Flowserve ACE User Manual

3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway Phone: 801 489-2234 Flow Control Division Springville, Utah 84663-3004 Facsimile: 801 489-2228
SR Limit Switch Method
Accord Controls
CENTURA™ ACE Series
Introduction
The Centura electric actuator is a rotary valve actuator with output torques from 250 to 1,500 in-lbs. It has been designed for NEMA 4, 4X, 7, 9 and can come with a 4-20 mA card for modulating service.
Storage
For short and long term storage refer to short and long term storage conditions CE Actuator.
Maintenance
Centura Series actuators contain a permanently lubricated, precision cut, heat treated gear train for long, reliable cycle life. There is no need to change gear train grease; however, should it become necessary to refill, use a multi-purpose grease such as DuBois MPG-2.
Permanent split capacitor gearmotors have been equipped with thermal protectors. After many operations, especially in warm environments, the motor will heat up. To guard the motor against overheating, the thermal cut-out blocks power to the motor and maintains this state until the motor’s temperature drops to a satisfactory level. This thermal protection means that the actuator will not move when overheated. Consideration must be given to the duty cycle requirements of the actuator.
When replacing the cover, the machined joints must be clean and clear of any obstructions. The integrity of the explosion-proof rating depends on the care of these joints.
actuator to determine its operating range, taking note of any explosion safety requirement. The electric actuators are factory set for 90 degree operation.
Caution:
for rubber lined butter fly valves & dampers or applications that may back drive the unit.
4. Mount Accord actuator to valve with Accord provided mounting hardware to ensure proper alignment. Use mounting hardware that has 1 and 1/2 times bolt length engagement. (Do not use the manual override to align actuator shaft to valve shaft, as this could drive the actuator out of its operating range). (
NOTE:
appropriate or set actuator to operate within those travel stops).
5. Care should be taken to align valve stem properly with Accord actuator output shaft (misalignment will cause premature failure of assembly).
6. To connect power to terminal strip of actuator, remove the cover and locate the terminal wiring schematic inside the cover.
7. Connect power to terminal strip according to schematic diagram (power should be fused with a 5 amp slow­blow fuse). The actuator should be wired and grounded in accordance with Local and National Electrical Codes.
Use heavy duty brake option ‘K’
Some valves have manual stops; remove if
Installation
1. This section of the instruction sheet applies to the on­off units. For instructions on Modulating units, please see the ESP3 Electronic Servo Positioner Instructions.
2. Manually open and close valve to ensure freeness of operation.
Caution:
To prevent ignition of hazardous atmospheres, keep unit tight while circuits are alive. Disconnect supply circuit before opening.
3. Be sure valve and Accord actuator rotate in the same direction and are in the same position (i.e., valve closed, actuator closed). If not sure, electrically operate the
FCD ACAIM0075-00 (AC-75) 08/04
©
2004, Flowserve Corporation, Printed in U.S.A.
Caution:
actuators in series or parallel. Serious damage may result. User must isolate unused winding.
8. Before replacing cover, actuate valve and check to see if it opens and closes to preferred positions. If valve does not perform correctly, adjust cams to set actuator travel properly.
9. Drive actuator to desired open position. The cams are adjusted in two ways. Simply depress the splined “Quick-Set” cam against the spring and rotate to desired location. Or, for very precise applications, turn the screw inside the cam to move the tip into the leaf of the micro switch.
Consult factory when wiring multiple
Page 1 of 8
3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway Phone: 801 489-2234 Flow Control Division Springville, Utah 84663-3004 Facsimile: 801 489-2228
SR Limit Switch Method
Accord Controls
10. To adjust closed position, repeat step 9 with actuator in desired closed position.
11. Operate the unit several times and recheck position. If unit is still out of adjustment, reset the cams by following steps 9 and 10.
12. Installation in hazardous areas requires that the electrical leads be sealed within 18 inches of the enclosure in accordance with Local and National Electrical Codes.
13. Open conduit entries must be closed up after installation is complete using a close-up plug engaging at least five full threads and approved for use in hazardous locations.
14. 60Hz actuator motors may be run on 50 Hz supply. However, the cycle time increases by 1.2 times and the duty cycle decreases by a factor of approximately 25%. The rated torque does not change.
Manual Override
The principle of the design is such that when the manual override shaft is in the up position, the shaft is disconnected from the drive train. When the shaft is in the down position it does two things. One, the shaft trips a switch to discon­nect the power to the motor and two, it releases the brake. By releasing the brake the motor can back drive along with the output. For 90 degree operation, the 250 in-lbs unit requires 1.6; the 700 in-lbs unit requires 3.1; the 1000 in-lbs unit requires 4.2; and 1500 in-lbs unit requires 6.3.
Automatic Operation
1. Pull hub away from the actuator cover.
2. The motor is now electrically connected and ready for automatic operation.
3. The manual override shaft will freewheel.
Position Indication Stickers:
Attached to the inside of the cover is a set of stickers with the words “CLOSED” and “OPEN”. These stickers are to be attached to the outside of the actuator near the base between the mounting feet. The stickers have an orange triangle on them, such that when properly attached to the actuator, they will line up with the triangle on the output shaft. A sticker can be placed on either side of the unit to produce a visual indication of the opened and closed position of the actuator.
Caution:
Turn manual override shaft slowly.
DO NOT jerk.
Manual Operation
1. The actuator cover should be securely attached.
2. Depress hub toward actuator cover.
3. Rotate the manual override shaft slowly; do not force.
4. The motor is now electrically disconnected.
5. Turn the manual override shaft clockwise for clockwise output.
6. Do not rotate actuator past full clockwise or counter­clockwise position.
FCD ACAIM0075-00 (AC-75) 08/04
©
2004, Flowserve Corporation, Printed in U.S.A.
Page 2 of 8
3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway Phone: 801 489-2234 Flow Control Division Springville, Utah 84663-3004 Facsimile: 801 489-2228
SR Limit Switch Method
Accord Controls
FCD ACAIM0075-00 (AC-75) 08/04–
©
2004, Flowserve Corporation, Printed in U.S.A.
Page 3 of 8