Read this manual before using the product in order to
achieve maximum performance.
Keep this manual in a safe place for future reference.
EtherNet/IP
CompatibleNetworkUnit
DL-EP1
User’s Manual
(SK-1000)
Page 2
Introduction
This manual describes the basic operations and hardware functions of the DL-EP1. Read
the manual carefully to ensure safe performance and function of the DL-EP1.
Keep this manual in a safe place for future reference.
Ensure that the end user of this product receives this manual.
Symbols
The following symbols alert you to matters concerning the prevention of injury and
product damage.
It indicates cautions and limitations that must be followed during operation.
It indicates additional information on proper operation.
It indicates tips for better understanding or useful information.
It indicates reference pages.
EtherNet/IP is a trademark of ODVA,inc
It indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
It indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
It indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
It indicates a situation which, if not avoided, could result in product
damage as well as property damage.
Point
Important
CAUTION
DANGER
NOTICE
WARNING
Reference
Page 3
Safety Information for DL-EP1
CAUTION
General Precautions
• Before and while operating this product, confirm its performance and functions
operate correctly.
• Implement sufficient safety measures to prevent human and property damage
in case this product fails.
• Be aware that the product functions and performance are not warranted if the product is
used outside the range of stated specifications or is modified by the customer.
• Combining this product with other equipment requires sufficient consideration
because the proper functions and performance may not be met depending on
the environment.
• Do not use this product for the purpose of protecting a human body or a part of
the human body.
• This product is not intended for use as an explosion-proof product. Do not use
this product in hazardous locations and/or in a potentially explosive atmosphere.
• Do not expose equipment, including peripherals, to rapid temperature
changes. Equipment failure may result from condensation build up.
Precautions for Use
• To avoid injury or failure, turn off the power immediately in the
following cases.
- Water or foreign matter enters the main unit.
- The case is broken, for example if it is dropped.
- Smoke or unusual smell is emitted from the product.
• Use the correct power voltage. Failure to observe may result in
injury, or failure.
• Do not disassemble or modify this product. Failure to observe
may result in injury.
NOTICE
Do not turn off the power while you are setting any item.
Doing this may cause loss of data settings.
Equipment Environment
For safe, trouble-free operation of this product, the product must not be installed
in the following environments:
• Humid, dusty, or poorly ventilated.
• Exposed to direct sunlight or heat source.
• Exposed to corrosive or flammable gases.
• Exposed directly to vibration or shock.
• Exposed to water, oil, or chemical splashes.
• Exposed to static electricity.
408GB
1
Page 4
Noise Protection
If this product is installed in a location near an electrical noise source, e.g., a power
source or high-voltage line, it may malfunction or fail because of noise. Take
protective measures, such as using a noise filter or running the cables separately.
About the Power Supply
• Noise superimposed on the power supply may result in malfunction. Use a
stabilized DC power supply configured with an isolation transformer.
• When using a commercially available switching regulator, be sure to ground the
frame ground terminal.
Precautions on Regulations and Standards
UL Certification
This product is an UL/C-UL Listed product.
• UL File No. E207185
• CategoryNRAQ, NRAQ7
Be sure to consider the following specifications when using this product as an UL/CUL Listed Product.
• Use this product under pollution degree 2.
• For wiring to the power supply connector, use a power supply with Class 2 output
defined in NFPA70 (NEC: National Electric Code).
• This product is an open type device. Therefore, it must be installed in an
enclosure with an IP 54 or higher rating. (e.g. Industrial control panel)
CE Marking
Keyence Corporation has confirmed that this product complies with the essential
requirements of the applicable EC Directive, based on the following specifications.
Be sure to consider the following specifications when using this product in a member
state of European Union.
EMC Directive (2004/108/EC)
EMI : EN55011, Class A
EMS : EN61000-6-2
• Use an STP (shielded twisted pair) cable for connection to the network.
These specifications do not give any guarantee that the end-product with this
product incorporated complies with the essential requirements of EMC Directive. The
manufacturer of the end-product is solely responsible for the compliance on the endproduct itself according to EMC Directive.
2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 5
Relevant Manuals
PLC CPU unit
EtherNet/IP scanner
unit
DL-EP1 (this unit)
Manuals related
to CPU unit
Manuals related to
EtherNet/IP unit
This
manual
KV-DN20
MS
NS
ON
TERM.
Sensor amplifiers
Manuals for each
sensor amplifier unit
Example) · SK-1000 series
instruction manual
The manuals relevant to this document are as follows:
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3
Page 6
MEMO
4
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 7
Manual Organization
1
2
3
4
5
Before Using
Connection and
Configuration
Communicating
with the SK-1000
Series
Specifications
Appendix
This chapter provides an overview of the DL-EP1
and describes its part names and functions.
This chapter describes the procedures from
installing the DL-EP1 and sensor amplifiers to
configuring communication.
This chapter describes the configuration of memory
that communicates with the EtherNet/IP compatible
network unit and a communication timing chart.
This chapter describes the specifications and
external dimensions of the DL-EP1.
This chapter provides the parameter list, as well as
troubleshooting instructions.
1
2
3
4
5
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5
Page 8
Table of Contents
Safety Information for DL-EP1 ..................................................................... 1
General Precautions ......................................................................... 1
Precautions for Use ........................................................................... 1
Precautions on Regulations and Standards ...................................... 2
1-2Checking the Package Contents ........................ 1-3
1-3Names and Functions of Each Part....................1-4
1
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
1-1
Page 12
1-1
DL-EP1 Overview
1
Overview
Before Using
The DL-EP1 operates as an EtherNet/IP communication adaptor. EtherNet/IP
communications enable you to output the ON/OFF control signals and current values
of the DL-EP1 and sensor amplifiers connected to the DL-EP1 as communication
data to a PLC or other equipment.
The DL-EP1 supports EtherNet/IP cyclic communication (Implicit messaging) and
message communication (Explicit messaging). Cyclic communication enables data
exchange without a ladder program. Message communication allows for reading/
writing sensor amplifier parameters and issuing commands to the sensor amplifiers.
■ System configuration example
Connectable Sensor Amplifiers
DL-EP1 (this unit)
PLC or other host device
(EtherNet/IP unit)
EtherNet
EtherNet/IP
adaptor
■ Number of Connectable Sensor Amplifiers
NameAmplifier form Main unit
SK-1000
Series
Sensor amplifiers supporting D-bus are connectable. You can connect one sensor to
the DL-EP1 as a main unit and one or more sensors to the main unit as expansion units.
(D-bus is the name of KEYENCE's wiring-saving system for sensor amplifiers.) If the
sensor amplifier is D-bus compatible, different models can be connected together.
How many and what types of sensor amplifiers can be connected depends on the
sensor amplifiers or units to be connected. Please inquire for details.
1-2
DIN rail mount
type
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
SK-1000SK-1050
Expansion
unit
Maximum number of
connectable units
8
(1 main unit, 7 expansion units)
Page 13
1-2
Before using the DL-EP1, make sure that the following equipment and accessories
are included in the package. We have thoroughly inspected the package contents
before shipment.
However, in the event of defective or broken items, contact your nearest KEYENCE
office.
Checking the Package Contents
Package Contents
■ Package contents
DL-EP1 main unit x 1Expansion connector
sticker x 1
Instruction manual x 1
■ List of Optional Parts
• STP (shielded twisted pair) cable
(Category 5e, straight)
- OP-51504 (0.2m)
- OP-51505 (0.5m)
- OP-51506 (1m)
- OP-51507 (3m)
- OP-51508 (5m)
* The working ambient temperature of the above
cables are 0 to 50°C.
End unit x 2
OP-26751
1
Before Using
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
1-3
Page 14
1-3
(8) Sensor amplifier connector
(for DIN rail mount type)
(1) RJ-45 connector
(2) Reset switch
(3) Link/activity indicator (green)
(4) Module status indicator (green/red)
(5) Network status indicator (green/red)
(6) Sensor communication indicator
(green/red)
(7) MAC address
(9) Sensor amplifier connector
(for panel mount type
and large display type)
This section describes the part names and functions of the DL-EP1.
1
Before Using
NameDescription
(1) RJ-45 connectorAttach the network cable to this connector.
(2) Reset switchWhen held down for three seconds or longer, the DL-EP1
(3) Link/activity
indicator
(4) Module status
indicator
(5) Network status
indicator
(6) Sensor communication
indicator
(7) MAC addressMAC address for this DL-EP1
(8) Sensor amplifier
connector (for DIN rail
mount type)
1-4
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Names and Functions of Each Part
settings will be reset to the default settings.
For details, refer to "Default Settings" (Page 5-5).
Normal: Green LED lights up or blinks
For details, refer to "Troubleshooting" (Page 5-3).
Normal: Green LED lights up
For details, refer to "Troubleshooting" (Page 5-3).
Normal: Green LED lights up
For details, refer to "Troubleshooting" (Page 5-3).
Indicates the status of communication between the DLEP1 and sensor amplifiers.
Normal: Green LED lights up
For details, refer to "Troubleshooting" (Page 5-3).
Attach the sensor amplifier to this connector. When not
using this connector, remove it and replace with the
protective sticker.
Page 15
NameDescription
(9) Sensor amplifier
connector (for panel
mount/large display
type)
1-3 Names and Functions of Each Part
Attach the sensor amplifier to this connector. A protective
seal is attached when shipped from the factory. The
optional expansion cable (OP-35361) is used for this
connection.
1
Before Using
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
1-5
Page 16
1
1-3 Names and Functions of Each Part
MEMO
Before Using
1-6
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 17
Connection and Configuration
This section describes procedures from installing the DL-EP1 and
sensor amplifiers to configuring communication.
2-1Procedures from Installation before Using the DL-EP1 to
2-4Configuring Communication with the DL-EP1.... 2-8
2-5Configuring Communication with the Scanner . 2-11
2-3
2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
2-1
Page 18
2-1
1. Installation and Connection to Sensor Amplifiers
Connecting the DL-EP1 to sensor amplifiers (Page 2-4)
Assigning ID Numbers (Page 2-5)
2. Wiring
3. Configuring Communication with the DL-EP1
4. Configuring Communication with the Scanner
Connecting a communication cable (Page 2-6)
Setting the IP address (Page 2-8)
Setting the IP address (Page 2-11)
Registering the device profile of the DL-EP1
(Page 2-11)
Configuring the Scanner Side
(Refer to each scanner manual.)
This section describes the procedures before you use the DL-EP1.
Procedures from Installation before Using the DL-EP1 to Configuration
Configuration Procedures
2
Connection and Configuration
The above configurations enable communication.
For the outline of scanner side configuration for communication with an Allen-Bradley
scanner, refer to "Procedures for Communicating with an Allen-Bradley
ControlLogix PLC" (Page 5-6).
2-2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 19
2-2
(3)
(2)
(1)
Number of Connectable Sensor Amplifiers
Installation and Connection to Sensor Amplifiers
NameAmplifier form Main unit
SK-1000
Series
This section describes how to mount the DL-EP1 on the DIN rail and to connect it to
sensor amplifiers.
Sensor amplifiers supporting D-bus are connectable. You can connect one sensor to
the DL-EP1 as a main unit and one or more sensors to the main unit as expansion
units. (D-bus is the name of KEYENCE's wiring-saving system for sensor amplifiers.)
If the sensor amplifier is D-bus compatible, different models can be connected
together.
How many and what types of sensor amplifiers can be connected depends on the
sensor amplifiers or units to be connected. Please inquire for details.
DIN rail mount
type
SK-1000SK-1050
Expansion
unit
Maximum number of
connectable units
8
(1 main unit, 7 expansion units)
Mounting and connection to Sensor Amplifiers
Mounting the DL-EP1 on the DIN rail
Align the claw on the bottom of the DL-EP1 with the DIN rail. While
1
pushing the amplifier in the direction of arrow (1), press down in the
direction of arrow (2).
2
Connection and Configuration
To remove the DL-EP1, raise the amplifier in the direction of arrow (3)
2
while pushing the DL-EP1 in the direction of arrow (1).
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
2-3
Page 20
2-2 Installation and Connection to Sensor Amplifiers
NOTICE
Point
Sensor amplifier
Expansion protective cover
Sensor amplifier
EtherNet/IP Compatible Network Unit
DL-EP1
Connector
NOTICE
Connecting the DL-EP1 to sensor amplifiers
The EtherNet/IP Compatible Network Unit DL-EP1 must be connected to sensor
amplifiers before it can function.
The connecting procedure varies with the mounting type of the sensor amplifiers to
be connected.
2
Connection and Configuration
Make sure that the sensor amplifiers are turned off before
connecting the EtherNet/IP Compatible Network Unit DL-EP1.
Connecting the DL-EP1 to the sensor amplifiers when they are
turned on may damage the DL-EP1.
For the instructions on connecting additional sensor amplifiers, refer to the
instruction manual of each sensor amplifier.
Connecting to sensor amplifiers of the DIN rail mount type
Remove the expansion protective cover from the sensor amplifier to be
1
connected.
Mount the EtherNet/IP Compatible Network Unit DL-EP1, on the DIN rail
2
and connect it to the sensor amplifier.
Insert the EtherNet I/P Compatible Network Unit DL-EP1 to the sensor amplifier
connector so as not to leave space between them.
2-4
Make sure that the sensor amplifier connector (for DIN rail mount
type) is not askew on the side face of the EtherNet/IP Compatible
Network Unit DL-EP1 according to the figure shown below.
Connecting the DL-EP1 to the sensor amplifier with the connector
being askew may damage the DL-EP1.
Sensor amplifier connector
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
EtherNet/IP Compatible Network Unit DL-EP1
Page 21
2-2 Installation and Connection to Sensor Amplifiers
End unit
End unit
NOTICE
Point
Mount the supplied end units (OP-26751: a set of two pieces) on the outer
3
ends of the amplifier and the EtherNet/IP Compatible Network Unit DLEP1. Then, fix the end units with the screws on the top of each end unit (2
points x 2 units). (Tightening torque : 0.6 Nm or less)
Mount the end units in the same way as the EtherNet/IP Compatible Network
Unit DL-EP1.
Press the EtherNet/IP Compatible Network Unit DL-EP1, into
full engagement with the sensor amplifier. Energizing the DLEP1 when not inserted fully may damage the DE-EP1.
Assigning ID Numbers
Several sensor amplifiers can be connected to the DL-EP1. ID numbers for data
identification are assigned to each sensor amplifier.
The method for assigning ID numbers is as follows:
• ID numbers are assigned in order, starting from the sensor amplifier that is the
main unit. (Optional numbers cannot be assigned.)
• 0 is assigned as the ID number of the DL-EP1.
2
Connection and Configuration
• You cannot change the ID numbers assigned to the sensor amplifiers.
• In this manual, ID number 00 to ID number 08 are denoted as ID00 to
ID08, respectively.
Also for cyclic communication, output, current value, and external input are assigned
one by one per ID number.
For DIN rail mount type
ID number01
Main
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
02070800
unit
Expansion
unit
Expansion
unit
Expansion
unit
2-5
Page 22
2
STP/UTP cable
Point
2-3
Connecting a communication cable
Connection and Configuration
Usable cable
Wiring
The DL-EP1 uses the power supplied to sensor amplifiers, so there is no power cable
wiring. This section describes the wiring of communication cables used by the DLEP1.
Use the following procedures to connect the DL-EP1 to the communication cable
required for EtherNet/IP communication.
Usable cables depend on whether the system is configured with 10BASE-T or
100BASE-TX.
Structuring a 10BASE-T system
When the system is configured
with 10BASE-T, use a Category
3 or higher shielded twisted-pair
(STP) cable or an unshielded
twisted-pair (UTP) cable.
Structuring a 100BASE-TX
network
When the system (network) is configured with 100BASE-TX, use a Category 5 or
higher STP or UTP cable. Do not use a Category 3 or Category 4 UTP cable.
2-6
• Use a STP/UTP straight cable when connecting the DL-EP1 to an
Ethernet switch.
• Use a STP/UTP cross cable when directly connecting the DL-EP1 to a
PC.
• Do not use the STP/UTP cross cable incorrectly because it is difficult to
distinguish this cable from the STP/UTP straight cable in appearance.
• When the system (Ethernet) is configured with a type (e.g., 10BASE-2
or 10BASE-5) other than 10BASE-T and 100BASE-TX, use an Ethernet
switch with an AUI (MAU) connector or a BNC connector or use a media
converter (10BASE5 10BASE-T or 10BASE2 10BASE-T).
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 23
2-3 Wiring
DL-EP1 connector port
The DL-EP1 connector port accepts an RJ-45 8-pole modular connector (ISO8877
compliant) used with 10BASE-T and 100BASE-TX and complies with the IEEE802.3
Standards.
Precautions for connecting a STP/UTP cable to the DL-EP1 connector port
Take care not to apply a load to the DL-EP1 connector port when connecting the
STP/UTP cable to the DL-EP1.
The cable may be bent and used when installed. Bending the cable
NOTICE
Connecting the DL-EP1 to EtherNet/IP
The following describes how to connect the DL-EP1 to the RJ-45 connector.
1
2
at a sharp angle may cut the wires in the cable or the cable may be
disconnected during use. Install or lay the cable to be used with
attention to the recommended bending radius R of the cable.
Turn off the power supply.
Connect one modular jack of the STP/UTP cable to the 10BASE-T/
100BASE port of the Ethernet switch to be used.
Insert the modular jack until a "click" is heard. The modular jack and connector
will lock.
2
Connection and Configuration
Point
・ Keep the length of the STP/UTP cable to be used 100 m or less.・ Carefully check the state of connector (port) on the Ethernet
switch before connecting the DL-EP1. There are various Ethernet
switches. Some Ethernet switches have a different shape
connector (AUI connector or BNC connector, etc.) from the RJ-45,
while some have connectors used to connect Ethernet switches
together (cascade ports).
Connect the modular jack on the other end of the STP/UTP cable to the
3
DL-EP1 connector port.
Insert the jack until a "click" is heard. The modular jack and connector will lock.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
2-7
Page 24
2-4
This section describes settings for connecting the DL-EP1 to the EtherNet/IP system.
Configuring Communication with the DL-EP1
DL-EP1 Settings
The following describes how to set communication with the DL-EP1.
2
Setting the IP address
Connection and Configuration
Set the IP address with the DL-EP1 wired and with the power supplied.
By default, the IP address is not set. However, you can use the BOOTP client function
to set the IP address via Ethernet.
The following 2 methods are available for setting the IP address.
• Use the IP address setting tool (this tool can be downloaded from the Keyence
web site http://www.keyence.com).
Refer to the following setting procedures or the "IP Setting Tool User's Manual".
• Use an IP address setting tool from other sources.
Refer to the manuals provided by the respective sources.
Using the IP address setting tool
Here briefly describes the procedures for setting the IP address with the IP
address setting tool. For details on how to use the IP address setting tool, refer to
the "IP Setting Tool User's Manual". You can view the "IP Setting Tool User's
Manual" from [Help(H)] of "IP Setting Tool" as the PDF file.
Start the IP Setting Tool.
1
Devices such as the DL-EP1 connected to the network and for which their IP
addresses are not set will appear.
To display the devices for which their IP addresses are not set, click the [Scan
EtherNet/IP devices (A)] button.
2-8
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 25
2-4 Configuring Communication with the DL-EP1
Point
To display "Not Set" for the IP address, the network status indicator
(NS) must be off (IP address not assigned). To unassign the IP
address, hold down the Reset switch on the DL-EP1 for three
seconds or longer.
Select the device for which to set the IP address and click [Setup IP addr.(I)] to
2
display [Setup IP addr.].
Compare the MAC address to be displayed with the front MAC address on the
DL-EP1 and select the device for which to set the IP address.
Set an IP address which is not currently used in "IP addr.(required)(I)" and click
the [OK] button.
2
Connection and Configuration
Reference
Using the [Search available IP addresses (F)] button enables you to
search for open IP addresses.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
2-9
Page 26
2
Reference
IP address assignment
BOOTP clientBOOTP server
Via Ethernet
Ethernet
2-4 Configuring Communication with the DL-EP1
The IP address has now been set.
3
Connection and Configuration
What is BOOTP?
BOOTP is the abbreviation of BOOT strap Protocol. This protocol is used
by the client device in the TCP/IP network to make the network settings
assigned from the server.
If there is a BOOTP server in the same network as the device running as
the BOOTP client, an IP address is assigned to the device connected as
the BOOTP client.
2-10
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 27
2-5
This section describes scanner side configuration for connecting the DL-EP1 to the
EtherNet/IP system.
When communicating with an Allen-Bradley scanner, also refer to the
"Procedures for Communicating with an Allen-Bradley ControlLogix PLC" (Page 5-6).
Configuring Communication with the Scanner
Setting the scanner
Connecting the DL-EP1 to the EtherNet/IP scanner requires the following settings:
Setting the IP address
Set the IP address of the scanner.
Registering the device profile of the DL-EP1
Register the device profile of the adaptor (DL-EP1) to be connected using the
scanner's setting software.
You can register the device profile manually or by reading the EDS (Electronic Data
Sheet) file. You can download the EDS file of the DL-EP1 from the Keyence web site
(http://www.keyence.com).
Configuring communication with the DL-EP1
The DL-EP1 uses EtherNet/IP cyclic communication or message communication to
communicate with the scanner.
Cyclic communication (Implicit messaging)
This function sends and receives data at a set RPI (Requested Packet Interval).
Selecting the communication method called "connection" and assigning the
devices to be sent and received on the scanner side enables the DL-EP1 to
communicate with the scanner without creating a ladder program.
Message communication (Explicit messaging)
This function is used to send and receive data which does not need to be timed.
Use this function when changing the sensor amplifier settings or when performing
EtherNet/IP communication with the scanner (e.g., Allen-Bradley SLC5/05 Series)
that does not support cyclic communication.
This function uses a ladder program to create a message on the scanner side for
communication.
2
Connection and Configuration
For more information on setting each communication method, refer to the chapters
titling "Communicating with...." of each sensor amplifier as well as the manuals
enclosed with each scanner.
Reference
This manual explains only the EtherNet/IP scanner functions and settings
required for communication with the DL-EP1. For details on the functions
and settings between the EtherNet/IP scanner and CPU unit, refer to the
manuals enclosed with the scanner and CPU unit.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
2-11
Page 28
2
2-5 Configuring Communication with the Scanner
MEMO
Connection and Configuration
2-12
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 29
Communicating with
the SK-1000 Series
This chapter describes the configuration of memory that
communicates with the EtherNet/IP compatible network unit
and a communication timing chart.
3-1What is EtherNet/IP?.......................................... 3-2
3-2DL-EP1 EtherNet/IP Communication Function .. 3-3
3-4Message Communication ................................. 3-22
3
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-1
Page 30
3
Scanner
AdaptorAdaptorAdaptor
High speed
(Communication cycle: 10 ms)
Regular speed
(Communication
cycle: 100 ms)
Low speed (Communication cycle: 1000 ms)
3-1
What is EtherNet/IP?
What is EtherNet/IP?
EtherNet/IP is an industrial communication network with open specifications. The
specifications are managed by ODVA (Open DeviceNet Vendor Association, Inc.).
Industrial protocol has been combined with the Ethernet and standardized as EtherNet/IP (Industrial Protocol).
Communication is realized by combining the protocols known as Common Industrial
Protocol (CIP) with TCP/IP and Ethernet. This allows regular Ethernet to be used
together with the network.
Communicating with the SK-1000 Series
Before starting EtherNet/IP communication, one of the devices must open a
communication line called a "connection" with the other device. The side which
opens the connection is called the "scanner", and the side to be opened is called the
"adaptor". (The DL-EP1 is an adaptor.)
EtherNet/IP includes cyclic communication (Implicit messaging) which sends and
receives data periodically. Message communication (Explicit messaging) which
sends and receives commands and responses at a random timing.
Cyclic communication enables you to set RPI (Requested Packet Interval) according
to the priority of the data to be exchanged, allowing the entire communication load to
be adjusted for data exchange.
Message communication enables you to exchange the required commands and
responses at the required timing. Message communication is used for applications
which do not require the punctuality of cyclic communication, such as reading and
writing adaptor settings.
3-2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 31
3-2
Output
Judgment Value
・・・・・・
Error information
External input
Setting value
Output
Judgment Value
・・・・・・
Error information
External input
Setting value
IN area
OUT area
Output
Current value
Error information
External input
EtherNet/IP scanner
DL-EP1
Sensor amplifier
Message communication
Output
Judgment Value
・・・・・・
Error information
IN area
OUT area
Direct read/write of various parameters
Cyclic communication
External input
Setting value
Cyclic communication
DL-EP1 EtherNet/IP Communication Function
This section describes the EtherNet/IP functions supported by the DL-EP1.
The DL-EP1 functions as an EtherNet/IP adaptor, and supports both cyclic and
message EtherNet/IP communications.
Overview of Communication Methods
3
Communicating with the SK-1000 Series
The EtherNet/IP scanner can use the following functions:
Communication Methods
Function of sensor amplifier
Read status
Read output
Read current value
Execute external input*
Change bank number
Rewrite setting value
Motion command
Read current value, setting, and
status
Read number of decimal places
Rewrite setting value
Lock all
* To use the message communication for this function, execute the function
assigned to the external input directly by using the message communication.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Cyclic communication
(Page 3-5)
X
Message Communication
(Page 3-22)
3-3
Page 32
3
PLC
EtherNet/IP scanner
RPI=3 (ms)*
RPI=0.5 (ms)*
RPI=5 (ms)*
RPI=10 (ms)*
Various EtherNet/IP adaptors
Ethernet
* RPI (Requested Packet Interval) can be set
individually for each connection.
Point
3-2 DL-EP1 EtherNet/IP Communication Function
Cyclic communication
This function sends and receives data between the scanner and DL-EP1 at the set
RPI (Requested Packet Interval). The function can exchange data such as the
sensor amplifier's output signals and judgment values and error status without ladder
programs.
Communicating with the SK-1000 Series
Configurations such as RPI and data size for cyclic communication are set
on the scanner side.
In a network which has many connected devices, including EtherNet/IP
devices, a delay or packet loss could occur if a large load is constantly or
temporarily applied on the network. Verify the settings carefully before
operation.
Message communication
Message communication can be used for applications which do not require a
punctuality like cyclic communication.
In message communication, various parameters, including data which can be
exchanged with cyclic communication, can be read and written. Functions specific
to sensors such as the sensor amplifier preset function can also be executed.
3-4
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 33
3-3
(1) Request connection open
(3) Open connection
(2) Check
compatibility
Output data
Data reflected in the
scanner
Input data
The data output from the
scanner is stored by the
DL-EP1.
EtherNet/IP scannerDL-EP1Sensor amplifier
IN area
OUT area
Cyclic
communication
Data between
sensors is
refreshed
Cyclic
communication
Data between
sensors is
refreshed
Reference
Cyclic communication
This section describes the cyclic communication functions and how to use them.
What is cyclic communication?
Cyclic communication is a function that exchanges data with the EtherNet/IP device
in a cyclic manner (at a set cycle).
In cyclic communication, data can be exchanged when one device successfully
opens a logical communication line called a "connection" with the other device.
The side which opens the connection is called the scanner, and the side to be
opened is called the adaptor. (The DL-EP1 is an adaptor.)
Cyclic communication is started in the following procedures:
(1) The scanner requests the adaptor to open the connection.
(2) The adaptor side checks compatibility.
(3) If no error occurs as a result the compatibility check, the adaptor opens the
connection.
(* If an error is found during the compatibility check, the adaptor does not open
the connection.)
"Checking the Device Compatibility" (Page 3-21)
Data is exchanged between the EtherNet/IP scanner, DL-EP1 and each sensor
amplifier as follows:
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
To carry out EtherNet/IP communication with a scanner which does not
support cyclic communication (Allen-Bradley SLC5/05 Series, etc.), use
"Message Communication" (Page 3-22).
3-5
Page 34
3-3 Cyclic communication
Configuring Cyclic Communication
The following settings are required to execute cyclic communication with the DLEP1.
[DL-EP1]
The DL-EP1 does not require any setting.
3
Communicating with the SK-1000 Series
[Scanner]
(1) Set the connection to be used.
(2) Set the devices used in cyclic communication.
Refer to the scanner manual for details on how to make the above settings.
(* No ladder program is required when cyclic communication is used.)
Actions which can be completed with Cyclic Communication
Cyclic communication can use the following functions:
(1) Read status
(2) Read output (Page 3-18)
Outputs that can be read: HI output, LO output, GO output, HH output, LL output
(3) Read P.V. value (Page 3-19)
(4) Execute external input (Page 3-20)
Inputs that can be used: External Input 1, External Input 2, External Input 3,
External Input 4,
3-6
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 35
3-3 Cyclic communication
Reference
Usable Connections
EtherNet/IP requires that a connection must be opened from the scanner when cyclic
communication is started. There are various types of connections, and the type
usable by each device is defined in the EDS file.
The DL-EP1 can use the following connections:
Connection
No
Name
Monitor Data And
1
External Input
Monitor Data
2
(Input Only)
Input/Output
DL-EP1 to
scanner
Scanner to
DL-EP1
DL-EP1 to
scanner
Scanner to
DL-EP1
・ Each connection's trigger timing is executed cyclically. The connection
type supports both point-to-point and multicast.
・ The details of each application type are as follows:
Exclusive Owner:
This connection allows simultaneous setting of both data
transmission from the scanner to the DL-EP1 and data
transmission from the DL-EP1 to the scanner. This setting is
made not only when the scanner monitors the adaptor (DL-EP1)
data, but also when it issues external inputs and rewrites the
settings, etc. Multiple "Exclusive Owner" connections cannot be
opened to one adaptor (DL-EP1).
Input Only:
This connection allows only data transmission from the DL-EP1
to the scanner. This setting is made when the scanner only
monitors adaptor (DL-EP1) data. Multiple scanners can open an
"Input Only" connection simultaneously to one adaptor (DLEP1).
(* To simultaneously open connections from multiple scanners,
set the Connection Type to Multicast.)
Assembly
Instance
64H (100)168
65H (101)10
64H (100)168
FEH (254)0
Size
(Byte)
RPI Range
(in 0.5 ms)
0.5 ms to
10000 ms
0.5 ms to
10000 ms
Application
Ty pe
Exclusive
Owner
Input Only
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-7
Page 36
3
DL-EP1 data
Scanner IN area
Address 0
Address 1
Address 167
Monitor Data
(Assembly Instance: 100)
1-byte (8-bit) data
Reference
A
A
A
3-3 Cyclic communication
Assignment to IN Area (DL-EP1 to Scanner)
The data from the DL-EP1 is assigned to the EtherNet/IP scanner's IN area.
Communicating with the SK-1000 Series
Example)
16-bit data
ddress 40 to 41
16-bit data
ddress 42 to 43
The data such as 16-bit data extending over multiple bytes is stored into
an area which starts with an even address in order from the lowest-order
byte.
High-order byte Low-order byte
12H34H
56H78H
43
56H
78H4212H4134H
40
3-8
32-bit data
ddress 48 to 51
High-order byte Low-order byte
12H 34H 56H 78H
51
12H
34H5056H4978H
48
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 37
3-3 Cyclic communication
Monitor Data (84 Words (168 Bytes)) Assembly Instance (Instance ID): 64H
This is the device map for the monitor data to be assigned to the IN area.
For details on each parameter, refer to "Parameter List" (Page 3-11).
For details on current value 0 and current value 1, refer to "Current Value 0/
Current Value 1" (Page 3-12).
ID numbers (ID01 to ID08) are assigned for each sensor amplifier according to the
number of sensor amplifiers. The ID numbers larger than the number of connected
sensor amplifiers and ID09 to ID15 are not assigned.
Name
Status
Sensor
Error Status
Sensor
Warning
Status
Current
Value 0
Over Range
Current
Value 0
Under
Range
Current
Value 0
Invalid
Current
Value 1
Over Range
(Unassigned)
Current
Value 1
Under Range
(Unassigned)
Current
Value 1
Invalid
(Unassigned)
Output 1
(HI)
Output 2
(LO)
Output 3
(GO)
Output 4
(Alarm
Output)
Address
(Byte)
0
1Error Status
2ID08. . . . .ID01
3
4ID08. . . . .ID01
5
6ID08. . . . .ID01
7
8ID08. . . . .ID01
9
10ID08. . . . .ID01
11
12ID08. . . . .ID01
13
14ID08. . . . .ID01
15
16ID08. . . . .ID01
17
18ID08. . . . .ID01
19
20ID08. . . . .ID01
21
22ID08. . . . .ID01
23
24ID08. . . . .ID01
25
bit7bit6bit5bit4bit3bit2bit1bit0
Reserved for system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Warning
Status
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
Reserved for system
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
DL-EP1
Error Status
3
Communicating with the SK-1000 Series
3-9
Page 38
3-3 Cyclic communication
3
Communicating with the SK-1000 Series
Name
Output 5
(Unassigned)
External
Input
Response 1
(External
Input 1)
External
Input
Response 2
(External
Input 2)
External
Input
Response 3
(External
Input 3)
External
Input
Response 4
(External
Input 4)
External
Input
Response 5
(Unassigned)
Error
ID Number
Error
Code
Warning
ID Number
Warning
Code
Current
Value 0
Judgment
(
Value (P.V.))
Address
(Byte)
26ID08. . . . .ID01
27
28ID08. . . . .ID01
29
30ID08. . . . .ID01
31
32ID08. . . . .ID01
33
34ID08. . . . .ID01
35
36ID08. . . . .ID01
37
40
41
42
43
44
45
46
47
48
49
50
51
::
104
105
106
107
bit7bit6bit5bit4bit3bit2bit1bit0
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
Current Error ID Number (16-bit unsigned integer)
Current Error Code (16-bit unsigned integer)
Current Warning ID Number (16-bit unsigned integer)
Current Warning Code (16-bit unsigned integer)
ID Number 1 (Current Value 0) (32-bit signed integer)
ID Number 15 (Current Value 0) (32-bit signed integer)
3-10
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 39
3-3 Cyclic communication
Name
Current
Value 1
Unassigned
(
Address
(Byte)
108
109
110
111
::
)
164
165
166
167
bit7bit6bit5bit4bit3bit2bit1bit0
ID Number 1 (Current Value 1) (32-bit signed integer)
ID Number 15 (Current Value 1) (32-bit signed integer)
Parameter List
ItemDescription
DL-EP1 Error
Status
Warning Status(Unassigned)
Error Status
Sensor Error Status
Sensor Warning
Status
Current Value n
Over Range
(n: 0 to 1)
Current Value n
Under Range
(n: 0 to 1)
Current Value n
Invalid
(n: 0 to 1)
The error status of the DL-EP1 is output.
ON: An error occurred.
OFF: No error occurred.
The error status of the DL-EP1 or the error statuses of all the connected sensor
amplifiers are output.
When ON, a value is stored in "Error ID Number" and "Error Code". When OFF, 0
is stored in "Error ID Number" and "Error Code".
ON: An error occurred in the DL-EP1 or in any of the connected sensor
amplifiers.
OFF: No error occurred in the DL-EP1 or in the connected sensor amplifiers.
The target ID number bit of the sensor amplifier where the error occurred is
output.
ON: An error occurred in the sensor amplifier with the target ID number.
OFF: No error occurred in the sensor amplifier with the target ID number.
(Unassigned)
The current value n (n: 0 to 1) of the sensor amplifier with the target ID number
is compared with the measurement upper limit and the comparison result is
output.
ON: The current value n (n: 0 to 1) of the sensor amplifier with the target ID
number is greater than the measurement upper limit.
OFF: The current value n (n: 0 to 1) of the sensor amplifier with the target ID
number is less than the measurement upper limit.
(* The current value 1 does not exist in the SK-1000 Series.)
The current value n (n: 0 to 1) of the sensor amplifier with the target ID number
is compared with the measurement lower limit and the comparison result is
output.
ON: The current value of the sensor amplifier with the target ID number is less
than the measurement lower limit.
OFF: The current value of the sensor amplifier with the target ID number is
greater than the measurement lower limit.
(* The current value 1 does not exist in the SK-1000 Series.)
The status of current value n (n: 0 to 1) of the sensor amplifier with the target ID
number is output.
ON: The current value of the sensor amplifier with the target ID number is
invalid.
OFF: The current value of the sensor amplifier with the target ID number is
valid (normal).
(* The current value 1 does not exist in the SK-1000 Series.)
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-11
Page 40
3
3-3 Cyclic communication
Output n (n: 1 to 5)
External Input
Response
Communicating with the SK-1000 Series
n (n: 1 to 5)
Error ID Number
Error Code
Warning ID
Number
Warning Code(Unassigned)
Current Value n
(n: 0 to 1)
Current Value 0/Current Value 1
ItemDescription
The ON/OFF status of output n (n: 1 to 5) of the sensor amplifier with the target
ID number is output.
Output 1: HI output
Output 2: LO output
Output 3: GO output
Output 4: Alarm output
Output 5: (Unassigned)
ON: Output n is output.
OFF: Output n is not output.
An external input response is output when the corresponding external input
request n (n: 1 to 5) is made via communication.
The ID number of an unexisting external input is also output.
ON: The external input request was made (ON).
OFF: The external input request was not made (OFF).
For details, refer to "Entering an external input to a sensor amplifier"
(Page 3-19).
If "Error Status" in ON, the ID number of the DL-EP1 where the error occurred and
the ID numbers of sensor amplifiers connected to the DL-EP1 are stored (the ID
number of the DL-EP1 is 0). If no error has occurred, 0 is stored. If an error occurs
in multiple IDs, the ID number of the DL-EP1 or sensor amplifier where the highest
priority error occurred is stored.
Error priority:
(1) DL-EP1 error
(2) Sensor amplifier errors (the error with the smallest error code has the
highest priority)
* If the same error code occurs in multiple sensor amplifiers, the error
with the smallest ID number has the highest priority.
If "Error Status" is ON, the error code is stored. If no error has occurred, 0 is
stored. If an error occurs in multiple IDs, the error code of the DL-EP1 or sensor
amplifier where the highest priority error occurred is stored.
Error priority:
(1) DL-EP1 error
(2) Sensor amplifier errors (the error with the smallest error code has the
highest priority)
* If the same error code occurs in multiple sensor amplifiers, the error
with the smallest ID number has the highest priority.
"Error code list" (Page 3-13)
(Unassigned)
The current value n (n: 0 to 1) of the sensor amplifier is stored. The current value
0 always exists without reference to sensor amplifier models. Whether the
current value 1 exists depends on sensor amplifier models. If the current value
1 does not exist, 0 is stored. The contents displayed in the current value n (n: 0
to 1) depend on the use conditions.
"Current Value 0/Current Value 1" (Page 3-12)
(* The current value 1 does not exist in the SK-1000 Series.)
*
*
Current Value 0
Current Value 1
3-12
NameModelConditionsFunction
Main unit/
expansion unit
Main unit/
expansion unit
-Judgment value (P.V.)
-(Unassigned)
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 41
3-3 Cyclic communication
Error code list
The following error codes may occur in the DL-EP1 and sensor amplifiers.
● DL-EP1
Error ID
Number
0
CodeDescriptionCauseActions
0No error--
• Check if the number of
connected sensor
amplifiers exceeds the
maximum number of
sensor amplifiers that can
be connected to the main
unit.
"Number of
Connectable Sensor
Amplifiers" (Page 2-3)
• Check the connection with
the sensor amplifiers and
then turn the power on
again.
If this error cannot be
recovered, contact your
nearest KEYENCE office.
Check the connection with
the sensor amplifiers and
then turn the power on again.
If this error cannot be
recovered, contact your
nearest KEYENCE office.
Check the model of the
connected sensor amplifier
and remove the sensor
amplifier if it is not supported
by the DL-EP1.
Check if the models are
mixable.
"Number of Connectable
Sensor Amplifiers" (Page 2-3)
Check the connection with
the sensor amplifiers and
then turn the power on again.
If this error cannot be
recovered, contact your
nearest KEYENCE office.
Use sensor amplifiers within
the allowable range.
Check if there is a noise
source around the DL-EP1.
If the sensor communication
indicator is flashing red, turn
the power on again.
Check the IP address
setting.
Unassigned ID
51
error
Start-time
52
communication error
Unsupported
53
sensor amplifier
connection error
Mixed model error
54
Start-time
55
communication error
Current limitation
56
error
Communication
57
error between
sensor amplifiers
IP address
70
duplicate error
The main unit assigned no ID
within 10 seconds after the
DL-EP1 had been started.
Communication between
sensor amplifiers ended
abnormally before ID
assignment completion.
A sensor amplifier not
supported by the DL-EP1 is
connected.
Sensor amplifiers outside the
specifications have a mixed
connection.
ID number assignment is
successful but
communication failed during
the subsequent initial
communication.
The number of connected
sensor amplifiers exceeds
the allowable range.
An error occurred during
communication between
sensor amplifiers.
The IP address is the same
as another device.
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-13
Page 42
3-3 Cyclic communication
3
Communicating with the SK-1000 Series
Error ID
Number
0
CodeDescriptionCauseActions
100
101
102
103
104
150
151
152
System error
System error
System error
System error
System error
System error
System error
System error
The IP address is incorrect.
A default gateway setting
error occurred.
An attempt to read data in
EEPROM such as the MAC
address has failed.
An attempt to start the
protocol stack has failed.
An attempt to access
FlashROM has failed.
The number of held IDs is
incorrect.
The number of sensors is
incorrect.
An initial read error occurred.
Contact your nearest
KEYENCE office.
3-14
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 43
● SK-1000 Series
Error
ID
Number
01H to
08H
(Each
ID
number
CodeDescriptionCauseActions
01H
02H
03H
04H to
07H
08H
09H
)
0AH to
0BH
0CH
0DH
0EH
0FH to
10H
Sensor amplifier
error 1 of each ID
number
Sensor amplifier
error 1 of each ID
number
Sensor amplifier
error 3 of each ID
number
Sensor amplifier
error 4 to 7 of
each ID number
Sensor amplifier
error 8 of each ID
number
Sensor amplifier
error 9 of each ID
number
Sensor amplifier
error 10 to 11 of
each ID number
Sensor amplifier
error 12 of each ID
number
Sensor amplifier
error 13 of each ID
number
Sensor amplifier
error 14 of each ID
number
Sensor amplifier
error 15 to 16 of
each ID number
Overcurrent error
EEPROM error
Sensor head error
(Unassigned)
Head temperature/humidity
error
(Unassigned)
(Unassigned)
Amplifier communication
error
(Unassigned)
(Unassigned)
(Unassigned)
3-3 Cyclic communication
3
Communicating with the SK-1000 Series
Refer to the SK-1000 Series
Instruction Manual.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-15
Page 44
3
DL-EP1 data
Scanner's OUT area
Address 0
Address 1
Address 9
External Input
(Assembly Instance: 101)
1-byte (8-bit) data
3-3 Cyclic communication
Warning code list
No warning code occurs in the DL-EP1 and in the SK-1000 Series sensor amplifiers
connected to the DL-EP1.
Assignment to OUT Area (Scanner to DL-EP1)
The data to the sensor amplifier is assigned to the OUT area of the EtherNet/IP
scanner.
ID numbers (ID01 to ID08) are assigned for each sensor amplifier according to the
number of sensor amplifiers. The ID numbers larger than the number of connected
sensor amplifiers and ID09 to ID15 are not assigned.
Name
External
Input
Request 1
(External
Input 1)
External
Input
Request 2
(External
Input 2)
External
Input
Request 3
(External
Input 3)
External
Input
Request 4
(
External
Input 4
External
Input
Request 5
(Unassigned)
Address
(Byte)
0ID08. . . . .ID01
1
2ID08. . . . .ID01
3
4ID08. . . . .ID01
5
6ID08. . . . .ID01
7
)
8ID08. . . . .ID01
9
bit7bit6bit5bit4bit3bit2bit1bit0
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
Reserved for
system
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
ID15. . . . .ID09
* You use the external inputs by assigning specific functions. For details of the
3-16
functions to be assigned, refer to “SK-1000 Series Instruction Manual”.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 45
Parameter List
NameFunctionOperation
External
Input
Request 1
External
Input
Request 2
External
Input
Request 3
External
Input
Request 4
External
Input
Request 5
External Input 1
External Input 2
External Input 3
External Input 4
(Unassigned)(Unassigned)
ON: Turns on external input 1. When external input 1 is turned on,
external input response 1 turns on.
OFF: Turns off external input 1. External input response 1 turns off.
ON: Turns on external input 2. When external input 2 is turned on,
external input response 2 turns on.
OFF: Turns off external input 2. External input response 2 turns off.
ON: Turns on external input 3. When external input 3 is turned on,
external input response 3 turns on.
OFF: Turns off external input 3. External input response 3 turns off.
ON: Turns on external input 4. When external input 4 is turned on,
external input response 4 turns on.
OFF: Turns off external input 4. External input response 4 turns off.
3-3 Cyclic communication
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-17
Page 46
3
PLC
Output of sensor amplifier
IN area [18] Bit0
Sensor amplifier
(1)
Output
HI output of ID 01
1
0
ON
OFF
3-3 Cyclic communication
Communication Methods
The following describes how the scanner cyclically communicates with the DL-EP1
(cyclic communication).
"Reading an output from a sensor amplifier" (Page 3-18)
"Entering an external input to a sensor amplifier" (Page 3-19)
"Reading judgment values (P.V. values) from sensor amplifiers" (Page 3-20)
For the message communication method, refer to "Message communication"
(Page 3-4).
Communicating with the SK-1000 Series
Reading an output from a sensor amplifier
Available outputs: HI, LO, GO, and alarm output
Device assignments: "Monitor Data (84 Words (168 Bytes)) Assembly Instance
(Instance ID): 64H" (Page 3-9)
This example shows how to read the HI output from the sensor amplifier ID01.
(1)The output from the sensor amplifier entered into the IN area via cyclic
communication.
3-18
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
This example shows how to enter a External input 2 to the sensor amplifier ID01.
(1)The device value in the OUT area to which an external input request was
assigned is linked via cyclic communication and the external input of the sensor
amplifier is turned on or off.
(2)You can check the input status of the sensor amplifier with the external input
response.
• When at least one of the external input from the communication or the
input signal cable of the sensor amplifier is on, the sensor amplifier
recognizes that the external input is turned on and then executes an
action assigned to the input (OR operation). If, for example, If, for
example, the reset input has been assigned to external input n, and
when either of the external input from the communication or the input
signal cable of the sensor amplifier is turned on, the reset input is
activated.
• To use the external input to switch banks, set "Bank switching method"
of the sensor amplifier settings to "External input".
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-19
Page 48
3
PLC
(2)
Judgment value property
Each bit of IN [6, 8,10]
Judgment value of ID 01
123445676789
IN area [48 to 51]
Judgment value of ID 02
234556787890
IN area [52 to 55]
Judgment value of ID 03
34568901
IN area [56 to 59]
Sensor amplifier
Judgment value of ID 01
123445676789
Judgment value of ID 02
234556787890
Judgment value of ID 03
34568901
(1)
3-3 Cyclic communication
Reading judgment values (P.V. values) from sensor amplifiers
Judgment values (P.V. values) are read from the IN area to which the ID number of
each sensor amplifier is assigned.
Device assignments: "Monitor Data (84 Words (168 Bytes)) Assembly Instance
(Instance ID): 64H" (Page 3-9)
Communicating with the SK-1000 Series
This example shows how to read the judgment values from the sensor amplifiers
ID01, ID02, and ID03.
(1)When the judgment value of a sensor amplifier is updated, the new judgment
value is entered into the IN area via cyclic communication.
If the judgment value is correct, the parameter range is -99.997 to +99.998.
If the current value is over range, under range, or invalid, the previous value is
retained without updating the current value. Use the value with the judgment
value property.
(2)The properties of the judgment value (Current Value n Over Range (each bit of IN
area [6]), Current Value n Under Range (each bit of IN area [8]), and Current
Value n Invalid (each bit of IN area [10]) are entered. If the judgment value of a
sensor amplifier is "over", "under," or "invalid," the bit corresponding to the ID
number of that sensor amplifier is set to 1.
*For the SK-1000 Series, the judgment value is stored in the current value 0.
3-20
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 49
3-3 Cyclic communication
Checking the Device Compatibility
Compatibility check is a function executed when the scanner communicates with the
DL-EP1. This function checks if the device set with the scanner matches the DL-EP1
to prevent communicating with the wrong device. This function is executed when a
connection is opened.
When using scanners of other manufacturers
For how to use the scanners of other manufacturers, refer to the manual of each
scanner.
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-21
Page 50
3
ScannerDL-EP1Sensor amplifier
Send
Receive
Receive
Send
(1) Message communication
command
(3) Message communication
response
(2) Interpret and
execute command
Reference
3-4
This section describes the message communication functions and how to use them.
What is Message communication (Explicit messaging)?
Message communication is a function that performs communication by issuing
commands using the objects and services (Service Codes) prepared for each
EtherNet/IP device. Message communication is used for applications which do not
require the punctuality of cyclic communication, such as reading and writing adaptor
settings.
The objects and service codes which can be used with message communication
include those which are specified as a standard and those which are unique to the
device. You can use the objects and services unique to the DL-EP1 to monitor data,
Communicating with the SK-1000 Series
to read and write parameters, and to perform operations such as reset.
Message Communication
The DL-EP1 message communication function supports CIP-defined
UCMM (unconnected) and Class 3 (connected) message communication.
3-22
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 51
3-4 Message Communication
Command
Response:
1235
SK Judgment values
(P. V. values): 1235
DL-EP1
Scanner
<Details of command>
Service code: 0EH
Class ID: 67H
Instance ID: 01H
Attribute ID: 0325H (805)
SK
Configuring Message Communication
The following settings are required to execute message communication with the DLEP1.
[DL-EP1]
The DL-EP1 does not require any setting.
[Scanner]
Set the applicable service, Class ID, Instance ID, Attribute ID, and service data, and
send the commands used for message communication. "Objects and Services"
(Page 3-26)
Refer to the scanner manual for details on the setting methods and applicable
commands.
Actions which can be Completed with Message Communication
The following lists the contents that can be executed by message communication
when the objects (DL Object) and services unique to the DL-EP1 are used.
(1) Reading data from a sensor amplifier
(2) Writing data to a sensor amplifier
(3) Issuing operation commands to a sensor amplifier
(4) Locking sensor amplifier operations
(5) Reading the number of decimal places from a sensor amplifier
3
Communicating with the SK-1000 Series
(1) Reading data from a sensor amplifier
Message communication reads parameters from the DL-EP1 and the sensor
amplifier connected to the DL-EP1.
"(1) Reading parameters from a sensor amplifier" (Page 3-46)
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-23
Page 52
3
Command:
1
Response
Hold function of the SK:
Sample hold → Peak hold
DL-EP1
Scanner
<Details of command>
Service code: 10H
Class ID: 67H
Instance ID: 01H
Attribute ID: 0388H (904)
Service data: 1
SK
Command
Response
The SK executes an operation assigned to
external input 1.
DL-EP1
Scanner
<Details of command>
Service code: 4BH
Class ID: 67H
Instance ID: 01H
Attribute ID: 0301H(769)
SK
Command
Response
Changes using the
sensor amplifier keys are locked.
DL-EP1
Scanner
<Details of command>
Service code: 4CH
Class ID: 67H
Instance ID: 00H
Service data: 01H
SK
3-4 Message Communication
(2) Writing data to a sensor amplifier
Message communication writes parameters to the DL-EP1 and the sensor
amplifier connected to the DL-EP1.
Communicating with the SK-1000 Series
"(2) Writing parameters to a sensor amplifier" (Page 3-47)
(3) Issuing operation commands to a sensor amplifier
Message communication issues operation commands such as zero shift to the DLEP1 and the sensor amplifiers connected to the DL-EP1.
"(3) Issuing operation commands to a sensor amplifier" (Page 3-48)
(4) Locking sensor amplifier operations
Message communication locks operations by keys on the sensor amplifier
connected to the DL-EP1.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 53
3-4 Message Communication
Command
Response
DL-EP1
Scanner
<Details of command>
Service code: 4CH
Class ID: 67H
Instance ID: 01H
Attribute ID: 0325H(805)
SK
Reads the number of decimal
places of the SK Judgment
value (P.V. value).
Reference
12530 12.530 12.53kV
Number of
decimal places
321
(5) Reading the number of decimal places from a sensor amplifier
Message communication reads the number of decimal places of settings read
from the sensor amplifier.
"(5) Reading the number of decimal places in the parameter from a sensor
amplifier" (Page 3-51)
For the SK-1000 Series, if the current value is 12.53kV mm, data is stored
as follows:
Data: 12530
Number of decimal places: 3
3
Communicating with the SK-1000 Series
Perform calculation from the read data and the number of decimal places.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-25
Page 54
3-4 Message Communication
ID: 0324H Output
Attribute
ID: 0325H
Judgment value (P.V. value)
ID: 0326H Raw value (R.V. value)
DL Object
(Class ID: 67H)
DL-EP1
Instance ID: 00H
ID number 1 sensor
Instance ID: 01H
ID number 2 sensor
Instance ID: 02H
:
:
Objects and Services
Message communication uses objects and services to send and receive data.
Executing a service (1) for a DL-EP1 object enables data read (2), parameter
change (3), specified operation execution (4), and read of the number of decimal
places (5), etc.
3
Communicating with the SK-1000 Series
DL-EP1 or sensor amplifier connected to DL-EP1
Service
Data output
Object
(1)
(2)
(3)
Parameter change
(4)
Operation command execution
(5)
Read of the number of decimal places
Taking DL Object as an example, one instance is provided for each of the sensor
amplifiers connected to the DL-EP1. Reading the attributes corresponding to the
judgment values (P.V. values) of the respective instances using a service makes it
possible to read the judgment values (P.V. values) of the sensor amplifiers
corresponding to the respective instances.
3-26
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 55
3-4 Message Communication
Command
Response
・Service
・Class ID
・Instance ID
・Attribute ID*
・Service data*
・General Status
・Additional Status*
・Service response data*
・ In EtherNet/IP (CIP), the method called "object modeling" is used to
Reference
express a device. The device is handled as a group of objects. Objects
abstractly express the configuration elements in the device. A class is a
group of objects expressing the configuration elements of the same
type. An instance actually expresses a specific object contained in a
class. Each instance in the class has the same attribute group, but each
uses a unique attribute value.
・ To execute a service for the DL-EP1, send a command from the scanner.
The DL-EP1 then returns the service execution results as a response. A
command requires a service, class ID (Class ID), instance ID (Instance
ID), and attribute ID (Attribute ID)
*
. When a parameter is written, the
command also requires a setting (service data).
* Some of the commands to be used may not require the above items.
"Basic Format and Processing Flow of Message Communication"
(Page 3-29)
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-27
Page 56
3
Command
Response
DL
Object
Message
Router
Object
Connection
Manager
Object
Assembly
Object
Identity
Object
TCP/IP
Interface
Object
Ethernet
Link
Object
EtherNet/IP unit
3-4 Message Communication
Objects Usable by DL-EP1
The following describes the objects usable by the DL-EP1.
Communicating with the SK-1000 Series
Object NameClass IDDescription
This object provides the statuses of the DL-EP1 and
DL Object67H
Identity Object01H
Message Router
Object
Assembly Object04H
Connection
Manager Object
TCP/IP Interface
Object
Ethernet Link ObjectF6HThis object provides Ethernet status information.5-31
the sensor amplifiers connected to the DL-EP1 and
writes and reads parameters. This object is unique to
the DL-EP1.
This object provides identification information,
general information and a reset service, etc.
This object provides connection points for message
02H
communication.
This object provides access to the devices via cyclic
communication. This object can be used to send data
to the devices that do not support cyclic
communication.
This object is used for connection-type
06H
communication.
This object provides the structure for setting the TCP/
F5H
IP network interface. You can set an IP address,
subnet mask and gateway, etc., in this object.
Reference
Page
3-32
5-19
5-22
5-23
5-25
5-27
3-28
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 57
3-4 Message Communication
Basic Format and Processing Flow of Message Communication
The EtherNet/IP scanner and the DL-EP1 exchange Explicit messages for
communication. The following provides a basic example of the command format of
Explicit messages to be sent and the response format returned from the DL-EP1 to
the scanner.
● Commands
・Command format
ItemDescription
Service code
Class IDDesignates a class ID (Class ID) tailored to the service
Instance ID
Attribute ID
Service DataDesignates service data (Service Data) tailored to the service
*1
*1 For details on usable services, refer to "DL Object (Class ID:67H)" (Page 3-
32) or "Objects Usable by DL-EP1" (Page 5-17).
● Responses
・Response format
Designates the service code to be used (Service Code).
Designates an instance ID (Instance ID) tailored to the service
used.
Designates an attribute ID (Attribute ID) tailored to the service
used.
*1
to be used.
*1
to be
*1
to be
*1
to be used.
3
Communicating with the SK-1000 Series
ItemDescription
General status
Additional statusReturns the additional status (Additional Status).
Service response
data
Returns a general status in respect to the command (General Status). 00H
is returned when the command ends normally.
Returns service response data Service Response Data) in respect to the
command.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-29
Page 58
3
Class ID check
Yes
No
Instance ID check
Yes
No
Service check
Yes
No
Attribute ID check
Executes supported service process
Yes
No
Path Destination Unknown (05H)
returned as general status
Path Destination Unknown (05H)
returned as general status
Service not Supported (08H)
returned as general status
Attribute not Supported (14H)
returned as general status
3-4 Message Communication
Command processing order and error response
Check whether each ID is within the supported range in the following order:
Communicating with the SK-1000 Series
● Supplement for object processing
• Get_Attribute_Single and Get_Attributes_All are executed, ignoring send service
data.
• The service (Get_Attributes_All, Reset) that does not designate an attribute ID is
executed, ignoring Attribute ID.
• If Set_Attribute_Single is designated for an attribute which cannot be written (Set),
"0EH" (Attribute not settable) is returned as the general status.
• If Set_Attribute_Single for the writable attribute is designated and the writing size
is less than the attribute size, the general status "13H" (Not enough data) is
returned. If the writing size is greater than the attribute size, the service is
executed, ignoring the excessive data.
3-30
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 59
3-4 Message Communication
Reading the DL Object Table
Reading the attribute ID
Example) Excerpt from DL Object attribute ID
(1)(2)(3)(4)(5)(6)
Instance IDAttribute
00H
(1) Instance IDRepresents the instance ID in hexadecimal notation.
(2) Attribute IDRepresents the attribute ID in hexadecimal (decimal) notation.
(3) NameRepresents the attribute name.
(4) Description
(5) Attribute
(6) Data typeRepresents the attribute data type.
74H
(116)
ItemDescription
NameDescription
ID
Stores the HI output (output 1) status of
each sensor amplifier. When HI is output,
Output 1
Describes the attribute and represents the data to be read and the range of
parameters that can be set.
Represents the direction of services for the attribute ID.
R (Read): The parameter read service (Get_Attribute_Single,
W (Write): The parameter write service (Set_Attribute_Single) can be used
the bit corresponding to the ID number of
the sensor amplifier is set to ON.
Bit 0 to bit 3: ID number 1 to ID number 4
Bit 4 to bit 15: Reserved for system
Get_Attributes_All) can be used to read the attribute value.
to write the attribute value.
Attribute
R
Data
Ty pe
WORD
3
Communicating with the SK-1000 Series
Data Type
The data type is defined in the EtherNet/IP specifications as follows:
Data TypeDescription
INTSigned 16-bit integer-3276832767
UINTUnsigned 16-bit integer065535
DINTSigned 32-bit integer-21474836482147483647
WORDBit string: 16 bits--
DWORDBit string: 32 bits--
STRING
Character string
(2-byte length information +
1-byte array per character)
MinimumMaximum
--
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Range
3-31
Page 60
3-4 Message Communication
DL Object (Class ID:67H)
The DL Object provides the DL-EP1 connection status and device write/read. This
object is unique to the DL-EP1.
● Services
3
Communicating with the SK-1000 Series
Service
Code
0EH
10H
*1
4BH
4CH
4DH
Service NameDescription
Reads parameters from the DL-EP1 and the sensor amplifier
Parameter
read
Parameter
write
Operation
command
Batch lock
*2
setting
Acquisition of the
number of decimal
places
*
connected to the DL-EP1. For examples of using this service,
refer to "(1) Reading parameters from a sensor amplifier"
(Page 3-46).
Writes parameters to the DL-EP1 and the sensor amplifier
connected to the DL-EP1. For examples of using this service,
refer to "(2) Writing parameters to a sensor amplifier"
(Page 3-47).
Requests processing such as zero shift and tuning from the
sensor amplifier connected to the DL-EP1. The contents of
processing that can be requested differ per sensor amplifier.
Set the contents of processing with the attribute ID in the
object.
refer to "Attribute IDs supported by the instance service
4BH (operation command)" (Page 3-48). For examples of
using this service, refer to
"(3) Issuing operation commands to a sensor amplifier"
(Page 3-48).
Collectively performs lock or unlock for all the connected
sensor amplifiers. Even if a lock setting that is not supported
by sensor amplifiers is designated, locks all the sensor
amplifiers without interrupting processing. Then, error code
09H is returned as a response.
Setting 0: Not lock
Setting 1: Key lock
"Lock setting" (Page 3-33)
For examples of using this service, refer to "(4) Locking
sensor amplifier operations" (Page 3-50).
Acquires the number of decimal places of the designated
parameter. For examples of using this service, refer to "(5)
Reading the number of decimal places in the parameter from
3
a sensor amplifier" (Page 3-51).
*1 This service cannot be used in the DL-EP1 (instance ID:00H).
*2 This service cannot be used in the sensor amplifier (instance ID: 01H to 08H)
connected to the DL-EP1.
*3 In the DL-EP1 (instance ID: 00H), this service can be used as the attribute ID
90H to 9EH and A0H to AEH.
3-32
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 61
3-4 Message Communication
・ Lock setting
SettingDescription
0
1
Does not execute lock.
Executes key lock (inhibition of operations other than basic screen display
switching and [RESET] button).
● Responses
The responses made when each service is used are as follows:
(1) Parameter read:: Service code 0EH
(2) Parameter write:: Service code 10H
(3) Operation command:: Service code 4BH
(4) Batch lock setting:: Service code 4CH
(5) Read of number of decimal places: : Service code 4DH
3
Communicating with the SK-1000 Series
General
Status
00HNormal end
05HThe instance ID is out of range.
08H-- -
09H ----The written data is out of range.
0CH- --
0EH----
10H----
13H--
14H - The attribute ID is out of range.
16H -
1FH
FEHSystem error. Contact your nearest KEYENCE office.
Command Type
(1) (2) (3) (4) (5)
Description
The designated instance ID does not support this service or
cannot be executed.
• Parameter write was executed for the function controlled
by cyclic communication.
• An attempt to execute the operation command has failed.
Check if the sensor amplifier can execute the operation
command.
An attempt was made to write data to the attribute ID that
cannot be written or to the attribute ID that is in the unwritable
status.
An attempt was made to read data from the attribute ID that
cannot be read or from the attribute ID that is in the
unreadable status.
The service data size is less than the defined size.
The defined data size is stored in the additional status.
The sensor amplifier corresponding to the designated
instance ID is not connected.
• This service is supported by the designated instance ID
but cannot be used by the designated attribute ID.
(Additional status: C350H)
• In the current mode, the designated setting cannot be
written into the parameter.
(Additional status: C351H)
• The DL-EP1 is now initializing communication. (Additional
status: C352H)
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-33
Page 62
3-4 Message Communication
● Attributes
3
Communicating with the SK-1000 Series
Instance
ID
00H
Attribute
ID
64H
(100)
65H
(101)
66H
(102)
67H
(103)
68H
(104)
69H
(105) to
6BH
(107)
6CH
(108)
6DH
(109)
6EH
(110)
6FH
(111)
70H
(112) to
73H
(115)
74H
(116)
75H
(117)
76H
(118)
NameDescription
Indicates the status of this unit and connected
sensor amplifier.
Status
Sensor Error
Status
Warning Status (Unassigned)
Reserved for system
Current Value 0
Property
Reserved for system
Error ID
Number
Error Code
Warning I D
Number
Warning Code(Unassigned)
Reserved for system
Output1
(HI)
Output2
(LO)
Output3
(GO)
bit0: DL-EP1 Error Status
Bit 1 to bit 13: Reserved for system
bit14: Warning Status
bit15: Error Status
Indicates the error status of the connected
sensor amplifiers. If an error occurs, the bit of
the corresponding ID number of amplifier is
turned to ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
Indicates the status of current value 0 of each
amplifier. If the current value 0 is “Over
Range", “Under Range", or "Invalid", the bit
corresponding to the ID number is turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
Indicates the ID number of the unit having
error.
Parameter range: 0 to 8
Indicates the error code that is happening.
Parameter range: 0 to 65535
(Unassigned)
Indicates the HI output (output 1) status of
each amplifier. When HI is output, the bit
corresponding to the ID number of the sensor
amplifier is turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
Indicates the LO output (output 2) status of
each amplifier. When LO is output, the bit
corresponding to the ID number of the sensor
amplifier is turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
Indicates the GO output (output 3) status of
each amplifier. When GO is output, the bit
corresponding to the ID number of the sensor
amplifier is turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
Data
Attribute
Ty p e
R
WORD
R
WORD
R
WORD
R
WORD
RUINT
RUINT
RUINT
RUINT
R
WORD
R
WORD
R
WORD
3-34
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 63
3-4 Message Communication
Instance
ID
00H
Attribute
ID
77H
(119)
78H(120)Output5
79H
(121) to
89H
(137)
8AH
(138)
8BH
(139)
8CH
(140)
8DH
(141)
8EH
(142)
8FH
(143)
90H
(144)
91H
(145) to
96H
(150)
97H
(151)
98H
(152) to
AFH
(175)
B0H
(176)
NameDescription
Output4
(Alarm output)
(Unassigned)
Reserved for system
Current Value 0
Invalid
Current Value 0
Under Range
Current Value 0
Over Range
Current Value 1
Invalid
Current Value 1
Under Range
Current Value 1
Over Range
Current Value 0
(ID Number 1)
Current Value 0
(ID Number 8)
Reserved for system
Sensor Status
Mask Setting
Data
Attribute
Ty pe
Indicates the status of alarm output (output 4)
of each amplifier. When alarm is output, the bit
corresponding to the ID number of the sensor
amplifier is turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
(Unassigned)
R
WORD
3
When the current value 0 of each amplifier is
invalid, the bit of corresponding ID number is
turned ON.
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
When the current value 0 of each amplifier is
less than the lower limit of the detection range,
the bit of the corresponding ID number is
turned ON
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
When the current value 0 of each amplifier is
higher than the upper limit of the detection
range,
turned ON
Bit 0 to bit 7: ID number 1 to ID number 8
Bit 8 to bit 15: Reserved for system
(Unassigned)
(Unassigned)
(Unassigned)
Indicates the current value 0 of the sensor of
ID number 1.
Parameter range:
-2147483648 to 2147483647
Indicates the current value 0 of the sensor ID
number 8.
Parameter range:
-2147483648 to 2147483647
Set up the condition to determine if the sensor
error or warning is the recoverable DL-EP1
error (MS LED blinks in red). If mask is
selected, MS LED does not blink in red when a
sensor error or warning occurs.
Parameter range: 0 to 1 (initial value: 0)
0: Not mask
1: Mask
.
the bit of corresponding ID number is
.
:
R
WORD
R
WORD
R
WORD
R
WORD
R
WORD
R
WORD
RDINT
RDINT
R/WUINT
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-35
Page 64
3-4 Message Communication
Reference
3
Communicating with the SK-1000 Series
Instance
ID
00H
Attribute
ID
B1H
(177)
B2H
(178) to
C7H
(199)
0300H
(768)
0301H
(769) to
0307H
(775)
0308H
(776)
0309H
(777) to
04FFH
(1279)
NameDescription
Sensor
Connected
Number
Reserved for system
Error Code
(ID number 1)
Error Code
(ID number 8)
Reserved for system
Indicates the number of connected sensor
amplifiers.
Parameter range: 0 to 8
Indicates the error code of ID number 1.
Parameter range: 0 to 65535 (initial value: 0)
Indicates the error code of ID number 8.
Parameter range: 0 to 65535 (initial value: 0)
Attribute
RUINT
RUINT
:
RUINT
For details on current value 0 and current value 1, refer to "Current
Value 0/Current Value 1" (Page 3-12).
Data
Ty p e
3-36
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 65
3-4 Message Communication
● Attributes for SK-1000 Series
Designate the ID number (01H to 08H) of a sensor amplifier as the instance ID.
When the parameter range includes decimal data, a value should be read or
written as an integer by ignoring the decimal point. For example, when writing
"+1.235" as the HI-side setting value (BANK 0), write "+1235".
Class
Group1
Attribute
ID
0320H
(800)
0321H
(801)
0322H
(802)
0323H
(803)
0324H
(804)
0325H
(805)
0326H
(806)
0327H
(807)
0328H
(808)
0329H
(809) to
032AH
(810)
NameDescription
Group1
Entry count
Sensor amplifier
*1
error
(Reserved for system)
(Reserved for system)
Judgment
output/Alarm
output
Judgment value
(P.V. Value)
Internal
measurement
value
(R.V. value)
Peak hold value
during hold
period
Bottom hold
value during
hold
period
(Reserved for system)
Indicates the number of items (entries) that
can be set in Group 1.
Parameter range: 24
Indicates the error status of the sensor
amplifier.
When an error occurs, the corresponding bit
turns on.
bit0: Overcurrent error
bit1: EEPROM error
bit2: Head error
bit7: Head temperature/humidity error
bit11: Amplifier communication error
Other than above: Fixed to 0
Indicates the output status of the sensor.
When an output is on, the corresponding bit
turns on.
Bit0:HI judgment output
Bit1:LO judgment output
Bit2:GO judgment output
Bit3:Alarm output
Indicates the judgment value (P.V. value).
Parameter range: -99.999 to +99.999
Indicates the internal measurement value (R.V.
value).
Parameter range:-99.999 to +99.999
• In the mode other than the sample hold
mode
Indicates the peak-hold value during the
sampling period.
Parameter range:
-99.999 to +99.999
• In the sample hold mode
Parameter range: -99.998
• In the mode other than the sample hold
mode
Indicates the bottom-hold value during the
sampling period.
Parameter range:
-99.999 to +99.999
• In the sample hold mode
Parameter range: -99.998
Data
Attribute
Ty pe
RDINT
DWORD
R
DWORD
R
RDINT
RDINT
RDINT
RDINT
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-37
Page 66
3-4 Message Communication
3
Communicating with the SK-1000 Series
Class
Group1
Attribute
ID
032BH
(811)
032CH
(812)
033DH
(813)
033EH
(814)
032FH
(815) to
0332H
(818)
0333H
(819)
0334H
(820)
0335H
(821)
0336H
(822)
0337H
(823)
NameDescription
Indicates the currently active bank No.
Use this attribute to check the bank No. for
which the sensor amplifier is actually
Bank status
Timing status
Temperature
*3
Humidity
(Reserved for system)
Abnormal
*4
setting
External input
status
EEPROM write
*5
result
Zero shift/Zero
shift reset
*6
result
Reset request
result
operating.
Parameter range: 0 to 3
0: Bank 0
1: Bank 1
2: Bank 2
3: Bank 3
Indicates the currently active timing status.
Use this attribute to check the timing status
under which the sensor amplifier is actually
operating.
Parameter range: 0 to 1
0: During Sampling
1: Not during sampling
Indicates the current temperature.
*2
Parameter range: -999.9 to +999.9
Indicates the current humidity.
Parameter range: 0.0 to 100.0
Indicates the abnormal setting state.
Parameter range: 0 to 1
0:Normal setting
1:Abnormal setting
Indicates the external input status. When the
external input cable of the sensor amplifier or
the external input of the cyclic communication
is on, the corresponding bit turns on.
This operation is enabled even when "Not
used" is selected for the function setting of
external inputs 1 through 4.
Bit0:External input 1
Bit1:External input 2
Bit2:External input 3
Bit3:External input 4
Indicates the result of writing to EEPROM.
Parameter range: 0 to 2
0:Writing
1:Normal termination
2:Abnormal termination
Indicates the result of zero shift or zero shift
reset.
Parameter range: 0 to 2
0:Executing
1:Normal termination
2:Abnormal termination
Indicates the result of reset.
Parameter range: 0 to 2
0:Executing
1:Normal termination
2:Abnormal termination
Data
Attribute
Ty p e
RDINT
RDINT
RDINT
RDINT
RDINT
DWORD
R
RDINT
RDINT
RDINT
3-38
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 67
3-4 Message Communication
Class
Group1
Group2
Attribute
ID
0338H
(824)
0339H
(825) to
033FH
(831)
0340H
(832)
0341H
(833)
0342H
(834)
0343H
(835) to
0345H
(837)
0346H
(838)
0347H
(839)
0348H
(840) to
034AH
(842)
034BH
(843)
034CH
(844)
034DH
(845) to
034FH
(847)
0350H
(848)
0351H
(849)
NameDescription
Indicates the current status of the system
parameters. Use this attribute to check the
system parameters with which the sensor
amplifier is actually operating.
The corresponding bit turns on according to
the current status.
Current system
parameters
(Reserved for system)
Group2 Entry
count
HI setting value
(BANK 0)
LO setting value
(BANK 0)
(Reserved for system)
HI setting value
(BANK 1)
LO setting value
(BANK 1)
(Reserved for system)
HI setting value
(BANK 2)
LO setting value
(BANK 2)
(Reserved for system)
HI setting value
(BANK 3)
LO setting value
(BANK 3)
bit 0:
*7
0:NPN
1:PNP
bits 1, 2 and 3 (For main unit only. Fixed to 000
for expansion unit)
000: Analog output OFF
001: 0 to 5 V
010: -5 to +5 V
011: 1 to 5 V
100: 4 to 20 mA
Indicates the No. of Group 2 entries.
Parameter range: 17
Set up setting value of HI side (BANK 0).
Parameter range: -99.999 to +99.999
(initial value: +1.000)
Set up setting value of LO side (BANK 0).
Parameter range: -99.999 to +99.999
(initial value: -1.000)
Set up setting value of HI side (BANK 1).
Parameter range: -99.999 to +99.999
(initial value: +1.000)
Set up setting value of LO side (BANK 1).
Parameter range: -99.999 to +99.999
(initial value: -1.000)
Set up setting value of HI side (BANK 2).
Parameter range: -99.999 to +99.999
(initial value: +1.000)
Set up setting value of LO side (BANK 2).
Parameter range: -99.999 to +99.999
(initial value: -1.000)
Set up setting value of HI side (BANK 3).
Parameter range: -99.999 to +99.999
(initial value: +1.000)
Set up setting value of LO side (BANK 3).
Parameter range: -99.999 to +99.999
(initial value: -1.000)
Data
Attribute
Ty pe
RDINT
RDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-39
Page 68
3-4 Message Communication
3
Communicating with the SK-1000 Series
Class
Group2
Group3
Attribute
ID
0352H
(850) to
035FH
(863)
03
60H
(864)
0361H
(865)
0362H
(866)
0363H
(867)
0364H
(868) to
0367H
(871)
0368H
(872)
NameDescription
(Reserved for system)
Group3 Entry
count
Key lock
function
Bank function
Timing input
(Reserved for system)
Sub display's
screen
Indicates the No. of Group 3 entries.
Parameter range: 9
For read:
Reads the current attribute. Use "Bank status"
(032BH (811)) to check the bank No. for which
the sensor amplifier is operating.
Parameter range: 0 to 3 (initial value: 0)
For write:
To use this attribute to change the bank No.,
set "Bank switching method" (0396H (918)) to
"Button". The change is disabled when
"External input" is set.
Parameter range: 0 to 3
0: Switches to bank 0.
1: Switches to bank 1.
2: Switches to bank 2.
3: Switches to bank 3.
Set up status of timing input.
Use "Timing status" (032CH (812)) to check
the timing input status under which the sensor
amplifier is operating.
The sensor amplifier operates based on the
*8
OR of the external input cable and cyclic
communication statuses.
Parameter range: 0 to 1 (initial value: 0)
0:Timing input OFF
1:Timing input ON
Set up sub display's screen.
Parameter range: 0 to 5 (initial value: 0)
0: Temperature and humidity
1: Temperature
2: Humidity
3: HI setting value
4: LO setting value
5: RV
Data
Attribute
Ty p e
RDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
3-40
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 69
3-4 Message Communication
Class
Group3
Group4
Attribute
ID
0369H
(873)
036AH
(874) to
037FH
(895)
0380H
(896)
0381H
(897)
0382H
(898)
0383H
(899) to
0384H
(900)
0385H
(901)
0386H
(902)
0387H
(903)
0388H
(904)
NameDescription
Set up system parameter.
To reflect the setting, you need to send
"System parameter set request" (0306H (774))
operation command after writing the setting.
Use 0338H (824) to check the system
parameter with which the sensor amplifier is
System
parameter
*7
settings
(Reserved for system)
Group4 Entry
count
(Reserved for system)
Range setting
(Reserved for system)
Averaging
Output mode
(Reserved for system)
Hold function
setting
operating.
bit 0:
0: NPN
1: PNP
bits 1, 2 and 3 (For main unit only. Fixed to 000
for expansion unit)
000: Analog output OFF
001: 0 to 5V
010: -5 to 5V
011: 1 to 5V
100: 4 to 20mA
Indicates the No. of Group 4 entries.
Parameter range: 26
Set up measurement range.
Parameter range: 0 to 2 (initial value: 0)
0: NEAR
1: FAR
2: Ib
Set up averaging/diff. count filter/high-pass
filter.
Parameter range: 0 to 8 (initial value: 5)
0: 1 time
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 64 times
6: 256 times
7: 1024 times
8: 4096 times
9: 16384 times
Set up output mode.
Parameter range: 0 to 1 (initial value: 0)
0: N.O.
1: N.C.
Set up hold function.
Parameter range: 0 to 5 (initial value: 0)
0:Sample hold
1:Peak hold
2:Bottom hold
3:Absolute value hold
4:Auto peak hold
5:Auto bottom hold
6:Auto absolute value hold
Data
Attribute
Ty pe
R/WDINT
RDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-41
Page 70
3-4 Message Communication
3
Communicating with the SK-1000 Series
Class
Group4
Attribute
ID
0389H
(905)
038AH
(906)
038BH
(907) to
038CH
(908)
038DH
(909)
038EH
(910)
038FH
(911)
0390H
(912)
0391H
(913)
0392H
(914)
0393H
(915)
0394H
(916)
0395H
(917)
NameDescription
(Reserved for system)
Timing input
setting
(Reserved for system)
Hysteresis
Analog output
*9
scaling
Analog output
upper limit
Analog output
lower limit
External input
*10
External input 1
*10
External input 2
*10
External input 3
*10
External input 4
*10
Set up timing input.
Parameter range: 0 to 1 (initial value: 0)
0:Level
1:Edge
Set up hysteresis.
Parameter range: 0.000 to 99.999
(initial value: 0.100)
Set the analog output scaling.
(For main unit only.)
Parameter range: 0 to 1 (initial value: 0)
0: Initial state
1: Free range
Set the analog output upper limit.
(For main unit only.)
*9
Parameter range: -99.999 to 99.999
(initial value: +10.000)
Set the analog output lower limit.
(For main unit only.)
*9
Parameter range: -99.999 to 99.999
(initial value: -10.000)
Set up whether to change the function
assigned to external input 1/2/3/4 from the
initial state.
Parameter range: 0 to 1 (initial value: 0)
0:Initial state
1:User setting
Set up function to be assigned to external
input 1.
Parameter range: 0 to 3 (initial value: 0)
0:Zero shift input
1:Bank A input
2:Bank B input
3:Not used
Set up function to be assigned to external
input 2.
Parameter range: 0 to 3 (initial value: 0)
0:Reset input
1:Bank A input
2:Bank B input
3:Not used
Set up function to be assigned to external
input 3.
Parameter range: 0 to 3 (initial value: 0)
0:Timing input
1:Bank A input
2:Bank B input
3:Not used
Set up function to be assigned to external
input 4.
Parameter range: 0 to 2 (initial value: 0)
0:Bank A input
1:Bank B input
2:Not used
Data
Attribute
Ty p e
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
3-42
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 71
3-4 Message Communication
Class
Group4
Group5
Group6
Attribute
ID
0396H
(918)
0397H
(919)
0398H
(920)
0399H
(921)
039AH
(922)
039BH
(923) to
039FH
(927)
03A0H
(928)
03A1H
(929)
03A2H
(930)
03A3H
(931)
03A4H
(932)
03A5H
(933) to
03BFH
(959)
03C0H
(960)
03C1H
(961)
03C2H
(962)
03C3H
(963)
NameDescription
Bank switching
method
(Reserved for system)
Zero shift value
memory
function
(Reserved for system)
Display digit
(Reserved for system)
Group5
Entry count
Distance
correction
method
Near-side
distance
correction
amount
Far-side
distance
correction
amount
Area scaling
(Reserved for system)
Group6
Entry count
Product code
Revision
Connected
sensor head
Set up method for switching the Bank.
Parameter range: 0 to 1 (initial value: 0)
0:Button
1:External input
Set up whether to save the zero-shift state.
Parameter range: 0 to 1 (initial value: 0)
0: OFF
1: ON
Set up display digit. (initial value: 0)
0:Initial state
1:0.001
2:0.01
3:0.1
4:1
Indicates the No. of Group 5 entries.
Parameter range: 4
Set the distance correction method.
Parameter range: 0 to 1 (initial value: 0)
0: Initial state
1: User setting
Set the near-side distance correction amount.
Parameter range: 5 to 50
(initial value: 25)
Set the far-side distance correction amount.
Parameter range: 60 to 120
(initial value: 100)
Set the area scaling.
Parameter range: 0.10 to 1.50
(initial value: 1.00)
Indicates the No. of Group 6 entries.
Parameter range: 11
Indicates the product code.
Main unit: 4024
Expansion unit : 4025
Indicates the revision.
The higher-order bytes in the lower-order word
indicate the major revision and the lower-order
bytes indicate the minor revision.
Parameter range: 0101H
Indicates model of sensor head connected to
the amplifier.
0:Not connected
1:The head is connected
Data
Attribute
Ty pe
R/WDINT
R/WDINT
R/WDINT
RDINT
R/WDINT
R/WDINT
R/WDINT
R/WDINT
RDINT
RDINT
RDINT
RDINT
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-43
Page 72
3-4 Message Communication
3
Communicating with the SK-1000 Series
Class
Group6
Attribute
ID
03C4H
(964) to
03C7H
(967)
03C8H
(968)
03C9H
(969) to
03D6H
(982)
03D7H
(983)
03D8H
(984)
03D9H
(985)
03DCH
(988) to
03DFH
(991)
NameDescription
(Reserved for system)
Product name
(Reserved for system)
Series code
Series version
Device type
(Reserved for system)
Indicates the product name.
Main unit: "SK-1000"
Expansion unit : "SK-1050"
Indicates the series code.
Main unit: 4024
Expansion unit : 4025
Indicates the series version.
Parameter range: 1
Indicates the device type.
Parameter range: 0
Data
Attribute
Ty p e
R
STRING
RDINT
RDINT
RDINT
*1The on/off status of the bits indicates the type of error occurred in the sensor
amplifier.
OFF (0): No error, ON (1): Error occurred
More than one error may occur simultaneously. For details of the errors, refer to
“SK-1000 Series Instruction Manual”.
*2This is -999.8 when the temperature is not acquired correctly.
*3This is 999.8 when the humidity is not acquired correctly.
*4If a prohibited combination of functions is written, an "abnormal setting (1)" will
result. For details on each function, see the "SK-1000 Series Instruction
Manual."
*5The results of the "Initial reset request" and "System parameter set request"
operation commands are also included in this item.
*6The result of "Zero shift execution request" or "Zero shift reset execution
request", whichever requested last, will be read.
*7By reading "Current system parameters", you can check the system
parameters of the sensor amplifier. The system parameters refer to the polarity
of the judgment and alarm outputs and the analog output setting. Specify the
system parameters to be set when "System parameter set request" is executed
in an operation command.
3-44
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 73
3-4 Message Communication
011 0
Bits 3, 2, 1: 1 to 5 VBit 0: NPN output
A value to be read or written is specified as on/off status of the bits
representing the value converted into binary.
BitSetting
0: NPN output
1: PNP output
000: Analog output OFF
001: 0 to 5 V
010: -5 to +5 V
011: 1 to 5 V
100: 4 to 20 mA
(Fixed to 000 for expansion unit)
When the read data is "6":
Reference
0
3, 2, 1
The decimal number "6" is represented in binary as "0110".
As a result, the sensor amplifier of the read data is set to "NPN output" and
"analog output of 1 to 5 V".
*8Operates as "off" only when input off (0) is written and the external input is off
for both cable and cyclic communication.
*9When a value is written to an expansion unit, a writing error occurs.
*10To reflect the settings written for the function selection of external inputs 1 to 4
(0392H (914) to 0395H (917)) to the sensor amplifier, you need to set the
external input setting (0391H (913)) to 1 (User setting) or to operate the sensor
amplifier's button to set the external input to "User setting".
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-45
Page 74
3-4 Message Communication
Using DL Object
The following describes how to perform message communication with a DL Object.
(1) Reading parameters from a sensor amplifier
(2) Writing parameters to a sensor amplifier
(3) Issuing operation commands to a sensor amplifier
(4) Locking sensor amplifier operations
(5) Reading the number of decimal places from a sensor amplifier
3
Communicating with the SK-1000 Series
(1) Reading parameters from a sensor amplifier
Message communication reads each parameter from the DL-EP1 and the sensor
amplifier connected to the DL-EP1.
Service code 0EH is used.
The following settings are required to use this object.
• Service Code
• Class ID
• Instance ID
• Attribute ID
• Commands
ItemDescriptionData Example
Service CodeDesignates "Parameter read (0EH)" (fixed value).
Class IDDesignates DL Object(67H) (fixed value).
Instance IDDesignates the ID number.
Attribute IDDesignates the attribute ID to be read from "Attribute".
Service Data There is no service data.
• Responses (when successful)
ItemDescriptionData Example
General status
Service response data The settings of the read parameter are returned.
A status (00H) is returned that indicates normal
completion of message communication.
• Responses (when unsuccessful)
0EH
67H
0AH
0324H(804)
-
00H
0000H
ItemDescriptionData Example
General statusA general status for the service is returned
Additional statusAn additional status is returned.
Service response data There is no service response data.
16H
-
-
For details on the attribute ID, settings, general status, and additional status of each
parameter, refer to "DL Object (Class ID:67H)" (Page 3-32) and "Attributes"
(Page 3-34).
3-46
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 75
3-4 Message Communication
(2) Writing parameters to a sensor amplifier
Message communication writes parameters to the DL-EP1 and the sensor amplifier
connected to the DL-EP1.
Service code 10H is used.
The following settings are required to use this object.
• Service Code
• Class ID
• Instance ID
• Attribute ID
• Service Data
• Commands
ItemDescriptionData Example
Service CodeDesignates "Parameter write (10H)" (fixed value).
Class IDDesignates DL Object(67H) (fixed value).
Instance IDDesignates the ID number.
Attribute IDDesignates the attribute ID to be written from "Attribute".
Service Data Writes the setting.
• Responses (when successful)
ItemDescriptionData Example
A status (00H) is returned that indicates normal
General status
Service response data There is no service response data.
completion of message communication. (The written
parameters are reflected in the sensor amplifier at the
status (00H) return timing.)
10H
67H
05H
0347H(839)
0064H
00H
-
3
Communicating with the SK-1000 Series
• Responses (when unsuccessful)
ItemDescriptionData Example
General status
Additional statusAn additional status is returned.
Service response data There is no service response data.
A general status for the service is returned
0EH
-
-
For details on the attribute ID, settings, general status, and additional status of each
parameter, refer to "DL Object (Class ID:67H)" (Page 3-32) and "Attributes"
(Page 3-34).
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-47
Page 76
3
Point
3-4 Message Communication
(3) Issuing operation commands to a sensor amplifier
Message communication issues operation commands such as zero shift or reset to
the sensor amplifiers connected to the DL-EP1.
Service code 4BH is used.
The following settings are required to use this object.
• Service Code
• Class ID
• Instance ID
• Attribute ID
Communicating with the SK-1000 Series
• Attribute IDs supported by the instance service 4BH (operation command)
The contents of processing performed by the instance service 4BH (operation
command) depend on the attribute ID to be selected.
The table below details the attribute IDs that can be selected.
Before executing an operation command, confirm that the sensor amplifier
is ready to execute operation commands. For the confirmation method,
refer to “SK-1000 Series Instruction Manual”. After executing an operation
command, confirm the successful completion of the command.
Attribute IDNameDescription
0301H
(769)
0302H
(770)
0303H
(771)
0305H
(773)
0306H
(774)
Executes zero shift. Turning off the power to the sensor
Zero shift execution
request
Zero shift reset execution
request
Reset requestExecutes resetting.
Initial reset request
System parameter set
request
amplifier after executing zero shift restores the state
that existed before the zero shift function was used. To
retain the shifted state after turning off the power, turn
on the zero shift value memory function.
Resets the zero shift value.
Initializes all settings, except for sensor amplifier
system parameters. Once an initial reset request is
executed, all parameters are stored into the nonvolatile
memory (EEPROM) in approximately three seconds.
When completed, the setting/status command
parameter "EEPROM write result" flips to "successfully
completed (1)". After the completion, "EEPROM write
result" of the attributes for SK-1000 Series changes to
Normal termination (1).
Changes the system parameters (the polarity of the
judgment and alarm outputs and the analog output
setting) to the values written in "System parameter
settings" of the attributes for SK-1000 Series.
To set the system parameters, confirm that the change
is proper according to the connected devices and
wiring.
A wrong change may damage the sensor amplifier or
the connected equipment.
3-48
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 77
• Commands
ItemDescriptionData Example
Service Code
Class IDDesignates DL Object (67H)(fixed value).
Instance ID
Attribute ID
Service Data There is no service response data.
Designates the "operation command (4BH)" (fixed
value).
Designates the ID number. The ID number (00H) of the
DL-EP1 cannot be designated.
Designates the attribute ID to be designated from
"Attribute". "(3) Issuing operation commands to a
sensor amplifier" "Attribute IDs supported by the
instance service 4BH (operation command)" (Page 3-
48)
• Responses (when successful)
ItemDescriptionData Example
General status
Service response data There is no service response data.
A status (00H) is returned that indicates normal
completion of message communication.
• Responses (when unsuccessful)
ItemDescriptionData Example
General statusA general status for the service is returned
Additional statusAn additional status is returned.
Service response data There is no service response data.
3-4 Message Communication
4BH
67H
08H
0301H(769)
-
00H
-
08H
-
-
3
Communicating with the SK-1000 Series
For details on the attribute ID, settings, general status, and additional status of each
parameter, refer to "DL Object (Class ID:67H)" (Page 3-32) and "Attributes"
(Page 3-34).
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-49
Page 78
3
Point
3-4 Message Communication
(4) Locking sensor amplifier operations
Message communication executes batch key lock for the sensor amplifier connected
to the DL-EP1.
Service code 4CH is used.
The following settings are required to use this object.
• Service Code
• Class ID
• Instance ID
• Attribute ID
• Service Data
Communicating with the SK-1000 Series
• Commands
ItemDescriptionData Example
Service CodeDesignates the "batch lock setting (4CH)" (fixed value).
Class IDDesignates DL Object (67H)(fixed value).
Instance ID
Attribute IDThere is no data.
Service Data Designates the batch lock setting.
Designates ID number 0 (00H) for issuing a command
to the DL-EP1 (fixed value).
• Responses (when successful)
ItemDescriptionData Example
General statusMessage communication has ended normally.
Service response data There is no service response data.
• Responses (when unsuccessful)
ItemDescriptionData Example
General statusA general status for the service is returned
Additional statusAn additional status is returned.
Service response data There is no service response data.
If a sensor amplifier that does not support key lock is connected to the DLEP1, the error code 09H is returned (the settings of the sensor amplifier are
not changed).
4CH
67H
00H
-
0001H
00H
-
08H
-
-
3-50
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 79
3-4 Message Communication
(5) Reading the number of decimal places in the parameter from a
sensor amplifier
Message communication reads the number of decimal places in the parameter from
the sensor amplifier connected to the DL-EP1.
Service code 4DH is used.
The following settings are required to use this object.
• Service Code
• Class ID
• Instance ID
• Attribute ID
3
• Commands
ItemDescriptionData Example
Service CodeDesignates parameter read (fixed value).
Class IDDesignates DL Object (67H)(fixed value).
Instance IDDesignates the ID number.
Attribute IDDesignates the attribute ID to be read from "Attribute".
Service Data There is no service data.
4DH
67H
01H
03A1H
(929)
-
• Responses (when successful)
ItemDescriptionData Example
General statusMessage communication has ended normally.
Service response data The read decimal point position is returned.
00H
04H
• Responses (when unsuccessful)
ItemDescriptionData Example
General statusA general status for the service is returned
Additional statusAn additional status is returned.
Service response data There is no service response data.
14H
-
-
For details on the attribute ID, settings, general status, and additional status of each
parameter, refer to "DL Object (Class ID:67H)" (Page 3-32) and "Attributes"
(Page 3-34).
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-51
Page 80
3
3-4Message Communication
MEMO
Communicating with the SK-1000 Series
3-52
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
4-1
Page 82
4
Specifications
4-1
Specifications
The specifications of the DL-EP1 are as follows:
Product nameEtherNet/IP Compatible Network Unit
Ethernet
specifications
EtherNet/IP
specifications
Sensor connection
specifications
Power consumption1500 mW or less (at 30 V 50 mA max)
Environmental
resistance
ModelDL-EP1
Compliant standards
Transmission rate
Transmission medium
Maximum cable length100 m (Distance between DL-EP1 and Ethernet switch)
Maximum number of
connectable hubs
Compatible functions
Number of connections64
RPI (Transmission cycle)0.5 to 10000 ms (0.5 ms unit)
Tolerable communication
bandwidth for cyclic
communication
Conformance testCompatible with Version A7
Connectable sensors
Number of connectable
sensor units
Indicators
Power voltage
Operating ambient air
temperature
Operating ambient air
humidity
Vibration resistance
Pollution degree2
MaterialsMain unit case: Polycarbonate
Weight Approx. 70g
IEEE802.3 (10BASE-T)
IEEE802.3u (100BASE-TX)
10Mbps (10BASE-T)
100Mbps (100BASE-TX)
STP cable or Category 3 or higher UTP cable (10BASE-T)
STP cable or Category 5 or higher UTP cable (100BASE-TX)
4 (10BASE-T)
2 (100BASE-TX)
Cyclic communication (Implicit messaging)
Message communication (Explicit messaging)
Compatible with UCMM and Class 3
6000pps
Sensor amplifiers with D-bus support
Up to 15 units
Link/activity indicator (LINK/ACT): Green LED
Module status indicator (MS): 2-color (green/red) LED
Network status indicator (NS): 2-color (green/red) LED
Sensor communication indicator (D-bus) 2-color (green/red) LED
Including 20 to 30 VDC ripple (p-p) 10%
(This voltage is supplied from the connected sensor amplifier)
-20 to +55 °C (no freezing)
35 to 85% RH (no condensation)
10 to 55 Hz compound amplitude 1.5 mm, 2 hours each in X, Y, Z
directions
*1
*2
*1D-bus is the name of KEYENCE's wiring-saving system for sensor amplifiers.
*2 The number of connectable sensor units varies with the sensor amplifiers to be
connected. (Up to 8 sensor units can be connected to the SK-10000 series.)
4-2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 83
4-2
CPU unit
EtherNet/IP
scanner
DL-EP1Sensor amplifier
(1)(2)(3)(4)
This section describes the length of time that lasts from detection by a sensor to data
processing by PLC.
Data Processing Time
Maximum data processing time = (1) + (2) + (3) + (4)
(1) PLC scan time
(2)RPI (Transmission cycle)
(3)DL-EP1 data communication time
(4)Sensor amplifier response time
(2)RPI is set with the scanner unit. It can be set in 0.5 ms increments between 0.5 ms
and 10000 ms.
(3)DL-EP1 data communication time
The time required for sending outputs and current value data from a sensor
amplifier to the DL-EP1 is as follows:
Sensor amplifier with calculation function OFF, or sensor amplifier with no
calculation function
Number of connected sensor
amplifiers
17.8 ms
29.8 ms
313.8 ms
415.8 ms
519.8 ms
621.8 ms
725.8 ms
827.8 ms
Output, judgment value, or
current value
4
Specifications
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
4-3
Page 84
4
4-2 Data Processing Time
Sensor amplifier with calculation function ON
Number of connected sensor
For details on the PLC scan time in (1) and the sensor amplifier response time in (4),
refer to the manual of each unit.
Specifications
amplifiers
Output, judgment value, or
111.3 ms
214.3 ms
320.3 ms
423.3 ms
529.3 ms
632.3 ms
738.3 ms
841.3 ms
current value
4-4
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 85
4-3
25.6
35.443.5
94.5
38.1
(42.5 )
29.4
(Unit : mm)
Dimensions
4
Specifications
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
4-5
Page 86
4
4-3 Dimensions
MEMO
Specifications
4-6
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-1
Page 88
5
5-1
General status
Appendix
Device Profile
CategoryItemDescription
Vendor nameKeyence Corporation
Vendor ID367
Device type0 (Generic Device)
Revision1.1
Product code4501
Product nameDL-EP1
5-2
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 89
5-2
Link/activity indicator (Green)
Module status indicator (Green, Red)
Network status indicator (Green, Red)
Sensor communication indicator (Green, Red)
Troubleshooting
The indicator LEDs on the DL-EP1 can be used to determine the causes of errors.
Link/activity indicator (LINK/ACT)
This indicator indicates whether the DL-EP1 is communicating correctly.
LED StatusConditionCorrective Action
SolidThe DL-EP1 is normally linked.-
Green
Not lit
Flashing
The DL-EP1 is normally linked and
is now exchanging data.
Power is not supplied to the DLEP1.
The DL-EP1 is not linked.
-
• Check if the power supply is correctly
connected.
• Check if the DL-EP1 is correctly connected
to the sensor amplifier.
• Check if the IP address is correct.
• Check if the power supply of the
connected device or Ethernet switch is
correctly connected.
• Check if the cable is correctly connected.
5
Appendix
Module status indicator (MS)
This indicator indicates whether the DL-EP1 is operating normally.
LED StatusConditionCorrective Action
Green SolidThe DL-EP1 is normally operating. -
Solid
Red
Flashing
Not lit
A system error may have occurred
in the DL-EP1.
One or more of the connector
sensors are in the error or warning
*
.
status
The number of connected sensor
may have exceed the maximum
number of connectable units.
The IP address may be duplicated. Check if the IP address is duplicated.
Power is not supplied to the DLEP1.
Contact your nearest KEYENCE office.
One or more of the connector sensors are in
the error or warning status
Check if the number of connected sensors is
less than or equal to the maximum number of
connectable units.
• Check if the power supply is correctly
connected.
• Check if the DL-EP1 is correctly connected
to the sensor amplifier.
* The setting can be changed so that the red LED does not flash.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
*
.
5-3
Page 90
5
5-2 Troubleshooting
Network status indicator (NS)
This indicator indicates whether the DL-EP1 is communicating correctly with
EtherNet/IP.
LED StatusConditionCorrective Action
Green
Red
Not lit
Solid
FlashingNo connection is established.Check if the DL-EP1 is registered in the scanner.
Solid
Flashing
One or more connections are
normally established.
A duplicated IP address was
detected.
One or more connections have
timed out.
Power is not supplied to the
DL-EP1.
The IP address is not assigned.Set the IP address.
Sensor communication indicator (D-bus)
This indicator indicates whether the DL-EP1 is communicating correctly with the
sensor amplifier.
If an error occurs, you can identify the cause of the error by reading the error code
Appendix
via cyclic communication or message communication.
"Error code list" (Page 3-13)
LED
Status
Solid green
Flashing
green
Solid red
Flashing
red
Repetition
of 4
consecutive
flashes)
Flashing
red
(Flashing at
fixed
intervals)
Not litPower is not supplied to the DL-EP1.
The DL-EP1 is communicating correctly with
the sensor amplifier.
After power-on, the DL-EP1 is now starting
up.
The DL-EP1 could not communicate with the
sensor amplifier during its start-up.
(Error ID number/code: 00H/52 or 00H/55)
An attempt to assign an ID number has
failed.
(Error ID number/code: 00H/51)
The DL-EP1 could not communicate
continuously with the sensor amplifier for
one second or longer.
(Error ID number/code: 00H/57)
A system error may have occurred in the
DL-EP1.
A current limitation error occurred.
(Error ID number/code: 00H/56)
An unsupported sensor amplifier was
connected.
(Error ID number/code: 00H/53)
Unconnectable models are mixed. (Error ID
number/code: 00H/54)
Sometimes the DL-EP1 cannot temporarily
communicate with the sensor amplifier.
(Error ID number/code: 00H/57)
ConditionCorrective Action
If multiple connections are used, the DL-EP1 may
be unable to communicate with EtherNet/IP even if
the green LED is solid.
Check if the IP address setting is duplicated with the
IP address setting of the scanner or other adaptors.
Locate the connections that have timed out and
check the power status and wiring of the
communication device.
• Check if the power supply is correctly
connected.
• Check if the DL-EP1 is correctly connected to the
sensor amplifier.
-
After it has started up, the DL-EP1 automatically shifts
to the normal status.
• Check if the DL-EP1 is correctly connected to the
sensor amplifier and turn on the power again.
• Check if an unsupported sensor amplifier is
connected to the DL-EP1 and turn on the power
again.
• Check if the number of connected sensor
amplifiers exceeds the maximum number of
connectable units.
• Check if there is an electrical noise source around
the DL-EP1.
If the error cannot be recovered after checking the
above, contact your nearest Keyence office.
Check the sensor amplifier configuration.
Check if there is an electrical noise source around the
DL-EP1. (The error is automatically reset if the cause
is removed.)
• Check if the DL-EP1 is correctly connected to the
sensor amplifier.
• Check if the power supply is correctly connected.
5-4
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 91
5-3
The DL-EP1 can be reset and initialized to the default settings by holding down the
reset switch ( Page 1-4) for three seconds or longer or by using the Identity Object
Reset service ( Page 5-21) for message communication.
The DL-EP1 default settings are as follows:
Communication speed10/100 Mbps automatic
IP address setting methodBOOTP
IP address
Netmask255.255.255.0
Default gateway0.0.0.0
Sensor status mask setting
Multicast TTL1
Multicast assignment method0 (Automatic)
Number of multicast addresses32
Multicast address239.255.0.0
Default Settings
Setting ItemValue after Initialization
*
0.0.0.0
MS LED flashes in red when a sensor error or warning
occurs.
5
* Only the BOOTP client function can be used when the IP address is 0.0.0.0. The
IP address must be set to use any other functions.
Appendix
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-5
Page 92
5
5-4
This section explains the procedures for communicating with the DL-EP1 using an
Allen-Bradley ControlLogix PLC (EtherNet/IP scanner).
Procedures for Communicating with an Allen-Bradley ControlLogix PLC
The DL-EP1 is capable of the following communication when connected to an AllenBradley ControlLogix PLC.
• Cyclic communication function maximum data size: 496 bytes
• Message communication function: Class3/UCMM
Changing the cyclic communication settings
Refer to the PLC instruction manual for details on the PLC unit configuration and
settings such as RsLinx, required for communicating with the PC.
1
Appendix
Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Select the EIP communication module (1756-ENBT) connected with the
DL-EP1 from RsLogix500 I/O Configuration, and then select "New Module"
with a right click.
5-6
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 93
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Add "ETHERNET-MODULE (Generic Ethernet Module)".
2
Change the settings as required.
3
5
Appendix
Name
Choose a name. The following tags are generated based on the name set
here, and are used as the data exchanged with cyclic communication.
• (Name): IData received from DL-EP1
• (Name): O Data sent to DL-EP1
• (Name): C Not used.
Comm Format
Designate [Data INT].
IP Address
Designate the DL-EP1's IP address.
Input (DL-EP1 send data size)
• Instance number: 100 (decimal)
• Data size: Value up to 84
Output (DL-EP1 receive data size)
• Instance number 101 (decimal)
• Data size: Value up to 5
Configuration
• Instance number: 1 (decimal)
• Data size: 0
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-7
Page 94
5
Reference
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
• For the details of InputOnly connection, refer to "Sending data to
multiple PLCs (InputOnly)" (Page 5-8).
• Refer to "Usable Connections" (Page 3-7) for details on the
connection.
RPI
Designate the cyclic communication interval.
Appendix
Designate a value between 0.5 and 3200 ms.
Download the settings to the PLC.
4
EtherNet/IP communication is enabled after the settings are downloaded
and the status is switched to online.
Sending data to multiple PLCs (InputOnly)
By connecting to multiple PLCs with the InputOnly connection format, multiple
PLCs can receive the data sent from the DL-EP1. Each PLC must be set as
shown below to use the InputOnly connection.
5-8
Bidirectional
Setting Item
RPI valueUser set valueSame value as left
InputAssembly Instance
number
InputAssembly data sizeUser set valueSame value as left
OutputAssembly Instance
number
OutputAssembly
Comm FormatData-INTInput Data INT
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
data sizeUser set value0 bite
Communication PLC
(maximum 1 unit)
No. 100 (decimal)Same value as left
No. 101 (decimal)No. 254 (decimal)
PLC Connected
with InputOnly
Page 95
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Point
To carry out cyclic communication with multiple PLCs using the
InputOnly connection, the DL-EP1 input data must be sent as a
Multicast packet. With ControlLogix, the DL-EP1 transmission is
fixed to Multicast packet. However, caution is required when using
devices, such as KV or SYSMAC, for which the connection method
can be selected from Multicast or Point to Point.
Changing the message communication settings
After completing "Changing the cyclic communication settings" (Page 5-6), issue
the MSG instruction from the ladder program to execute message communication.)
5
Appendix
Reference
1
• Refer to "Logix500 Controllers General Instructions" (1756-RM003) for
details on the MSG instructions.
• Select Inhibit Module when not using cyclic communication.
Define the following tags under the RsLogix5000 "Controller Tags" field.
• Tag for storing control information for MSG instruction (message- Message
type)
• Tag for storing data exchanged with MSG instruction (tx_param, rx_param INT type)
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-9
Page 96
5
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Add the MSG instruction to the RsLogix5000 ladder.
2
Open the "Configuration" tab in the Message instruction setting dialog,
3
and change the MSG instruction setting.
Appendix
5-10
Message Type
Select "CIP Generic".
ServiceType, Class, Instance, Attribute
Designate a value which matches the message to be sent.
• Example 1: Writing data to DL Object "Bank 0 HI setting" when writing data
to attributes
ItemSetting Value
ServiceTypeSetAttributeSingle
ServiceCode- (Cannot be designated)
Class67H
Instance01H
Attribute0341H
SourceElementName of tag storing send data
SourceLength4 byte (attribute size is 4)
Destination- (Cannot be designated)
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 97
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
• Example 2: Retrieving DL Object "Output 3 (GO)" data when reading
attributes
ItemSetting Value
ServiceTypeGetAttributeSingle
ServiceCode- (cannot be designated)
Class67H
Instance02H
Attribute76H
SourceElement- (cannot be designated)
SourceLength- (cannot be designated)
DestinationName of tag storing received data.
Open the "Communication" tab, and change the MSG communication
4
settings.
5
Appendix
Path
Designate the device name set in "Configuration for cyclic communication".
(An example for the DLEP1 device is shown above.)
Connected, Cache Connections
• For UCMM connection: Invalidate bidirectional (default setting)
• For Class3 connection: Validate bidirectional
Describe the process for setting the send data and retrieving the receive
5
data with the ladder program, and download it to the PLC.
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-11
Page 98
5
Point
Reference
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Procedures for Communication with an Allen-Bradley SLC5/05 PLC
The DL-EP1 is capable of the following communication when connected to an AllenBradley SLC5/05 PLC.
• Message communication function: Class3
The size of attribute ID used for SLC5/05 Series is 1 byte or smaller.
The SLC5/05 Series does not support the parameter which contains 2 byte
attribute ID.
• The SLC5/05 Series does not support the cyclic communication
function, but by accessing the DL-EP1's Assembly Object with
messages, control can be executed with the same data type and
procedures as cyclic communication.
• Up to 248 bytes can be exchanged with the SLC5/05 series message
communication.
Appendix
• Do not exceed this size when exchanging data with message
communication.
• The Assembly Object data size is the same as the cyclic
communication data size set in the DL-EP1 properties. When using
the SLC5/05, confirm that this value is 248 bytes.
5-12
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Page 99
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Changing the message communication configuration
Message communication is carried out with a ladder program using EEM
instructions.
Reference
1
2
Refer to the "SLC 500 Instruction Set Reference Manual" (1747-RM001),
etc., for details on the EEM instructions.
Define the following file in the RsLogix500 "Data Files" field.
• File storing EEM instruction control information (message-Integer type)
• File storing data exchanged with EEM instruction (tx_param, rx_param Integer type)
Add EEM instruction to RsLogix500 ladder.
5
Appendix
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
5-13
Page 100
5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Designate the File used in the EEM instruction defined in Step 1 for the
3
EEM instruction Control Block, and open the SetupScreen.
Service, Class, Instance, Attribute
Designate a value which matches the message to be sent.
• Example 1: Retrieving DL Object "Output 3 (GO)" data when reading
attributes
5
ItemSetting Value
Appendix
ServiceTypeGeneric Set Attribute Single
ServiceCode- (Cannot be designated)
Class67H
Instance02H
Attribute76H
Data Table Address (Send data)- (Cannot be designated)
Size In Words (Send data)- (Cannot be designated)
Data Table Address (Received
data)
Size In Words (Received data)1 word (attribute size is 1)
Name of file storing send data
5-14
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.