Pressure sensor with CONTITETM measuring cell
Condensate-resistant
Applications
The device is used for the following measuring tasks:
• Level, volume or mass measurements in liquids
• Pressure measurement in liquids, gases and paste-like media in all areas of process
engineering, process measurement technology, pharmaceutics and the food
industry
Your benefits
• Very good reproducibility and long-term stability
• Maximum plant safety provided by one-of-a-kind, condensate-resistant CONTITE
measuring cell
• High reference accuracy up to 0.075 %
• Used for process level and pressure monitoring up to SIL3, certified according to
IEC 61508 by TÜV SÜD
• High level of safety during operation thanks to function monitoring from the
measuring cell to the electronics
• Easy electronics replacement guaranteed with HistoROM®/M-DAT
• For use in drinking water
Table of contents
Deltapilot S FMB70
About this document ........................ 4
Document function ............................ 4
Symbols used ................................ 4
Documentation ............................... 5
Terms and abbreviations ........................ 6
Turn down calculation .......................... 7
The document contains all the technical data on the device and provides an overview of the
accessories and other products that can be ordered for the device.
Symbols usedSafety symbols
SymbolMeaning
Electrical symbols
SymbolMeaningSymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTICE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
Ground connection
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
4Endress+Hauser
Deltapilot S FMB70
,…,
1.
2.
3.
Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ... Sections
Documentation
See the "Supplementary documentation" section → 63
The document types listed are available:
In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
Safety Instructions (XA)
See the "Safety instructions" section → 63
Endress+Hauser5
Terms and abbreviations
URLOPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Deltapilot S FMB70
A0029505
Item Term/abbreviationExplanation
1OPLThe OPL (over pressure limit = sensor overload limit) for the measuring device depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in
addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and
additional information, see the "Pressure specifications" section.
The OPL may only be applied for a limited period of time.
2MWPThe MWP (maximum working pressure) for the sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the
measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional
information, see the "Pressure specifications" section.
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.
3Maximum sensor
measuring range
4Calibrated/adjusted
span
p-Pressure
-LRLLower range limit
-URLUpper range limit
-LRVLower range value
-URVUpper range value
-TD (turn down)Turn down
Span between LRL and URL
This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
Span between LRV and URV
Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
TD =
In this example, the TD is 2:1.
This span is based on the zero point.
Registered trademarksHART®
Registered trademark of the FieldComm Group, Austin, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATIONTMFieldbus
Registered trademark of the FieldComm Group, Austin, Texas, USA
URL
|URV-LRV|
10 bar (150 psi)
= 2
|5 bar (75 psi)-0 bar (0 psi)|
Endress+Hauser7
Device selection
T14
T15
T17
Deltapilot S FMB70
Function and system design
A0019982
Field of application
• Level measurement
• Pressure measurement
Industries
Food, pharmaceutical, environment (fresh water and wastewater), chemical
Process connections
• Thread
• Flanges
• Flush-mounted hygienic connections
Process connection material
• AISI 316L (1.4435 or 1.4404) - see "Materials" section)
• Alloy C276 (2.4819)
Measuring ranges
from –100 to +100 mbar (–1.5 to +1.5 psi)
to –1000 to +10000 mbar (–15 to +150 psi)
OPL
max. 40 bar (600 psi)
Process temperature range(temperature at process connection)
–10 to +100 °C (+14 to +212 °F); +135 °C (275 °F) for maximum 30 minutes
Ambient temperature range
• Without LCD display: –40 to +85 °C (–40 to +185 °F) lower temperatures on request
• With LCD display: –20 to +70 °C (–4 to +158 °F)
(extended temperature application range–40 to +85 °C (–40 to +185 °F) with limitations in optical
properties, such as display speed and contrast)
• Separate housing:–20 to +60 °C (–4 to +140 °F)
Reference accuracy
±0.1 % of the set span (0.075 % platinum)
Supply voltage
Supply voltage non-Ex
• 4 to 20 mA HART: 10.5 to 45 V DC
• PROFIBUS PA and FOUNDATION Fieldbus: 9 to 32 V DC
Supply voltage Ex ia
10.5 to 30 V DC
8Endress+Hauser
Deltapilot S FMB70
3
2
1
p
atm
p = p+ p
atmhydr.
Output
4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options
• Gold/rhodium-coated process isolating diaphragm
• Inspection certificate 3.1
• 3A and EHEDG approval
• HistoROM®/M-DAT memory chip
• Separate housing
Specialties
• Absolute resistance to condensate thanks to hermetically sealed CONTITETM cell
• Maximum flexibility thanks to modular design
• Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops
Measuring principle
CONTITE™ measuring cell
A0027095
1Process isolating diaphragm
2Measuring element
3Rear isolating membrane of the CONTITE™ measuring cell
P
Atmospheric pressure
atm
P
Hydrostatic pressure
hydr.
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the
hydrostatic pressure depends solely on the height h of the liquid column. The CONTITE™ measuring
cell, which works according to the principle of the gauge pressure sensor, constitutes the core of the
Deltapilot S. In contrast to conventional gauge pressure sensors, the precision measuring element (2)
in the CONTITE™ measuring cell is absolutely protected between the process isolating diaphragm (1)
and the rear isolating membrane (3).
Advantages:
• Thanks to this hermetic sealing of the measuring element, the CONTITE™ measuring cell is
absolutely insensitive to condensate/condensation and aggressive gases. The pressure applied is
transferred from the process isolating diaphragm to the measuring element by means of an oil
without any loss in pressure.
• The sensor temperature is measured by means of the resistance bridge in the measuring cell. The
electronics can compensate any measuring errors resulting from fluctuations in temperature with
these measured temperature values.
• A linearization with max. 32 points, based on a table entered either manually or semiautomatically, can be activated locally or remotely. This function allows, for example,
measurement in engineering units and provides a linear output signal for spherical and horizontal
cylindrical tanks, and containers with a conical outlet.
Endress+Hauser9
Product design
h
h =
p
r · g
p
atm
p
atm
p
ges
p
hydr.
h ~ p
p= p - p
meastotatm
p= (p+ p) - p
measatmhydr.atm
p = p+ p
totatmhydr.
1
2
3
Hydrostatic level measurement
Deltapilot S FMB70
A0033934-EN
gGravitational acceleration
hLevel height
P
Total pressure = hydrostatic pressure + atmospheric pressure
tot
P
Atmospheric pressure
atm
P
Hydrostatic pressure
hydr.
P
Measured pressure in the measuring cell = hydrostatic pressure
meas
ρDensity of the medium
Level measurement in closed tanks with pressure overlay
You can determine the differential pressure in tanks with pressure overlay using two Deltapilot S
devices. The measured pressure values of the two Deltapilot S devices are sent to a signal processing
unit such as Endress+Hauser RMA or a PLC. The signal processing unit or PLC determines the
difference in pressure and uses this to calculate the level and the density where necessary.
1Deltapilot 1 measures the total pressure (hydrostatic pressure and top pressure)
2Deltapilot 2 measures the top pressure
3Signal processing unit determines the difference in pressure and uses this to calculate the level
10Endress+Hauser
A0019984
Deltapilot S FMB70
p
2
∆h
p
1
1
2
3
NOTICE
Measured errors may occur
Large measured errors can occur if the ratio of the level to the top pressure is >1:6. This does not
affect reproducibility.
When selecting the Deltapilot S, make sure you choose sufficiently large measuring ranges (see
‣
the following example).
Specific applications can be simulated with the Endress + Hauser Applicator
‣
(https://portal.endress.com/webapp/applicator10).
Example:
• Max. hydrostatic pressure = 600 mbar (9 psi)
• Max. top pressure (Deltapilot 2):
300 mbar (4.5 psi)
• Max. total pressure, measured with Deltapilot 1:
300 mbar (4.5 psi) + 600 mbar (9 psi) = 900 mbar (13.5 psi) measuring cell to be selected:
0 to 1200 mbar (0 to 18 psi)
• Max. pressure, measured with Deltapilot 2:
300 mbar (4.5 psi) → measuring cell to be selected: 0 to 400 mbar (0 to 6 psi)
NOTICE
Possibility of probe 2 flooding during differential pressure measurement.
Measured errors can occur.
When installing, make sure that probe 2 cannot be flooded.
‣
Communication protocol
Density measurement
You can measure the density in tanks with pressure overlay using two Deltapilot S devices and a
signal processing unit or a PLC. The signal processing unit or the PLC calculates the density from the
known distance Δh between the two Deltapilot S devices and the two measured values p1 and p2.
A0019985
1Deltapilot 1 determines pressure measured value p
2Deltapilot 2 determines pressure measured value p
3Signal processing unit determines the density from the two measured values p1 and p2 and the distance Δh
1
2
• 4 to 20 mA with HART communication protocol
• PROFIBUS PA
• Endress+Hauser devices meet the requirements specified by the FISCO model.
• Due to a low current consumption of 13 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 7 devices for Ex ia, CSA IS and FM
IS applications or up to 27 devices for all other applications e.g. in non-hazardous areas, Ex nA
etc. Further information on PROFIBUS PA can be found in Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
• Endress+Hauser devices meet the requirements specified by the FISCO model.
• Due to a low current consumption of 15.5 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO: up to 6 devices for Ex ia, CSA IS and FM
IS applications or up to 24 devices for all other applications e.g. in non-hazardous areas, Ex nA
etc. Further information on FOUNDATION Fieldbus, such as requirements for bus system
components, can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus
Overview".
1.2 bar (18 psi)–1.0 (-15)+1.2 (+18)0.1 (1.5)16 (240)24 (360)1H
4 bar (60 psi)–1.0 (-15)+4 (+60)0.1 (1.5)16 (240)24 (360)1M
10 bar (150 psi)–1.0 (-15)+10 (+150)0.1 (1.5)27 (405)40 (600)1P
1)The vacuum resistance applies for the measuring cell under reference operating conditions.
2)Product Configurator, order code for "Sensor range; sensor over pressure limit"
MWPOPLVacuum resistance
calibratable
span
1)
Inert oil
(psi
abs
)]
abs
0.01/0.04 (0.15/0.6)
Option
1C
2)
12Endress+Hauser
Deltapilot S FMB70
onon
offoff
damp.
damp.
DisplayDisplay
SensorSensor
HARTHART
RR
FIELD COMMUNICATION PROTOCOLFIELD COMMUNICATION PROTOCOL
SW /min
SW /min
E
+
–
E
+
–
Output
Output signal
• 4 to 20 mA with superimposed digital communication protocol HART, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0), 2-wire
• Signal coding: Manchester Bus Powered (MBP): Manchester II
• Transmission rate: 31.25 KBit/s voltage mode
• Digital communication signal FOUNDATION Fieldbus, 2-wire
• Signal coding: Manchester Bus Powered (MBP): Manchester II
• Transmission rate: 31.25 KBit/s voltage mode
OutputInternal + LCDExternal + LCDInternal
1)
Option
4 to 20mA HARTBAC
4 to 20mA HART, Li=0EDF
PROFIBUS PANMO
FOUNDATION FieldbusQPR
1)Product Configurator, order code for "Display, operation: "
Signal range4 to 20 mA
3.8 mA to 20.5 mA
A0021280
Signal on alarm4 to 20 mA HART
As per NAMUR NE43.
• Max. alarm: can be set from 21 to 23 mA (factory setting: 22 mA)
• Hold measured value: last measured value is held
• Min. alarm: 3.6 mA
PROFIBUS PA
As per NAMUR NE43.
Can be set in the Analog Input Block.
Options:
• Last Valid Out Value (factory setting)
• Fail Safe Value
• Status bad
FOUNDATION Fieldbus
As per NAMUR NE43.
Can be set in the Analog Input Block.
Options:
• Last Good Value
• Fail Safe Value (factory setting)
• Wrong Value
Load4 to 20 mA HART
In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load resistance R
(including line resistance) must not be exceeded depending on the supply voltage U0 of the supply
unit. In the following load diagrams, observe the position of the jumper and the explosion protection:
Endress+Hauser13
Deltapilot S FMB70
U – 11.5 V
23 mA
[ ]W
30
20
11.5
40 45
1239
1456
804
369
Test
£
B
U – 10.5 V
R
L
max
23 mA
£
30
20
10.5
UU
[V][V]
40 45
1282
1500
847
413
[ ]W
R
L
max
Test
3
A
1
2
1
2
R
L
max
3
R
L
max
I
63 %
t
t1t
2
90 %
t
3
A0019988
AJumper for 4 to 20 mA test signal set to "Non-test" position
BJumper for 4 to 20 mA test signal set to "Test" position
1Power supply 10.5 (11.5) to 30 V DC for 1/2 G, 1 GD, 1/2 GD, FM IS, CSA IS, NEPSI Ex ia and IEC Ex ia
2Power supply 10.5 (11.5) to 45 V DC for devices for non-hazardous areas, 1/2 D, 1/3 D, 3 G Ex nA, FM DIP,
FM NI and CSA dust ignition-proof
3R
USupply voltage
maximum load resistance
Lmax
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 Ω must be taken into account.
Dead time, time constant
Dynamic behavior,
current output
Dynamic behavior, digital
output (HART electronics)
Presentation of the dead time and the time constant:
Dead time (t1) [ms]Time constant T63 (t2) [ms]Time constant T90 (t3) [ms]
Max.403069
A typical burst rate of 300 ms results in the following behavior:
Dead time (t1) [ms]Dead time (t1) [ms] +
min.200230230
Max.100010301030
Time constant T63 (t2) [ms]
Dead time (t1) [ms] +
Time constant T90 (t3) [ms]
14Endress+Hauser
A0019786
Deltapilot S FMB70
Reading cycle
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (burst): max. 3/s, typical 2/s
The device commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (burst): min. 300 ms
Response time
• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of
preambles)
Dynamic behavior,
PROFIBUS PA
Dynamic behavior,
FOUNDATION Fieldbus
A typical PLC cycle time of 1 s results in the following behavior:
Dead time (t1) [ms]Dead time (t1) [ms] +
Time constant T63 (t2) [ms]
min.75105105
Max.127513051305
Dead time (t1) [ms] +
Time constant T90 (t3) [ms]
Reading cycle (PLC)
• Acyclic: typically 25/s
• Cyclic: typically 30/s (dependent on the number and type of function blocks used in a closedcontrol loop)
Cycle time (update time)
min. 200 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on
the segment coupler used and on the internal PLC cycle time. A new measured value can be
determined up to five times a second.
Response time
• Acyclic: approx. 60 ms to 70 ms (depending on Min. Slave Interval)
• Cyclic: approx. 10 ms to 13 ms (depending on Min. Slave Interval)
A typical configuration for the macro cycle time (host system) of 1 s results in the following
behavior:
Dead time (t1) [ms]Dead time (t1) [ms] +
Time constant T63 (t2) [ms]
min.85115115
Max.108511151115
Dead time (t1) [ms] +
Time constant T90 (t3) [ms]
Reading cycle
• Acyclic: typically 10/s
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
Cycle time (update time)
Cyclic: min. 100 ms
Response time
• Acyclic: typically 100 ms (for standard bus parameter settings)
• Cyclic: max. 20 ms (for standard bus parameter settings)
Endress+Hauser15
Deltapilot S FMB70
Damping
Alarm current setting
Firmware version
A damping affects all outputs (output signal, display):
• Via local display, handheld terminal or PC with operating program, continuous from 0 to 999 s
• Also for HART and PROFIBUS PA: Via DIP switch on the electronic insert,
switch position "on" = set value and "off"
• Factory setting: 2 s
DesignationOption
Min alarm currentJ
HART burst mode PVJ
Min alarm current + HART burst mode PVJ
1)Product Configurator, order code for "Additional options 1" and "Additional options 2"
DesignationOption
02.20.zz, HART 7, DevRev2272
02.11.zz, HART 5, DevRev2173
04.00.zz, FF, DevRev0774
04.01.zz, PROFIBUS PA, DevRev0375
02.10.zz, HART 5, DevRev2176
03.00.zz, FF, DevRev0677
04.00.zz, PROFIBUS PA78
02.30.zz, HART 771
1)
1)
Protocol-specific data HART
1)Product Configurator, order code for "Firmware version"
DD revision• 4 (Russian in language selection) for device revision 21
• 3 (Dutch in language selection) for device revision 21
• 1 for device revision 22
Device description files (DTM, DD)Information and files under:
• www.endress.com
• www.fieldcommgroup.org
HART loadMin. 250 Ω
HART device variablesThe measured values are assigned to the device variables as follows:
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
Pressure
Measured values for QV (fourth variable)
Temperature
Supported functions• Burst mode
• Additional transmitter status
• Device locking
• Alternative measuring modes
16Endress+Hauser
Deltapilot S FMB70
Protocol-specific data
PROFIBUS PA
Manufacturer ID17 (11 hex)
Identification number154F hex
Profile version3.0
• SW version 03.00.zz
• SW version 04.00.zz
3.02
SW version 04.01.zz ( device revision 3)
Compatibility with SW version 03.00.zz and higher.
GSD revision• 4 (SW version 3.00.zz and 4.00.zz)
• 5 (device revision 3)
DD revision• 1 (SW version 3.00.zz and 4.00.zz)
• 1 (device revision 3)
GSD fileInformation and files under:
DD files
Output valuesMeasured values for PV (via Analog Input Function Block)
Input valuesInput value sent from PLC, can be shown on display
Supported functions• Identification & maintenance, simplest device identifier on the
• www.endress.com
• www.profibus.org
• Pressure
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
control system and nameplate
• Condensed status (only with Profile Version 3.02)
• Automatic ID number adjustment and switchable to the following ID
numbers (only with Profile Version 3.02):
• 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status.
• 1503: Compatibility mode for the old Deltapilot S generation
(DB50, DB50L, DB51, DB52, DB53).
• 154F: Identification number for the new Deltapilot S generation
(FMB70).
• Device locking: The device can be locked by hardware or software.
Protocol-specific data
FOUNDATION Fieldbus
Manufacturer ID452B48 hex
Device type100B hex
Device revision• 6 - SW version 03.00.zz
• 7 - SW version 04.00.zz (FF-912)
DD revision• 3 (device revision 6)
• 2 (device revision 7)
CFF revision• 4 (device revision 6)
• 1 (device revision 7)
DD filesInformation and files under:
CFF files
Device tester version (ITK version)• 5.0 (device revision 6)
Number of ITK test campaign• IT054800 (device revision 6)
Link-Master (LAS) capableYes
Choice of "Link Master" and "Basic
Device"
Node addressFactory setting: 247 (F7 hex)
• www.endress.com
• www.fieldcommgroup.org
• 6.01 (device revision 7)
• IT085600 (device revision 7)
Yes; Factory setting: Basic Device
Endress+Hauser17
Supported functionsField diagnostics profile (only with FF912)
The following methods are supported:
• Reboot
• Configure error as warning or alarm
• HistoROM
• Peakhold
• Alarm info
• Sensor trim
Number of VCRs• 44 (device revision 6)
• 24 (device revision 7)
Number of Link Objects in VFD50
Virtual communication references (VCRs)
Device revision 6Device revision 7
Permanent Entries441
Client VCRs00
Server VCRs510
Source VCRs843
Sink VCRs00
Subscriber VCRs1243
Publisher VCRs1943
Deltapilot S FMB70
Link settings
Device revision 6Device revision 7
Slot time44
Min. Inter PDU delay1210
Max. response delay1010
Transducer Blocks
BlockContentOutput values
TRD1 BlockContains all parameters related to the
measurement
Service BlockContains service information• Pressure after damping (channel 3)
Diagnostic block Contains diagnostic informationError code via DI channels (channel 0 to 16)
Display blockContains parameters to configure the
onsite display
Process temperature (channel 2)
• Pressure peakhold indicator (channel 4)
• Counter for max. pressure transgressions (channel
5)
No output values
18Endress+Hauser
Deltapilot S FMB70
Function blocks
BlockContentNumber
Blocks
Resource BlockThe Resource Block contains all the data that uniquely identify the
device. It is an electronic version of a nameplate of the device.
Analog Input
Block 1
Analog Input
Block 2
Digital Input
Block
Digital Output
Block
PID BlockThis block is used as a proportional-integral-derivative controller and
Arithmetic
Block
Input Selector
Block
Signal
Characterizer
Block
Integrator Block The Integrator Block integrates a variable as a function of the time or
Analog Alarm
Block
The AI Block receives the measuring data from the Sensor Block,
(selectable via a channel number) and makes the data available to
other function blocks at its output. Enhancement: Digital outputs for
process alarms, fail safe mode
This block contains the discrete data of the Diagnose Block (selectable
via a channel number 0 to 16) and provides them for other blocks at
the output.
This block converts the discrete input and thus initiates an action
(selectable via a channel number) in the DP Flow Block or in the
Service Block. Channel 1 resets the counter for max. pressure
transgressions.
can be used universally for closed-loop-control in the field. It enables
cascade mode and feedforward control. Input IN can be indicated on
the display. The selection is performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
This block is designed to permit simple use of popular measurement
math functions. The user does not have to know how to write
equations. The math algorithm is selected by name, chosen by the
user for the function to be performed.
The Input Selector Block facilitates the selection of up to four inputs
and generates an output value based on the configured action. This
block normally receives its inputs from AI Blocks. The block enables
the selection of maximum, minimum, average and ‘first good’ values.
Inputs IN1 to IN4 can be shown on the display. The selection is
performed in the Display Block (DISPLAY_MAIN_LINE_CONTENT).
The Signal Characterizer Block has two sections, each with an output
value that is a non-linear function of the input value. The non-linear
function is generated by a single look-up table with 21 arbitrary x-y
pairs.
accumulates the counts from a Pulse Input Block. The block may be
used as a totalizer that counts up until reset or as a batch totalizer
that has a setpoint, where the integrated or accumulated value is
compared to pre-trip and trip settings, generating a binary signal
when the setpoint is reached.
This block contains all process alarm conditions (working like a
comparator) and presents them at the output.
1Enhanced Enhanced
245 ms45 ms
140 ms30 msStandardEnhanced
160 ms40 msStandardEnhanced
1120 ms70 msStandardEnhanced
150 ms40 msStandardEnhanced
135 ms35 msStandardEnhanced
130 ms40 msStandardEnhanced
135 ms40 msStandardEnhanced
135 ms35 msStandardEnhanced
Execution timeFunctionality
Device
Revision 6
Device
Revision 7
(without
trend and
alarm
reports)
Device
Revision 6
Enhanced Enhanced
Device
Revision 7
Additional function block information:
Instantiate Function BlockYESYES
Number of additional instantiatable function blocks115
Endress+Hauser19
Power supply
4... 20mA
Test
Test
Test
4... 20mATest
1
8
6
7
2
3
4
5
1
4
5
2
3
WARNING
L
Electrical safety is compromised by an incorrect connection!
When using the measuring device in hazardous areas, the relevant national standards and
‣
regulations as well as the Safety Instructions or Installation or Control Drawings must be
observed → 63.
All explosion protection data are given in separate documentation which is available upon
‣
request. The Ex documentation is supplied as standard with all Ex-systems → 63.
Devices with integrated overvoltage protection must be grounded → 23.
‣
Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.
‣
Terminal assignment4 to 20 mA HART
Deltapilot S FMB70
A0019989
1Housing
2Supply voltage
34 to 20 mA
4Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here.
5External ground terminal
64 to 20 mA test signal between positive and test terminal
7Internal ground terminal
8Jumper for 4 to 20 mA test signal → 21
PROFIBUS PA and FOUNDATION Fieldbus
A0020158
1Housing
2Supply voltage
3Devices with integrated overvoltage protection are labeled "OVP" (overvoltage protection) here.
4External ground terminal
5Internal ground terminal
20Endress+Hauser
Deltapilot S FMB70
Test
Test
Supply voltage4 to 20 mA HART
Electronic versionJumper for 4 to 20 mA test signal in
"Test" position (delivery status)
Version for nonhazardous area
Intrinsically safe11.5 to 30 V DC10.5 to 30 V DC
• Other types of
protection
• Devices without
certificate
11.5 to 45 V DC10.5 to 45 V DC
11.5 to 45 V DC
(versions with 35 V DC plug-in
connection)
Jumper for 4 to 20 mA test signal in
"Non-test" position
10.5 to 45 V DC
(versions with 35 V DC plug-in
connection)
Measuring a 4 to 20 mA test signal
Jumper position for test
signal
Description
• Measurement of 4-20 mA test signal via the positive and test terminal:
Possible. (Thus, the output current can be measured without interruption via
the diode.)
• As-delivered state
• Minimum supply voltage: 11.5 V DC
A0019992
• Measurement of 4-20 mA test signal via positive and test terminal: Not
possible.
• Minimum supply voltage: 10.5 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
• Ex ia: 10.5 to 30 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
• Ex ia: 10.5 to 30 V DC
Current consumption
• PROFIBUS PA: 13 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15.5 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause
21
Electrical connectionPROFIBUS PA
The digital communication signal is transmitted over the bus via a two-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO
Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted over the bus via a two-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
A0019993
Terminals
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
Endress+Hauser21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.