KROHNE IFC-010 User Manual

04/98
Signal converters
Installation and operating intructions
for electromagnetic flowmeters
IFC 010 K IFC 010 F
How to use these Instructions
instructions inside the packing of the primary head.
- Installation location and connection to power (Section 1) Pages 1/1-1/6
- Electrical connection of outputs and inputs (Section 2) Pages 2/1-2/6
- Factory settings and start-up (Section 3) Pages 3/1-3/2
- Operator control of the signal converter is described in Sections 4 and 5.
Power the flowmeter. THAT’S ALL. The system is operative.
16-page pull-out condensed instructions
are located in the centrefold of these Installation and Operation Instructions.
Contents:
Installation (Sect. 1), electrical connection (Sect. 1 + 2), start-up (Sect. 3) and operator control of the signal converter (Sect. 4)
Applicable to Software Versions
IFC 010 _/ D Display version No. 806325.07 and No. 317551.02 and higher
IFC 010 _/ B Basic version operator-controllable with HHT 010 No. 806323.06 and higher
3.1M61EA4 049821 Order No. 7.02140.34.00 US size: 7.02140.74.00
Contents
Versions IFC 010 signal converter 0/3 Items included with supply 0/3 Software history 0/3 System description 0/4 Product liability and warranty 0/4 CE / EMC / Standards / Approvals 0/4
Part A System installation and start-up 1/1-3/2 1 Electrical connection: power supply 1/1-1/6
1.1 Important installation notes – PLEASE NOTE ! 1/1
1.1.1 Location 1/1
1.1.2 Only for separate systems/signal converters (F versions) 1/1
1.1.3 Cable entries 1/1
1.2 Connection to power 1/2
1.3 Electrical connection of separate primary head (F Version) 1/3-1/6
1.3.1 General information on signal cable A and field current cable C 1/3
1.3.2 Grounding of primary head 1/3
1.3.3 Stripping (preparation) of signal converter 1/4
1.3.4 Cable length (max. distance between signal converter and primary head) 1/5
1.3.5 Connection diagrams I and II (power supply, converter and primary head) 1/6
2
2.1 Current output I 2/1
2.2 Pulse output P and status output S 2/1
2.3 Connection diagrams for outputs and inputs 2/2
Electrical connection of outputs 2/1-2/2
3.
3.1 Power-on and measurement 3/1
3.2 Factory settings 3/2
Part B IFC 010
4 Operation of the signal converter 4/1-4/10
4.1 Krohne operator control concept 4/1
4.2 Operating and check elements 4/2
4.3 Function of keys 4/3-4/4
4.4 Table of settable functions 4/5-4/9
4.5 Error messages in measuring mode 4/9
4.6 Reset totalizer and cancel error messages, RESET/QUIT menu 4/10
4.7 Examples of setting the signal converter 4/10
5
5.1 Full-scale range Q100% 5/1
5.2 Time constant 5/1
5.3 Low-flow cutoff 5/2
5.4 Display 5/2-5/3
5.5 Internal electronic totalizer 5/3
5.6 Current output I 5/4
5.7 Pulse output P 5/5-5/6
5.8 Status output S 5/7
5.9 Language 5/8
5.10 Entry code 5/8
5.11 Primary head 5/9
5.12 User-defined unit 5/10
5.13 F/R mode, forward/reverse flow measurement 5/11
5.14 Characteristic of outputs 5/11
5.15 Applications 5/12
5.16 Setting data 5/12
Start-up 3/1-3/2
/D Signal converter 4/1-5/14
Description of functions 5/1-5/12
0/1
Part C Special applications, functional checks, service, and order numbers 6/1-9/1 6 Special applications 6/1-6/2
6.1
HHT 010 hand held terminal and RS 232 adapter incl. CONFIG software (options)
6/1
6.2 Stable signal outputs when measuring tube empty 6/2
7
Functional checks 7/1-7/11
7.1 Zero check with IFC 010 /D, signal converter, Fct. 3.03 7/1
7.2 Test of measuring range Q, Fct. 2.01 7/1
7.3 Hardware information and error status, Fct. 2.02 7/2
7.4 Faults and symptoms during start-up and process flow measurement 7/3-7/6
7.5 Test of primary head 7/7
7.6 Test of signal converter 7/8
7.7 Test of signal converter using GS 8A simulator (option) 7/9-7/11
8
Service 8/1-8/6
8.1 Cleaning the signal converter housing 8/1
8.2 Replacement of power fuse(s) 8/1
8.3 Changeover of operating voltage on AC Versions 1, 2 and 3 (not DC Version) 8/2
8.4 Replacement of electronic unit of signal converter 8/2
8.5 Illustrations to Sect. 8.2 to 8.7 8/3
8.6 Turning the display PCB 8/4
8.7 Retrofitting the display unit 8/4
8.8 IFC 080 and SC 80 AS Replacement of electronic unit by IFC 010 8/4
8.9 Illustrations of the PCBs 8/6
9
Order numbers 9/1
Part D Technical data, measuring principle and block diagram 10/1-12/1 10 Technical data 10/1-10/5
10.1 Full-scale range Q
100%
10/1
10.2 Error limits at reference conditions 10/2
10.3 IFC 010 Signal converter 10/3-10/4
10.4 IFC 010 F and ZD dimensions and weights 10/4
10.5 Instrument name plates 10/5
1
1 Measuring principle and function of the system 11/1
12 Block diagram - signal converter 12/1
Part E Index E1-E2
Printed form to accompany flowmeters returned to Krohne E3
0/2
Versions IFC 010 signal converter
IFC 010_ / B Basic version (standard)
without local display and control elements.
All operating data factory-set to your order specifications. Optionally available for operator control:
- RS 232 adapter, incl. software for DOS-PC or
- HHT hand-held terminal
IFC 010_ / D Display version (option)
with local display and control elements.
All operating data factory-set to your order specifications.
IFC 010 K / _ Compact flowmeter
signal converter mounted direct on primary head.
IFC 010 F / _ Signal converter in field housing,
electrical connection to primary head via field power and signal cables.
Items included with supply
• Signal converter in the version as ordered, see above.
• These installation and operating instructions for the signal converter, including 16-page pull-out condensed instructions for installation, electrical connection, start-up and operator control of the signal converter.
• 2 plug connectors for connection of power supply and outputs/inputs
• for separate system version only signal cable in the version and length as ordered (standard: signal cable A, length 10 m / 30 ft)
Software history
Display & control unit Hand-held HHT 010 CONFIG user software IFC 010 _ / D IFC 010 _ / B** IMoCom RS 485
Software Status Software Status Software Software
806325.07* current 806328.06 current
replaces
317551.02* 806325.07 806328.06 current
813269.00*** current Czech user interface ***
813340.00*** current Swedish user interface ***
* At least the same setting ranges and functional scope as preceding versions.
Also, customer- and application-specific add-on equipment possible, which has to be installed and activated by the factory. Documented by enclosures to these Installation and Operating Instructions.
** Please note: Connect HHT 010 only to devices without display and operator
control software.
*** Does not contain the functional scope of the currently valid standard version;
this has been taken into account in the documentation of the respective national language.
, F Version:
V 2.00 V 3.15 and higher and higher
0/3
System description
Electromagnetic flowmeters with the IFC 010 signal converter are precision instruments designed for linear flow measurement of liquid products.
The process liquids must be electrically conductive: 5 µS/cm (for cold demineralized water 20 µS/cm).
The full-scale range Q DN 2.5.- 1000 / 01/10” - 40” Q
can be set as a function of the meter size:
100%
= 0.010 - 34 000 m3/hr = 0.03 - 151 000 US Gal/min
100%
This is equivalent to a flow velocity of 0.3 - 12 m/s or 1 - 40 ft/s.
Product liability and warranty
The electromagnetic flowmeters with the IFC 010 signal converter are designed solely for measuring the volumetric flowrate of electrically conductive, liquid process products.
These flowmeters are not certified for use in hazardous areas. Other flowmeter series are available for such applications.
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests solely with the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty. In addition, the “General conditions of sale” forming the basis of the purchase contract are
applicable. If flowmeters need to be returned to Krohne, please note the information given on the last-but-one
page of these Instructions. Krohne regrets that it cannot repair or check your flowmeter(s) unless accompanied by the completed form sheet.
CE / EMC / Standards / Approvals
• Electromagnetic flowmeters with the IFC 010 signal converter meet the protection requirements of Directive 89/336/EEC in conjunction with EN 50081-1 (1992) and EN 50082-2 (1995), as well as Directives 73/23/EEC and 93/68/EEC in conjunction with EN 61010-1, and bear the
CE marking.
0/4
Part A System installation and start-up
1 Electrical connection: power supply
1.1 Important installation notes PLEASE NOTE !
1.1.1 Location
Electrical connection in accordance with VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V” or equivalent national regulations.
Do not cross or loop cables inside the terminal compartment.
Use separate cable entries (see below) for power supply, field current cables, signal lines,
outputs and inputs.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunlight. Fit a sunshade if necessary.
When installed in switchgear cabinets, signal converters must be adequately cooled, e.g. use fans or heat exchangers.
Do not expose signal converters to intense vibration.
1.1.2 Onl
Keep distance between primary head and signal converter as short as possible.
Refer to Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied Krohne signal cable A (Type DS), standard length 10 m (33 ft).
Always calibrate primary head and signal converter together. Therefore, when installing,
ensure primary constant GKL is identical; refer to instrument nameplate for the primary head. If the GKL is not identical, set the signal converter to the GKL of the primary head. Refer also to Sections 4.
Dimensions of signal converter; refer to Section 10.4.
1.1.3 Cable entries
Number of cable entries: 2 for the compact flowmeters
y for separate systems/signal converters (F versions)
4 for the IFC 010 F signal converter
NOTE: Ensure gaskets are fitted correctly and maintain
the following max. torques! 1 Max. torques for PG 13.5,
1/2“ NPT or 1/2“ PF adapters: 4 Nm / 2.8 ft
2 Max. torques for PG 13.5 only: 3 Nm / 2.1 ft
x
lbf
x
lbf
1
3
2
3 Gasket
A) PG 13.5 cable entries
These cable entries may only be used for flexible electrical cables if the relevant electrical regulations so allow, e.g. National Electric Code (NEC). Do not fix rigid metal conduits (IMC) or flexible plastic conduits to the PG 13.5 cable entries, refer to “Point B, C” below (1/2” NPT or PF adapters).
B) 1/2“ NPT adapters C) 1/2“ PF adapters
For most North American systems the regulations require that electrical conductors be laid in conduits, particularly where power voltages > 100 V AC are concerned. In such cases, use the 1/2” NPT or 1/2” PF adapters to which flexible plastic conduits can be screwed. Do not use rigid metal conduits (IMC)! Lay conduits such that no moisture can penetrate into the converter housing. Should there be risk of any condensation water forming, fill the cross-section of the conduit around the cables at these adapters with a suitable sealing compound.
1/1
PLEASE NOTE !
Connection to power 1.2
Rated values:
The flowmeter housings protecting the electronic equipment from dust and moisture must always be kept closed. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage classes III and II, respectively.
Safet
y isolation: the flowmeters (signal converters) must be provided with an
isolating facility.
1. AC V
ersion 2. AC Version
230/240 V AC (200 - 260 V AC) 200 V AC (170 - 220 V AC)
switch-selectable to switch-selectable to
115/120 V AC (100 - 130 V AC) 100 V AC (85 - 110 V AC)
Note information on instrument nameplate: supply voltage and frequency
The PE protective ground conductor for the power supply must be connected to the
separate U-clamp terminal in the terminal compartment of the signal converter. For exceptions (compact systems), refer to installation instructions for the primary head.
Connection diagrams I and II for electrical connection between primary head and signal converter: refer to Section 1.3.5.
3. AC V
ersion DC Version
48 V AC (41 - 53 V AC) 24 V DC (11-32 V DC)
switch-selectable to
24 V AC (20 - 26 V AC)
Note information on instrument nameplate: supply voltage and frequency.
For measurement reasons, connect an FE functional ground conductor to the separate
U-clamp terminal in the terminal compartment of the signal converter.
If connected to a functional extra-low voltage source (24 V AC / DC, 48 V AC), provide for protective separation (PELV) in conformity with VDE 0100 / VDE 0106 or IEC 364 / IEC 536, or equivalent national regulations.
Connection diagrams I and II for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.5.
Connection to power
Power fuse F1
(see Sect. 8.2)
AC: 100 – 240 V AC: 24 / 48 V DC: 24 V
Power
LN
1L 0L
L+ L–
for
internal
use only
U-clamp terminal
PE protective conductor FE
functional ground
}
FE
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
1/2
1.3 Electrical connection of separate primary head (F Versions)
1.3.1 General information on signal cable A and field current cable C
Use of the Krohne signal cable A with foil screen and magnetic shield will ensure proper operation of the equipment.
• Signal cable to be solidly laid.
• Connect shields via stranded drain wires.
• Underwater and underground installation possible.
• Insulating material is flame-retardant to IEC IEC 332.1 / VDE 0742.
• Signal cables are low in halogen, unplasticized, and stay flexible at low temperatures.
Si
gnal cable A (Type DS), with double shielding
2
1 Stranded drain wire, 1st shield, 1.5 mm 2 Insulation 3 Conductor 0.5 mm
2
or AWG 20 (3.1 red / 3.2 white)
or AWG14
4 Special foil, 1st shield 5 Inner sheath 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm
2
or AWG20
8 Outer sheath
Field current cable C
with single shielding
Cross-section is dependent on required length of cable, see Table in Sect. 1.3.4.
1.3.2 Grounding of primary head
All flowmeters must be properly grounded.
• The grounding conductor should not transmit any interference voltages.
• Do not ground any other electrical device together with this conductor.
• The primary head is connected to ground by means of an FE functional ground conductor.
• Special information on grounding various primary heads is contained in the separate
installation instructions for primary heads.
• These instructions also contain detailed descriptions on how to use grounding rings and how to install primary heads in metal or plastic pipes or internally coated pipelines.
1/3
Stripping (preparation) of signal cable A 1.3.3
Please note the different lengths given in the table for signal converter and primary head.
Length Converter Primary
head
mm (inch) mm (inch)
a 55 (2.17) 90 (3.60) b 10 (0.39) 8 (0.30) c 15 (0.59) 25 (1.00) d 8 (0.30) 8 (0.30)
Preparation for connection to primary head
Customer-supplied materials W X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
Insulation tubing (PVC), Ø 2.0 - 2.5 mm (dia. 1”)
Signal cable A bending radius 50 mm (2“)
Preparation for connection to IFC 010 F signal converter
Signal cable A bending radius 50 mm (2“)
External shielding of signal cable A (Type DS)
Wrap stranded drain wire (7) around the mu-metal foil (6) and clamp under the shield terminal in the signal converter terminal box (see also diagram in Sect. 1.3.5).
Cable routing in signal converter housing
see illustration in Sect. 10.4.
1/4
1.3.4 Cable lengths (max. distance between signal converter and primary head)
Abbreviations and ex
planatory notes
used in the following tables, diagrams and connection diagrams
A Signal cable A (type DS), with double shielding, see diagram for max. length C Field current cable C, with single shielding,
type and length see Table
2
D High-temperature silicone cable, 3 × 1.5 mm
(14 AWG) Cu, with single shielding,
max. length 5 m (16 ft)
2
E High-temperature silicone cable, 2 × 1.5 mm
(14 AWG) Cu, max. length 5 m (16 ft)
L Cable length
κκ
Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
Recommended len
gth of signal cable
for magnetic field frequency 1/6 × power frequency
Primary head
ECOFLUX IFS 1000 F
AQUAFLUX F ALTOFLUX IFS 4000 F
PROFIFLUX IFS 5000 F
VARIFLUX IFS 6000 F
Meter size
DN mm
010.0 - 0015
025.5 - 0150
010.0 - 1000
010.0 - 0150
200.0 - 1000
002.5 - 0015
025.0 - 0100
010.5 - 0015
025.5 - 0080
Nennweite
inch
3
/8- 1/
2
1 - 06
3
/8- 40
3
/8- 06
8 - 40
1
/10-1/
2
1 - 04
1
/80- 1/
2
1- 03
Signal cable
A4 A3 A1 A2 A1 A4 A2 A4 A2
Field current cable C: max. length and min. cross-section Length Type of cable,single shielding
0 - 150 m 5 - 500 ft 2 × 0.75 mm2Cu / 2 × 18 AWG
150 - 300 m 500 - 1000 ft 2 × 1.50 mm2Cu / 2 × 14 AWG
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
1/5
Connection diagrams I and II (power supply, converter and primary head) 1.3.5
Im
portant information PLEASE NOTE !
The figures in brackets indicate the stranded drain wires for the shields,
see cross-sectional drawing of signal cable in Section 1.3.1.
• Electrical connection to VDE 0100 ”Regulations governing heavy-current installations with line voltages up to 1000 V“ or equivalent national regulations.
• Power supply 24 V AC / DC: functional extra-low voltage with protective separation in
conformity with VDE 0100, Part 410 or equivalent national regulations.
•PE= protective conductor FE = functional ground conductor
Process temperature < 150°C (302°F) Process temperature > 150°C (302°F)
I II
IFC 010 F IFC 010 F
Primary heads
Connection of shields at the IFC 010
1 Signal cable A
(Type DS)
2 Shield terminal
2
6
1
4
6
3
for shielded signal cable
3 Field power cable
5
4 Shield terminal
for shielded field power cable
5 Housing wall,
signal converter
6 Cable entries
Primary heads
1/6
2 Electrical connection of outputs
2.1 Current output I
The current output is galvanically isolated from all input and output circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
Typical current output
I+ approx. 15 V DC positive
voltage of current output
I current sink
chassis ground, current output
I
All operating data and functions can be set.
Display version: IFC 010 D, see Sect. 4 and 5.6, Fct. 1.05 for operator control Basic version: IFC 010 B, see Sect. 6.1 for operator control
The current output can also be used as an internal voltage source for the outputs.
= 15 V DC I = 23 mA when operated without receiver instruments at the current output
U
int
I = 3 mA when operated with receiver instruments at the current output
Connection diagrams,
see Sect. 2.3: diagrams 1 2 4 6
2.2 Pulse output P and status output S
The pulse and status outputs are galvanically isolated from the current output and all input circuits.
Factory-set data and functions can be noted down in Sect. 5.16.
Please also refer to Sect. 3.2 “Factory settings”.
• Typical pulse and status outputs B1
S status output
P⊥chassis ground
P pulse output
• All operating data and functions can be set:
Display version: IFC 010 D, see Sect. 4 and 5.7, Fct. 1.06 for operator control Basic version: IFC 010 B, see Sect. 6.1 for operator control
• The pulse and status outputs can be operated in the active or passive mode.
Active mode: The current output is the internal voltage source,
connection of electronic totalizers (EC)
Passive mode: External DC or AC voltage source required, connection of electronic (EC)
or electromechanical (EMC) totalizers
• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or
cycle counters are connected, allow for minimum counting interval: gate time, counter
1000
P
100% [ Hz]
Connection diagrams see Sect. 2.3: diagrams - pulse output 3 4
diagrams - status output 5 6
2/1
Connection diagrams for outputs 2.3
Milliammeter Totalizer
– electronic (EC) – electromechanical (EMC)
Stromausgang
1 2
I
active
U
15 V DC
ext
I = 0/4 - 20 mA Ri≤ 500
Pulse output P
3 4
for electronic (EC) or electromechanical (EMC) totalizers
Stromausgang I
passive
U
ext
I = 0/4 - 20 mA
15...20V DC 20...32 VDC
U
ext
Ri0...500 250...750
passive
DC voltage, external power source (U
ext
),
note connection polarity External voltage source (U
ext
), DC or AC voltage, connection polarity arbitrary
Active mode
The current output supplies the power for operation of the outputs.
Passive mode
External power source required for operation of the outputs.
Pulse output P
for electronic (EC) totalizers
with and without current output I
active (and current output I
active
)
U
I
max
U
32V DC/24 VAC
ext
I
150 mA
max
(incl. status output)
5
Status output S
Load
ext
passive
U I
(incl. pulse output)
32V DC/24 VAC
ext
150 mA
max
U
15V DC from current output
int
Operation with current output: I
3 mA
max
Operation without current output: I
23 mA
max
15 V
R
I
max
Status output S
6
with and without current output I
active
Load
U
15V DC
int
from current output
I
3 mA
max
Operation with current output
I
23 mA
max
Operation without current output
2/2
3 Start-up
3.1 Power-on and measurement
Before powering the system, please check that it has been correctly installed according
to Sect. 1 and 2.
The flowmeter is delivered ready for operational use. All operating data have been factory set in accordance with your specifications.
Please refer to Sect. 3.2 “factory settings”.
Power the unit, and the flowmeter will immediately start process flow
measurement.
Basic version
A light emitting diode (LED) under the cover of the electronic section shows the
measurement status.
LED flashing . . .
Refer to Sect. 6.1 for operator control of the “basic version”.
play version, signal converter IFC 010 / D
Dis
When powered, the display shows in succession: START UP and READY.
This is followed by display of the current flow rate and/or the current totalizer count on either a continuous or alternating basis, depending on the setting under Fct. 1.04.
Refer to Sect. 4 and 5 for operator control of the “display version”.
, signal converter IFC 010 / B
green: measurement correct, everything all right. green/red: momentary overdriving of outputs
and/or A/D converter.
red: fatal error, parameter error or hardware fault,
please consult factory.
3/1
Factory settings 3.2
All operating data are factory set according to your order specifications. If you have not made any particular specifications at the time of ordering, the instruments will be
delivered with the standard parameters and functions listed in the Table below. To facilitate easy and rapid initial start-up, current output and pulse output are set to process flow
measurement in “2 flow directions”, so that the current flowrate is displayed and the volumetric flow counted independent of the flow direction. On instruments equipped with a display, measured values may possibly be shown with a “ – ” sign.
This factory setting for the current and pulse outputs may possibly lead to measuring errors, particularly in the case of volume flow counting:
for example, if pumps are switched off and a “backflow” occurs which is not within the range of the low-flow cutoff (SMU), or if separate displays and counts are required for both flow directions.
To avoid faulty measurements, therefore, it may be necessary to change the factory setting of some or all of the following functions: – low-flow cutoff SMU, Fct. 1.03, Sect. 5.3 – current output I, Fct. 1.05, Sect. 5.6 – pulse output P, Fct. 1.06, Sect. 5.7 – display (option), Fct. 1.04, Sect. 5.4
Instrument o
peration:
Display versions: IFC 010 _/ D, operation: refer to Sect. 4 and 5. Basic versions: IFC 010 _/ B, operation: refer to Sect. 6.1.
Standard factory settings
Function Setting
1.01 Full-scale range Q
1.02 Time constant 3 s, for I, S
1.03 Low-flow ON: 1 % cutoff SMU OFF: 2 %
1.04 Display (option) flow rate m totalizer(s) m3 or US Gal
1.05 Current output I function 2 directions range 4 - 20 mA error message 22 mA
1.06 Pulse output P function 2 directions pulse value 1 pulse/s pulse width 50 ms
1.07 Status output P flow direction
100%
see nameplate
and display
3
/hr or US Gal/min
Function Setting
3.01
Language for display only
3.02 Flowmeter diameter see nameplate flow direction (see arrow on primary head)
3.04 Entry code no
3.05 User unit
English
+ direction
}
Liter/hrorUSMGal/day
3/2
Teil B IFC 010 _/ D Signal converter
4 Operation of the signal converter
4.1 Krohne operator control concept
1 3 6. 4 9
m3/hr
Measuring mode
CodE 1
Menu column Function column Data column
3.00 INSTALL.
When this display appears, press following keys:
→ → → ↵ ↵ ↵ ↑ ↑ ↑
3.05 USER UNIT
3.04 ENTRY CODE
3.03 ZERO SET
3.02 FLOWMETER
3.01 LANGUAGE
2.02 HARDW. INFO
Direction of movement
4/1
2.00 TEST
1.00 OPERATION
2.01 TEST Q
1.07 IND. OUTP. S
1.06 PULS. OUTP. P
1.05 CUR. OUTP. I
1.04 DISPLAY
1.03 L.F. CUTOFF
1.02 TIMECONST.
1.01 FULL SCALE
see
Sect.
4.4
Operating and check elements 4.2
The controls are accessible after unscrewing the 4 screws and removing the housing cover.
Display, 1st line
Display, 2nd line
Display, 3rd line: arrows to identify display
Flowrate Totalizer
Overrange
+ totalizer – totalizer Σ sum totalizer (+ and –)
I overranging, current output I P overranging, pulse output P
current flowrate
Keys for operator control of signal converter
Compass field, signals actuation of a key.
4/2
4.3 Function of keys
The cursor (flashing part of display) has a grey background in the following descriptions.
o start operator control
T
Measuring mode
Operator control mode
1 3 . 5 7 1 m 3 / h r
PLEASE NOTE: When “YES” is set under Fct. 3.04 ENTRY CODE, “CodE 1 - - - - - - - - -”
appears in the display after pressing the key. The 9-keystroke Entry Code 1 must now be entered: → → → ↵ ↵ ↵ ↑ ↑ ↑
(each keystroke acknowledged by “
o terminate operator control
T
Press key repeatedly until one of the following menus
Fct. 1.00 OPERATION, Fct. 2.00 TEST or Fct. 3.00 INSTALL. is displayed.
F c t . 3. 0 0
INSTALL.
”).
*
Press key
F c t . 1. 0 0
O P E R AT I O N
S T O R E Y E S
Store new parameters: acknowledge by
pressing key↵ . Measuring mode continued with the new parameters.
New parameters not to be stored:
press key to display
„STORE.NO“.
Measuring mode continued with the „old“
parameters after pressing key
.
4/3
To change numbers
increase number
3 9 7. 3 5
m 3 / h r
decrease number
To shift cursor (flashing position)
shift to right
3 9 7. 3 5
m 3 / h r
shift to left
To alter texts (units)
For units, the numerical value is converted automatically.
3. 7 6 9 9
select next text
L i t e r / S e c
select preceding text
To transfer from text (unit) to number setting
Change to number setting
3 9 7. 4 5
m 3 / h r
3 9 7. 3 5
m 3/hr
9 3. 3 6 5
U S. G a l / m i n
1 3. 5 7 1
m 3 / h r
Return to text setting
To transfer to subfunction
Subfunctions do not have a “Fct.No.“ and are identified by a “ ”.
1 D I R.
To revert to function display
1 0. 3
Sec
1 3. 5 7 1
m 3/hr
R A N G E I
F c t. 1. 02
T I M E C O N S T.
4/4
4.4 Table of settable functions
Abbreviations used
DN Nominal size, meter size F F F
F F/R Forward/reverse flow in F/R mode
GKL Primary constant I Current output P Pulse output P P
Highest frequency of the pulse output
max
Lowest frequency of the pulse output
min
Conversion factor volume for any unit,
M
see Fct. “FACT. VOL.” Conversion factor time for any unit,
T
see Fct. 3.05 “FACT. Time”
= F = F
max min
/ Q
/ Q
100%
100%
max min
Q actual flowrate Q
100%
Q
max
Q
min
S Status output, control input SMU Low-flow cutoff for I and P v Flow velocity v
max
v
min
Fct. Text Description and settings
1.00 OPERATION Operations menu
1.01 FULL SCALE Full-scale range for flowrate Q
Select unit
m3/hr Liter/Sec US.Gal/min
user unit, factory set is “Liter/hr” or “US MGal/day” (see Fct. 3.05)
Press →key to transfer to number setting.
Setting ranges The ranges are dependent on the meter size (DN) and the flow
π
velocity (v): Q
= DN2x v
min
4
Nom. dia./meter size vmin = 0,3 m/s (1 ft/s) vmax = 12 m/s(40 ft/s)
DN 2.5–1000 /
1
/10”–40”: 0.0053 – 033 900 m3/hr
Press ↵key to return to Fct. FULL SCALE.
VALUE P Pulse value (Fct. 1.06
“VALUE P”
With the “old” pulse values the output frequency (F) would have been exceeded or not reached.
P
= F
min
/ Q
100% Pmax
min
1.02 TIMECONST. Time constant
Select:
Press ↵key to transfer to number setting.
ALL (applies to display and all outputs)
ONLY I+S (only display, current and status outputs)
Range: 0.2 – 99.9 Sec
Press ↵key to return to Fct. 1.02 TIMECONST.
1.03 L.F.CUTOFF Low-flow cutoff (SMU)
OFF (fixed trip points: ON = 0.1% / OFF = 0.2%
for 100 and 1000 Hz, see Fct. 1.06, 1% or 2%)
PERCENT (variable values) ON OFF
Press →key to transfer to number setting.
Note: Cutoff “off” value must be greater than cutoff “on” value.
Press ↵key to return to Fct. 1.03 L.F. CUTOFF.
100% flow = full scale range
π
= DN2x v
4
at v
max
π
= DN2x v
4
at v
min
Max. flow velocity (12 m/s / 40 ft/s) at Q Min. flow velocity (0.3 m/s / 1 ft/s) at Q
100%
minQmax
/ max. full-scale range (Q
max
= 12 m/s / 40 ft/s
/ min. full-scale range (Q
min
= 0.3 m/s / 1 ft/s
π
= DN2x v
4
100%
100%
100%
100%
max
0.0237 – 152 000 US.Gal/min ) has been changed.
= F
max
/ Q
Check new values!
100%
1 – 19% 2 – 20%
)
)
4/5
Fct. Text Description and settings
1.04 DISPLAY Display functions
DISP.FLOW Select flow display
DISP.TOTAL. Select totalizer display
DISP.MSG. Additional messages required in measuring mode?
1.05 CURRENT I Current output I
FUNCT. I Select function for current output I
NO DISP.
m3/hr PERCENT
Liter/Sec BARGRAPH (value and bargraph display in %)
US.Gal/min
Press ↵key to transfer to subfunction “DISP. TOTAL.”.
NO DISP. (totalizer switched on but not displayed)
OFF (totalizer switched off)
• +TOTAL. • –TOTAL. • +/–TOTAL. • SUM (Σ)
• ALL (displaysingle counts or all)
m3 Liter US.Gal
user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).
Press →key to transfer to format setting.
Format setting
• Auto (exponent notation)
# . ####### ##### . ###
## . ###### ###### . ##
### . ##### ####### . #
#### . #### ########
Press ↵key to transfer to subfunction “DISP.MSG”.
NO YES (cyclic change with displays of measured values)
Press ↵key to return to Fct. 1.04 DISPLAY.
OFF (switched off)
1 DIR. (1 flow direction)
2 DIR. (forward/reverse flow, F/R flow measurement)
user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
Press key ↵, transfer to subfunction if
“2 DIR.”
RANGE I Select measuring range
0 - 20 mA 4 - 20 mA (fixed ranges)
selected, transfer to subfunction
Press key ↵ to transfer to subfunction
I ERROR Select error value
0 mA 3.6 mA (only with range 4-20 mA) 22 mA
Press key ↵to revert to
“RANGE I”;
“REV.RANGE”!
“I ERROR“.
Fct. 1.05 CURRENT. I.
4/6
Loading...
+ 46 hidden pages