Flowserve WXCL User Manual

Worcester Controls
Installation
Operation
Maintenance
UltraSwitch WXCL/WXML
FCD WCENIM2076-05
Description:
Worcester Controls UltraSwitch™ limit switch enclosures provide local and remote position indication for automated valves. They generally feature a visual indicator with “red=closed” and “green=open” for intuitive local position determination. The UltraSwitch™ is available with a number of limit switch options for remote indication in a variety of electrical applications. They may also be used as a junction box for direct installation of solenoid valves.
Installation:
UltraSwitches may be installed to valves or valve actuators with a variety of mounting hardware. For best results, specify the NAMUR shaft option and NAMUR mounting hardware when installing to NAMUR compliant actuator. These options allow direct coupling to actuators without couplings, reducing dead band.
Simply bolt bracket to actuator and UltraSwitch™ to bracket, leaving bolts finger tight. For NAMUR applications the UltraSwitch™ shaft features an integral alignment pin. This pin must engage the tapped hole in the actuator
shaft. For non-NAMUR applications, make sure to properly install a coupler between UltraSwitch™ and actuator. Once the UltraSwitch™ is installed with fasteners loosely tightened, stroke the actuator two or three times to align the bracket. Then tighten all fasteners.
Wiring Instructions:
UltraSwitch™ enclosures feature pre-wired switches. All user connections are made at a numbered terminal strip. Both external bonding and internal grounding locations have been provided for use in installation. A wiring diagram is located inside the cover and indicates which terminal numbers correspond to switch contacts: normally open, normally closed, common, etc. Simply follow the wiring diagram and electric code to connect switches to your system.
For field wiring: ensure that any excess wire lengths or loops are routed away from any moving parts and are
short enough, or secured to ensure a ¼” clearance between the wire and the inside surface of the switchbox
cover. Note: for all magnetically tripped proximity switches, the top switch (top and third switches for 4-switch
versions) should only be used to indicate the clockwise position: the bottom switch (second and fourth switches for 4-switch versions) should only be used to indicate the counter-clockwise position. Any deviation from these settings may result in erratic indication.
Solenoids may also be wired through the UltraSwitch™ enclosure. At least two auxiliary terminals are included as standard.
A ground screw is also included. Simply wire the solenoid to auxiliary terminals, then connect power leads to the opposite terminal side. Be sure to properly ground the solenoid at provided ground terminal.
UltraSwitch™ XCL series enclosures include two 3⁄4" NPT conduit entries and the XML series includes two
M25x1.5 conduit entries. Installation shall be per National Electric Code, local codes, and manufacturers’ instructions. In all cases, environmental seals must be used to protect against ingress of water through the conduit.
Special Hazardous Location Instructions:
For North America installations you must install a conduit sealing fitting within 18 inches of the enclosure to meet NEC regulations. For ATEX and IECEx installations an appropriately rated Cable Gland is required. Any unused conduit entry must have a suitably rated blanking element.
Substitution of components may impair suitability for Zone 2 Increased Safety.  Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.  Cleaning this housing by rubbing should be done in a non-hazardous area.  Potential electrostatic charging hazard, clean only with a damp cloth – danger of propagating discharge.  All grounding and bonding installation requirements must be addressed  All installation, inspection, and maintenance of the equipment should be performed by suitably trained
personnel. In addition, for ATEX, all installation, inspection, maintenance and repair must be done by suitably trained personnel. For more information refer to EN 60079-14:1997, EN 60079-17, EN 60079-19
Replacement parts not to invalidate certification and to be only obtained direct from the manufacturer.
Adjusting Limit Switches:
Ultra Switch™ enclosures feature quick-set cams which are used to trip the limit switches. These cams are easily adjusted without tools. Caution: disconnect power before removing cover when installed in hazardous locations. Remove cover and set aside. Rotate actuator/valve to full clockwise (CW) position. Adjust cam(s) associated with CW as follows:
1. Push or pull cam against spring to disengage it from splines.
2. Rotate cam CW breaking contact with switch (or moving magnet away from switch).
3. Continue rotating cam CW just until switch trips.
4. Release cam and reengage it with splines. Rotate actuator/valve to full counterclockwise (CCW) position. Adjust cam(s) associated with CCW as described
insteps 1 through 4, except rotate cam(s) CCW.
Note: factory setting is top switch = CW (closed), second switch = CCW (open), third switch = CW, and fourth switch = CCW.
CAUTION:
Fine Cam Adjustment:
Some cams have a fine adjustment available. These cams will have a small screw embedded into the side of the cam. Adjusting this screw inward or outward will deform the cam, changing the trip point slightly.
Adjusting UltraDome Position Indicator:
UltraDome visual indicators are easily adjusted to match the dome’s clear windows to the rotor’s colored sections. The dome is secured to the UltraSwitch housing with screws mounted through slotted holes. The slotted holes allow approximately 20° adjustment of the dome. In addition, the dome can be completely removed and reoriented in 45° and 90° increments. The rotor may be reoriented with respect to the shaft by removing the shaftcoupler and rotating 90° before reinstalling. This may be necessary to obtain the correct orientation of windows in a multi-way application.
Calibrating 4-20 mA Transmitter:
Setting direct/reverse action: A dip-switch setting controls the direction of increasing travel. For 4 mA in the full clockwise position, select "D," for 4 mA in the full counterclockwise position, select "R." Adjusting zero/span:
1. Attach a DC mA meter to +/- terminals.
2. Operate valve/switchbox to position corresponding to 4 mA.
3. Adjust feedback board zero trim pot to yield 4 mA. (Turning CW increases value, turning CCW decreases value).
4. Operate valve/switchbox to position corresponding to 20 mA feedback.
5. Adjust feedback board span trim pot to yield 20 mA. (Turning CW increases value, turning CCW decreases value).
6. The zero and span adjustments are interactive. Repeat steps 1 through 5 as necessary.
Note: If transmitter adjustment gets difficult (i.e., trim pots do not have desired effect) start over by "centering" the trim pots. This is accomplished by turning in one direction for 20 turns and reversing direction for 10 turns.
Switch Option
Manufacturer
Part Number
Load Capacity
M1 – SPDT Mechanical
Honeywell MicroSwitch
V7-1C13D8-201
15.1A (1/2 HP) at 125/250 VAC; ½A at 125 VDC; 1/4A at 250VDC; 5A at 120Vac
MC – SPDT
Mechanical 250°F
Honeywell MicroSwitch
V7-1C13D8-201
15.1A (1/2 HP) at 125 VAC; ½A at 125 VDC; 1/4A at 250VDC; 5A at 120Vac
MG – SPDT Gold Mechanical
Honeywell MicroSwitch
V7-1D19D8-201
1A at 125 VAC / 50 mA at 24 VDC
MA – 3-Position Control
Honeywell MicroSwitch
V7-1C13D8-201
15.1A (1/2 HP) at 125 VAC; ½A at 125 VDC; 1/4A at 250VDC; 5A at 120Vac
M3 – DPDT Mechanical
Cherry
E19-00A
15A, 125/250 VAC 3/5HP
MB – DPDT Mechanical
Licon
22-104
10A (1/2 HP) at 125 VAC
MD – 3-Pos. Control w/Indication (DA)
Licon
22-104
10A (1/2 HP) at 125 VAC
MS – 3-Pos. Control w/Indication (SR)
Licon
22-104
10A (1/2 HP) at 125 VAC P4 – SPST Proximity
Aleph
PS-6132
0.35A at 140 VAC / .25A at 200VDC (50 W Max.)
P5 – SPDT Proximity
Hamlin
59135-030
0.25A at 120 VAC / 0.25A at 28 VDC (3 W Max.)
PE – SPDT Sabre Proximity
Flowserve
XA0199
1A at 120 VAC / 2A at 24 VDC
PP – SPDT Phazer Proximity
Flowserve
XA0155
3A at 120 VAC / 2A at 24 VDC
PL – SPDT Phazer w/LED
Flowserve
XA0154
0.5A at 120 VAC /0.3A at 24 VDC
PT – SPST BRS Proximity
Flowserve
XA0157
3A at 120 VAC / 0.5 at 24 VDC
PX – SPST BRS
w/LED
Flowserve
XA0156
0.5A at 120 VAC / 0.3A at 24 VDC
N8 – Solid State
Proximity
Pepperl + Fuchs
NJ2-V3-N
NAMUR Sensor Output / 5-25 VDC
Supply
NP – Solid State
Proximity
Pepperl + Fuchs
SJ3.5-N
NQ – Solid State
Proximity
Pepperl + Fuchs
NJ4-12GK-N
NR – Solid State
Proximity
Pepperl + Fuchs
NJ4-12GM40-E1
PNP Sinking / 200 mA max. Current / 10-
60 VDC
NS – Solid State
Proximity
Pepperl + Fuchs
NJ4-12GM40-E2
NPN Sourcing / 200 mA max. Current /
10-60 VDC
NT - Solid State
Proximity
Pepperl + Fuchs
NJ4-12GK40-E2
NPN Sourcing / 200 mA max. Current /
10-60 VDC
NU – SPDT GO
Proximity
GO
35-13319-A1A
4A at 120 VAC / 2A at 240 VAC
N9 – Solid State
Proximity
Pepperl + Fuchs
NBB3-V3-Z4
NPN Sourcing/ 100 mA max. Current /
5-60 VDC
SN – 3-way
Pneumatic
Consult factory for technical specifications
FZ – AS-I Bus Card
31VDC 28 mA
Switch Option Specifications: