KROHNE IFC-110 User Manual

© KROHNE 09/2003
Supplementary
Installation and
HART Communicator 275
Asset Management Solutions (AMS)
Process Device Manager (PDM)
IFC 110
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg 1/15 Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
1 General Information 3
2 IDs and Revision numbers 5
3 Implementation Peculiarities 6
4 HART Communicator 275 (HC275) 6
4.1 Installation 6
4.2 Operating 6
5 Asset Management Solutions (AMS) 6
5.1 Installation 6
5.2 Operating 6
6 Process Device Manager (PDM) 7
6.1 Installation 7
6.2 Operating 7
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg 2/15 Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
1 General Information
The IFC110 is a "four -wire" transmitter with 4...20mA current output and HART capability. It is available with active current output or active/passive current output.
General characteristics of the IFC110 HART interface:
Multidrop Mode is supported
Burst Mode is not supported
Electrical connection: Refer to sections 2.1, 2.2, 2.6 of the “Installation and Operating Instructions Electromagnetic flowmeters ALTOFLU X IFC 110 F” (KROHNE).
There are two ways of using the HART communication: a) As a point -to-point connection between the IFC110 and the HART master equipment.
Point-to-Point Analog/Digital Mode
Primary Master
250 O
Secondary Master
HART
Modem
HART
Analog
mA
4 20
Terminal I Terminal I
4...20 mA
IFC110
Addr. 0
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg 3/15 Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
b) As a multipoint connection (multidrop) with up to 15 devices (IFC110 or other HART equipment).
Multidrop Mode
Primary Master
HART
Modem
HART
Power Supply
250 O
4 mA 4 mA
Terminal I Terminal I
. . .
Secondary Master Up to 15
Slaves
. . .
IFC110
Addr. > 0
(passive Current Output)
IFC110
Addr. > 0
(passive Current Output)
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg 4/15 Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
If the IFC110 is equipped with a continously active current output a 'third wire' is needed to properly connect it together with two-wire loop powered devices in the same network.
Multidrop Mode (‘three-wire’)
(Connecting two-wire and four-wire devices in the same network)
Secondary Master
Primary Master
HART
Modem
Power Supply
HART
HART
250 O
4 mA
two-wire loop powered devices
4 mA
. . .
Addr. > 0 Addr. > 0
Terminal I
4 mA
IFC110 Addr. > 0
4 mA
four-wire active source devices
. . .
Terminal I
IFC110 Addr. > 0
2 IDs and Revision Numbers
The HART Device Descriptions described in this document have the following IDs and revision numbers: Manufacturer ID: 69 (0x45) Device Type: 243 (0xF3) Device Revision: 2 DD Revision: 1 HART Universal Revision: 5 HC 275 OS Revision: 4.9 AMS Version: 5.0
PDM Version: 5.1 For information about Transmitter Revisions and related Device Descriptions refer to the KROHNE HART Device
List.
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg 5/15 Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de