Flowserve RT92 User Manual

Worcester Actuation Systems
FCD WCAIM2011-00
(Part 09599)
Series RT92 Remote Terminal Unit
Installation, Operation and Maintenance Instructions
I. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
II. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1. TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2. CIRCUIT BOARD TEMPERATURE CONSIDERATIONS . .2
3. HUMIDITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
4. INPUT CIRCUIT NOISE PROTECTION . . . . . . . . . . . . . .2
III. ELECTRONIC CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . .2
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
B. CIRCUIT BOARD CONFIGURATIONS . . . . . . . . . . . . . . . . .2
C. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
D. DC POWER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
IV. INSTALLATION OF RTU INTERFACE
INTO SERIES 75 ACTUATOR . . . . . . . . . . . . . . . . . . . . . . . .3
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1. CHECK KIT FOR PARTS . . . . . . . . . . . . . . . . . . . . . . . . .3
2. TOOLS NEEDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3. OPERATIONAL CHECK OF BASIC ACTUATOR . . . . . . . .4
B. MOUNTING POTENTIOMETER . . . . . . . . . . . . . . . . . . . . .4
1. MOUNTING SINGLE POTENTIOMETER
INTO SERIES 75 ACTUATOR . . . . . . . . . . . . . . . . . . . . .4
2. POTENTIOMETER WIRING . . . . . . . . . . . . . . . . . . . . . .4
3. ADJUSTING POTENTIOMETER . . . . . . . . . . . . . . . . . . .5
4. DUAL POTENTIOMETER . . . . . . . . . . . . . . . . . . . . . . . .5
C. MOUNTING CIRCUIT BOARD . . . . . . . . . . . . . . . . . . . . . .5
D. POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . .6
V. CIRCUIT BOARD ADJUSTMENTS AND INFORMATION . . . . . .6
A. I-LIMIT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
B. LOCAL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
C. REMOTE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
D. FUSE PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
E. RELAY OUTPUT OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . .8
VI. CUSTOMER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . .8
VII. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2
I. INTRODUCTION
The Flowserve Worcester RTU (Remote Terminal Unit) Interface Card is designed for use with the low power Worcester Series 75 DC Electric Actuators. The low power actuators are those with standard DC motors mounted on 15-second gearboxes. This increases duty cycle while lowering current draw for a given torque output. The RTU card acts as an interface between the customer’s RTU and the actuator’s DC motors. Its primary function is to protect the customer’s DC solar power supply in the event of a stuck valve or some other condition that could cause an overcurrent condition. It does this by electronically disconnecting the motor drive circuits when an overcurrent condition exists. Removing the control signal and reapplying it resets the logic in the drive circuits.
II. GENERAL
A. Environmental Considerations
CAUTION: The RTU Interface is relatively insensitive to electrical noise on signal or supply lines and in the environment. Follow installation, calibration and adjustment guidelines carefully and use shielded wire as stated in paragraph 4.
Flowserve recommends that all products which must be stored prior to installation be stored indoors, in an environment suitable for human occupancy. Do not store product in areas where exposure to relative humidity above 85%, acid or alkali fumes, radiation above normal background, ultraviolet light, or temperatures above 120°F or below 40°F may occur. Do not store within 50 feet of any source of ozone.
Temperature and humidity are the two most important factors that determine the usefulness and life of electronic equipment.
1. Temperature: Operating solid state electronic equipment near or beyond its high temperature rating is the primary cause for most failures. It is, therefore, very important that the user be aware of, and take into consideration, factors that affect the temperature at which the electronic circuits will operate.
Operating an electronic device at or below its low temperature rating generally results in a unit operating poorly or not at all, but it will usually resume normal operation as soon as rated operating temperatures are reached. Low temperature problems can be easily cured by addition of a thermostatically controlled heater to the unit's housing.
At high temperatures, some components will destruct completely when their maximum temperature is exceeded, others will cease operation at temperatures above ratings and will return to operation at normal temperatures, but may have been permanently changed in one or another parameter causing a device to operate poorly, and may also cause greatly reduced component life.
2. Circuit Board Temperature Considerations: The Worcester RTU Interface is rated for operation between
-40°F and 160°F. When using the interface inside the Worcester 75 Series actuators, do not exceed a maximum ambient
temperature limit of 115°F in order to ensure that the circuit board maximum temperature of 160°F is not exceeded.
3. Humidity: Most electronic equipment has a reasonable degree of inherent humidity protection and additional protection is supplied by the manufacturer, in the form of moisture proofing and fungicidal coatings.
Such protection will generally suffice for environments where the average relative humidity is in the area of 80% or less and ambient temperatures are in the order of 70°F average with only occasional short term exposure to temperatures up to 90°F. Where relative humidity is consistently 80 to 90% and the ambient temperature is high or subject to large variations, considerations should be given to installing a heater and thermostat option in the enclosure. The heater should not increase the enclosure temperature to the point where the circuit board assembly’s temperature rating of 160°F is exceeded.
In those instances where the internal heater would bring the circuit board’s operating temperature near or above its maximum rating, the user might consider purging the enclosure with a cool, dry gas. The initial costs can usually be paid off quickly in the form of greatly extended equipment life, low maintenance needs, and much less process downtime.
4. Input Circuit Noise Protection: Shielded wiring should be used for all signal input circuit wiring regardless of length.
With a separately housed interface board, the wiring from the feedback potentiometer to the remote interface board is considered as signal input wiring and should also be shielded wire.
The shields should never be used in place of one of the input wires, and the shields normally should be grounded to equipment housings at one end of the wiring run only. Grounding both ends of shielding can eliminate the shielding benefits because of current ground loops. If two or more shielded cables come to the RTU card from different locations, ground the shields at the RTU card location.
III. ELECTRONIC CIRCUIT BOARD
A. General
Figures 1 through 3 show the location of major components of the various RTU cards. The RTU card is wired into the terminal strip through two amphenol 6-pin quick disconnects. This makes it very quick and easy to replace a circuit board in the field.
B. Circuit Board Configurations
There are three basic circuit board configurations. All versions contain the same basic input, logic, and motor control circuitry including overcurrent trip. The difference is in the type of output indication desired. The first version (Figure 1) has no output indication circuitry. The second version (Figure 2) is set up to provide a 0-5 volt position indication output. The third version (Figure 3) is set up to provide a relay trip condition indication (positive, negative, or contact closure). The three boards are physically different in this respect and are not interchangeable. All three versions will work with either 12 VDC or 24 VDC.
Flow Control
Worcester Actuation Systems
3
C. Controls
There is only one control that is common to all three versions of the RTU Interface and that is the current limit adjustment (I-Limit). This control allows adjustment of the level of load current that will cause an overcurrent trip.
A second control is found on the version with 0-5 volt position indication output and is used to adjust for a 5 volt output at the valve full open position.
D. DC Power Control
The DC power circuitry is 100% solid state and utilizes power MOSFETS for switching. In addition, DC opto-couplers are used to isolate the output circuits from the logic and input circuits.
The two circuit board versions with output indication have two glass envelope fuses for board and motor protection as well as to protect the power supply in the unlikely event of a board or motor failure. The smaller fuse protects the circuit board in case of a logic component failure and the larger fuse protects the power supply in case of a power MOSFET failure.
IV. INSTALLATION OF RTU INTERFACE
INTO SERIES 75 ELECTRIC ACTUATOR
A. General
If the actuator was purchased with the RTU Interface board factory installed, proceed to Section V.
NOTE: All wiring to terminal strip should be inserted only to mid-point of terminal strip.
1. Check Kit For Parts:
a. Common Parts For Sizes 10-23:
Qty. Name
1 Circuit Board Subassembly 1 Insulating Board 5 Washers (Nylon) 5 Grommets (Rubber) 5 Mounting Screws (Circuit Board) 1 Nameplate - Circuit Board 1 Nameplate - Base 1 Wiring Label - Cover 1 Instruction Manual 5 Cable Ties 1 Bracket - Right (Long) 1 Bracket - Left (Short) 4 Spacer (Bracket) 4 Mounting Screw (Bracket/Spacer) 2 Connector Cable Assemblies
(One “A” & One “B” Assembly)
Flow Control
Worcester Actuation Systems
Figure 1: No Output Indication
Figure 2: Position Output Indication
Figure 3: Current Trip Indicator
b. Additional Parts For Version With 0-5 Volt Position
Indication Output:
Qty. Name
1 Potentiometer Kit Subassembly
2. Tools Needed:
1
/
4" nut driver,
1
/
8" screwdriver, needle nose pliers,
1
/
16" Allen wrench
(cams and spur gear), volt/Ohmmeter (checking feedback potentiometer resistance, voltages, incoming control signal).
3. Operational Check of Basic Actuator:
The cams that actuate limit switches 1 and 2 should be set such that SW-1 trips at the full closed position and SW-2 trips at the full open position.
NOTE: If extra limit switches are installed for position indication, their cams should be set to trip the appropriate extra limit switch 1-2 degrees prior to SW-1 or SW-2 tripping. If valve torque is not too high, the actuator shaft may be repositioned manually using the actuator declutch mechanism to declutch the output shaft and turning the output shaft with a wrench. If the valve torque is too high, the actuator may be repositioned electrically by disconnecting connector ‘A’ and applying the appropriate voltage and polarity to the connector pins attached to the blu
e and yellow wires.
B. Mounting Potentiometer
For Version with 0-5 Volt Output or Where Resistive Position Feedback is Desired (See Figure 4)
1. Mounting Single Potentiometer Into Series 75 Actuator
With the potentiometer mounted to the potentiometer bracket and the spur gear loosely fitted to the potentiometer shaft, mount the potentiometer bracket to the motor module (if not already mounted) as follows:
Remove the motor module mounting screws on the side of the module furthest away from the actuator shaft. Position potentiometer assembly bracket holes over screw holes and line up potentiometer shaft with center of actuator shaft, replace and tighten screws.
2. Potentiometer Wiring:
The feedback potentiometer leads are connected to the actuator terminal strip as follows:
NOTE: The feedback pot is wired to the terminal strip for No Output Indication and Position Output Indication circuit boards. In the case of the No Output Indication board, the two wires on the external side of terminal 7 and 8 are removed and taped with electrical tape. For the Current Trip Indicator board it will be necessary to hardwire the feedback pot directly to the customer’s wiring.
4
Flow Control
Worcester Actuation Systems
Figure 4
ITEM DESCRIPTION
1 Limit Switches 2 Motor Module 3 Motor Module Mounting Screws (2) 4 Terminal Strip 5 Actuator Shaft 6 Potentiometer 7 Potentiometer Bracket 8 Spur Gear
9 Spur Gear Set Screw 10 Potentiometer Leads 11 Potentiometer Shaft 12 Face Gear 13 Snap Ring 14 Lockwashers (2) 15 Nut
For Resistive Position Output For 0-5 Volt Position Output
Terminal Wire Color Terminal Wire Color
7 Green 1 Purple 8 Wht/Blk 7 Green 9 Purple 8 Wht/Blk
View A-A
5
3. Adjusting Potentiometer: (Reference Figure 4)
a. Place the large face gear (item 12) over the actuator shaft
with the gear teeth down and secure with snap ring (item
13) provided.
NOTE: The face gear utilizes a friction fit to the shaft. For best results, wipe off any lubricant that may be on the shaft before sliding on the face gear.
CAUTION: Do not overstretch the snap ring, use the minimum opening to allow snap ring to slip over the gear.
b. Adjust the potentiometer spur gear until there is
approximately
1
/
16" engagement with the large face gear.
Tighten the spur gear set screw.
c. Rotate the face gear back and forth to ensure smooth and
easy operation of the potentiometer.
d. For units with 0-5 volt position output calibrate the
potentiometer per paragraph IV.B.3.f.
e. For units with resistive position indication, calibrate the
potentiometer as follows:
i. Position the actuator shaft in the full clockwise
position if it is not already there.
ii. With power off and using an ohmmeter, measure the
resistance between the purple and the white/black leads from the potentiometer. The measured resistance should be 80 ohms plus or minus 10 ohms. Rotate the large face gear to achieve this resistance. Note: It is not necessary to loosen or remove face gear snap ring to rotate gear.
f. For units with 0-5 volt position output calibrate the
potentiometer as follows:
i. Connect 12 VDC power to terminals 1 and 2. Terminal
1 is common or negative and terminal two is positive.
ii. Connect a digital voltmeter to terminals 1 and 10, with
the negative lead to terminal 1 and the positive lead to terminal 10.
iii. Set the voltmeter to a full scale reading of at least 5
volts.
iv. Turn the 5 volt adjust pot on the RTU card to the mid-
position. With the switches on the RTU card, run the actuator in the CW direction until the closed limit switch trips. This should be the full closed position. If not, readjust the closed limit switch cam until the actuator stops in the proper position.
v. Rotate the large face gear on the actuator shaft until a
positive voltage reading is observed on the voltmeter. Now slowly rotate the face gear to reduce the voltage reading towards zero volts. The lowest reading you will probably observe is .02 to .03 volts. Stop rotating the gear as soon as the voltage stops dropping. This
adjustment is important. You may want to move the face gear back and forth several times to get the feel for the proper adjustment.
vi. Once this adjustment has been made satisfactorily,
use the switches on the RTU card to run the actuator to the full CCW position. If necessary, readjust the CCW limit switch cam to achieve the proper full open position. Now adjust the 5 volt adjust pot on the RTU card to read 5 volts on the voltmeter.
vii. This completes the calibration of the 0-5 volt position
indication output. However, you may want to operate the actuator full open and closed several times to verify proper adjustment of the position indication output. Disconnect the voltmeter from terminals 1 and 10.
IMPORTANT: The feedback potentiometer is calibrated for only one 90° quadrant of valve operation. If the output shaft is repositioned to another 90° quadrant or if the output shaft is rotated a multiple of 360° from its original position the feedback potentiometer will no longer be in calibration and must be recalibrated as directed in section IV.B.3.
4. Dual Potentiometer:
a. In the case of a dual potentiometer, D75, “A” (front, close
to the potentiometer bracket) potentiometer wires are wired as stated in IV.B.2. “B” (rear, far from the bracket) potentiometer wires must be wired directly to external instrumentation.
NOTE: Voltage limit of “B” pot is 30 volts maximum.
C. Mounting Circuit Board
1. For 12 or 24 VDC 10-23 Size Electric Actuators: (See Figures 5 and 6).
a. Pre-tap circuit board bracket holes with the self-tapping
circuit board mounting screws (item 5). Remove the outside corner motor screws and mount the brackets to the appropriate spacers using the self-tapping spacer/bracket mounting screws (item 8) being careful to avoid stripping the threaded holes in motor base. The longer bracket is mounted to the right side of the actuator when facing the terminal strip.
NOTE: For actuators with single motor, be sure that shorter spacers are used on side with motor.
b. Once these screws and brackets are firmly secured, firmly
tap the motor stators with a plastic faced hammer to force realignment of the motor bearings.
c. Loosen all terminal strip screws and install the A and B
connector cable assemblies into the actuator terminal strip. See figure 6 (next page) for proper wiring of cable assemblies to terminal strip. Wire routing is important. Ensure that wiring is not pinched and is not touching any moving parts such as cams or switch arms.
Flow Control
Worcester Actuation Systems
6
d. Assemble circuit board into actuator. Slide rubber
grommets onto insulating board. Put nylon washers under heads of self-tapping screws (Five screws will be used to install the circuit board onto the brackets).
e. Place the circuit board over the brackets with the
insulating board between the circuit board and the mounting brackets. Loosely tighten the four screws securing the board and insulator. Use a nylon washer and a rubber grommet on the self-tapping screw securing the right front corner of circuit board (as you face the terminal strip). Place the rubber grommet between the circuit board and the mounting bracket. Tighten all the mounting screws so that the grommets are about half compressed.
f. Insert each of the cable assembly connectors into its
respective circuit board socket (A and B).
D. Power Connections
The appropriate power source (12 VDC) is connected to terminals 1 (common or negative) and 2 (plus or positive).
NOTES:
1. Actuator shown in the counterclockwise extreme of travel or "open" position.
2. For a 10, 20 (motor module on fast side) or 23 75, reverse the red/black motor leads.
3. Grounding wires should be connected to green colored grounding screw (if present) on actuator base or to any base plate mounting screw in the actuator.
For resistive position indication instead of voltage indication, remove purple wire from terminal #1 and put in rear of terminal #9. Remove
wires from front of terminals #7 and #8 and tape
same.
CAUTION: It is important that the DC voltage power source be connected properly to the actuator’s terminal strip. Terminal one (1) of this strip is to have the negative or common wire connected to it. Terminal two (2) is to have the positive wire connected to it. The board has a diode and a fuse installed to prevent damage in the case of reverse voltage polarity, but if the diode happens to be defective, damage could be done before the fuse blows.
V. CIRCUIT BOARD ADJUSTMENTS
A. I-Limit Adjustment
1. The RTU card as shipped from the factory should have the
I-Limit pot on the card turned full clockwise. This will allow the maximum permissable actuator output torque. The customer can then turn the trimpot counterclockwise in order to reduce the current trip level. Because of various motor, gearbox, and voltage combinations possible, different sense resistor (R8) values are used on the circuit board to allow operation in a particular current/torque range. The resistor values are selected as follows:
Flow Control
Worcester Actuation Systems
ITEM DESCRIPTION
1 Circuit Board Subassembly 2 Insulating Board 3 Bracket-Right (Long) 4 Grommet-Rubber 5 Mounting Screws (Circuit Board) 6 Washer-Nylon 7 Bracket-Left (Short) 8 Mounting Screws (Bracket) 9 Spacer (Bracket)
Figure 5
Figure 6
7
Resistor Resistance Value (R8) Approx. Current Trip Range
A .75 ohm 5 watt .8 to 1.6 amp B 1.5 ohm 5 watt .4 to .8 amp C 2.5 ohm 5 watt .25 to .5 amp D .51 ohm 5 watt 1.18 to 2.35 amp
These values were selected to keep the actuator within the maximum acceptable torque limits.
2. The following table lists the various low power actuator ordering codes, the motor voltage, and the current sense resistor to be supplied on the RTU card.
Actuator Code Supply Voltage Resistor Code
10 R 75 4-12D 12 volts B 12 R 75 4-12D 12 volts B 10 R 75 4-24D 12 volts C 12 R 75 4-24D 12 volts C 20 R 75 4-12D 12 volts A 22 R 75 4-12D 12 volts A 23 R 75 4-12D 12 volts D 20 R 75 4-24D 12 volts B 22 R 75 4-24D 12 volts B 23 R 75 4-24D 12 volts A
3. The actuator codes are broken down as follows:
10R75 Single motor Gearbox mtd. on fast side 4 Duty cycle - 75%
12R75 Single motor Gearbox mtd. on slow side
20R75 Dual motor Gearbox mtd. on fast side 12D Motor voltage - 12 VDC
22R75 Dual motor Gearbox mtd. on slow side 24D Motor voltage - 24 VDC
23R75 Dual motor Gearbox mtd. on slow side
B. Local Operation
The RTU card has been provided with momentary push-button switches to enable local operation of the actuator for maintenance, calibration, etc. Depressing switch SW1 will cause the actuator to operate in the clockwise direction until the switch is released, an overcurrent condition causes a trip, or the end of travel limit is reached. Depressing switch SW2 will cause the actuator to operate in the counterclockwise direction until it is released, an overcurrent trip occurs, or the end of travel limit is reached.
C. Remote Operation
1. Remote operation of the RTU is initiated by bringing terminal 11 for clockwise operation or terminal 12 for counterclockwise operation to the common/negative voltage reference level (i.e. same as terminal 1). This will cause the actuator to operate in the appropriate direction until the signal is removed, the end of travel limit switch trips, or the unit trips out on overcurrent. The controller/PLC need only sink approximately .03 mA in order for the board to operate. In the event of an overcurrent trip, removal of the control signal and
subsequent reapplication of the signal will reset the trip circuit. If the cause of the overcurrent condition still exists, the circuit will again trip.
2. The circuit has also been designed to operate such that the power can be removed from the board when actuator motion is not needed. Then when motion is desired, both the power and the appropriate control signal may be applied at the same time. This feature can be used when the standby current draw of the circuit board (about 10 mA) is too much for the solar power supply when many actuators are involved. Turning circuit board power on and off along with the control signal keeps power consumption to an absolute minimum.
D. Fuse Protection
Each of the three circuit board versions has a main power supply fuse (F1) to protect the power source and circuit board in the event of a circuit board or motor failure. This fuse is a standard
1.25" 3AG fuse rated at 3 A 250 V. In addition to this fuse, the
Position Output Indication circuit board with the 0-5 volt position
Flow Control
Worcester Actuation Systems
Figure 7
Figure 8
output has a second fuse (F2) which supplies power to the position output circuit so that there will still be position output available even if the main fuse blows. This second fuse is a .6" 2AG fuse rated at .25 A 250 V.
E. Relay Output Options
Refer to Figure 7. The RTU card with the current trip indicator has been designed such that several different jumper configurable output options are available. These are:
a. Contact closure to +V (terminal 2)
b. Contact opening from +V (terminal 2)
c. Contact closure to common (terminal 1)
d. Contact opening from common (terminal 1)
e. Straight contact closure (closed circuit)
f. Straight contact opening (open circuit)
VI. CUSTOMER CONNECTIONS
A. For the No Output Indication board, refer to Figure 8. However,
there would be no feedback pot connected to terminals 1, 7, and
8. If the customer did request a feedback pot, it would be connected as described in paragraph IV.B.2. There would be no meter connected to terminal 10 because there is no 0-5 volt output from this board.
B. For the Position Output Indication board, refer to Figure 8.
C. For the Current Trip Indicator board, refer to Figures 7 and 8.
There would be no feedback pot connected to the terminal strip and no meter connected to terminal 10. The actuator side of terminal 10 still comes from connector B3 but it is not the 0-5 volt output. It is the circuit shown in Figure 7.
VII. TROUBLESHOOTING
To determine whether the basic actuator or the circuit board is at fault, replace circuit board with a known good board.
NOTE: When ordering replacement parts, i.e., actuator motor(s), etc., please use both the actuator code and the RTU code as found on the nameplates attached to the actuator base.
Flow Control
Worcester Actuation Systems
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices.
For more information about Flowserve Corporation, visit www.flowserve.com or call USA 1-800-225-6989.
FLOWSERVE CORPORATION Flow Control Worcester Actuation Systems
5114 Woodall Road P.O. Box 11318 Lynchburg, VA 24506-1318 Phone (434) 528-4400 Fax (434) 845-9736
© 2004 Flowserve Corporation, Irving, Texas, USA. Flowserve and Worcester Controls are registered trademarks of Flowserve Corporation. FCD WCAIM2011-00 Printed in USA.
(Part 09599)
SYMPTOMS
1. No response from unit in remote or local control
2. Works with local switches but no response under remote control.
3. Motor starts to run but then trips off before actuator has reached desired position.
POSSIBLE CAUSES
No power; Main fuse blown; Logic fuse blown; One or both remote input(s) grounded; Board defective; Defective motor(s); Defective limit switches
Remote input circuit broken; Input voltage not close enough to ground potential at Terminal 1
I-Limit pot not set correctly; (Full CW=Maximum trip current); Torque of valve too high; Defective board; Defective motor(s)
Loading...