INFICON PEG100-P User Manual

OPERATING MANUAL
Profibus-DP Interface for the Penning Gauge
tina15e1-a
PEG100-P
Part Number 351-005
The main instrument’s (PEG100-P) manual is still valid!
General Remarks
We reserve the right to alter the design or any data given in these Operating Instructions. The illustrations are not binding.

Contents

Page
1 Description . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2.1 Penning Gauge PEG100-P . . . . . . . . . . . . . 3
1.2.2 Profibus DP . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2.3 Profibus-DP Master Configuration Software . 3
1.3 Technical Description . . . . . . . . . . . . . . . . . 4
1.3.1 Configuration of Fieldbus nodes in
Profibus-DP . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.1.1 GSD File / Main Equipment File . . . . . . . . . 4
1.4 Technical Data . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Supplied Equipment . . . . . . . . . . . . . . . . . . 4
2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Operation of PEG100-P . . . . . . . . . . . . . . . 5
2.1.1 Setting Slave’s Address . . . . . . . . . . . . . . . 5
2.2 Input and Output Data . . . . . . . . . . . . . . . . 5
2.2.1 Meaning of PEG100-P (slave) input
and output data . . . . . . . . . . . . . . . . . . . . . 6
2.2.1.1 PEG100-P output data (output data
from the master’s view point) . . . . . . . . . . . 6
2.2.1.2 PEG100-P input data
(from master’s view point) . . . . . . . . . . . . . . 6
2.3 Data of diagnosis . . . . . . . . . . . . . . . . . . . . 7
3 Service at INFICON . . . . . . . . . . . . . . . . . . 7
4 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . 7
EEC Declaration of Conformity . . . . . . . . . . . . . . . 8
Declaration of Contamination . . . . . . . . . . . . . . . . 9
2
tina15e1-a (0206) PEG100-P.ga

1 Description

1.1 General
The Penning Gauge PEG100-P is supplied ready for operation. Even so, we recom­mend to read these Operating Instructions with care so as to ensure optimum operating conditions right from the start.
These Operating Instructions contain important informati­on on the functions, installation, start-up, operation and troubleshooting of the

Penning Gauge PEG100-P

.
Important remarks concerning operational safety and protection are emphazised as follows:
Warning Indicates procedures that must be strict-
ly observed to prevent hazards to per­sons.
Caution Indicates procedures that must strictly
be observed to prevent damage to, or destruction of the PEG100-P.
Note
Indicates special technical requirements that the user must comply with.
The references to diagrams, e.g. (1/3), consist of the Fig. No. and the item No. in that order.
Unpack the PEG100-P immediately after delivery, even if it is to be installed at a later date.
Examine the packaging for any external damage. Com­pletely remove all packaging materials.
Note
Retain the shipping container and the packaging materi­als in the event of complaints about damage.
Check that the PEG100-P is complete Carefully examine the PEG100-P visually. If any damage is discovered, report it immediately to the
forwarding agent and insurer. If the damaged part has to be replaced, please get in touch with the orders depart­ment.
1.2 Purpose
1.2.1 Penning Gauge PEG100-P
The PEG100-P is equipped with the fieldbus interface Profibus-DP. Automated process instruments can be lin­ked easily.
1.2.2 Profibus-DP
The norm EN 50170 decribes the fieldbus system Profi­bus-DP. Technical and functional features of the Profi­bus-DP are specified here. The Profibus-DP distinguis­hes between master and slave instruments. Master instruments determine the data circulation. They trans­mit data to their related slaves and request data from them. It is possible to configure the fieldbus as a mono­master or multi-master system.
The PEG100-P represents a slave unit which may recei­ve different messages from the Profibus master and out­put corresponding replies in response to the informati­on/commands from the master. In a Profibus system up to 126 units including the master may be operated. Acor­responding slave address must be set up for the PEG100-P.
1.2.3 Profibus-DP Master Configuration Software
In order to configure the master together with the indivi­dual slaves software packages are available from the manufacturers of the master units.
3
tina15e1-a (0206) PEG100-P.ga
1.3 Technical Description
1.3.1 Configuration of Fieldbus nodes in Profibus-DP
1.3.1.1 GSD File / Main Equipment File
Note
The GSD file is available in the internet. The properties and capabilities of a Profibus-DP unit are
documented in the GSD-File. This is a file format which is defined by the standard, so that manufacturer inde­pendent project tools may be implemented for Profibus­DP systems by various manufacturers. For operation of the configuration software please refer to the correspon­ding operation instructions provided by the manufacturer of the configuration software.
1.4 Technical Data
The technical data as specified in the Operating Instruc­tions for the PEG100 - tina14e1 apply . The following data apply in addition to the Profibus-DP interface:
Supported Baud Rates:
9.6 k Baud
19.2 k Baud
93.75 k Baud
187.5 k Baud 500 k Baud
1.5 M Baud
Expanded User Parameter Data
5 bytes of parameter data are required.
Configuring
The number of input and output data is 2 bytes each.
Sync-Mode and Freeze-Mode
The sync-mode and the freeze-mode are supported.
1.5 Supplied Equipment
The supplied equipment is the same as detailed for the PEG100 in Operating Instructions tina14e1. The follo­wing items are supplied in addition:
- Profibus DP interface built into the PEG100, PEG100-P Part Number 351-005
- Operating Instructions tina15e1
4
tina15e1-a (0206) PEG100-P.ga
for automatic baud rate detection

2 Operation

2.1 Operation of PEG100-P
The fieldbus’ operation requires
- the master’s configuration,
- setting of the slave’s address and
- electrical installation of entire system.
2.1.1 Setting Slave’s Address
The two rotary switches on the right side of the PEG100-P are for the setting of the address. Possible setting addresses are in the range of 0 to 99. With the use of both switches the address has to be switched into the decimal code. The instruments has to be switched off during the setting of the address. A change will not be registered after the instrument is switched on.
The required decimal address is set by the address swit­ches. Switch x10 sets the High Value (see example) and switch x1 sets the Low Value.
After applying the operation voltage to the PEG100-P, the device expects -in line with the Profibus specificati­ons- an address message, a parameter message and a configuration message. If these data have been received by the device and if the received data match the unit’s settings (slave address, configuration data and parame­ter data/ nominal configuration = actual configuration) the unit will then enter the data exchange mode and the „RUN“ LED (1/2) will come on. If this LED does not come on after having started the system, an error has occurred during the configuration phase. Please check the slave
5
tina15e1-a (0206) PEG100-P.ga
address set up in the master, the configuration and para­meter data by referring to the GSD file.
Caution After having removed the cause for the
error in the configuration for the master, the bus logic of the PEG100-P can only be set to its normal operating state by switching the POWER ON once more.
Factory default settings: slave address „34“.
2.2 Input and Output Data
The designations used in the following for the input and output data must always be seen from the controlling (master) side. Thus, for example, measurement data sent by the slave are designated as input data (as seen by the master).
After successful run-up, i. e. slave address configuration and parameter data have been received by the PEG100-P corresponding to the data stored in the PEG100-P, the unit will enter the „date exchange“ mode. Here 2 data bytes are transmitted as input and output data corresponding to the configuration (as stored in the GSD file).
Fig. 1 Side view of the PEG100-P
1 32 4
Key to Fig. 1
1 Status-LED Profibus (FAIL) 2 Status-LED Profibus (RUN) 3 Address Switch 4 Profibus-DP Plug
2.2.1 Meaning of PEG100-P (slave) input and output data
2.2.1.1 PEG100-P output data
(output data from the master’s view point)
The following two 2 bytes are sent to the device:
Output data
———————————————–
Byte 0
Bit 7 not used Bit 6 not used Bit 5 not used Bit 4 not used Bit 3 not used Bit 2 not used Bit 1 Control Bit Bit 0 Control Bit
———————————————–
Byte 1 not used
Semantics Byte 0 / Bit 0 and Bit 1
The high voltage could be switched on by the digital inputs (Pin 7 or Pin 8) at the FCC 68 plug or directly by a profibus command. The input has to be selected by these two bits.
Bit 1 Bit 0 Meaning HEX-
Value
————————————————————————–
0 0 Digital Inputs active 0 1 0
Fieldbus active, High Voltage OFF
2
1 1
Fieldbus active, High Voltage ON
3
2.2.1.2 PEG100-P input data
(from master’s view point)
The input data contain the following information: status information and measurement results (as 12-bit values).
Input data
—————————————————————–
Byte 0
Bit 7 Status bit Bit 6 Status bit Bit 5 Status bit Bit 4 Status bit Bit 3 Measurement value: Bit 11: MSB Bit 2 Measurement value Bit 10 Bit 1 Measurement value Bit 9 Bit 0 Measurement value Bit 8
———————————————–——————
Byte 1
Bit 7 Measurement value Bit 7 Bit 6 Measurement value Bit 6 Bit 5 Measurement value Bit 5 Bit 4 Measurement value Bit 4 Bit 3 Measurement value Bit 3 Bit 2 Measurement value Bit 2 Bit 1 Measurement value Bit 1 Bit 0 Measurement value Bit 0: LSB
Explanation Byte 0 / Bit 4 - Bit 7 - Status messages
Bit 7 Bit 6 Bit 5 Bit 4 meaning HEX-
Value
———————————————————————————
1 0 1 0 High Voltage OFF A 1 1 1 0 High Voltage ON, E
No Ignition
1 1 0 0 High Voltage ON, C
Measurement Value ok
0 1 1 0 HV on, but no ignition 6
after 1 min of HV on
Measurement values - representation
The measurement value is given as a 12-bit value. Byte 0/Bit 3 represents the MSB, byte 1/Bit 0 the LSB.
How to calculate the measurement value
The measurement values are calculated according to the following formulas in the corresponding measurement units.
Calculation formula in unit „mbar“
pressure p / mbar= 10
(output value / 500 - 9.5)
A special pressure’s value is calculated with the follo­wing formula:
value = 500 · (log (p / mbar) + 9,5)
Calculation formula in unit „torr“
pressure p = 10
(output value / 500 - 9.6249)
A special pressure’s value is calculated with the follo­wing formula:
value = 500 · (log (p / Torr) + 9,6249)
Calculation formula in unit „Pascal“
pressure p = 10
(output value / 500 - 7.5)
A special pressure’s value is calculated with the follo­wing formula:
value = 500 · (log (p / Pa) +7,5)
6
tina15e1-a (0206) PEG100-P.ga
2.3 Diagnosis Data
In case of error, a user’s specific diagnosis byte is given. However, only bit 0 is used. Bit 0 ↔ 0: High Voltage ON for more than 1 min, but no
ignition Bit 0 1: ok or high voltage just switched on All other bits are set to „1“.

3 Service at INFICON

Warning Contaminated products (e.g. radioac-
tive, toxic, caustic or microbiological hazard) can be detrimental to health and environment.
Products returned to INFICON should preferably be free of harmful substances. Adhere to the forwarding regula­tions of all involved countries and forwarding companies and enclose a duly completed declaration of contamina­tion (see Annex).
Products that are not clearly declared as „free of harmful substances“ are decontaminated at the expense of the customer.
Products not accompanied by a duly completed declara­tion of contamination are returned to the sender at his own expense.

4 Disposal

Warning Contaminated parts
Contaminated parts can be detrimental to health and environment.
Before beginning to work, find out whether any parts are contaminated. Adhere to the relevant regulations and take the necessary precautions when handlinmg conta­minated parts.
Warning Substance detrimental to the environ-
ment Products or parts thereof (mechanical
and electric components, operating fluids etc.) can be detrimental to the environment.
Dispose of such substance in accordance with the rele­vant local regulations.
Separating the components
After disassembling the product, separate its compo­nents according to the following criteria: Contaminated components
Contaminated components (radioactive, toxic, caustic or biological hazard etc.) must be decontaminated in accordance with the relevant national regulations, separated according to their materials, and disposed of.
Other components
Such components must be separated according to their materials and recycled.
7
tina15e1-a (0206) PEG100-P.ga
8
tina15e1-a (0206) PEG100-P.ga

EEC Declaration of Conformity

as defined by the Directive relating to machinery 98/37/EG, Appendix IIb.
We -INFICON - herewith declare that the products defined below meet the basic requirements regarding safety and health of the relevant EEC directives by design, type and the versions which are brought in to circulation by us.
We also declare that the equipment mentioned below complies with the provisions of the Directive relating to electrical equipment designed for use within certain vol­tage limits 73/23/ EEC and the Directive relating to elec­tromagnetic compatibility 89/336/EEC.
Product:
Profibus-DP Interface PEG100-P
Part Number
351-005
Standards
Harmonized and international / national standards and specifications:
EN 61010 - 1 - 1993
EN 50081 - 2 - 1993
EN 50082 - 2 - 1995
VDE 0411 Part 1 / 03.94
VDE 0839 Part 81 - 2 / 03.94
VDE 0839 Part 82 - 2 / 02.96
Balzers, 18 July .2001
————————————————————— Hannes Fischer, Product Manager
Balzers, 18 July .2001
————————————————————— Dr. Georg Sele, Technical Support Manager;
Quality Representative
9
tina15e1-a (0206) PEG100-P.ga

Declaration of Contamination

tina15e1-a (0206) PEG100-P.ga
INFICON LIMITED:
FL-9496 Balzers, Principality of Liechtenstein Phone: +423 388 3111 Fax: +423 388 3700 www.inficon.com
UNITED STATES FRANCE GERMANY LIECHTENSTEIN UNITED KINGDOM CHINA JAPAN KOREA SINGAPORE TAIWAN
Due to INFICONÕs continuing program of product improvements, specifications are subject to change without notice. Visit our website for contact information and other sales offices worldwide.
www.inficon.com
Loading...