Variable Speed SCR Control Designed for
Shunt Wound and PM DC Motors
FULL WAVE • 4 QUADRANT
See Safety Warning
on Page 3
The information contained in this manual is
intended to be accurate. However, the
manufacturer retains the right to make changes in
design which may not be included herein.
IMPORTANT – You must read these simplified operating instructions before you proceed.
These instructions are to be used as a reference only and are not intended to replace the
detailed instructions provided herein. You must read the Safety Warning before proceeding.
1.CONNECTIONS.
A.AC Line – Wire AC line voltage to terminals L1 and L2. Be sure jumpers J1A and
J1B are both set to the correct input line voltage 115 or 230 VAC. Connect ground
wire (earth) to green ground screw.
B. Motor.
1. Permanent Magnet (PM Type). Connect motor armature leads to M1(+) and
M2 (–). Be sure jumper J3 is set to the proper position “A90" for 90 volt DC
motors and “A180" for 180 volt DC motors. Note: 180 volt DC motors must be
used with 230 VAC line, 90 volt motors can be used with a 230 VAC or 115 VAC
line.
Note: Motor performance and efficiency, including brush life, can be
adversely affected when using 90 volt motors with a 230 VAC line. Contact
motor manufacturer for derating information.
2. Shunt Wound Motors. Connect motor armature leads as above. Connect full
voltage shunt field leads (90 volt motors with 100 volt fields and 180 volt with
200 volt fields) to F+ and F-. Connect half voltage field leads (90 volt motors
with 50 volt fields and 180 volt motors with 100 volt fields) to F+ and L1.
2.MOTOR CURRENT.
Jumper J2 is factory set for 7.5 amp motors (7.5A). For lower amperage motors, place
J2 in the proper position. If motor amperage is less than 1.7 amps, use the 1.7 amp
position and readjust the IR and CL trimpots according to section VII, C and D on pages
28 and 29. Note: The factory setting for Current Limit is 150% of the nominal current
setting (e.g., if J2 is selected for 5 amps, the actual CL setting will be 7.5 amps). Note:
If the 10.0 amp setting (10.0A) is required, an auxiliary heatsink (KB P/N 9861) must be
used.
3.TRIMPOT SETTINGS.
All trimpots have been factory set in accordance with figure 12, p. 20.
4.ENABLE.
A jumper must be connected between “EN” and “COM” terminals or control will not
operate. (See sec. V, G, page 22.)
Note: For the location of jumpers and trimpots, see fig. 12, control layout, on page 20.
5.SPEED OR TORQUE MODE.
Jumper J5 is factory set for speed control operation (SPD). For torque control, set J5
to the “TRQ” position.
1
2
ii. SAFETY WARNING! — PLEASE READ CAREFULLY
This product should be installed and serviced by a qualified technician, electrician
or electrical maintenance person familiar with its operation and the hazards involved.
Proper installation, which includes wiring, mounting in proper enclosure, fusing or other
overcurrent protection and grounding, can reduce the chance of electric shocks, fires or
explosion in this product or products used with this product, such as electric motors,
switches, coils, solenoids or relays. Eye protection must be worn and insulated
adjustment tools must be used when working with control under power. This product is
constructed of materials (plastics, metals, carbon, silicon, etc.) which may be a potential
hazard. Proper shielding, grounding and filtering of this product can reduce the emission
of radio frequency interference (RFI) which may adversely affect sensitive electronic
equipment. If information is required on this product, contact our factory. It is the
responsibility of the equipment manufacturer and individual installer to supply this safety
warning to the ultimate user of this product. (SW effective 11/92)
This control contains electronic Start/Stop and enable circuits that can be used to
start and stop the control. However, these circuits are never to be used as safety
disconnects since they are not fail-safe. Use only the AC line for this purpose.
The input circuits of this control (potentiometer, start/stop, enable) are not isolated
from AC line. Be sure to follow all instructions carefully. Fire and/or electrocution
can result due to improper use of this product.
This product complies with all CE directives pertinent at the time of
manufacture. Contact factory for detailed installation instructions and
Declaration of Conformity. Installation of a CE approved RFI filter (KBRF-200A,
KB P/N 9945C or equivalent) is required. Additional shielded motor cable and/or
AC line cables may be required along with a signal isolator (model SIMG, KB P/N
8832 or equivalent).
I.GENERAL INFORMATION.
The KBMG-212D is a full-wave regenerative control, capable of operating a DC motor
(Permanent Magnet or Shunt) in a bidirectional mode. It provides 4-quadrant operation
which allows forward and reverse torque in both speed directions. The drive offers
excellent controllability, which closely approximates the performance of servo-type
drives. Ratings and specifications are presented in tables 1 and 3. Be sure the drive
is used within these ratings and specifications.
(Note: Regenerative drives normally produce more motor heating than standard
unidirectional SCR speed controls, especially under low speed operation. This
should be taken into consideration when specifying motor rating.)
3
Safety Warning.
4
WARNING! Be sure to follow all instructions carefully. Fire or
electrocution can result due to improper use of this product. Read
The KBMG-212D will vary motor speed or torque as a function of the signal voltage on
input terminals “SIG" (signal) and “COM” (common). The input voltage can be derived
from the wiper of the main speed potentiometer or from an isolated analog input (signal
voltage following mode). Since the KBMG-212D is a 4-quadrant regenerative drive, the
motor speed will follow both a positive and negative signal voltage and drive the motor
in both the forward direction and reverse direction. In addition, it will apply both forward
and reverse torque in order to stabilize motor speed.
To understand the concept of a regenerative drive, the operation of an elevator can be
used. If one were to enter the elevator on the first floor and press 10, the motor and
control would have to lift the elevator against gravity. In this mode, the drive would
operate like a conventional speed control which is called “motoring” (the applied load
is opposite to the direction of motor rotation). When the elevator is at floor 10 and floor
1 is pressed, gravity will try to pull the elevator car down faster than the speed for which
it is set. The control will then provide reverse torque to keep the car from falling faster
than the set speed. This operation is regeneration (the applied load is in the same
direction as the direction of motor rotation).
The table below summarizes the different modes of operation.
TABLE 2 – SUMMARY OF CONTROL OPERATION
QuadrantType of Operation
IMotoringCWCWCCW
IIRegenerationCCWCWCCW
Motor Rotation
Direction
Motor Torque
Direction
Applied Load
Direction
5
IIIMotoringCCWCCWCW
IVRegenerationCWCCWCW
6
TABLE 3 – GENERAL PERFORMANCE SPECIFICATIONS
ParameterSpecification
AC Line Input Voltage (VAC ±10% 50/60 Hz)
AC Line Frequency (Hz)
Armature Voltage Range 115VAC Line (VDC)
Armature Voltage Range 230VAC Line (VDC)
Field Voltage at 115VAC Line (VDC)
Field Voltage at 230VAC Line (VDC)
Max Load Capacity (% for 2 Minutes)
Ambient Temperature Operating Range (ºC)
Speed Range (Ratio)
Armature Feedback Load Regulation (% Base Speed)
Tach-generator Feedback Load Regulation (% Set Speed)
AC Line Regulation (% Base Speed)
Current Ranges (Amps DC)
Forward Accel (FACC) and Reverse Accel (RACC) Range (Sec.)
Dead Band Range (% Base Speed)
Max Speed Trimpot Range (% Base Speed)
IR Comp Range at 115VAC Line (VDC @ Full Load)
IR Comp Range at 230VAC Line (VDC @ Full Load)
TABLE 3 – GENERAL PERFORMANCE SPECIFICATIONS (Continued)
ParameterSpecification
Forward CL (FCL) and Reverse CL (RCL) Range (% Range Setting)
Voltage Following Input Range (VDC)**
Voltage Following Linearity (% Base Speed)
*Requires Auxiliary Heatsink KB P/N 9861.
** Requires isolated input or signal isolator.
0 – 175
0 – ±10, 0 – ±15
±0.5
III.SETTING SELECTABLE JUMPERS.
The KBMG-212D has customer selectable jumpers which must be set before the control
can be used (refer to fig. 1, p. 10). Bold indicates factory setting. See fig. 12, p. 20 for
location of jumpers.
A.J1A, J1B – Input AC Line Voltage – Select proper input line voltage, 115VAC or
230VAC, by placing both J1A and J1B in the correct corresponding position, “115"
or “230.” (See fig. 1, p. 10.)
B. J2 – Armature Current – Select the J2 position (1.7, 2.5, 5.0, 7.5, 10) closest to
the rated motor current. (Note: The maximum output current is set to 150% of the
J2 position, which may be readjusted using the FWD CL and REV CL trimpots.)
C. J3 – Motor Armature Voltage – Select the desired armature voltage by placing J4
in the proper position, “A90" or “A180.” Note: For 115 volt AC line input, J3
must be set to “A90.” For 230 input, the armature voltage is normally set for
“A180.” However, it is also possible to set the armature voltage to “A90" for stepdown operation. (See fig. 2 and table 5 on page 10.)
J3 – Tach-Generator Feedback (for use with 1800 RPM motors.) – Jumper J3
is also used if tach-generator feedback is to be used. (See fig. 2, p. 10) If a 7 volt
per 1000 RPM tach-generator is used, set jumper J4 in the “T7" position. For a 50
volt per 1000 RPM tach-generator, set the jumper in the “T50" position. Note:
When using tach-generator feedback, the IR Comp trimpot should be turned to a
minimum setting (full CCW).
FIG. 1 – AC LINE VOLTAGE
JUMPER SETTING (J1A, J1B)
115VAC230VAC
FIG. 2 – MOTOR ARMATURE VOLTAGE
JUMPER SETTING (J3)
90VDC180VDC
TABLE 5 – RELATIONSHIP of AC LINE INPUT AND MOTOR
VOLTAGE with J1A, J1B and J3 JUMPER POSITION
AC LINE INPUT VOLTAGEJ1A, J1B POSITIONJ3 POSITIONMOTOR VOLTAGE
1151159090
9
230230180180
23023090*90*
*A 90VDC motor can be used with a 230VAC line (J3 set in “A90" position). However, speed range may
be reduced and motor derating may be required.
10
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.