PROXIMITY SENSORS
EZ Series
INSTRUCTION MANUAL
96M0211
Specifications
Type Shield type
Model EZ-8M EZ-12M EZ-18M EZ-30M EZ-18T
Appearance M8
Detecting distance
1.5mm±10% 2.5mm±10% 5.0mm±10% 10.0mm±10% 5.0mm±10%
Supply voltage* DC 12 to 24V±10%, Ripple (p-p): 10% max.
Current consumption
Control output
NPN open-collector 100mA max. (40V max.) Residual voltage: 1V max.
Output mode N.O./N.C.
Response frequency
800Hz 600Hz 350Hz 250Hz 350Hz
Target All metals (See Characteristics for nonferrous materials.)
Standard target
(iron, t=1mm)
10×10mm 12×12mm 18×18mm 30×30mm 18×18mm
Hysteresis 10% max. of detecting distance
Temperature fluctuation
Ambient
temperature
±10% max. of detecting distance at 23°C (73.4°F), within 25° to 80°C (–13 to 176°F)
Ralative humidity 35 to 95%, No condensation
Degree of protection
Vibration
10 to 55 Hz 1.5mm double amplitude (in X, Y, and Z directions, respectively for 2 hours)
Housing material SUS303 Nickel-plated brass
Cord length 2 m
Weight
(g approx.)**
* If ripple takes place, use the sensor within a voltage range of DC 12 to 24V.
** The weights of the cord and nut are included.
50 65 130 235 55
M12 M18 M30 20×32×8mm
13mA max.
–25 to +80°C (–13 to 176°F), No freezing
IEC IP67, NEMA type 6 (waterproof)
Aluminum die-cast
Connections Diagram
Color of output lines
Brown
To drive
current load
To drive
voltage load
Black or White
Blue
Brown
Black or White
Blue
Output circuits
Brown
Load
Main circuit
Black
(Output 1)
White
Blue
Load
(Output 2)
Dimensions
EZ-8M EZ-12M
M8, P=1
Toothed washer
Across-flats: 12 t= 3
17 7 12
0.67" 0.26"0.47"
36
1.42"
EZ-30M EZ-18T
30 7 14
51
2.01"
Operation indicator
φ4, 4-core x 0.15 mm
φ0.17"
Cable length: 2 m
M30, P=1.5
Toothed washer
Across-flats: 36 t= 5
Operation indicator
φ0.25"
0.26"1.18" 0.55"
0.47" t= 0.12"
6.6'
1.42" t= 0.20"
φ
6, 4-core x 0.3 mm
Cable length: 2 m
M12, P=1
Toothed washer
Across-flats:17 t=4
Operation indicator
2
6.6'
20 7 12
0.26"0.79" 0.47"
39
1.54"
1.26"
0.06"
φ0.17"
0.35"
32
0.79"
1.5
2
Load
4.7kΩ
12 to
24 VDC
0.67" t=0.16"
φ
4, 4-core x 0.15 mm
Cable length: 2 m
9
20
Operation
indicator
2-φ3.3
mounting hole
13 5
0.51"
20
0.79"
DC12 to 24V
0V
DC12 to 24V
Voltage output
0V
2
6.6'
φ
0.13"
Black (output1) White (output2)
N.O. N.C.
Low level
(at detection)
EZ-18M
M18, P=1
Toothed washer
Across-flats: 24 t=4
Operation indicator
φ
6, 4-core x 0.3 mm
φ0.25"
Cable length: 2 m
20 7 14
0.26"0.55"0.79"
41
1.61"
φ
0.17"
φ4, 4-core x 0.15 mm
Cable length: 2 m
0.20"
8
0.31"
High level
(at detection)
0.94" t= 0.16"
2
6.6'
2
6.6'
Hints on Correct Use
Warn ing
Clamping torque
• Be sure to use the supplied toothed lock
washer when mounting the sensor.
• Do not tighten the sensor’s mounting
screw with a clamping torque higher than
the following values.
Torque
Model
EZ-8M
EZ-12M
EZ-18M
EZ-30M
Wiring
• Separate the wirings of the sensor cable
from power lines and high-tension lines;
Otherwise, the sensor may be caused to
malfunction by noise.
• To extend the wiring, use a cable whose
diameter is almost the same as that of
the sensor cord.
WARRANTIES AND DISCLAIMERS: KEYENCE, at its sole option, will refund, repair or replace at no
charge any defective Products within 1 year from the date of shipment. Unless stated otherwise herein, the
Products should not be used internally in humans, for human transportation, as safety devices or fail-safe
systems. EXCEPT FOR THE FOREGOING, ALL EXPRESS, IMPLIED AND STATUTORY WARRANTIES,
INCLUDING WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND
NONINFRINGEMENT OF PROPRIETARY RIGHTS, ARE EXPRESSLY DISCLAIMED. KEYENCE SHALL
NOT BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL OR OTHER
DAMAGES, EVEN IF DAMAGES RESULT FROM THE USE OF THE PRODUCTS IN ACCORDANCE
WITH ANY SUGGESTIONS OR INFORMATION PROVIDED BY KEYENCE. In some jurisdictions, some
of the foregoing warranty disclaimers or damage limitations may not apply.
E 1110-2
Do not use this product for
the purpose of protecting the
human body.
AB
Dimension A
10.0
At A
(Nm)
3
6
15
50
2008
At B
(Nm)
100
(mm)
3.0
6.0
6.0
0211E 1021-17 96M0211
10
20
Mutual interference
To install plural proximity sensors of the
same model face to face or side by side,
provide the minimum distance indicated in
this table between the sensors.
Screw-mounted type
Face-to-face
Distance
installation (mm)
Model
EZ-8M
EZ-12M
EZ-18M
5
EZ-30M
20
30
40
100
Flat type
Face-to-face
Distance
installation (mm)
Model
EZ-18T
40 35
Side-by side
installation (mm)
23
32
48
100
Side-by side
installation (mm)