The flow sensor must be installed in the pipeline as described in the instructions for
installation inside the packing of the flow sensor.
– Connection of power supply (Sect. 1.1-1.2)Pages 4- 5
– Electrical connection between IFC 110 F and primary head (Sect. 1.3)Pages 6-13
– Electrical connection of outputs and inputs (Sect. 2)Pages 14-22
– Start-up (Sect. 3)Pages23
Power the flowmeter. THAT’S ALL. The system is operative.
Operator control of the IFC 110 F signal converter is described in Sect. 4.
● Display & control unit
No. 3.19937.02.00
● A/D converter
No. 8.13393.02.00
● Outputs/inputs (I/O)
No. 3.16230.01.00
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications technology
Engineering systems & solutions
Switches, counters, displays and recorders
Heat metering
Pressure and temperature
A
The operating data are factory-set to your ordered specifications.
Signal converter versions
IFC 110 F / D Standard version, with local display and control elements
(Standard)
IFC 110 F / D / MP Same as display version, additional with magnetic sensors (MP)
(Option)
IFC 110 F / D / MP / EEx Same as display version (D + MP),
(Option) for operation with flow sensors installed in hazardous areas
IFC 110 F / RS 485 Same as standard version,
but additionally with different interfaces
• Signal converter in the version as ordered, see above.
Items included with supply
• Signal cable in the version and length as ordered (standard: signal cable A,
length 10 m / 30 ft)
• Condensed installation and operating manual in the ordered language for installation,
electrical connection, start-up and operator control of the signal converter.
• Service Manual in english language.
Please note!
In the Installation and Operating Manual there are hints with Sect. Numbers which you can find
in the Handbook / Service Manual only!
Instrument nameplates
Signal converter (example)
IFC 110 F
Signal converter IFC 110F-EEx (example)
Flow sensor (example)
LTOFLUX 4000 F
2 IFC 110 F
05/2003
System description
Electromagnetic flowmeters are precision instruments designed for linear flow measurement of
liquid products
The process liquids must be electrically conductive:, ≥ 5 µS/cm
(for cold demineralized water ≥ 20 µS/cm).
The full-scale range Q
can be set as a function of the meter size: flow velocity of 0.3 - 12 m/s
100%
or 1 - 40 ft/s (s. Section 10.4.).
Product liability and warranty
The electromagnetic flowmeters are designed solely for measuring the volumetric flowrate of
electrically conductive, liquid process products.
These flowmeters are available for use in hazardous areas.
Special regulations apply in this case, which are given in the special EEx directions.
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests
solelywith the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty.
In addition, the “General conditions of sale” forming the basis of the purchase contract are
applicable.
If flowmeters need to be returned to KROHNE, please note the information given on the last-butone page of these Instructions. KROHNE regrets that it cannot repair or check your flowmeter(s)
unless accompanied by the completed form sheet.
CE / EMC / Standards / Approvals
The here described Electromagnetic flowmeters meet the NAMUR Directive NE21,
the protection requirements of Directive 89/336/EEC in conjunction with EN61326-1 (1997) and A1 (1998), as well as Directives 73/23/EEC and 93/68/EEC
in conjunction with EN 61010-1, and bear the CE marking.
Software history
Display & control unit Amplifier (ADC) Inputs and outputs (I/O)
Software Status Software Status Software Status
3.19937.02.00
current
IMPORTANT!
In respect of EEx versions, pay regard to all directions marked with the
and also the information given in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
8.13393.02.00
current
3.16230.01.00
current
symbol,
IFC 110 F3
05/2003
1 Electrical connection: power supply
1.1 Location and important installation notes ……………………. PLEASE NOTE !
• Electrical connection in accordance with VDE 0100 ”Regulations for the erection of power
installations with nominal voltages up to 1000 V” or equivalent national regulations.
• Do not cross or loop cables inside the terminal compartment.
• Use separate wiring (PG screwed cable entries) for power supply, field current lines, signal
lines, outputs and inputs.
• Hazardous areas are subject to special regulations, see Section 6.1 and special installation
instructions for hazardous-duty versions.
• Do not expose signal converter and switchgear cabinets with built-in converters to direct
sunlight. Install a sunshade if necessary.
• Signal converters installed in switchgear cabinets require adequate cooling (e.g. by fans
or heat exchangers).
• Do not expose signal converters to intense vibration.
• Keep the distance between the flow sensor and signal converter as small as possible, for
empty pipe detection (EPD) ≤ 20 m / ≤ 66 ft. Observe maximum lengths of signal and field
current lines (see Section 1.3.4).
• Use KROHNE signal line A (type DS, standard) or signal line B (type BTS, bootstrap,
optional), standard length 10 m (33 ft).
• Generally use bootstrap signal lines B (type BTS) for PROFIFLUX 5000 F and VARIFLUX
6000 F flow sensors sized at DN 2.5-15 and 1/10’’-1/2’’ and for contaminated liquids which
tend to form electrically insulating deposits.
• Always calibrate flow sensor and signal converter together. During installation particular care
should therefore be given to identical settings of flow sensor constant GK (see instrument
nameplate of flow sensor). In case GK constants are not identical, the signal converter must
be adjusted to the flow sensor GK (see Sections 4 and 8.5).
• Dimensions of signal converter see Section 10.3.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
4 IFC 110 F
05/2003
1.2 Power supply - connection
PLEASE NOTE !
• Type of enclosure
• Dimensioning:
moisture must always be kept closed. The selected clearances and creeping distances comply
with VDE 0110 and/or IEC 664 regulations for contamination grade 2. Supply circuits and
output circuits are designed to meet standards of overvoltage classes III and II, respectively.
• Fuse protection, disconnecting device: fuse protection for the feeding power circuit, and also a
disconnecting device (switch, circuit breaker) for isolating the signal converters must be
provided (see also Sect. 1.3.5 and 1.3.6).
100-230 V AC (tolerance range 85-255 V AC)
• Observe information on the instrument nameplate, power supply voltage and frequency.
• The protective conductor PE of the power supply must be connected to the separate
U-clamp terminal inside the terminal compartment of the signal converter.
• CAUTION: do not remove the internal connection (line) inside the terminal compartment of the
signal converter (yellow/green wire) between the U-clamp terminal and terminal 10 protective conductor (protection class I instrument).
• Connection diagrams I - IV for the power supply and for the electrical connection between
flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
24 V AC / DC (tolerance ranges: AC 20.4 - 26.4 V / DC 18 - 31.2 V)
• Observe information on the instrument nameplate, power supply voltage and frequency.
• For technical reasons concerning the measuring process, a functional grounding conductor
FE has to be connected to the separate U-clamp terminal inside the terminal compartment of
the signal converter.
• A facility providing a reliable electrical separation (PELV) has to be provided for connections
to functional extra-low voltages (24 V AC / DC) - (VDE 0100 / VDE 0106 and/or IEC 364 /
IEC 536 or equivalent national regulations).
• Connection diagrams I - IV for the power supply and for the electrical connection between
flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
IP 65 to IEC 529 / EN 60529 equivalent to NEMA 4/4X.
the flowmeter housing protecting the electronic equipment against dust and
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
IFC 110 F5
05/2003
1.3 Electrical connection of flow sensors
1.3.1 General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when KROHNE signal lines A and B are used with
foil screen and magnetic shield.
• Signal lines must be firmly installed.
• Shields are connected via stranded drain wires.
• Underwater or underground routing is possible.
• Insulating material flame-retardant to IEC 332.1 / VDE 0742.
• Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Signal line B (type BTS) with triple shielding (bootstrap line)
8 Outer sheath
The bootstrap technology always controls the individual shields (3) of the signal converter exactly
to the voltage which is supplied to the signal conductors (5). As this prevents voltage differences
between the individual shields (3) and signal conductors (5), no current flows via the line
capacitances between 3 and 5. The line capacitance seems to become ”zero”.
This allows greater cable lengths in case the electric conductivity of the liquid to be measured is
low.
1
Dummy glider wire
2
Insulation (2.1 red/2.2 white)
3
Special foil, 1st shield (3.1/3.2)
4
Insulation (4.1/4.2)
5
Stranded wire 0.5 mm² or AWG 20
(5.1 red/5.2 white)
Stranded drain wire, 2nd shield, 1.5 mm² or AWG 14
9
Insulation
10
Mu-metal foil, 3rd shield
11
Stranded drain wire, 3rd shield, 0.5 mm² or AWG 20
12
Outer sheath
Field current line C1
Line 2 x 0.75 mm² (18 AWG) Cu or 2 x (4 x) 1.5 mm² (14 AWG) Cu (Cu = copper cross section)
The cross section depends on the required cable length.
For max. permissible cable lengths please refer to Section 1.3.4
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
6 IFC 110 F
05/2003
1.3.2 Stripping (preparation) of signal cables
Please note: The numbers in the drawings designate the stranded drain wires of signalling cables
A and B, see sectional drawings in Sect. 1.3.1.
Flow sensor Converter
Length flow sensor Length Converter
mm inch mm inch
a 90 3.60 a 50 2.00
b 8 0.30 b 8 0.40
c 25 1.00 d 8 0.40
d 8 0.30 e 20 0.80
e 70 2.80
Signal cable A (type DS),
double shielding
for flow sensor
Signal cable A (type DS),
double shielding
for IFC 110 F Converter
Signal cable A
bending radius
≥ 50 mm (≥ 2”)
Signal cable B (type BTS),
with triple shielding (bootstrap)
for flow sensor
Signal cable B
bending radius
≥ 50 mm (≥ 2”)
Customer-supplied materials
W
Insulation tubing (PVC), Ø 2.0-2.5 mm (Ø 1”)
X
Heat-shrinkable tubing or cable sleeve
Y
Wire end sleeve to DIN 41 228: E 1.5-8
Z
Wire end sleeve to DIN 41 228: E 0.5-8
Signal cable A
bending radius
≥ 50 mm (≥ 2”)
Signal cable B (type BTS),
with triple shielding (bootstrap)
for IFC 110 F Converter
Signal cable B
bending radius
≥ 50 mm (≥ 2”)
IFC 110 F7
05/2003
1.3.3 Grounding of flow sensor
• The flow sensor must be correctly connected to ground.
• The grounding cable may not transfer interference voltages.
• Do not use the grounding cable to connect more than one device to ground.
• In hazardous areas the grounding line is also used for potential equalizing purposes. Special
grounding instructions are contained in the installation instructions for hazardous-duty
instruments (only supplied together with such instruments).
• The flow sensor is connected to ground by means of a functional grounding conductor FE.
• Special grounding instructions for the connection of several flow sensors are contained in the
separate installation instructions of the flow sensors.
• These instructions also contain detailed descriptions on how to use grounding rings and how
to install flow sensors in metal or plastic pipes or in pipes which are coated on the inside.
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
8 IFC 110 F
05/2003
1.3.4 Cable lengths (max. distance between signal converter and flow sensor)
Abbreviations and explanations
The abbreviations used in the following tables, diagrams and connection diagrams stand for:
A Signal line A (type DS) with double shielding, max. length see diagram
B Signal line B (type BTS) with triple shielding, max. length see diagram
C Field current line, minimum cross section (A
) and max. length see table
F
D High-temperature silicone line, 3x1.5 mm² (14 AWG) Cu, with single shield,
max. length 5 m (16 ft)
E High-temperature silicone line, 2 x 1.5 mm² (14 AWG) Cu, max. length 5 m (16 ft)
Cross section of field current line C in Cu, see table
A
F
L Cable length in m or ft
Electrical conductivity of the process liquid
Κ
ZD Intermediate connection box required in connection with lines D and E for flow sensors
ALTOFLUX 4000 F, PROFIFLUX 5000 F and VARIFLUX 6000 F for process temperatures
exceeding 150°C (302°F).
Recommended length of signal line
for magnetic field frequencies ≤ 1/6 x power frequency
Flow Meter size Signal Please note!
sensor DN mm Inch line
Max. length and minimum cross section of field current line
Length L Cross section AF (Cu), minimum
0 to 150 m 5 to 500 ft 2 x 0.75 mm² Cu 2 x 18 AWG
150 to 300 m 500 to 1000 ft 2 x 1.50 mm² Cu 2 x 14 AWG
300 to 600 m 1000 to 1900 ft 4 x 1.50 mm² Cu 4 x 14 AWG
05/2003
IFC 110 F9
1.3.5 Connection diagrams for power supply and flow sensors
Important remarks for circuit diagrams PLEASE NOTE !
• The figures in brackets indicate the stranded drain wires of the shields (see cross-sectional
drawings of signal lines in Section 1.3.1).
• Electrical connection to VDE 0100 ”Regulations for the erection of power installations with
nominal voltages up to 1000 V”
• Power supply 24 V AC / DC:
• Systems to be used in hazardous areas are subject to special regulations applying to
electrical connections (see Section 1.3.6) for hazardous-duty instruments.
• PE = protective conductor
Do not remove the internal connection (cable) inside the terminal compartment of the signal
converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective
*
conductor for protection class I instruments).
IMPORTANT!
Electrical connection of EEx flow sensors and EEx signal converters to be carried
out as described in Sect. 1.3.6.
protective extra-low voltages (PELV) acc. to VDE 0100/
VDE 0106 and/or IEC 364/IEC 365, or corresponding
national regulations.
FE = functional ground conductor
10 IFC 110 F
05/2003
Process temperature below 150°C (302°F)
I Signal cable A (type DS) II Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Flow sensor Flow sensor
III Signal cable A (type DS) IV Signal cable B (type BTS)
Process temperature above 150°C (302°F)
IFC 110 F V 2.0 IFC 110 F V 2.0
Flow sensor Flow sensor
IFC 110 F11
05/2003
1.3.6 EEx-Connection diagrams for power supply and flow sensors
PLEASE NOTE!
• The figures in brackets indicate the stranded drain wires for the shields (see cross-sectional
drawing of signal cable in Section 1.3.1).
• The connections for the intrinsically safe electrode circuit including the shield terminals
are safety-separated up to a peak value of 375 V from the terminals for thepower supply,
for the inputs/outputs and for the field circuit. They are galvanically isolated from the housing
(PE/PA).
• For connection of the intrinsically safe electrode circuit including shield terminals to the
primary head, please refer to Item 12 in EN 60079-14.
The non-intrinsically safe field circuit to be connected to the primary head in keeping with the
requirements of Item 9 in EN 60079-14 .
• The non-intrinsically safe input and output circuits may only be routed into the hazardous
area in compliance with appropriate measures as specified in EN 60079-14.
• Supply power (terminals 11,12)
In conformity with current regulations for electrical installations, an isolating facility is required
to be provided for the signal converter. The housing of the IFC 110 F – EEx signal converter
must be incorporated in the equipotential bonding system (via external PA connection).
Note!
A PE safety conductor is not connected if a functional extra-low voltage with safety
separation (PELV) is used. Grounding is then carried out by way of the equipotential
In conformity with the requirements for separation of intrinsically safe circuits, Category ib to
EN 50 020, the cable for the intrinsically safe electrode circuit must, up to the terminals, be
separated from all non-intrinsically safe circuits.
Terminals 20 and 30 are optionally provided for connecting cables with single shielding. The
terminal for the outer shield (S) is capacitance grounded in the signal converter. The outer
overall shield to be connected by the shortest possible wire to the shield terminal. Shields to
be carefully insulated from ground and from each other.
• Field circuit FSV (terminals 7, 8)
The field circuit is all-pole protected on the FSV circuit board with an internal fusible link 160mA / 250V.
• Input/output circuits
The connection is made to functional extra-low voltage circuits with safety separation (PELV).
The I/O functions and technical data are described in the Standard Installation and Operating
Instructions.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx
certified signal converter must be installed outside the hazardous area!
Do not remove the internal connection (cable) inside the terminal compartment of the signal
converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective
*
conductor for protection class I instruments).
12 IFC 110 F
05/2003
Process temperature below 150°C (302°F)
I Signal cable A (type DS) II Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Hazardous area
Hazardous area
Flow sensor Flow sensor
III Signal cable A (type DS) IV Signal cable B (type BTS)
IFC 110 F V 2.0 IFC 110 F V 2.0
Process temperature above 150°C (302°F)
Hazardous area
Hazardous area
Flow sensor Flow sensor
IFC 110 F13
05/2003
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.