KROHNE IFC-090 User Manual

Signal converters for
Installation and operating instructions
electromagnetic flowmeters
IFC 090 K IFC 090 F
How to use these Instructions
The flowmeters are supplied ready for operation. The primary head must be installed in the pipeline as described in the installation
instructions inside the packing of the primary head.
- Installation location and connection to power (Section 1) Pages 1/1-1/6
- Electrical connection of outputs and inputs (Section 2) Pages 2/1-2/6
- Factory settings and start-up (Section 3) Pages 3/1-3/2
Power the flowmeter. THAT’S ALL. The system is operative. Operator control of the IFC 090 signal converter is described in Sections 4 and 5. Pull-out condensed instructions are located in the centrefold of this manual, pages A – D.
3.1M61EA3 119721 Order No. DIN A4: 7.02144.33.00 US size: 7.02144.73.00
Contents
System description 0/4 Product liability and waranty 0/4 CE / EMC / Standards / Approvals 0/4 Items included with supply 0/4
Part A System installation and start-up 1/1-3/2 1 Electrical connection: power supply 1/1-1/6
1.1 Location and important installation notes – PLEASE NOTE ! 1/1
1.2 Connection to power 1/2
1.3 Electrical connection of separate primary head (F Version) 1/3-1/6
1.3.1 General information on signal cable A and field current cable C 1/3
1.3.2 Stripping (preparation) of signal converter 1/3
1.3.3 Grounding of primary head 1/4
1.3.4 Cable length (max. distance between signal converter and primary head) 1/5
1.3.5 Connection diagrams I and II (power supply, converter and primary head) 1/6
2
2.1 Combinations of outputs and inputs 2/1
2.2 Current output I 2/1
2.3 Pulse output B1 (terminals B1 / B) 2/2
2.4 Status outputs B1 and B2 (terminals B1 / Band B2 / B) 2/3
2.5 Control inputs B1 and B2 (terminals B1 / Band B2 / B) 2/4
2.6 Connection diagrams for outputs and inputs 2/5-2/6
Electrical connection of outputs and inputs 2/1-2/6
3.
3.1 Switch-on and measurement 3/1
3.2 Factory settings 3/2
Part B IFC 090 4 Operation of the signal converter 4/1-4/12
4.1 Krohne operator control concept 4/1
4.2 Operating and check elements 4/2
4.3 Function of keys 4/3-4/4
4.4 Table of settable functions 4/5-4/9
4.5 Error messages in measuring mode 4/10
4.6 Reset totalizer and cancel error messages, RESET/QUIT menu 4/11
4.7 Examples of setting the signal converter 4/12
5
5.1 Full-scale range Q100% 5/1
5.2 Time constant 5/1
5.3 Low-flow cutoff 5/2
5.4 Display 5/2-5/3
5.5 Internal electronic totalizer 5/3
5.6 Current output I 5/4
5.7 Pulse output B1 5/5-5/6
5.8 Status outputs B1 and B2 5/7
5.9 Control inputs B1 and B2 5/8
5.10 Language 5/8
5.11 Entry code 5/8
5.12 Primary head 5/9
5.13 User-defined unit 5/10
5.14 F/R mode, forward/reverse flow measurement 5/11
5.15 Characteristic of outputs 5/11
5.16 Combinations of binary outputs and inputs 5/12
5.17 Limit switches 5/12
5.18 Automatic range change BA 5/13
5.19 Applications 5/14
Start-up 3/1-3/2
/D Signal converter 4/1-5/14
Description of functions 5/1-5/14
0/1
Part C Special applications, functional checks, service, and order numbers 6/1-9/1 6 Special applications 6/1-6/4
6.1 Use in hazardous areas 6/1
6.2
RS 232 adapter incl. CONFIG software (option)
6/1
6.3 Stable signal outputs when measuring tube empty 6/2
6.4 Pulsating flow 6/3
6.5 Rapid changes in flowrate 6/3
6.6 Unsteady display and outputs 6/4
6.7 HART interface 6/5-6/6
7
Functional checks 7/1-7/12
7.1 Zero check with IFC 090 /D, signal converter, Fct. 3.03 7/1
7.2 Test of measuring range Q, Fct. 2.01 7/1
7.3 Hardware information and error status, Fct. 2.02 7/2
7.4 Faults and symptoms during start-up and process flow measurement 7/3-7/8
7.5 Test of primary head 7/9
7.6 Test of signal converter using GS 8A simulator (option) 7/10-7/12
8
Service 8/1-8/5
8.1 Replacement of power fuses 8/1
8.2 Changeover of operating voltage on AC Versions 1 and 2 8/1
8.3 Turning the display PCB 8/1
8.4 Retrofitting the display unit 8/2
8.5 Power fuses and illustrations to Sect. 8.1 to 8.4 8/2
8.6 Turning the converter housing of the compact flowmeters 8/3
8.7 IFC 090 Replacement of converter electronic unit 8/3
8.8 IFC 080 and SC 80 AS Replacement of electronic unit by IFC 090 8/4
8.9 Illustrations of the PCBs 8/5
9
Order numbers 9/1
Part D Technical data, measuring principle and block diagram 10/1-12/1 10 IFC 090 Technical data 10/1-10/5
10.1 Full-scale range Q
100%
10/1
10.2 IFC 090 F and ZD Dimensions and weights 10/1
10.3 Error limits at reference conditions 10/2
10.4 IFC 090 Signal converter 10/3-10/4
10.5 Instrument name plates 10/5
1
1 Measuring principle and function of the system 11/1
12 Block diagram - signal converter 12/1
Part E Index E1-E2
Printed form to accompany flowmeters returned to Krohne E3
0/2
Here you can note down the settings of the signal converter !
Fct. No. Function Settings
1.01 Full-scale range
1.02 Time constant
1.03 Low-flow cut-off - ON: - OFF:
1.04 Display Flow
Totalizer Messages
1.05 Current output I Function Reverse range Range I Error
1.06 Output or input B1
(setting: see Fct. 3.07, terminal B1)
1.07 Output or input B2
(setting: see Fct. 3.07, terminal B2)
3.01 Language
3.02 Primary head Meter size
GK value Field frequency Power frequency Flow direction
3.04 Entry code required ? - no - yes
→ → → ↵ ↵ ↵ ↑ ↑ ↑
3.05 User-defined unit
3.06 Application Flow is - steady
- pulsating
3.07 Hardware settings Terminal B1 is - pulse output
- status output
- control input
Terminal B2 is - status output
- control input
0/3
System description
Electromagnetic flowmeters with the IFC 090 signal converter are precision instruments designed for linear flow measurement of liquid products.
The process liquids must be electrically conductive: 5 µS/cm (for cold demineralized water 20 µS/cm).
The full-scale range Q DN 2.5.- 1000 / 01/10” - 40” Q
can be set as a function of the meter size:
100%
= 0.010 - 34 000 m3/hr = 0.03 - 151 000 US Gal/min
100%
This is equivalent to a flow velocity of 0.3 - 12 m/s or 1 - 40 ft/s.
Product liability and warranty
The electromagnetic flowmeters with the IFC 090 signal converter are designed solely for measuring the volumetric flowrate of electrically conductive, liquid process products.
Special codes and regulations apply to their use in hazardous areas and these are referred to in the special “Ex” Installation and Operating Instructions (supplied only with hazardous-duty equipment).
Responsibility as to suitability and intended use of these compact electromagnetic flowmeters rests solely with the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty. In addition, the “General conditions of sale” forming the basis of the purchase contract are
applicable. If flowmeters need to be returned to Krohne, please note the information given on the last-but-one
page of these Instructions. Krohne regrets that it cannot repair or check your flowmeter(s) unless accompanied by the completed form sheet.
CE / EMV / Standards / Approvals
• Electro magnetic flowmeters with the IFC 090 signal converter meet the requirements of the EU-EMC Directives and bear the CE symbol.
• All factories and production sequences are ISO 9001 certified.
• Flowmeters are approved as hazardous-duty equipment to the harmonized European Standards and to Factory Mutual (FM). Further details are given in the “Ex” supplementary instructions provided only with hazardous-duty equipment.
Items included with supply
• Signal converter as ordered
• Installation and operating instructions
• 2 plug connectors for power supply and outputs/inputs
• Special wrench for opening the housing covers
• Bar magnet to operate the display converter without opening the housing
• Additional instructions for hazardous-duty versions (applies only to hazardous-duty equipment)
0/4
Part A System installation and start-up
1 Electrical connection: power supply
1.1 Location and important installation notes PLEASE NOTE !
Electrical connection in accordance with VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V” or equivalent national regulations.
Do not cross or loop cables inside the terminal compartment.
Use separate cable entries (PG screwed conduit entries) for power supply,
field current cables, signal lines, outputs and inputs.
Hazardous locations are subject to special regulations, see Section 6.1 and special installation instructions for hazardous-duty (”Ex”) versions.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunlight. Fit a sunshade if necessary.
When installed in switchgear cabinets, signal converters must be adequately cooled, e.g. use fans or heat exchangers.
Do not expose signal converters to intense vibration.
Onl
y for separate systems/signal converters (F Versions)
Keep distance between primary head and signal converter as short as possible.
Refer to Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied Krohne signal cable A (Type DS), standard length 10 m (33 ft).
Always calibrate primary head and signal converter together. Therefore, when installing,
ensure primary constant GK is identical; refer to instrument nameplate for the primary head. If the GK is not identical, set the signal converter to the GK of the primary head. Refer also to Sections 4 and 8.5.
Dimensions of signal converter; refer to Section 10.2.
1/1
PLEASE NOTE !
Connection to power 1.2
Rated values:
The flowmeter housings protecting the electronic equipment from dust and moisture must always be kept closed. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage classes III and II, respectively.
Safet
y isolation: the flowmeters (signal converters) must be provided with an
isolating facility.
1. AC V
ersion 2. AC Version
230/240 V AC (200 - 260 V AC) 200 V AC (170 - 220 V AC) switch-selectable to switch-selectable to 115/120 V AC (100 - 130 V AC) 100 V AC (85 - 110 V AC)
Note information on instrument nameplate: supply voltage and frequency
The PE protective ground conductor for the power supply must be connected to the
separate U-clamp terminal in the terminal compartment of the signal converter. For exceptions (compact systems), refer to installation instructions for the primary head.
Connection diagrams I and II for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.5.
24 V AC
/ DC (tolerance bands: AC 20 - 27 V / DC 18 - 32 V)
Note information on instrument nameplate: supply voltage and frequency.
For measurement reasons, connect an FE functional ground conductor to the separate
U-clamp terminal in the terminal compartment of the signal converter.
If connected to a functional extra-low voltage source (24 V AC / DC), provide for protective separation (PELV) in conformity with VDE 0100 / VDE 0106 or IEC 364 / IEC 536,
or equivalent national regulations.
Connection diagrams I and II for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.5.
Connection to power
for
internal
use only
L N
0L∼
1L
PE 100 -240 V AC FE 24 V AC/DC
(PE protective ground conductor) (FE functional ground conductor)
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
1/2
1.3 Electrical connection of separate primary head (F Versions)
1.3.1 General information on signal cable A and field current cable C
Use of the Krohne signal cable A with foil screen and magnetic shield will ensure proper operation of the equipment.
• Signal cable to be solidly laid.
• Connect shields via stranded drain wires.
• Underwater and underground installation possible.
• Insulating material is flame-retardant to IEC IEC 332.1 / VDE 0742.
• Signal cables are low in halogen, unplasticized, and stay flexible at low temperatures.
Si
gnal cable A (Type DS), with double shielding
2
1 Stranded drain wire, 1st shield, 1.5 mm 2 Insulation 3 Conductor 0.5 mm
2
or AWG 20 (3.1 red / 3.2 white)
or AWG14
4 Special foil, 1st shield 5 Inner sheath 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG20
8 Outher sheath
Field current cable C
with single shielding
Cross-section is dependent on required length of cable, see Table in Sect. 1.3.4.
1.3.2 Stripping (preparation) of signal cable A
Please note the different lengths given in the table for signal converter and primary head. Length Converter Primary
head
mm (inch) mm (inch)
a 70 (2.80) 90 (3.60) b 08 (0.30) 08 (0.30) c 25 (1.00) 25 (1.00) d 08 (0.30) 08 (0.30) e 50 (2.00) 70 (2.80)
See Section 1.3.4 for max. permissible cable lengths
Customer-supplied materials W
Insulation tubing (PVC), 2.0 - 2.5 mm dia. (1”)
X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
Please note:
For primary heads, stranded drain wire 1 must have the same length as stranded drain wire 7.
Signal cable A bending radius 50 mm (2”)
1/3
Grounding of primary head 1.3.3
• All flowmeters must be properly grounded.
• The grounding conductor should not transmit any interference voltages.
• Do not ground any other electrical device together with this conductor.
• In hazardous locations, the grounding conductor is used simultaneously for equipotential
bonding. Special grounding instructions are contained in the ”Ex” installation instructions for hazardous-duty devices, supplied only with such devices).
• The primary head is connected to ground by means of an FE functional ground conductor.
• Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
• These instructions also contain detailed descriptions on how to use grounding rings and
how to install primary heads in metal or plastic pipes or internally coated pipelines.
1/4
1.3.4 Cable lengths (max. distance between signal converter and primary head)
Abbreviations and ex
planatory notes
used in the following tables, diagrams and connection diagrams
A Signal cable A (type DS), with double shielding, see diagram for max. length C Field current cable C, with single shielding,
type and length see Table
2
D High-temperature silicone cable, 3 × 1.5 mm
(14 AWG) Cu, with single shielding,
max. length 5 m (16 ft)
2
E High-temperature silicone cable, 2 × 1.5 mm
(14 AWG) Cu, max. length 5 m (16 ft)
L Cable length
κκ
Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
Recommended len
gth of signal cable
for magnetic field frequency 1/6 × power frequency
Primary head
ECOFLUX IFS 1000 F
AQUAFLUX F ALTOFLUX IFS 4000 F
PROFIFLUX IFS 5000 F
VARIFLUX IFS 6000 F
Meter size
DN mm
010.0 - 0015
025.5 - 0150
010.0 - 1000
010.0 - 0150
200.0 - 1000
002.5 - 0015
025.0 - 0100
002.5 - 0015
025.5 - 0080
Nennweite
inch
3
/8- 1/
2
1 - 06
3
/8- 40
3
/8- 06
8 - 40
1
/10-1/
2
1 - 04
1
/10- 1/
2
1- 03
Signal line
Kurve
A4 A3 A1 A2 A1 A4 A2 A4 A2
Field current cable C: max. length and min. crosssection Length Type of cable,single shielding
000 - 150 m 0005-0500 ft 2 × 0,75 mm2Cu / 2 × 18 AWG
150 - 300 m 0500 - 1000 ft 2 × 1,50 mm2Cu / 2 × 14 AWG
2
300 - 600 m 1000 - 1900 ft 2 × 2,50 mm
Cu / 2 × 12 AWG
1/5
Connection diagrams I and II (power supply, converter and primary head) 1.3.5
Im
portant information PLEASE NOTE !
The figures in brackets indicate the stranded drain wires for the shields,
see cross-sectional drawing of signal cable in Section 1.3.1.
• Electrical connection to VDE 0100 ”Regulations governing heavy-current installations with
line voltages up to 1000 V“ or equivalent national regulations.
• Power supply 24 V AC / DC: functional extra-low voltage with protective separation in
conformity with VDE 0100, Part 410 or equivalent national regulations.
• Systems used in hazardous locations are subject to special regulations applying to the
electrical connection; refer to special installation instructions for hazardous-duty devices that are only supplied with such devices.
•PE= protective conductor FE = functional ground conductor
Process temperature < 150°C (302°F) Process temperature > 150°C (302°F)
I II
Primary heads
Primary heads
1/6
2 Electrical connection of outputs and inputs
2.1 Combinations of outputs and inputs
Assignment of the binary outputs and inputs as required, see 3.07 Fct. “HARDWARE” and Sect. 3.2 “Factory settings”.
Current output I – active or passive mode
– internal power source for the binary outputs and inputs
Binary outputs/inputs terminal B1: Terminals
pulse output B1 status output B1 or control input B1
terminal B2:
B1 B⊥B2 I+ I I
status output B2 or control input B2
Binary outputs
and inputs
Output/input combinations 1) – 6)
T
erminals: I+ / I / I
B1 / B
B2 / B
Combination: 1) IPS
2) IPC
3) ICS
4) ISC
5) IS1S2
6) IC1C2
2.2 Current output I
The current output is galvanically isolated from all input and output circuits.
Setting data and functions can note down on page 0/3.
Please also refer to Sect. 3.2 “Factory settings”.
Current output
I = current output P = pulse output S = status output C = control input
Typical current output I+ approx. 15 V DC positive
voltage of current output
I current sink
I chassis ground,
current output
All operating data and functions can be set.
Display version: IFC 090 D, see Sect. 4 and 5.6, Fct. 1.05 for operator control
Basic version: IFC 090 B, see Sect. 6.2 for operator control
The current output can also be used as an internal voltage source for the binary
outputs and inputs. U
= 15 V DC I = 23 mA when operated without receiver instruments at the current output
int
I = 3 mA when operated with receiver instruments at the current output
Connection diagrams,
see Sect. 2.6: diagrams 1 2 3 6 9 10 11
2/1
Pulse output B1 (terminals B1 / B) 2.3
• The pulse output is galvanically isolated from the current output and all input circuits.
Setting data and functions can note down on page 0/3.
Please also refer to Sect. 3.2 “Factory settings” and Sect. 2.1 “Combinations of the binary outputs and inputs”, Fct. 3.07 HARDWARE.
• Typical pulse output B1
B2 status output B2
or control input B2
B⊥chassis ground, binary
outputs and inputs
B1 pulse output B1 (or status
output, control input)
• All operating data and functions can be set:
Display version: IFC 090 D, see Sect. 4 and 5.7, Fct. 1.06 for operator control Basis version: IFC 090 B, see Sect. 6.2 for operator control
• The pulse output can be operated in the active or passive mode. Active mode: The current output is the internal voltage source,
connection of electronic totalizers (EC)
Passive mode: External DC or AC voltage source required, connection of electronic (EC)
or electromechanical (EMC) totalizers
• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or cycle counters are connected, allow for minimum counting interval:
gate time, counter
1000
P
100% [ Hz]
Connection diagrams, see Sect. 2.6: diagrams 3 4 5 9
2/2
2.4 Status outputs B1 and B2 (terminals B1 / Band B2 / B)
The status outputs are galvanically isolated from the current output and all input circuits.
Setting data and functions can note down on page 0/3.
Please also refer to Sect. 3.2 “Factory settings” and Sect. 2.1 “Combinations of binary outputs and inputs”, Fct. 3.07 HARDWARE.
• Typical status outputs B1 and B2
B2 status output B2
(or control input B2)
B⊥chassis ground, binary
outputs and inputs
B1 status output B1 (or pulse
output, control input)
All operating data and functions can be set: Display version: IFC 090 D, see Sect. 4 and 5.8, Fct 1.06 or 1.07 for operator control Basic version: IFC 090 B, see Sect. 6.2 for operator control
The status outputs can be operated in the active or passive mode.
Active mode: The current output is the internal voltage source. Passive mode: External DC or AC voltage source required.
Characteristics of the status outputs
Switch open Switch closed
OFF (switched off) no function ON (e.g. operation indicator) power OFF power ON SIGN I (F/R mode) Forward flow Reverse flow SIGN P (F/R mode) Forward flow Reverse flow TRIP POINT (limit switch) inactive active AUTO RANGE (automatic range change)
high range low range
OVERFLOW I (I overranged) current output OK current output overranged OVERFLOW. P (P overranged) pulse output OK pulse output overranged ALL. ERROR (all errors) errors no error FATAL.ERROR (fatal errors only) errors no error EMPTY PIPE (option) when measuring when measuring
tube is empty tube is full
Connection diagrams, see Sect. 2.6: diagrams 6 7 9 10 11
2/3
Control inputs B1 and B2 (terminals B1 / Band B2 / B) 2.5
The control inputs are galvanically isolated from the current output and all input circuits.
Setting data and functions can note down on page 0/3.
• Please also refer to Sect. 3.2 “Factory settings” and Sect. 2.1 “Combinations of binary outputs and inputs”, Fct. 3.07 HARDWARE.
Typical current inputs B1 and B2
B1 / B2
B
All operating data and functions can be set:
Display version: IFC 090 D, see Sect. 4 and 5.19, Fct. 1.06 and 1.07 for operator control Basic version: IFC 090 B, see Sect. 6.2 for operator control
The control inputs must be operated in the passive mode.
• Function of the control inputs
OFF switched off EXT. RANGE external range change OUTP. HOLD hold value of outputs OUTP. ZERO set outputs to “MIN.VALUES” TOTAL.RESET reset totalizer(s) ERROR.RESET delete error messages
Connection diagram, see Sect. 2.6: diagram 8
2/4
2.6 Connection diagrams for outputs and inputs
Current output
1
I
active
Ri≤ 500 Ω
Pulse output
3
P
active
for EC
Milliammeter Totalizer
– electronic (EC) – electromechanical (EMC)
DC voltage, external power source (U
ext
note connection polarity External voltage source (U
DC or AC voltage, connection polarity arbitrary
Current output
2
I
passive
U
U
15 V DC
ext
Ri≤ 500 Ω
ext
ext
),
),
Key, N/O contact
Relay for forward/reverse flow measurement (F/R) and/or automatic range change (BA) with 1 or 2 changeover contacts
Please note! This terminal is not provided for hazardous-duty signal converters. There is no passive current
output, see connection diagrams 2 , 3 , 6 and 11 .
Active mode
The current output supplies the power for operation of the inputs and outputs.
Passive mode
External power source required for operation of the inputs and outputs.
Pulse output
4
P
passive
for EC or EMC
Pulse output
5
P
active EC
passive
I
U 15 V DC from current output I 23 mA I 03 mA
6
operation without current output operation with current output
Status output S
active
(connection to B2 and/or B1)
Last
U 15 V DC from current output I 23 mA I 03 mA
operation without current output operation with current output
2/5
U
32 V DC/24 VAC
ext
I 150 mA
Status output
7
S
passive
to B2 and/or B1)
I
U
U
32 V DC/24 V AC
ext
I 150 mA
U
ext
(
connection
Last
ext
U
32 V DC
ext
I 150 mA
Control input
8
C
passive
to B2 and/or B1)
U
32 V DC/24 VAC
ext
I 6 mA
(
connection
I
U
ext
F/R flow measurement
9
I
and P
active
F/R changeover via S
R
U
32 V DC / 24 V AC
ext
I 150 mA
Automatic range change (BA) with F/R flow measurement
10
/ BA changeover via S2
I
active
passive
(B1)
VV
passive
(B2)
R
passive
U
ext
I
I
(B2) / F/R changeover via S1
y type
Rela e.g. Siemens D1
(B1)
passive
BA
V/R
U
ext
I
I
U
32 V DC/24 V AC
ext
I 150 mA
Automatic range change (BA)
11
I
/ BA changeover via S
active
V
RR
high
range
(B2)
active
V
low
range
Relay type e.g. Siemens D1
U 15 V DC I 03 mA
high
range
low
range
Relay type e.g. NAIS-Matsushita
type RH-C or DR-C
2/6
3 Start-up
3.1 Switch-on and measurement
Before powering the system, please check that it has been correctly installed according
to Sect. 1 and 2.
The flowmeter is delivered ready for operational use. All operating data have been factory set in accordance with your specifications.
Please refer to Sect. 3.2 “factory settings”.
Power the unit, and the flowmeter will immediately start process flow
measurement.
Basic version
A light emitting diode (LED) under the cover of the electronic section shows the
measurement status. Remove the cover using the special wrench.
LED flashing . . .
Refer to Sect. 6.2 for operator control of the “basic version”.
Display version, signal converter IFC 090 / D
When powered, the display shows in succession: START UP and READY.
This is followed by display of the current flow rate and/or the current totalizer count on either a continuous or alternating basis, depending on the setting under Fct. 1.04.
Refer to Sect. 4 and 5 for operator control of the “display version”.
, signal converter IFC 090 / B
green: measurement correct, everything all right. green/ red: momentary overdriving of outputs
and/or A/D converter.
red: fatal error, parameter error or hardware fault,
please consult factory.
3/1
Factory settings 3.2
All operating data are factory set according to your order specifications. If you have not made any particular specifications at the time of ordering, the instruments will be
delivered with the standard parameters and functions listed in the Table below. To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow
measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric flow counted independent of the flow direction. On instruments equipped with a display, measured values may possibly be shown with a “ – ” sign.
This factory setting for the current and pulse outputs may possibly lead to measuring errors, particularly in the case of volume flow counting:
for example, if pumps are switched off and a “backflow” occurs which is not within the range of the low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.
To avoid faulty measurements, therefore, it may be necessary to change the factory setting of some or all of the following functions: – low-flow cutoff SMU, Fct. 1.03, Sect. 5.3 – current output I, Fct. 1.05, Sect. 5.6 – pulse output P, Fct. 1.06, Sect. 5.7 – display (option), Fct. 1.04, Sect. 5.4
For special applications, for example “pulsating flow”, see Sect. 6. Instrument o
peration:
Display versions: IFC 090 _/ D, operation: refer to Sect. 4 and 5. Basic versions: IFC 090 _/ B, operation: refer to Sect. 6.2.
Table of standard factory settings
Function Setting
1.01 Full-scale range Q
1.02 Time constant 3 s, for I, S
1.03 Low-flow ON: 1 % cutoff SMU OFF: 2 %
1.04 Display (option) flow rate m totalizer(s) m3 or US Gal
1.05 Current output I function 2 directions range 4 - 20 mA error message 22 mA
1.06 Pulse output B1 function 2 directions pulse value 1 pulse/s pulse width 500 ms
1.07 Status output B2 flow direction
100%
see nameplate
and display
3
/hr or US Gal/min
Function Setting
3.01
Language for display only
3.02 Flowmeter diameter see nameplate flow direction (see arrow on primary head)
3.04 Entry code no
3.05 User unit
3.06 Application steady
3.07 Hardware Terminal B1 pulse output Terminal B2 status output
English
+ direction
}
Liter/hrorUSMGal/day
3/2
Part B IFC 090 _/ D Signal converter
4 Operation of the signal converter
4.1 Krohne operator control concept
1 3 6. 4 9 m3/hr
Measuring mode
CodE 1
Menu column Function column Data column
3.00 INSTALL.
2.00 TEST
When this display appears, press following keys:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
3.07 HARDWARE
3.06 APPLICAT.
3.05 USER UNIT
3.04 ENTRY CODE
3.03 ZERO SET
3.02 FLOWMETER
3.01 LANGUAGE
2.02 HARDW. INFO
2.01 TEST Q
Direction of movement
4/1
1.00 OPERATION
1.07
OUTPUT B2 INPUT B2
1.06
OUTPUT B1 INPUT B1
1.05 CURRENT I
1.04 DISPLAY
1.03 L.F. CUTOFF
1.02 TIMECONST.
1.01 FULL SCALE
see
Sect.
4.4
5
Operating and check elements 4.2
IFC 090 D
1
2
+ –
Totalizer
ΣΣ
I P
Overrange
Operator control by way of ...
... the 3 keys 4 . The keys are
accessible after unscrewing the cover
Flow
rate
6
3
of the electronic section using the special wrench (supplied).
... the 3 magnetic sensors 5 and the
4
supplied bar magnet
without opening the housing.
PLEASE NOTE!
Do not damage the screw thread and the gasket, never allow dirt to accumulate, and make sure they are well greased at all times. Damaged gasket must be replaced immediately!
1
Display, 1st line
2
Display, 2nd line
Display, 3rd line: arrows to identify display
3
Flowrate Totalizer
+ totalizer
current flowrate
totalizer
Overrange
Σ
I overranging, current output I
sum totalizer (+ and –)
P overranging, pulse output P
4
Keys for operator control of signal converter
5
Magnetic sensors to set the converter by means of a handheld bar magnet without opening housing. Function of sensors same as keys .
6
Compass field, signals actuation of a key.
4
4/2
4.3 Function of keys
The cursor (flashing part of display) has a grey background in the following descriptions.
o start operator control
T
Measuring mode
Operator control mode
1 3 . 5 7 1 m 3 / h r
PLEASE NOTE: When “YES” is set under Fct. 3.04 ENTRY CODE, “CodE 1 - - - - - - - - -”
appears in the display after pressing the key. The 9-keystroke Entry Code 1 must now be entered: → → → ↵ ↵ ↵ ↑ ↑ ↑
(each keystroke acknowledged by “
o terminate operator control
T
Press key repeatedly until one of the following menus
Fct. 1.00 OPERATION, Fct. 2.00 TEST or Fct. 3.00 INSTALL. is displayed.
F c t . 3. 0 0
INSTALL.
”).
*
Press key
F c t . 1. 0 0
O P E R AT I O N
S T O R E Y E S
Store new parameters: acknowledge by
pressing key↵ . Measuring mode continued with the new parameters.
New parameters not to be stored:
press key to display
„STORE.NO“.
Measuring mode continued with the „old“
parameters after pressing key
.
4/3
To change numbers
select next number
3 9 7. 3 5
m 3 / h r
To shift cursor (flashing position)
shift to right
3 9 7. 3 5
m 3 / h r
To alter texts (units)
For units, the numerical value is converted automatically.
3. 7 6 9 9
select next text
L i t e r / S e c
To transfer from text (unit) to number setting
Change to number setting
3 9 7. 4 5 m 3 / h r
3 9 7. 3 5
m 3/hr
9 3. 3 6 5
U S. G a l / m i n
1 3. 5 7 1
m 3 / h r
To transfer to subfunction
Subfunctions do not have a “Fct.No.“ and are identified by a “ ”.
1 D I R.
To revert to function display
1 0. 3
Sec
1 3. 5 7 1
m 3/hr
R A N G E I
F c t. 1. 0 2
T IME CONST.
4/4
4.4 Table of settable functions
Abbreviations used
B1/B2 Status output, control input DN Nominal size, meter size F
= 1/2 x pulse width [s]
max
1 kHz, if “AUTO” or “SYM.” is selected
Q actual flowrate Q
100%
Q
max
under subfunction “PULSWIDTH”
F F
F F/R Forward/reverse flow in F/R mode
GK Primary constant I Current output I
0%
I
100%
P Pulse output P P
= 10 pulse/h
min
Conversion factor volume for any unit,
M
see Fct. “FACT. VOL.” Conversion factor time for any unit,
T
see Fct. 3.05 “FACT. Time”
Current at 0% flow Current at 100% flow
= F = F
max min
/ Q
/ Q
100%
100%
max min
Q
min
SMU Low-flow cutoff for I and P v Flow velocity v
max
v
min
Fct. Text Description and settings
1.00 OPERATION Operations menu
1.01 FULL SCALE Full-scale range for flowrate Q
Select unit
m3/hr Liter/Sec US.Gal/min
user unit, factory set is “Liter/hr” or “US MGal/day” (see Fct. 3.05)
Press →key to transfer to number setting.
Setting ranges The ranges are dependent on the meter size (DN) and the flow
π
velocity (v): Q
= DN2x v
min
4
Nom. dia./meter size vmin = 0,3 m/s (1 ft/s) vmax = 12 m/s (40 ft/s)
DN 2.5–1000 /
1
/10”–40”: 0.0053 – 033 900 m3/hr
Press ↵key to return to Fct. FULL SCALE.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
= F
min
/ Q
100% Pmax
min
1.02 TIMECONST. Time constant
Select:
Press ↵key to transfer to number setting.
ALL (applies to display and all outputs)
ONLY I (only display, current and status outputs)
Range: 0.2 – 99.9 Sec
Press ↵key to return to Fct. 1.02 TIMECONST.
1.03 L.F.CUTOFF Low-flow cutoff (SMU)
OFF (fixed values: ON = 0.1% / OFF = 0.2%)
PERCENT (variable values) ON OFF
Press →key to transfer to number setting.
Note: Cutoff “off” value must be greater than cutoff “on” value.
Press ↵key to return to Fct. 1.03 L.F. CUTOFF.
100% flow = full scale range
π
= DN2x v
4
at v
max
π
= DN2x v
4
at v
min
Max. flow velocity (12 m/s / 40 ft/s) at Q Min. flow velocity (0.3 m/s / 1 ft/s) at Q
100%
minQmax
/ max. full-scale range (Q
max
= 12 m/s / 40 ft/s
/ min. full-scale range (Q
min
= 0.3 m/s / 1 ft/s
π
= DN2x v
4
100%
100%
100%
100%
max
0.0237 – 152 000 US.Gal/min ) has been changed.
= F
max
/ Q
Check new values!
100%
1 – 19% 2 – 20%
)
)
4/5
Loading...
+ 55 hidden pages