The following instructions are designed to assist in
unpacking, installing and performing maintenance as
required on FLOWSERVE products. Product users
and maintenance personnel should thoroughly review
this bulletin prior to installing, operating or performing any maintenance.
In most cases FLOWSERVE valves, actuators and
accessories are designed for specific applications
(e.g. with regard to medium, pressure, temperature).
For this reason they should not be used in other applications without first contacting the manufacturer.
1.2Terms concerning safety
The safety terms DANGER, WARNING, CAUTION and
NOTE are used in these instructions to highlight par-
ticular dangers and/or to provide additional information on aspects that may not be readily apparent.
1.3Protective clothing
FLOWSERVE products are often used in problematic
applications (e.g. extremely high pressures, dangerous, toxic or corrosive mediums). In particular valves
with bellows seals point to such applications. When
performing service, inspection or repair operations
always ensure, that the valve and actuator are depressurised and that the valve has been cleaned and
is free from harmful substances. In such cases pay
particular attention to personal protection (protective
clothing, gloves, glasses etc.).
1.4Qualified personnel
Qualified personnel are people who, on account of
their training, experience and instruction and their
knowledge of relevant standards, specifications, accident prevention regulations and operating conditions, have been authorised by those responsible for
the safety of the plant to perform the necessary work
and who can recognise and avoid possible dangers.
DANGER:
indicates that death, severe personal injury and/or substantial property damage will occur if
proper precautions are not taken.
WARNING:
jury and/or substantial property damage can occur if
STOP!
indicates that death, severe personal in-
proper precautions are not taken.
CAUTION:
indicates that minor personal injury and/
or property damage can occur if proper precautions
are not taken.
NOTE:
indicates and provides additional technical
information, which may not be very obvious even to
qualified personnel.
Compliance with other, not particularly emphasised
notes, with regard to transport, assembly, operation
and maintenance and with regard to technical documentation (e.g. in the operating instruction, product
documentation or on the product itself) is essential,
in order to avoid faults, which in themselves might
directly or indirectly cause severe personal injury or
property damage.
1.5Installation
DANGER:
serial-no. and/or the tag-no. to ensure that the valve/
actuator is correct for the intended application.
Do not insulate extensions that are provided for hot
or cold services.
Pipelines must be correctly aligned to ensure that the
valve is not fitted under tension.
Fire protection must be provided by the user.
Before installation check the order-no,
3
Page 4
1.6Spare parts
1.9Valve and actuator variations
Use only FLOWSERVE original spare parts.
FLOWSERVE cannot accept responsibility for any
damages that occur from using spare parts or
fastening materials from other manufactures. If
FLOWSERVE products (especially sealing materials)
have been on store for longer periods check these
for corrosion or deterioration before using these
products. Fire protection for FLOWSERVE products
must be provided by the end user.
1.7Service / repair
To avoid possible injury to personnel or damage to
products, safety terms must be strictly adhered to.
Modifying this product, substituting nonfactory parts,
or using maintenance procedures other than outlined
in this instruction could drastically affect performance
and be hazardous to personnel and equipment, and
may void existing warranties. Between actuator and
valve there are moving parts. To avoid injury
FLOWSERVE provides pinch-point-protection in the
form of cover plates, especially where side-mounted
positioners are fitted. If these plates are removed for
inspection, service or repair special attention is
required. After completing work the cover plates must
be refitted.
These instructions cannot claim to cover all details
of all possible product variations, nor in particular
can they provide information for every possible
example of installation, operation or maintenance.
This means that the instructions normally include only
the directions to be followed by qualified personal
where the product is being used for is defined
purpose. If there are any uncertainties in this respect
particularly in the event of missing product-related
information, clarification must be obtained via the
appropriate FLOWSERVE sales office.
2UNPACKING
Each delivery includes a packing slip. When
unpacking, check all delivered valves and accessories
using this packing slip.
Report transport damage to the carrier immediately.
In case of discrepancies, contact your nearest
FLOWSERVE location.
Apart from the operating instructions and the
obligatory accident prevention directives valid in the
country of use, all recognised regulations for safety
and good engineering practices must be followed.
WARNING:
FLOWSERVE for repair or service FLOWSERVE must
STOP!
be provided with a certificate which confirms that the
product has been decontaminated and is clean.
FLOWSERVE will not accept deliveries if a certificate
has not been provided (a form can be obtained from
FLOWSERVE).
1.8Storage
In most cases FLOWSERVE products are
manufactured from stainless steel. Products not
manufactured from stainless steel are provided with
an epoxy resin coating. This means that FLOWSERVE
products are well protected from corrosion.
Nevertheless FLOWSERVE products must be stored
adequately in a clean, dry environment. Plastic caps
are fitted to protect the flange faces to prevent the
ingress of foreign materials. These caps should not
be removed until the valve is actually mounted into
the system.
Before products are returned to
4
Page 5
3 LOGIX 520 si OVERVIEW
The Logix 520 si is a two-wire, 4-20 mA input digital valve
positioner. The Logix 520 also utilizes the HART protocol to
allow two-way remote communication with the positioner. The
Logix 520 si positioner controls single-acting actuators with
linear and rotary mountings. The Logix 520 si is completely
powered by the 4-20 mA input signal. The minimum input
signal required to function is 3,6 mA.
Since the positioner is insensitive to supply pressure changes
and can handle supply pressures from 1,5 to 6 barg (22 to 87
psig), a supply regulator is usually not required; however, in
applications where the supply pressure is higher than the
4 SPECIFICATIONS
Table 1: Input Signal
Input Signal Range4 - 20 mA
(with HART)
Compliance Voltage12,0 VDC
(with HART signal)
maximum actuator pressure rating a supply regulator is required to lower the pressure to the actuator’s maximum rating (not to be confused with operating range). A coalescing
air filter is recommended for all applications due to the close
tolerances in the positioner.
NOTE:
The air supply must conform to ISA 7.0.01or
IEC 770 (a dew point at least 10 ˚C / 18 ˚F below
ambient temperature, particle size below five microns
– one micron recommended – and oil content not to
exceed one part per million).
Table 5: Performance
Characteristics (typical)
Linearity< ± 1,0%
Resolution< 0,1%
Repeatability< 0,2%
Voltage Supply (maximum)30 VDC
Minimum Required3,6 mA
Operating Current
Table 2: Stroke Output
Feedback Shaft0° to 90° normal
Rotation0° to 40° minimum
Table 3: Supply Air
Supply Air QualityFree from moisture, oil and
dust per IEC 770 and ISA-7.0.01
Input Pressure Range1,5 to 6,0 bar (22 – 87 psi)
Air Consumption0,08 Nm3/h @ 1,5 bar
(steady state)0,047 SCFM @ 22 psi
0,120 Nm3/h @ 6,0 bar
0,071 SCFM @ 87 psi
Table 4: Output Signal
Output Pressure0 - 100 % of supply air
Rangepressure
powder-painted
Soft GoodsNitrile
Weight1,2 kg (2,7 lbs)
Table 8: Shipping weights
Shipping weights
(incl. mounting kit)
SpecificationLogix 520 si
with pressure gauges1,6 kg
without pressure gauges 1,2 kg
5
Page 6
Supply Air
Filter / Regulator
for Supply Air
22 – 87 psi (1.5 – 6.0 bar)
2 Electro-pneumatic
Converter Module
1 Digital Control Circuit
Inner Loop
Piezo Control
-
Inner Loop
Position Feedback
Local
User
Interface
4 – 20 mA
+ HART
HART
∑
+
Micro
Processor
Gain
Figure 1: Logix 520 si Principle of Operation
5 PRINCIPLE OF OPERATION
The Logix 520 si positioner is a digital positioner that incorporates HART protocol for communication. The positioner
consists of three main modules:
1. The microprocessor-based electronic control
module includes HART communications and direct local
user interface switches
2. The piezo valve-based electro-pneumatic converter
module
3. The infinite resolution valve position sensor.
The basic positioner operation is best understood by referring to Figure 1. The complete control circuit is powered by
the two-wire, 4-20 mA command signal. The HART module
sends and receives the superimposed FSK HART digital communications over the 4-20 mA signal wires providing twoway remote digital communications to the microprocessor.
The analog 4-20 mA command is passed to the microprocessor, where it is compared to the measured valve stem
position. The control algorithm in the processor performs
control calculations and produces an output command to
the piezo valve, which drives the pneumatic amplifier. The
position of the pilot valve in the pneumatic amplifier is measured and relayed to the inner loop control circuit. This twostage control provides for more responsive and tighter control than is possible with a single stage control algorithm.
The pneumatic amplifier controls the airflow to the actuator.
The change of pressure and volume of the air in the actuator
causes the valve to stroke. As the valve approaches the desired position, the difference between the commanded position and the measured position becomes smaller and the
output to the piezo is decreased. This, in turn, causes the
pilot valve to close and the resulting flow to decrease, which
slows the actuator movement as it approaches, the new commanded position. When the valve actuator is at the desired
6
Pressure Regulator
Pneumatic
Piezo Valve
Amplifier
3 Valve Position
Sensor
Stroke
Control
Valve
position, the pneumatic amplifier output is held at zero, which
holds the valve in a constant position.
6 TUBING POSITIONER TO ACTUATOR
After mounting has been completed, tube the positioner to
the actuator using the appropriate compression fitting connectors:
Air connections: 1/4” NPT (standard air connection)
Auxiliary power: Pressurized air or permissible gases, free
of moisture and dust in according with IEC 770 or ISA
7.0.01.
Pressure range: 1,5 – 6,0 bar (22 – 87 psi)
For connecting the air piping, the following notes should be
observed:
1. The positioner passageways are equipped with filters,
which remove medium and coarse size dirt from the
pressurized air. If necessary, they are easily accessible for
cleaning.
2. Supply air should meet IEC 770 or ISA 7.0.01 requirements. A coalescing filter should be installed in front of
the supply air connection Z. Now connect the air supply
to the filter, which is connected to the Logix 500 si series
positioner.
3. With a maximum supply pressure of 6 bar (87 psi) a
regulator is not required.
4. With an operating pressure of more than 6 bar (87 psi), a
reducing regulator is required. The flow capacity of the
regulator must be larger than the air consumption of the
positioner (7 Nm3/hr @ 6 bar / 4,12 scfm @ 87 psi).
5. Connect the outlet connector Y of the positioner to the
actuator with tubing, independent of the action (direct or
reverse).
Page 7
M8
47
M6
17.7
17.7
28.6
173,5
63,5
17.7
17.7
28.6
100
28.6
1/4" NPT
ø 10
19,9
M 8
ø 10
M 20 x 1,5 or 1/2" NPT
11,9
23,9
60
96.5
Figure 2: Dimensional Drawing of the Logix 500 si Series Digital Positioner
7 WIRING AND GROUNDING GUIDELINES
Electrical connections: signal cable with cable passage (NPT,
PG13,5, or M20 x 1,5) to terminals 2 x 2,5 mm
Input signal: 4 – 20 mA
NOTE:
Observe the minimum requirements of voltage
and equivalent electrical load: 12,0 VDC / 600 Ω / at
20 mA
To calculate the maximum network capacitance use the following formula.
The performance is ensured only for a minimum input current of 3,6 mA.
For wiring, the following notes should be observed:
NOTE: The input loop current signal to the Logix 520
should be in shielded cable. Shields must be tied to a
ground at only one end of the cable to provide a place
for environmental electrical noise to be removed from
the cable. In general, shield wire should be connected
at the source. (Figure 8)
Connect the 4-20 mA current source to terminals +11 and
-12 (Figure 5).
Grounding Screw
The grounding screw, located inside the positioner cover,
should be used to provide the unit with an adequate and reliable earth ground reference. This ground should be tied to
the same ground as the electrical conduit. Additionally, the
electrical conduit should be earth grounded at both ends of
its run. The grounded screw must not be used to terminate
signal shield wires.
ø 4,8
ø 10
11,9
23,9
Compliance Voltage (Figure 4)
Output compliance voltage refers to the voltage limit the cur-
rent source can provide. A current loop system consists of
the current source, wiring resistance, barrier resistance (if
present), and the Logix 520 si impedance. The Logix 520 si
requires that the current loop system allow for a 12,0 VDC
drop across the positioner at maximum loop current.
CAUTION: Never connect a voltage source directly
across the positioner terminals. This could cause permanent circuit board damage.
In order to determine if the loop will support the Logix 520 si,
perform the following calculation.
Voltage = Compliance Voltage (@Current
- Current
MAX
*(R
barrier
+ R
wire
)
MAX
)
The calculated voltage must be greater than 12.0 VDC in order to support the Logix 520.
Example:DCS Compliance Voltage = 19 V
R
= 300 Ω
barrier
R
= 25 Ω
wire
CURRENT
= 20 mA
MAX
Voltage = 19 V - 0,020 A*(300 Ω + 25 Ω)
= 12,5 V
The voltage 12,5 V is greater than the required 12.0 V; therefore, this system will support the Logix 520. The Logix 520 si
has an input resistance equivalent to 600 Ω at a 20 mA input
current.
7
Page 8
Enhanced
Quick-Cal
Configuration
Switches
LED Status
Lights
Autotune
Lockout
Switch
4-20 mA input
with HART
Communications
Terminals for Optional Limit Switches
Figure 3: Logix 520 si Local Interface
8 CABLE REQUIREMENTS
The Logix 520 si digital positioner utilizes the HART communication protocol. This communication signal is
superimposed on the DC 4-20 mA current signal. The two
frequencies used by the HART protocol are 1200 Hz and 2200
Hz. To prevent distortion of the HART communication, cable
capacitance and cable length restrictions must be calculated.
The cable length must be limited if the capacitance is too high.
Selecting a cable with lower capacitance/mm rating will allow
longer cable runs. In addition to cable capacitance, the network resistance also affects the allowable cable length.
Jog Calibrate
Buttons
Gain Selector
Quick-Cal Button
To control cable resistance, No. 24 AWG cable should be used
for runs less than 1500 m. For cable runs longer than this,
No. 20 AWG cable should be used.
Electromagnetic Compatibility
The Logix 520 si digital positioner has been designed to operate correctly in electromagnetic (EM) fields found in typical
industrial environments. Care should be taken to prevent the
positioner from being used in environments with excessively
high EM field strengths (greater than 10 V/m). Portable EM
devices such as hand-held two-way radios should not be used
within 30 cm of the device.
65Ω
C
(µF) < - 0,0032
network
(R
barrier
+ R
+ 390Ω)
wire
Example:
R
= 300 Ω (if present)
barrier
R
= 50 Ω
wire
C
(300 + 50 + 390)
Max. Cable Length =
72 ρF 0.000072 µF
= =
cable
m m
65
- 0,0032 = 0,08 µF= C
C
(µF)
network
C
cable
0,08 µF
Max. Cable Length = = 1111 m
0.000072 µF/m
network
(µF)(Max)
Ensure proper wiring and shielding techniques of the control
lines, and route control lines away from electromagnetic
sources that may cause unwanted noise. An electromagnetic
line filter can be used to further eliminate noise (FLOWSERVE
Part Number 10156843).
In the event of a severe electrostatic discharge near the
positioner, the device should be inspected to ensure correct
operability. It may be necessary to recalibrate the Logix 520 si
positioner to restore operation.
9 STARTUP
9.1 Logix 520 si Local Interface
The Logix 520 si local user interface allows the user to
configure the basic operation of the positioner, tune the response, and calibrate the positioner without additional tools
or configurators. The local interface consists of a Quick-Cal™
button for automatic zero and span setting, along with two
jog buttons for spanning valve/actuators with no fixed internal stop in the open position. There is also a switch block
containing eight switches. Six of the switches are for basic
configuration settings, two are for calibration options. There
is also a rotaryselector switch for adjusting the positioner gain
8
Page 9
settings. For indication of operational status or alarm conditions there are three LEDs on the local user interface.
Initial DIP Switch Setting
Before placing the unit in service, set the DIP switches in the
“Configuration” and “Cal” boxes to the desired control options.
NOTE:
The switch settings in the Configuration box
are activated only by pressing the Quick-Cal button or
by utilizing the stroke calibration features provided by
a handheld or by Flowserve PC software.
9.2 Operation of Configuration DIP Switches Setup
The first six DIP switches are for basic configuration
1. Air Action – Must be set to match the configuration of the
valve/actuator mechanical configuration.
ATO
(air-to-open) – Select ATO if increasing output pres-
sure from the positioner is tubed so it will cause the valve
to open.
ATC
(air-to-close) – Selecting ATC if increasing output
pressure from the positioner is tubed so it will cause the
valve to close.
2. Signal at Closed – Normally this will be set to 4 mA for an
air-to-open actuator, and 20 mA for an air-to-close actuator configuration.
Selecting
signal is 4 mA and fully open when the signal is 20 mA.
Selecting
signal is 20 mA and fully open when the signal is 4 mA.
3. Pos. Characterization
Select
proportional to the input signal.
Select
is set in conjunction with the next switch, labeled
tional Pos. Char
4. Optional Pos. Char. – If the
is set to optional, this switch is active with the following
options:
The =% option will characterize the actuator
response to the input signal based on a standard 30:1
equal percent rangability curve.
If
Custom
to a custom table that must be set-up using a properly
configured HART 275 handheld or other host software.
5. Auto Tune – This switch controls whether the positioner
will auto tune itself every time the Quick-Cal button is
pressed
On
determine the positioner gain settings every time a QuickCal is performed based on the setting of the rotary
switch.
If the rotary
autotune switch On, a Flowserve nominal
response tuning set will be calculated and used.
If the rotary
the
4 mA
will make the valve fully closed when the
20 mA
will make the valve fully closed when the
Linear
if the actuator position should be directly
Optional
if another characteristic is desired, which
Op-
.
Pos. Characterization
is selected, the positioner will be characterized
enables an auto tune feature that will automatically
switch
Gain
Gain
selector switch is set to E with the
Gain
Auto Tune
selector switch is set to
switch On, progressively lower gain set-
D, C, B,
or A with
tings will be calculated and used.
If the rotary
the
Auto Tune
tings will be calculated and used.
Off
forces the positioner to use one of the factory preset
tuning sets determined by the rotary
Settings A through H are progressively higher gain
predefined tuning sets. The positioner is preset to Autotune
- On at the factory. This is the recomended setting.
6. Config. Switches — By selecting
will read all of the configuration switches each time a
Quick-Cal
Selecting
(from the last successful calibration) before the switch
was set to
zeros and spans the positioner.
9.3Calibration switches
9.3.1Stability Switch – This switch adjusts the position
control algorithm of the positioner for use with low
friction control valves or high friction automated
valves.
•Placing the switch to the left optimizes the response
for low friction, high performance control valves.
This setting provides for optimum response times
when used with most low friction control valves.
•Placing the switch to the right optimizes the response
for valves and actuators with high friction levels. This
setting slightly slows the response and will normally
stop limit cycling that can occur on high friction
valves.
9.3.2 Setup of the Cal DIP Switch for the Quick
Calibration operating mode
•Select
internal stop in the 100% stroke position. In
mode the positioner will fully close the valve and
register the 0% position and then open the valve to
the stop to register the 100% position when performing a self-calibration. See detailed instructions in the
next section on how to perform an auto positioner
calibration.
•Select
calibration stop in the open position. In the
the positioner will fully close the valve for the 0%
position and then wait for the user to set the open
position using the
down arrows. See the detailed instructions in the next
section on how to perform a manual calibration using
the
WARNING:
may stroke unexpectedly. Notify proper personnel
STOP!
that the valve will stroke, and make sure the valve is
Gain
selector switch is set to
switch On, progressively higher gain set-
Enabled
is performed to determine the configuration.
Disabled
retains the last configuration in memory
Disabled
Auto
Jog
. With this setting a
if the valve/actuator assembly has an
if the valve/actuator assembly has no
F, G,
Gain
selector switch.
, the Logix 520 si
Quick-Cal
or H with
Jog
Jog
buttons labeled with the up and
Jog
buttons.
During the Quick-Cal operation the valve
only
Auto
mode
properly isolated.
Quick-Cal Operation
The
Quick-Cal
the positioner. Pressing and holding the
button is used to locally initiate a calibration of
Quick-Cal
button for
9
Page 10
approximately three seconds will initiate the calibration. If the
Config-Switches
option is enabled, the settings of all the
configuration switches are read and the operation of the
positioner adjusted accordingly. The
Gain Selector
switch is
also read and action will be taken to adjust the gain according
to the settings of the calibration switches as described in the
previous section. A
briefly pressing the
Quick-Cal
Quick-Cal
can be aborted at any time by
button and the previous settings
will be retained.
If the
Quick calibration
Quick-Cal
button) is set to Auto and the valve/actuator as-
switch (not to be confused with the
sembly has the necessary internal stops, the calibration will
complete automatically. While the calibration is in progress
you will notice a series of different lights flashing indicating
the calibration progress. When the lights return to a sequence
that starts with a green light, the calibration is complete. (See
the appendix for an explanation of the various light sequences.)
WARNING:
When operating using local control of the
valve, the valve will not respond to external
commands. Notify proper personnel that the valve
STOP!
will not respond to remote command changes, and
make sure the valve is properly isolated.
If the
Quick calibration
switch is set to
Jog
, the calibration
will initially close the valve then cause a small jump in the
valve position. The jog calibration process will only allow
the user to manually set the span; zero position is automatically always set at the seat. If an elevated zero is needed
a handheld or other PC based configuration software is required. The LEDs will then flash in a sequence of Y-R-R-G
(yellow-red-red-green) which indicates the user must now use
the
Jog
keys to manually position the valve to the desired
100% position. Now press both
Jog
buttons simultaneously
to proceed to the next step. The valve will then stroke and
then wait while flashing the Y-R-R-G sequence again, allowing the user to adjust the valve position a second time to exactly 100% using the
positioned press both
Jog
buttons. When the stem is properly
Jog
buttons simultaneously again to
register the 100% position and proceed. No more user actions are required while the calibration process is completed.
When the lights return to a sequence that starts with a green
light the calibration is complete. (See the appendix for an explanation of the various light sequences.)
Factory reset — hold
Quick-Cal
button while applying power
and all of the internal variables including calibration will be
reset to factory defaults. The positioner must be re-calibrated
after a factory reset. Tag names and other user configured
limits, alarm settings, and valve information will also need to
be restored. A factory reset will always reset the command
source to analog 4-20 mA.
Special settings––several adjustments to the Logix 520 such
as split-range, MPC, soft stop, etc. cannot be set using the
local interface.
To set these parameters please refer to the appropriate communications tool manual.
9.4 HART 275 HANDHELD COMMUNICATOR
The Logix 520 si supports and is supported by the HART 275
Handheld Communicator. The DD and the manuals listed below can be obtained from the HART Communication Foundation or from your Flowserve representative. For more information please see the following guides:
•
Product Manual for the HART Communicator
• Logix 520 si Digital Positioner with HART 275
Communicator User Guide
9.5 USE OF SOFTTOOLS COMMUNICATION SOFTWARE
Flowserve corporation has written custom configuration and
diagnostic software for the Logix 500 si series called
SoftTools™. This software and the
SoftTools Quick Start Guide
are available from a Flowserve representative.
9.6 INTEGRATION OF THIRD-PARTY SOFTWARE
The Logix 520 si positioner can be used with:
– Siemens PDM™
– Fisher Rosemount AMS™
Local control of valve position — Can be done from the user
interface by holding both jog buttons and then simultaneously
pressing the
Quick-Cal
button. While in this mode the LEDs
will flash a Y-G-R-R (yellow-green-red-red) sequence. To exit
the local control mode and return to normal operation, briefly
press the
Quick-Cal
button.
10
Page 11
12.0 VDC
520
si
Figure 4: Compliance Voltage
PIEZO
Y
RELAY
4-20 mA Signal
Internal Housing
EARTH Terminal
Shielded Cable
Z
Limit Switch 1
Limit Switch2
Connect Shield at Source Ground
4-20 mA Current Source
+
Figure 5: Wiring Diagram
POT.
LS1
LS2
Table 9: Connection Table
ConnectionDescription
+11Input+ 4..20 mA
-12Input- 4..20 mA
+41*Limit switch 1+
-42*Limit switch 1-
+51*Limit switch 2+
-52*Limit switch 2YPneumatic output signal (outlet)
ZAir supply
* 0ptional
11
Page 12
10 STATUS CODES
Logix 520 si Status Condition Codes
Colors IdentifierIndication and resolution
G - - -Any sequence starting with a Green light flashing first is a normal operating mode and indicates that
there are no internal problems.
GGGG1No errors, alerts, or warnings; and the unit is in analog control mode.
GGGY2MPC active - The command is below the user set limit for tight shutoff feature. This is a normal
condition for a closed valve. The factory default setting is 1% command. To clear the condition use
handheld or Flowserve supplied software to reset the MPC if the range is incorrect or adjust the
command signal above the specified MPC value.
GGYG3Digital command mode - The analog 4-20 mA input signal is ignored in this mode and a handheld or
Flowserve supplied software is needed to change the position command. (Note a factory reset is the only
method to reset the command back to analog control mode from the local interface if a PC or handheld
configurator is not available. A reset will cause the loss of other data.
(See page 14 for more information)
GGYR4Initializing, or LED test mode - This sequence should only be visible for 3 sequences when powering
up the unit.
GGRG5Cycle limit - The cycle limit set by the user has been exceeded. To clear use handheld or Flowserve
supplied software to reset.
GGRY6Travel limit -The total accumulated travel limit set by the user has been exceeded. To clear use handheld
or Flowserve supplied software to reset.
GYYR7Soft Stop Lower - The unit is being commanded to exceed a user defined lower travel limit and the
internal software is holding the position at the limit. To clear the condition use handheld or Flowserve
supplied software to reset the limit if more travel is needed or adjust the command signal back in the
specified range.
GYRY8Soft Stop Upper - The unit is being commanded to exceed a user defined upper travel limit and the
internal software is holding the position at the limit. To clear the condition use handheld or Flowserve
supplied software to reset the limit if more travel is needed or adjust the command signal back in the
specified range.
GRYR9Position Lower - The position has reached or is exceeding a user defined lower travel indicator similar to
a limit switch indicator. To clear the condition use handheld or Flowserve supplied software to reset the
indicator if more travel is needed or adjust the command signal back in the specified range.
GRRY10Position Upper - The position has reached or is exceeding a user defined upper travel indicator similar to
a limit switch indicator. To clear the condition use handheld or Flowserve supplied software to reset the
indicator if more travel is needed or adjust the command signal back in the specified range.
12
Page 13
Logix 520 si Status Condition Codes
Colors IdentifierIndication and resolution
Y - - -Any sequence starting with a yellow light indicates that the unit is in a special calibration or test mode, or
that there was a calibration problem.
YGYG11Signature test in progress- This is a test initiated by Flowserve supplied software that can only be
cancelled by that software.
YYYG12Loop Calibration in Progress - Calibration sequence controlled by a handheld or Flowserve supplied
software that can only be cancelled by that software.
YRGG13Stroke Calibration in Progress - Calibration sequence started either using the local Quick-Cal button or
by a handheld or Flowserve supplied software. It may be cancelled by briefly pushing the Quick-Cal
button.
YGRR14JOG Control Mode - the unit has been placed in a local override mode where the valve can only be
stroked using the two local jog buttons. It may be cancelled by briefly pushing the Quick-Cal button.
YYYR15Command 0 saturated - Calibration error indicating that the 4-20 mA signal corresponding to 0%
position was out of range. Adjust the signal to the correct range and re-do the calibration. This error may
be cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration.
YYRY16Command 100 saturated - Calibration error indicating that the 4-20 mA signal corresponding to 100%
position was out of range. Adjust the signal to the correct range and re-do the calibration. This error may
be cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration.
YYRR17Command span - Calibration error indicating that the 4-20 mA signal was below the minimum calibration
span. The minimum calibration span is 1.28 mA. This error may be cleared by briefly pushing the QuickCal button, which will force the positioner to use the parameters from the last good calibration.
YRRG18Waiting for JOG set point from User - only used during Jog calibration see explanation in Quick-Cal
section of main document for operation.
YRYG19Setting IL Offset (in Stroke Cal) - An automatic step in the calibration process that is done with the valve
at 50% position. This must be completed for proper calibration.
YRYY20Feedback no-motion during calibration - Indicates that there was no motion of the actuator based on the
current stroking time configuration. Check linkages and air supply to make sure the system is properly
connected. If the time out occurred because the actuator is very large then simply retry the Quick-Cal and
the positioner will automatically adjust for a larger actuator by doubling the time allowed for movement.
This error may be cleared by briefly pushing the Quick-Cal button, which will force the positioner to use
the parameters from the last good calibration.
YRYR21Feedback 0 saturated - Calibration error indicating that the position sensor was out of range during the
calibration. To correct the condition, adjust the positioner mounting, linkage or feedback potentiometer to
move the position sensor back into range then restart the calibration. This error may be cleared by briefly
pushing the Quick-Cal button, which will force the positioner to use the parameters from the last good
calibration.
YRRY22Feedback 100 saturated - Calibration error indicating that the position sensor was out of range during
the calibration. To correct the condition, adjust the positioner mounting, linkage or feedback
potentiometer to move the position sensor back into range then restart the calibration. This error may be
cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration.
YRRR23Feedback span - The range of motion of the position feedback arm was too small. Check for loose
linkages and/or adjust the feedback pin to a position closer to the follower arm pivot to create a larger
angle of rotation. This error may be cleared by briefly pushing the Quick-Cal button, which will force the
positioner to use the parameters from the last good calibration.
YRGR24Feedback unstable during calibration - Check for loose linkages or loose position sensor. This error
may be cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the
parameters from the last good calibration.
YRGY25Feedback unstable setting IL Offset - Check for loose linkages or loose positioner sensor. This can also
be caused by over tightened packing, very sticky packing, or very high gain settings. This error may be
cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration.
13
Page 14
Logix 520 si Status Condition Codes
Colors IdentifierIndication and resolution
R - - -Any sequence starting with a red light indicates that there is an operational problem with the unit.
RGRR26Position Deviation - The position has exceeded user defined error band between command and
position.
RYYY27Hall sensor non-motion - Check to make sure the air supply is connected. This error may be cleared
by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters from the
last good calibration. If the positioner still does not operate replace the pneumatic relay assembly.
RYYR28Hall sensor lower position - Check to make sure the air supply is connected. This error may be
cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration. If the positioner still does not operate replace the pneumatic relay
assembly.
RYRY29Hall sensor upper position - Check to make sure the air supply is connected. This error may be
cleared by briefly pushing the Quick-Cal button, which will force the positioner to use the parameters
from the last good calibration. If the positioner still does not operate replace the pneumatic relay
assembly.
RRGG301,23 V reference - Bad electronic assembly, replace.
RRGR3112-bit A/D reference - Bad electronic assembly, replace.
RRYG32Temperature limit - The internal positioner temperature is currently exceeding operational limits of
-40 ˚C (-40 ˚F) or 85 ˚C (185 ˚F).
RRYY33Piezo voltage - Bad electronic assembly, replace.
RRYR34Board current high - Check internal wiring and connectors for electrical shorts, if no shorts bad
electronic assembly, replace.
RRRG3512-bit D/A reference - Bad electronic assembly, replace.
RRRY36EEprom checksum error - The checksum of the internal data has become corrupted. Cycle power and
complete a Quick-Cal if needed. Check internal data to verify correct settings. If the error still occurs,
bad electronic assembly, replace.
13Version number checking- The version number of the embedded code may be checked at any time except during a
calibration by holding down the ∆ button. This will not alter the operation of the unit other than to change the blink
sequence to 3 blinks indicating the major version number. Holding the ∇ button will give the minor version number
without affecting operation. The version codes are interpreted by adding up the numbers assigned according to the
following table:
ColorFirst blink valueSecond blink value Third blink value
Green000
Yellow931
Red1862
For example if holding the ∆ button gave a G-G-R code, and holding the ∇ button gave a Y-Y-G code then the resulting version number
would be (0+0+2).(9+3+0) or version 2.12.
14
Page 15
11 TROUBLE SHOOTING
Logix 520 si Symptoms and Solutions
FailureProbable CauseCorrective action
No LED is blinking1. Current source below 3,6 mA1. Verify current source suppies at least 3,6 mA
2. Incorrect wiring polarity2. Check wiring for correct polarity
Erratic communications1. Current source bandwidth not1. Maximum allowable current source rate of
limited to 25Hzchange is 924 mA per second
2. Maximum cable length or cable2. Check cable conductor size, length and
impedance exceededcapacitance. Refer to ‘Cable Requirements’ on
page 11.
3. HART modem connected to PC RS-232 3. Verify laptop battery is not low
port not receiving enough power
4. Interference with I.S. barrier4. Must use HART compatible I.S. barrier
5. Current source stripping (filtering)5. Use the HART filter (VHF) available from
HART signalFlowserve (FLS part-No. 10156843)
Alternatively a 250 Ω and a 22 µF capacitor,
installed according to the following schematic
drawing can be used to establish communication
22 µF
250 Ω
Control system
Unit does not respond1. Unit is in digital command mode1. Switch to analog command mode with handheld
to analog commandscommunicator or Soft Tools.
2. Error occurred during calibration 2. Correct calibration error. Recalibrate
Valve position reading1. Stem position sensor mounting1. Reposition sensor
is not what is expectedis off 180 degrees
2. Stroke not calibrated2. Calibrate stroke
3. Tight shutoff MPC (Minimum3. No action
position cutoff) is active
4. Custom characterization or soft4. No action
stops active
Position is driven fully1. Stroke not calibrated1. Calibrate valve stroke
open or closed and will2. Inner-loop hall sensor not connected 2. Verify hardware connections
not respond to command3. Wrong air action entered in software3. Check ATO (Air-to-open) and ATC (Air-to-Close)
6. Control parameter inner-loop offset6. Adjust inner-loop and see if proper control
is too high/lowresumes
Sticking or hunting1. Contamination of the1. Check air supply for proper filtering and meeting
operation of the positionerelectro-pneumatic converter.ISA specifications ISA-7.0.01
2. Control tuning parameters not correct2. Lower proportional gain settings
15
Page 16
12 SPARE PART KITS
Item No.DescriptionPart-No.
.
1Cover AssemblyYellow
White
2PC Board AssemblyH10014000
3Repair kit for Logix 500-Relay Module AssemblyH10011500
4Repair kit for Potentiometer AssemblyH10011600
5Position Feedback AssemblyH194500003
8Follower Arm AssemblyMax. stroke 65 mmH194512001
Max. stroke 110 mmH194512002
Mounting Kits
Item No.DescriptionPart-No.
–IEC 534 part 6 (Valtek 2000, Kämmer KA, Kämmer KP, and standard NAMUR linear valves)H192685001
–Rotary VDI/VDE 3845 (DIN ISO 5211)H194984001
Gauge Kits
Item No.DescriptionPart-No.
–2 gauge set, 6 bar / 4 bar, brass, nickel platedH179379013
–2 gauge set, 6 bar / 4 bar, stainless steelH179379015