The document contains all the technical data on the device and provides an overview of the
accessories and other products that can be ordered for the device.
Symbols usedSafety symbols
SymbolMeaning
Electrical symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
4Endress+Hauser
Deltabar FMD71, FMD72
,…,
1.
2.
3.
SymbolMeaning
Reference to graphic
Visual inspection
Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ... Sections
Documentation
The document types listed are available:
In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
Brief Operating Instructions (KA): getting the 1st measured value quickly
KA01105P:
The Brief Operating Instructions contain all the essential information from incoming acceptance to
initial commissioning.
Operating Instructions (BA): your comprehensive reference
BA01044P:
These Operating Instructions contain all the information that is required in various phases of the life
cycle of the device: from product identification, incoming acceptance and storage, to mounting,
connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Description of Device Parameters (GP): reference for your parameters
GP01013P:
The document provides a detailed explanation of each individual parameter in the operating menu.
The description is aimed at those who work with the device over the entire life cycle and perform
specific configurations.
Safety Instructions (XA)
Safety Instructions (XA) are supplied with the device depending on the approval. These instructions
are an integral part of the Operating Instructions.
DeviceDirectiveDocumentationOption
FMD71, FMD72ATEX II 1/2G Ex ia IIC T6 Ga/GbXA00619PBA
FMD71, FMD72ATEX II 1/2G Ex d [ia] IIC T6 Ga/GbXA00620PBC
FMD71, FMD72ATEX II 3G Ex nA IIC T6 GCXA00621PBD
FMD71, FMD72IEC Ex ia IIC T6 Ga/GbXA00622PIA
FMD71, FMD72IEC Ex d [ia] IIC T6 Ga/GbXA00623PIB
FMD71, FMD72CSA General Purpose-CD
FMD71, FMD72NEPSI Ex ia IIC T4/T6 Ga/GbXA01352PNA
FMD71, FMD72NEPSI Ex d [ia] IIC T4/T6 Ga/GbXA01353PNB
FMD71, FMD72INMETRO Ex ia IIC T6...T4 Ga/GbXA01378PMA
FMD71, FMD72INMETRO Ex d [ia] IIC T6...T4 Ga/GbXA01379PMC
FMD71, FMD72EAC Ga/Gb Ex ia IIC T6...T4XA01594PGA
FMD71, FMD72EAC Ga/Gb Ex d [ia] IIC T6...T4 XXA01595PGB
1)
Endress+Hauser5
Deltabar FMD71, FMD72
DeviceDirectiveDocumentationOption
FMD71FM C/US IS Cl.I Div.1 Gr.A-D, AEx ia, Zone 0,1,2XA00628PFA
FMD71FM C/US XP AIS Cl.I Div.1 Gr.A-D, Exd [ia] Zone 0,1,2XA00629PFB
FMD71CSA C/US XP Cl.I Div.1 Gr.A-D, Ex d [ia], Zone 0,1,2XA00631PCB
FMD71FM C/US NI Cl.I Div.2 Gr.A-D, Zone 2XA00668PFD
FMD71CSA C/US IS Cl.I Div.1 Gr.A-D, Ex ia Zone 0,1,2XA00630PCA
FMD72CSA C/US IS Cl.I Div.1 Gr.A-D, Ex ia Zone 0,1,2XA00626PCA
FMD72CSA C/US XP Cl.I Div.1 Gr.A-D, Ex d [ia], Zone 0,1,2XA00627PCB
FMD72CSA C/US NI, Cl.I Div.2 Gr.A-D, Zone 2XA00671PCC
FMD72FM C/US IS Cl.I Div.1 Gr.A-D, AEx ia, Zone 0,1,2XA00624PFA
FMD72FM C/US XP AIS Cl.I Div.1 Gr.A-D, Exd [ia] Zone 0,1,2XA00625PFB
FMD72FM C/US NI Cl.I Div.2 Gr.A-D, Zone 2XA00669PFD
1)Product Configurator order code for "Approval"
The nameplate provides information on the Safety Instructions (XA) that are relevant for the
device.
1)
6Endress+Hauser
Deltabar FMD71, FMD72
URLOPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Terms and abbreviations
A0029505
Position Term/
abbreviation
1OPLThe OPL (over pressure limit = sensor overload limit) for the measuring device
2MWPThe MWP (maximum working pressure) for the sensors depends on the lowest-
3Maximum sensor
measuring range
4Calibrated/
adjusted span
p-Pressure
-LRLLower range limit
-URLUpper range limit
-LRVLower range value
-URVUpper range value
-TD (Turn down)Turn down
Explanation
depends on the lowest-rated element, with regard to pressure, of the selected
components, i.e. the process connection has to be taken into consideration in
addition to the measuring cell. Also observe pressure-temperature dependency.
For the relevant standards and additional notes, see the "Pressure specifications"
section → 31.
The OPL may only be applied for a limited period of time.
rated element, with regard to pressure, of the selected components, i.e. the
process connection has to be taken into consideration in addition to the
measuring cell. Also observe pressure-temperature dependency. For the
relevant standards and additional notes, see the "Pressure specifications" section
→ 31.
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.
Span between LRL and URL
This sensor measuring range is equivalent to the maximum calibratable/
adjustable span.
Span between LRV and URV
Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.
FMD71 - Devices with ceramic process isolating diaphragm (Ceraphire®)
The ceramic sensor is an oil-free sensor, i.e. the process pressure acts directly on the robust ceramic
process isolating diaphragm and causes it to deflect. A pressure-dependent change in capacitance is
measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The
measuring range is determined by the thickness of the ceramic process isolating diaphragm.
Advantages:
• Guaranteed overload resistance up to 40 times the nominal pressure
• The ultrapure 99.9% ceramic (Ceraphire®, see also "www.endress.com/ceraphire") ensures:
– Extremely high chemical durability
– Less relaxation
– High mechanical durability
• Can be used in absolute vacuums up to 150 °C (302 °F)
FMD72 - Devices with metal process isolating diaphragm
The process pressure deflects the metal process isolating diaphragm of the sensor and a fill fluid
transfers the pressure to a Wheatstone bridge (semiconductor technology). The pressure-dependent
change in the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for process pressures up to 40 bar (600 psi)
• Fully welded process isolating diaphragm
• Small, flush-mounted process connections
• Significantly reduced thermal effect e.g. compared to diaphragm seal systems with capillaries
1Silicon measuring element, substrate
2Wheatstone bridge
3Channel with fill fluid
4Metal process isolating diaphragm
A0016448
Endress+Hauser9
Deltabar FMD71, FMD72
Measuring system
Device selectionField of application
The FMD71/FMD72 consists of 2 sensor modules and one transmitter. One sensor module measures
the hydrostatic pressure (high pressure) and the other one the head pressure (low pressure). The
level (electronic differential pressure) is calculated in the transmitter using these two digital values.
• Level
• Differential pressure
Process connections
• Thread
• EN and ASME flanges
• Flush-mounted hygienic connections
Measuring ranges (differential pressure)
FMD71:
from –100 to +100 mbar (–1.5 to +1.5 psi)
to –1 to +40 bar (–15 to +600 psi)
FMD72:
from –400 to +400 mbar (–6 to +6 psi)
to –1 to +40 bar (–15 to +600 psi)
MWP (depends on the lowest-rated element, with regard to pressure, of the selected
components)
FMD71:
to 60 bar (900 psi)
FMD72:
to 160 bar (2400 psi)
Process temperature limits
FMD71:
• Thread / Flanges:
–25 to +125 °C (–13 to +257 °F)/150 °C (302 °F)
• Hygienic process connections:
–25 to +130 °C (–13 to +266 °F) , 150 °C (302 °F) for max. 1 hour
FMD72:
• Process connections with internal process isolating diaphragm:
–40 to +125 °C (–40 to +257 °F)
• Process connections with flush-mounted process isolating diaphragm:
–40 to +100 °C (–40 to +212 °F)
• Hygienic process connections with flush-mounted process isolating diaphragm:
–40 to +130 °C (–40 to +266 °F) , 150 °C (302 °F) for max. 1 hour
• Higher process temperature limits available on request (up to +250 °C (480 °F))
Ambient temperature range
–40 to +80 °C (–40 to +176 °F)
Reference accuracy of the individual sensors
• Up to ±0.075% of the set span
• PLATINUM version: up to ±0.05 % of the set span
Supply voltage
• Version for non-hazardous areas: 12 (13) to 45 V DC
• Ex ia: 12 (13) to 30 V DC
Output
4 to 20 mA with superimposed HART protocol
10Endress+Hauser
Deltabar FMD71, FMD72
LP1
HP
p1
p2
P = p2
LP
P = p1 + p2
HP
Options
• NACE-compliant materials
• Software pre-configurations
Product design
Level measurement (level, volume and mass) with Deltabar:
A0016449
LP Sensor module LP (low pressure)
HP Sensor module HP (high pressure)
p2 Head pressure
p1 Hydrostatic pressure
1Transmitter
System integration
The FMD71/FMD72 is best suited to level measurement in vessels with pressure overlay or in
vacuum vessels and tanks, high distillation columns and other vessels with changing ambient
temperatures.
The sensor module HP is mounted on the lower measuring connection and the sensor module LP is
mounted above the maximum level. The transmitter can be mounted on pipes or walls with the
mounting bracket.
The sensor signal is transmitted digitally. In addition, sensor temperatures and the individual process
pressures present at the respective sensor modules can be individually evaluated and transmitted.
NOTICE
Incorrect sizing/order of sensor modules
In a closed system, please note that the sensor module is affected by the superimposed head
‣
pressure (p2) in addition to the hydrostatic pressure (p1). This must be taken into account when
sizing the sensor module on the high-pressure side (HP).
The device can be given a tag name (max. 8 alphanumeric characters).
Measuring point (TAG), see additional specifications.: Product Configurator order code for
"Identification", option "Z1"
Endress+Hauser11
Input
Measured variableMeasured process variables
• Pressure HP and Pressure LP
• Sensor temperature HP and sensor temperature LP
• Transmitter temperature
Calculated process variables
• Differential pressure
• Level (level, volume or mass)
Deltabar FMD71, FMD72
FMD71: measuring range of
The maximum span of the differential pressure corresponds to the URL of the HP sensor.
1 bar (15 psi)0+1 (+15)6.7 (100)10 (150)0.01 (0.15)2H
2 bar (30 psi)0+2 (+30)13.3 (200)20 (300)0.01 (0.15)2K
4 bar (60 psi)0+4 (+60)18.7 (280.5)28 (420)0.01 (0.15)2M
10 bar (150 psi)0+10 (+150)26.7 (400.5)40 (600)0.01 (0.15)2P
40 bar (600 psi)0+40 (+600)100 (1500)160 (2400)0.01 (0.15)2S
2)
2)
1)The vacuum resistance applies for the measuring cell under reference operating conditions. (see "Reference operating conditions" section)
2)Product Configurator order code for "Sensor range"
Endress+Hauser13
Output
onon
offoff
damp.
damp.
DisplayDisplay
SensorSensor
HARTHART
RR
FIELD COMMUNICATION PROTOCOLFIELD COMMUNICATION PROTOCOL
SW /min
SW /min
E
+
–
E
+
–
U – 12 V
U – 13 V
R
L
max
23 mA
23 mA
£
30
20
12
U
[V]
40 45
1217
1435
783
348
[ ]W
[ ]W
R
L
max
R
L
max
30
20
13
40 45
1174
1391
739
304
Test
Test
£
3
AB
1
3
2
1
2
R
L
max
U
[V]
Deltabar FMD71, FMD72
Output Signal
Software operationInternal + LCDExternal
Order code option
2)
4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
1)
+ LCDInternal
458
1)In the case of the T17 transmitter housing, the operating keys are always arranged internally on the electronic insert.
2)Product Configurator order code for "Display, operation:"
Signal range 4 to 20 mA
Signal on alarm 4 to 20 mA
3.8 mA to 20.5 mA
As per NAMUR NE43
• Max. alarm: (factory setting: 22 mA) can be set from 21 to 23 mA
• Hold measured value: last measured value is held
• Min. alarm: 3.6 mA
Maximum load
In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load resistance R
(including line resistance) must not be exceeded depending on the supply voltage U0 of the supply
unit. In the following load diagrams, observe the position of the jumper and the explosion protection:
A0021280
AJumper for 4 to 20 mA test signal set to "Non-test" position
BJumper for 4 to 20 mA test signal set to "Test" position
1Power supply for II 1/2 G Ex ia, FM IS, CSA IS
2Power supply for devices for the non-hazardous area, 2 G Ex d, 3 G Ex nA, FM XP, FM NI, CSA XP, CSA dust
ignition-proof
3R
USupply voltage
maximum load resistance
Lmax
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 Ω must be taken into account.
14Endress+Hauser
A0017533
Deltabar FMD71, FMD72
I
63 %
100 %
t
t1t
2
90 %
t
3
Dead time, Time constant
Dynamic behavior,
current output
Dynamic behavior, HART
Presentation of the dead time and the time constant:
A0019786
Dead time (t1) [ms]Time constant (T63), t
max.120120280
Dead time (t1) [ms]Dead time (t1) [ms] +
Time constant T63 (= t2) [ms]
min.280400560
max.110012201380
2
Time constant (T90), t
Dead time (t1) [ms] +
Time constant T90 (= t3) [ms]
3
Reading cycle
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (Burst): max. 3/s, typical 2/s
The Deltabar FMD71/FMD72 offers BURST MODE functionality for cyclical value transmission via
the HART communication protocol.
Damping
alarm current setting
Firmware version
Cycle time (update time)
Cyclic (burst): min. 300 ms
Response time
• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of
preambles)
A damping affects all outputs (output signal, display):
• Via onsite display, handheld terminal or PC with operating program, continuous from 0 to 999 s
• Via DIP switch on the electronic insert, switch position "on" = set value and "off"
• Factory setting: 2 s
Damping can be switched on or off using a switch on the electronic insert. If the switch is on, the
time constant can be set via a parameter in the menu and if the switch is off, the output signal is not
damped (time constant = 0.0).
Adjusted min. alarm current: Product configurator order code for "Service", option "IA"
DescriptionOption
01.00.zz, HART, DevRev0178
1)Product Configurator, order code for "Firmware version"
1)
Endress+Hauser15
Deltabar FMD71, FMD72
Protocol-specific data
Manufacturer ID17 (0x11)
Device type ID39 (0x27)
HART specification6.0
Device description files (DTM, DD)Information and files can be found:
• www.endress.com
• www.fieldcommgroup.org
HART device variablesMeasured values for PV (primary variable)
• Differential pressure
• Level linear (before lin.)
• Level after linearization table
Measured values for SV, TV, QV (second, third and fourth variable)
• Measured differential pressure
• Corrected pressure
• Measured pressure HP
• Sensor pressure HP
• Sensor temperature HP
• Measured pressure LP
• Sensor pressure LP
• Sensor temperature LP
• Level before linearization
• Tank content
• Electronic temperature
Supported functions• Burst mode
• Additional transmitter status
16Endress+Hauser
Deltabar FMD71, FMD72
4... 20mA
Test
Test
Test
4... 20mATest
1
8
6
7
2
3
4
5
Power supply
WARNING
L
Electrical safety is compromised by an incorrect connection!
In accordance with IEC/EN61010 a separate circuit breaker must be provided for the device .
‣
When using the measuring device in hazardous areas, installation must comply with the
‣
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
All explosion protection data are given in separate documentation which is available upon
‣
request. The Ex documentation is supplied as standard with all devices approved for use in
explosion hazardous areas.
Devices with integrated overvoltage protection must be grounded.
‣
Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.
‣
Terminals
Terminal assignment
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
A0019989
1Housing
2Supply voltage
34 to 20 mA
4Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here.
5External ground terminal
64 to 20 mA test signal between positive and test terminal
7Internal ground terminal, minimum supply voltage = 12 V DC, jumper is set as illustrated in the diagram.
8Jumper for 4 to 20 mA test signal
Supply voltage
Electronic versionJumper for 4 to 20 mA test signal in
"Test" position (delivery status)
4 to 20 mA HART, version for
non-hazardous areas
13 to 45 V DC12 to 45 V DC
Jumper for 4 to 20 mA test signal
in "Non-test" position
Measuring a 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the positive and test terminal without interrupting
the measurement. The minimum supply voltage of the device can be reduced by simply changing the
position of the jumper. As a result, operation is also possible with a lower supply voltage. To keep the
measured error below 0.1 %, the current measuring device should exhibit an internal resistance of
<0.7Ω. Observe the position of the jumper in accordance with the following table.
• Measurement of 4 to 20 mA test signal via the positive and test terminal:
possible. (Thus, the output current can be measured without interruption via
the diode.)
• Delivery status
• Minimum supply voltage: 13 V DC
A0019992
• Measurement of 4 to 20 mA test signal via positive and test terminal: not
possible.
• Minimum supply voltage: 12 V DC
A0019993
Plastic M20x1.55 to 10 mm (0.2 to 0.39 in)0.5 to 2.5 mm2 (20 to 14 AWG)
Metal M20 x 1.5 7 to 10.5 mm (0.28 to 0.41 in)
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• Terminals for core cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• The cable outer diameter depends on the cable entry used.
Residual ripple
Without influence on 4 to 20 mA signal up to ±5 % residual ripple within the permitted voltage
range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply
≤0.0006 % of URL/1 V
Overvoltage protectionStandard version
The standard version of the pressure instruments does not contain any special elements to protect
against overvoltage ("wire to ground"). Nevertheless the requirements of the applicable EMC
standard EN 61000-4-5 (testing voltage 1kV EMC wire/ground) are met.
Optional overvoltage protection
Devices showing version "NA" in feature 610 "Accessory Mounted" in the order code are equipped
with overvoltage protection.
• Overvoltage protection:
– Nominal functioning DC voltage: 600 V
– Nominal discharge current: 10 kA
• Surge current check î = 20 kA satisfied as per DIN EN 60079-14: 8/20 μs
• Arrester AC current check I = 10 A satisfied
NOTICE
Device could be destroyed!
Devices with integrated overvoltage protection must be grounded.
‣
18Endress+Hauser
Deltabar FMD71, FMD72
90°
90°
C
A
B
Performance characteristics of ceramic process isolating
diaphragm
Reference operating
conditions
Influence of the installation
position depending on sensor
• As per IEC 60770
• Ambient temperature TA = constant, in the range of:+21 to +33 °C (+70 to +91 °F)
•
Humidity j= constant, in the range of: 5 to 80 % RH
• Ambient pressure pA = constant, in the range of:860 to 1060 mbar (12.47 to 15.37 psi)
• Position of measuring cell = constant, in range: horizontal ±1° (see also "Influence of the
installation position" section → 19)
• Input of Lo Trim Sensor and Hi Trim Sensor for lower range value and upper range value
• Zero based span
• Material of process isolating diaphragm: Al2O3 (aluminum-oxide ceramic, Ceraphire®)
• Supply voltage: 24 V DC ±3 V DC
• Load with HART: 250 Ω
Process isolating diaphragm axis is horizontal (A) Process isolating diaphragm pointing
This effect can be corrected using the function to adjust the position (position adjustment) for the
differential pressure. Additional position adjustments for individual pressure signals are not
available.
A position-dependent zero shift can be corrected on the device.
Resolution
Vibration effects
Application limits
• Current output: 1 μA
• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
Test standardVibration effects
IEC 61298-3≤ Reference accuracy up to 10 to 60 Hz: ±0.35 mm (±0.01 in); 60 to 500 Hz: 2 g
A high ratio between the level and head pressure or between the differential pressure and static
pressure can result in large measured errors. A maximum ratio of 1:10 is recommended. For
calculation purposes, please use the free "Applicator" calculation tool, which is available online at
"www.endress.com/applicator" or on CD-ROM.
Process isolating diaphragm pointing
downwards (C)
A0016465
Endress+Hauser19
Deltabar FMD71, FMD72
A
Diff
HPHP
2
(AURL )
+=
.
LPLP
2
(AURL )
.
100100
A[%]
P
100
.
Diff
Diff
=
A
Diff
T
Diff
HPHP
2
(TURL )
+=
.
LPLP
2
(TURL )
.
100100
T[%]
P
100
.
Diff
Diff
=
T
Diff
Reference accuracy
The reference accuracy contains the non-linearity [DIN EN 61298-2 3.11] including the pressure
hysteresis [DIN EN 61298-23.13] and non-repeatability [DIN EN 61298-2 3.11] in accordance with
the limit point method as per [DIN EN 60770].
Measuring cellSensorReference accuracy (A)
[%URL for every sensor]
StandardPlatinum
100 mbar (1.5 psi)Gauge pressureA =
250 mbar (3.75 psi) Gauge pressureA =
400 mbar (6 psi)Gauge pressureA =
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
1)For hygienic process connections
Gauge pressure/ Absolute pressure A =
A =
A =
A =
A =
±0.075
±0.15
±0.075
±0.15
±0.075
±0.15
±0.075
±0.15
-Calculation (mbar, bar or psi):
1)
-
1)
-
1)
A =±0.05
1)
Ordering Information
DescriptionOption
PlatinumD
StandardG
±0.075
Calculated reference accuracy (A
of the differential pressure
Percentage calculation of URL dP:
1)
1)
Diff
)
A0016468
A0016469
1)Product Configurator order code for "Reference accuracy"
Thermal change in the zero
output and the output spanStandard version
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)Absolute
1)For hygienic process connections
Total performance
Gauge
pressure
Gauge
pressure
Absolute
pressure
pressure
T
= ±0.176
T
T
T
T
T
T
T
total
Total
total
total
total
total
total
total
= ±0.352
= ±0.092
= ±0.184
= ±0.092
= ±0.184
= ±0.092
= ±0.184
1)
1)
1)
1)
The "Total performance" specification comprises the non-linearity including hysteresis, nonreproducibility as well as the thermal change in the zero point. All specifications apply to the
temperature range –10 to +60 °C (+14 to +140 °F).
>
+60 to +150 °C
(140 to +302 °F)
T = ±0.75
T = ±1.25
T = ±0.5
T = ±0.75
T = ±0.75
T = ±1.25
T = ±0.5
T = ±0.75
1)
1)
1)
1)
Calculated thermal change (T
of the differential pressure
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
TP = ±0.2TP = ±0.46TP = ±0.575Calculation (mbar, bar or psi):
TP = ±0.15TP = ±0.46TP = ±0.5
% of URL for every
sensor - hightemperature version
% of URL for every
sensor - hygienic
version
Calculated total performance (TP
of the differential pressure
Percentage calculation of URL dP:
The "Applicator Sizing Electronic dp" selection tool, available free of charge on the Endress
+Hauser web site (www.endress.com/applicator), enables detailed calculations for your
respective applications.
1 bar (15 psi)
2 bar (30 psi)
4 bar (60 psi)
10 bar (150 psi)
40 bar (600 psi)
1)For hygienic process connections
Gauge pressureL = ±0.05
Absolute pressureL = ±0.3
Total error
1 year10 years
% of URL for every sensor
L = ±0.2
L = ±0.1
1)
The total error comprises the total performance and long-term stability. All specifications apply to
the temperature range –10 to +60 °C (+14 to +140 °F).