SR Limit Switch Method
A25N NAMUR Directional Valve
The Automax NAMUR Directional valve mounts directly to SuperNova series actuators which eliminates the cost of tubing and fittings. The valves are available for double acting and spring return actuators with NEMA 4X, NEMA 4X, 7 & 9, or weatherproof intrinsically-safe and low power solenoid operators. These valves have been tested and proven reliable for over 1 million cycles.
Operation
Solenoid will not shift without backpressure on ports 2 and 4. Air supply lines to the valve must have I.D. at least as large as the NPT size of valve ports.
Temperature: NEMA 4X: -20°F to 150°F
NEMA 4X, 7 & 9: -20°F to 125°F For temperatures below 40°F, air must be free of water vapor.
Pressure: Minimum: 35 psig
Maximum: 150 psig
Media: Dry or lubricated non-corrosive gas
compatible with nitrile seals.
CV = 1.8 Flow Schematics:
(Port 1 - air supply)
3-way Valve (Spring Return Actuators)
4
2
315
When operator is energized, the spool shifts allowing the air pressure to enter the actuator and compress the springs. When de-energized, the spool returns, exhausting the air.
4-way Valve (Double-acting Actuators)
4
2
315
When operator is energized, the spool shifts, driving the actuator CCW. When de-energized the spool returns, driving the actuator CW. For de-energized CCW, rotate directional valve 180°.
Options:
Dual coil 2-position and 3-position valves are available. Consult factory. Sandwich NAMUR mount accessories: APS1 - Air purge system to purge spring chambers
with solenoid valve exhaust.
FC1, FCSR and FCDA - Single port and dual port
exhaust flow controls.
LV1 - Lockout and vent valve for lockout and
manual override applications. Automax sandwich NAMUR mount accessories provide compact, clean control packages for the SuperNova actuator.
Solenoid Information
NEMA 4X Weatherproof
• Coil is U.L. and C.S.A. recognized.
• Standard 1/2" NPT connector meets NEMA 4X rating.
• Connectors with strain relief for wiring with 3 lead, 18ga cord available.
• Eliminates junction boxes at solenoid. Simply plug in and tighten screw for easy installation and service.
• Standard with non-locking override.
• Continuous duty molded class H coil.
NEMA 4X, 7 & 9 "Explosion-proof"
• 1/2" NPT conduit
• 24" Electrical leads
• Meets U.L., C.S.A. and NEMA requirements for Class I, Gr C & D Div. 1 & 2 Class II, Gr E, F & G Div. 1 & 2
• Standard with non-locking override
• Continuous duty molded Class B Coil
Solenoid Electrical Characteristics
Characteristics for standard coils are shown below. All common voltages and hertz are available.
AC VOLTAGE ±10% DC VOLTAGE
WEATHERPROOF 120 VAC 240 VAC 12 VDC 24 VDC
Inrush Amps 0.078 0.041 0.400 0.200 Holding Amps 0.058 0.030 0.400 0.200 Resistance ( ) 840 3310 31.6 121
EXPLOSION-PROOF
Inrush Amps 0.127 0.063 0.632 0.320 Holding Amps 0.057 0.038 0.632 0.320 Resistance ( ) 475 2000 19.0 75
Weatherproof intrinsically-safe/low power
A .67 watt coil is available with 1/2" NPT weatherproof housing. The operator has Factory Mutual Entity approval. See the separate I.S. operator I.O.M. for further information.
LMR0012-1 (Auto-12) 2/03
©
2003, Flowserve Corporation, Printed in USA
Page 1 of 2
Automax Valve Automation Systems
3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr. Flow Control Division Springville, Utah 84663 Cookeville, TN 38501 www.flowserve.com Phone: 801 489 8611 Phone: 931 432 4021
SR Limit Switch Method
Installation Instructions
The Automax A25N directional valve is installed very easily to any SuperNova series actuator.
1. Place the O-rings provided into the O-ring bores on the face of the valve. Each O-ring should be completely seated in the bore.
2. Place the actuator with the two ports facing you, and the pinion pointing up. Orient the Automax solenoid valve with the (3) O-rings toward the actuator and the operator towards the right. (The small O-ring is for use with the optional APS1 module).
3. The valve is then mounted to the actuator with the two screws provided. Apply Locktite Threadlocker 222 or equal to the screws prior to assembly.
4. Connect the air supply to port #1 and wire solenoid per local and national electrical codes. The assembly is now ready for operation.
5. Optional porous bronze vents (P/N 101602) or adjustable speed controls (P/N 100531) can be added to ports #3 & #5.
6. The A25N directional valve is easily converted from 4-way to 3-way configuration (see figures below). Move the conversion screw from the front of the body to the NAMUR port (port #2) on the back of the valve for 3-way operation. Apply a small amount of thread sealant to eliminate leakage past the conversion screw.
3-way Configuration
CONVERSION SCREW
LUBRICATION:
• Lubrication of AUTOMAX products is not required but is recommended to maximize service life. Where devices not made by AUTOMAX are used in the system the manufacturer should be consulted regarding their lubrication requirements.
• Lubricators should be installed downstream of regulators per the manufacturer's instructions.
• AUTOMAX positioner supply air must be clean, dry and oil free. Do not use lubricators in conjunction with AUTOMAX positioners.
• Oils used in air line lubricators should be compatible with seals used in the system. Generally AUTOMAX products use Buna-N (Nitrile) with Viton seals available as an option. Oils should be petroleum based with oxidation inhibitors, an ISO 32 or lighter viscosity, and an aniline point between 82°C (180°F) and 104°C (220°F).
Note: See appropriate IOM's for installation of sandwich NAMUR mount accessories.
SuperNova Actuator
24˝ Leads
O-ring
(1) 103606
NEMA 4x Operator
4-way Configuration
CONVERSION SCREW
1/4" NPT
O-ring
(2) 105775
Conversion Screw
#3
#5
Air Supply
(Port #1)
1/4˝ NPT
M5 x 30mm
Socket Head Screws
Ordering Guide
Automax A25N Spool Type Body Type Operator Spring Voltages
A- 2-position 4-way A- single operator A - Remote air pilot D - 3 position spring center 1- 110/50, 120/60 C- 3-position 4-way - B- dual operator W - NEMA 4X R - 2 position spring return 2- 220/50, 240/60, 120VDC blocked center X - NEMA 4X, 7 & 9 Repeat operator code for 3- 12VDC, 22/50, 24/60 F- 2-position 3-way I - Intrinsically Safe 2 position, dual operator 4- 24VDC
Ordering Example: Automax 4-way solenoid valve with NEMA 4X, 7 & 9 operator, spring return, 120 VAC / 60 HZ
would be: A25NAAXR1
LMR0012-1 (Auto-12) 2/03
©
2003, Flowserve Corporation, Printed in USA
L - Low Power 5- 15.5VDC (12 & 24VDC only) (intrinsically safe only) V - 1.8 Watt Low Power NEMA 4X, 7, & 9
Nom. (30VDC Max.)
For other options - consult factory.
NEMA 4X, 7 & 9
Operator