1 kΩ
0.5 W 0.35 W
16 V 18 V
* Shielded cables
must be used to prevent radio interference at pulse output frequencies > 100 Hz
IFC 110 F23
05/2003
Sect. 2.6 Part A System installation and start-up
Status outputs D1 / D2 / A1 / A2 active
I ≤ 100 mA
e.g. message display
9
Control inputs C1 / C2 active
Status outputs D1 / D2 / A1 / A2 passive
≤ 32 V DC / ≤ 24 V AC
U
ext.
I ≤ 100 mA
9
e.g. message display
Control inputs C1 / C2 passive
Contacts 24 V, 10 mA
I ≤ 7 mA I ≤ 10 mA
24 IFC 110 F
≤ 32 V DC / ≤ 24 V AC
U
ext.
05/2003
Part A System installation and start-up Sect. 2.7
2.7 Standard factory settings
• All operating data are set at the factory in accordance with the specifications contained in the
order.
• If no specifications are made in the order, instruments will be delivered with the standard
parameters and functions indicated in the table below.
• To facilitate the start-up of the instrument, current and pulse outputs are set to handle
measurements in ”two flow directions” so that the current flow rates and volumes are displayed
and/or counted independent of the direction of flow. The figures displayed may have a
preceding sign.
• Such factory setting of current and pulse outputs may lead to measuring errors, particularly
when volumes are metered and totalized.
• If e.g. pumps are switched off and ”backflows” occur which are not within the low-flow cutoff
(SMU) range, or if separate displays and counts are required for both flow directions.
• To avoid faulty measurements, it may therefore be necessary to change the setting of the
following functions:
- SMU low-flow cutoff Fct. 1.03, Section 5.3
- display Fct. 1.04, Section 5.5
- current output I Fct. 1.05, Section 5.6
- pulse output P Fct. 1.06, Section 5.7
• For special applications, such as pulsating flows, see Sections 6.5 to 6.10
Standard factory settings
Fct. No. Function Setting Fct. No. Function Setting
1.01 Full-scale range See instr. nameplate 1.08 Status output A2 ON
of flow sensor 1.09 Status output D1 All error
1.02 Time constant 3 Sec. for display, 1.10 Status output D2 Indication F/R
pulse, current and 1.11 Control input C1 Totalizer reset
status ouputs 1.12 Control input C2 OFF
1.03 Low-flow cutoff ON: 1% 3.01 Language German
OFF: 2% 3.02 Flow sensor
1.04 Display meter size See instr. nameplate
flow rate m³/h direction of flow + direction,
totalizer m³ see arrow on
1.05 Current output I
function 2 directions 3.04 Entry code NO
range 4-20 mA 3.05 User unit Liter/h
error detection 22 mA 3.06 Application
1.06 Pulse output P flow steady
function 2 directions empty pipe NO
pulse value 1000 pulses/Sec. ADC gain automatic
pulse width symmetric special filter OFF
1.07 Pulse output 2, A1 3.07 Hardware
function 2 directions terminal A1 pulse output A1
pulse value 1 pulse/s selfcheck NO
pulse width 50 ms
flow sensor
active
IFC 110 F25
05/2003
Sect. 3 Part A System installation and start-up
3 Start-up
• Before connecting to power, check that the instrument is correctly installed as described in
Sections 1 and 2.
• The flowmeter, flow sensor and signal converter are delivered ready for operation. All
operating data are set at the factory in accordance with your specifications.
Please also refer to Section 2.7 ”Standard factory settings”.
• Switch on the power supply. The flowmeter immediately begins to measure the flow.
• When the power supply is switched on, the display successively shows START UP and
READY. Then the current flow rate and/or the current totalizer count are displayed. Displays
are either steady or cyclic depending on the setting described for Fct. 1.04.
• 2 light-emitting diodes (LED) in the ”diagnostics” field on the front panel of the signal
converter indicate the status of measurement.
LED displays Status of measurement
Green ”normal” LED Everything O.K.
is flashing
Green ”normal” LED Momentary overload of outputs and/or A/D converter.
and red ”error” LED Detailed error messages by setting Fct. 1.04 DISPLAY,
are flashing alternately subfunction ”MESSAGES” to ”YES”, see Sections 4.4 and 5.5.
Red ”error” LED is Fatal Error, see Sections 7.3 and 7.4
flashing
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
26 IFC 110 F
05/2003
Part B IFC 110 F Signal converter Sect. 3
Setting data: Here you can note down the settings of the signal converter !
Fct. No. Function Settings
1.01 Full-scale range
1.02 Time constant
1.03 Low-flow cut-off
1.04 Display
1.05 Current output I
1.06 Pulse output P
1.07 Pulse output A1 or
Status output A1
(for setting see below, Fct. 3.07,
terminal A1)
1.08 Status output A2
1.09 Status output A3
1.10 Status output A4
1.11 Control input C1
1.12 Control input C2
3.01 Language
3.02 Flow sensor
3.04 Entry code required ?
3.05 User-defined unit
3.06 Application
3.07 Hardware-settings Terminal A1 is or
3.08 Measuring point
3.09 Communication
ON: OFF:
Flow
Totalizer
Messages
Trend
Function
Reverse range
Range I
Error
Function
Pulswidth
Pulse value
Meter size
GK value
Field frequency
Power frequency
Flow direction
no yes
→ → → ↵ ↵ ↵ ↑ ↑ ↑
Flow is steady
pulsating
Empty Pipe no
Detection (EPD) yes
Pulse output
Status output
of
HART or
KROHNE RS 485
Address:
Baud rate:
IFC 110 F27
05/2003
Sect. 4.1 Part B IFC 110 F Signal converter
4 Operating of the signal converter
4.1 KROHNE operating concept
28 IFC 110 F
05/2003
Part B IFC 110 F Signal converter Sect. 4.2
4.2 Operating and control elements
The instrument can be operated
by means of ....
…
the 15 keys ~
after removal of the glass cover,
…
the 3 magnetic sensors
bar magnet without opening the
housing (optional).
Display, 1st line Displaying numerical data
{
Display, 2nd line Displaying units and texts
|
Display, 3rd line 6 arrows to mark the current display
}
flow rate current flow rate
+
totalizer
-
control in
~
5 keys for operating the signal converter ← → ↵ ↑ ↓
10 keys for direct numerical setting of function values (not function numbers)
Compass field showing that a key is pressed
magnet active
green
red
3 magnetic sensors (optional), operated by bar magnet without opening the housing,
function of the sensors as described for the three keys → ↵ ↑, see
diagnostics
normal
error
IMoCom
supplementary equipment, see Section 6.4, slide window to the left
totalizer
totalizer
sum totalizer (+ and -)
Σ
1/2
control input 1 or 2 active
LED green/red, magnetic sensors active
= built-in magnetic sensors (optional), see
= operation of one of the 3 magnetic sensors
2 LEDs signalling the status of measurement
green LED
red LED
IMoCom bus, multipoint connector for connecting external
= correct measurement, everything O.K.
= error, parameter or hardware error
and accessible
.
~
and the
IFC 110 F29
05/2003
Sect. 4.3 Part B IFC 110 F Signal converter
4.3 Key functions
In the following, the cursor or flashing part of the display is shown against a grey background.
To start operator control
Measuring mode
1 3 . 5 7 1
m 3 / h
PLEASE NOTE: if ”YES” is selected in Fct. 3.04 ENTRY CODE, ”CodE 1 - - - - - - - - -”
appears in the display after pressing the → key.
Enter the password for the entry code which is a sequence of 9 keys: → → → ↵ ↵ ↵ ↑ ↑ ↑
(each keystroke confirmed by ” * ”).
To terminate operator control
Press key ↵ any number of times until one of the following menus
Fct. 1.0 OPERATION, Fct. 2.0 TEST or Fct. 3.0 INSTALL is displayed.
F c t . 3. 0
I N S T A L L.
Store new parameters: acknowledge by
New parameters not to be stored:
Keyboard with 10 keys
The keyboard with the 10 keys (0-9) is used for setting all flashing numbers (cursor).
Exception: the digits of the function numbers, such as Fct. 1.03, can only be changed with
keys ↑ or ↓.
→
Press key ↵
↵
Operator control mode
F c t . 1. 0
O P E R A T I O N
S T O R E Y E S
pressing key ↵. Measuring mode is
continued with new parameters.
press key ↑ to display
”STORE NO”.
Measuring mode is continued with the ”old”
parameters after pressing key ↵.
30 IFC 110 F
05/2003
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.