Flowserve Accord Centura Analog Output Options User Manual

Accord Controls
Installation, Operation and Maintenance Instructions
Flowserve Corporation
1350 N. Mountain Springs Parkway
Phone: 801 489 2234
Flow Control Division
Springville, Utah 84663-3004
Facsimile: 801 489 2228
FCD ACAIM0073-00 (AC-73) 06/04 Page 1 of 2 © 2004, Flowserve Corporation, Printed in USA
NOTE:
1. Both resistive and current feedback signals are geared for quarter turn operation. Consult factory for other rotations.
2. The ‘TX’ option is a loop powered transmitter. For ‘TT’ options (transmitter with servo) see IOM for electronic servo position.
Caution: To Pr
event ignition of hazardous atmospheres, keep unit tight
while circuits are alive. Disconnect supply circuit before opening.
Division 1 applications must be calibrated in a secured area.
Calibration
Resistive Feedback:
1. Remove cover and rotate actuator/valve to fail or start position.
2. Note desired resistance values at fail or start position.
3. Connect an ohmmeter to feedback terminals.
4. Using a 0.035 allen hex driver, loosen the set screw on the potentiometer gear. With a flat blade screwdriver, rotate the end of the potentiometer shaft to yield desired resistance.
5. Alternatively, the jam nut holding the potentiometer to the bracket may be loosened. Slide the potentiometer and gear away from the camshaft gear and rotate to desired resistance. Re-align and tighten.
6. Rotate actuator/valve to end position. Check that resistance increases (or decreases) over stroke and that the potentiometer does not rotate past maximum (or minimum) resistance.
7. Replace cover.
4-20 mA Current Transmitter:
Figure 1 shows a diagram of the transmitter board and all necessary current loop components for calibration.
1. The controller board action DIP switch selects direction. For 4 mA in the full clockwise direction, select “D”. For 4 mA in the full counterclockwise direction, select “R”. The factory setting is “D”.
Note:
Steps 2 through 4 are normally not necessary.
2. Rotate actuator/valve to mid position (45 degrees or 50%).
3. Using a 0.035 allen hex driver, loosen the set screw on the potentiometer gear. With a flat blade screwdriver, rotate the end of the potentiometer shaft to yield desired resistance.
4. Alternatively, the jam nut holding the potentiometer to the bracket may be loosened. Slide the potentiometer and gear from the camshaft gear and rotate to desired resistance. Re-align and tighten.
5. Rotate actuator/valve to fail or start position.
6. Adjust controller board zero trim pot. to yield 4 mA.
7. Rotate actuator/valve to end position.
8. Adjust controller board span trim pot. to yield 20 mA.
9. The zero and span adjustments are interactive. Repeat steps 5 through 8 until further zero adjustment does not affect span and vice versa.
10. Disconnect test equipment (if necessary) and replace cover.
Note:
If transmitter adjustment gets difficult (i.e., trim pots do not have desired effect) start over by “centering” the trim pots. This is accomplished by turning in one direction 20 turns or until a clicking is heard. Turn in the opposite direction 10 turns. Repeat for other trim pot. Start calibration over at step 2.
Centura Analog Output Options
Calibration and Operating Instructions
TYPE TX TYPE P2 TYPE P3 TYPE P4
4-20 mA Current Transmitter 0-1 K ohm resistive 0-5K ohm resistive 0-10 K ohm resistive Voltage required: 6-30 Vdc 1 Watt max. Ioad 1 Watt max. Ioad 1 Watt max. Ioad Input resistance: 750 ohms max. Temp. range: 32 to 158°F Temp. range: 32 to 158°F Temp. range: 32 to 158°F
@ 24 Vdc
Temp. range: 32 to 158°F
Electrical Specifications
Resistive feedback modules use a 1% linearity precision potentiometer operated by precision gears. The current feedback option combines the potentiometer with a 4-20 mA transmitter card.
Flowserve Corporation
1350 N. Mountain Springs Parkway
Phone: 801 489 2234
Flow Control Division
Springville, Utah 84663-3004
Facsimile: 801 489 2228
Accord Controls
Installation, Operation and Maintenance Instructions
FCD ACAIM0073-00 (AC-73) 06/04 Page 2 of 2 © 2004, Flowserve Corporation, Printed in USA
Figure 1 – 4-20 mA Transmitter Diagram
Probable Cause/Solution
Potentiometer is out of adjustment (see “Resistive Feedback Calibration” or 4-20 mA Current Transmitter Calibration” steps 2-4).
Zero or span trim potentiometer is out of adjustment (see 4-20 mA Current Transmitter Calibration).
Circuit Board LED not lit:
1. Loose or shorted signal connection (no loop power).
2. Controller board not responding (replace board).
Circuit Board LED lit:
1. Potentiometer disengaged.
2. Defective potentiometer or controller board. Replace defective component.
Input signal not linear. Linkage or drive mechanism is introducing non-linearity. Zero span trim potentiometer is out of adjustment (see 4-20 mA Current Transmitter Calibration).
Problem
Output is not continuous throughout actuator/valve stroke (experience a band of max. output)
Transmitter does not out 4 or 20 mA at desired end of travel.
Transmitter module does not provide current signal or provide constant signal.
Output not linear or does not track valve position/rotation
Troubleshooting
Loading...