Pressure sensor with the CONTITETM measuring cell
Condensate-resistant
Application
The device is used for the following measuring tasks:
• Hydrostatic pressure measurement in liquids and paste-like media in all areas of
process engineering, process measuring technology, pharmaceuticals and the food
industry
• Level, volume or mass measurements in liquids
Your benefits
• Very good reproducibility and long-term stability
• Maximum plant safety provided by one-of-a-kind, condensate-proofed CONTITE
measuring cell
• High reference accuracy: ±0.2 %
optionally ±0.1 %
• Turn down 100:1
• Standardized platform for differential pressure, hydrostatics, and pressure
(Deltabar M – Deltapilot M – Cerabar M)
• Simple, fast commissioning through a user interface designed for real-world
applications
• Used for process pressure monitoring up to SIL2, certified to IEC 61508 Edition 2.0
and IEC 61511 by TÜV NORD
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol Meaning
Direct current
A terminal at which DC voltage is present or through which direct current flows.
A0018335
Alternating current
A terminal at which alternating voltage is present or through which alternating current
A0018336
flows.
Direct current and alternating current
• A terminal at which alternating voltage or DC voltage is present.
A0018337
• A terminal through which alternating current or direct current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
A0018338
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0018339
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
A0011201
potential equalization line or a star grounding system depending on national or company
codes of practice.
Tool symbols
SymbolMeaning
Phillips head screwdriver
A0011219
Flat-blade screwdriver
A0011220
Torx screwdriver
A0013442
Hexagon wrench
A0011222
Allen screw
A0011221
4Endress+Hauser
Deltapilot M FMB50/51/52/53
1.
2.
1.
2.
-
.
Symbols for certain types of information
Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0015483
Reference to page
Refers to the corresponding page number.
A0015484
Reference to graphics
Refers to the corresponding graphic number and page number.
A0015486
, , ...Series of steps
Help in the event of a problem
A0015488
Symbols in graphics
SymbolMeaning
1, 2, 3, 4 etc.Numbering for main items
, , ...Series of steps
A, B, C, D etc.Views
A-A, B-B, etc.Sections
Hazardous area
Indicates the hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates the non-hazardous area.
A0011188
Endress+Hauser5
Terms and abbreviations
URLOPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Deltapilot M FMB50/51/52/53
Position Term/AbbreviationExplanation
1OPLThe OPL (over pressure limit = sensor overload limit) for the sensors
depends on the lowest-rated element, with regard to pressure, of the
selected components, i.e. the process connection must be taken into
consideration in addition to the measuring cell. Also observe pressuretemperature dependency. For the relevant standards and additional notes,
see the " ä 35" section.
The OPL may be applied for a limited time period.
2MWPThe MWP (maximum working pressure) for the sensors depends on the
lowest-rated element, with regard to pressure, of the selected components,
i.e. the process connection has to be taken into consideration in addition to
the measuring cell. Also observe pressure-temperature dependency. For the
relevant standards and additional notes, see the " ä 35" section.
The MWP may be applied for an unlimited time.
3Maximum sensor
4Calibrated/Adjusted
p-Pressure
-LRLLower range limit
-URLUpper range limit
-LRVLower range value
-URVUpper range value
-TDTurn down
measuring range
measuring span
Range between LRL and URL
This span is the maximum calibratable/adjustable measuring span.
Range between LRV and URV
Factory setting: 0...URL
Other calibrated spans can be ordered with customised settings.
A0029505
6Endress+Hauser
Deltapilot M FMB50/51/52/53
LRV
URLURV
LRL
1 = 2
3
Turn down calculation
1Calibrated/Adjusted measuring span
2Zero-based span
3Upper range limit
Example
• Sensor: 10 bar (150 psi)
• Upper range limit (URL) = 10 bar (150 psi)
Turn down (TD):
TD =
|URV-LRV|
URL
A0029545
• Calibrated/Adjusted measuring span: 0...5 bar
(0...75 psi)
• Lower range value (LRV) = 0 bar
• Upper range value (URV) = 5 bar (75 psi)
TD =
In this example, the TD is thus 2:1.
This span is based on the zero point.
|5 bar (75 psi)-0 bar (0 psi)|
10 bar (150 psi)
=2
Endress+Hauser7
Device selection
Deltapilot M FMB50/51/52/53
Function and system design
Deltapilot M –
FMB50
FMB51
FMB52
FMB53
Product family
Compact version
A0023537
Rod version
A0023538
Cable version
A0023539
Cable version with
A0023540
Mounting bracket
Field of application– Level measurement
– Pressure measurement
IndustriesFood, pharmaceuticals, chemicals, power plants, automotive, etc.Environment (freshwater
and wastewater)
Process connections– Thread
–Flanges
–Thread
–Flanges
–Thread
–Flanges
Suspension clamp
– Flush-mounted hygienic
connections
Measuring rangesFrom –0.1 to +0.1 (-1.5 to +1.5 psi) bar to –1 bar to +10 bar (-15 to 150 psi)
OPLMax. 40 bar (600 psi)
Process temperature range–10 to +100 °C (+14 to
+212°F) (+135 °C (275°F) for
30 minutes maximum)
–10 to +85 °C
(+14 to +185°F)
With PE cable (unmoved): –10 to +70 °C (+14 to +158°F)
With FEP cable (unmoved):
–10 to +80 °C (+14 to +176°F)
Ambient temperature range• Without LCD display: -40 to +85 °C (-40 to +185°F)
• With LCD display: -20 to +70 °C (-4 to +158°F) (extended temperature application range -40 to 85 °C
(-40 to +158°F) with restrictions in optical properties such as display speed and contrast)
• Separate housing: -20 to +60 °C (-4 to +140°F)
Reference accuracy0.2 % (option 0.1 %) depends on the measuring range ä 27
Supply voltage– 11.5 to 45 V DC (versions with plug-in connection 35 V DC)
– For intrinsically safe device versions: 11.5 to 30 V DC
Output4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options– Gold/rhodium-coated process isolating diaphragm
– 3.1 inspection certificate
– 3A approval and EHEDG approval for FMB50
– Specific firmware versions
– Initial device settings can be ordered
– Separate housing
Specialties– Absolute resistance to condensate thanks to hermetically sealed CONTITE
TM
cell
– Maximum flexibility thanks to modular design
– Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops
8Endress+Hauser
Deltapilot M FMB50/51/52/53
TYPE EL
February 2010
74 -
FMB50, FMB51, FMB52 universal application
• Modular probe program to ensure optimum process adaptation
• FMB50 compact version: installation in the tank from below or from the side
• FMB51, FMB52 rod and cable extension: installation from above, i.e. easy to retrofit ground tanks,
no additional opening in the vessel floor
FMB50 optimized for hygienic applications
• All typical flush-mounted process connections can be supplied
• Welding flanges
• Stainless steel housing
• All the sanitary process connections are gap-free and can be cleaned so that the unit is free of
residue, e.g. CIP cleaning
• USDA/H1-approved transfer liquid as per FDA Directive
• 3A approval or EHEDG approvals
A0023536
A0020029
FMB53 for level measurement in water and wastewater
• The housing with the electronic insert is mounted outside shafts and vessels in such a way that it is
protected from flooding. The extension cable is secured with a suspension clamp.
• The measuring cell tube made of stainless steel (AISI 316L) and the Alloy process isolating
diaphragm allow use in aggressive media such as wastewater for example.
• Extension cable up to 400 m (1312 ft) in length (up to 100 m (328 ft) in Ex-areas) without strain
relief.
• Special measuring cell with gold/rhodium coating for applications in which severe hydrogen
formation can occur (e.g. digested sludge); ä 32.
• Special measuring cell with gold/platinum coating for acids, alkalis or sea water; ä 32.
Endress+Hauser9
Measuring principle
h
h =
p
r · g
p= p - p
messgesatm
p= (p+ p
messatmhydr.
) - p
atm
3
2
1
p
atm
p
atm
p
ges
p
hydr.
h ~ p
p
atm
p= p+ p
atmhydr.
p = p+ p
gesatmhydr.
Deltapilot M FMB50/51/52/53
A0023541
Deltapilot M hydrostatic level measurement and measuring principle
1Rear isolating membrane of the CONTITE™ measuring cell
2Measuring element
3Process isolating diaphragm
gGravitational acceleration
hLevel height
Total pressure = hydrostatic pressure + atmospheric pressure
p
ges
Atmospheric pressure
p
atm
Hydrostatic pressure
p
hydr.
Measured pressure in the measuring cell = hydrostatic pressure
p
mess
Density of the medium
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the
hydrostatic pressure depends solely on the height h of the liquid column.
The CONTITE™ measuring cell, which works on the principle of the gauge pressure sensor, constitutes
the core of Deltapilot M. In contrast to conventional gauge pressure sensors, the precision measuring
element (2) in the CONTITE™ measuring cell is absolutely protected, situated between the process
isolating diaphragm (3) and the rear isolating membrane (1). Thanks to this hermetic sealing of the
measuring element, the CONTITE™ measuring cell is absolutely insensitive to condensate/
condensation and aggressive gases. The pressure applied is transferred from the process isolating
diaphragm to the measuring element by means of an oil without any loss in pressure.
Any measured errors due to fluctuations in temperature are compensated for in the electronics unit by
means of the sensor temperature.
A linearization function with max. 32 points, based on a table entered either manually or
semi-automatically, can be activated locally or remotely. This function facilitates measurement in
engineering units, and provides a linear output signal for spherical and horizontal cylindrical vessels,
and vessels with a conical outlet.
10Endress+Hauser
Deltapilot M FMB50/51/52/53
NOTICE
NOTICE
1
2
3
Level measurement in closed
tanks with pressure overlay
You can determine the differential pressure in tanks with pressure overlay using two Deltapilot M. The
pressure measured values of the two probes are sent to a signal processing unit such as
Endress+Hauser RMA or a PLC. The signal processing unit or PLC determines the difference in pressure
and uses this to calculate the level and the density where necessary.
A0023542
Level measurement in a closed tank with pressure overlay
1Deltapilot 1 measures the total pressure (hydrostatic pressure and top pressure)
2Deltapilot 2 measures the top pressure
3Signal processing unit determines the difference in pressure and uses this to calculate the level
Measured errors can occur.
Large measured errors can occur if the ratio of the level to the top pressure is >1:6. This does not affect
reproducibility.
‣ When selecting the measuring cell, make sure you select measuring ranges that are sufficiently
• Max. total pressure, measured with Deltapilot 1 = 300 mbar (4.5 psi) + 600 mbar (9 psi) = 900 mbar
(13.5 psi) measuring cell to be selected: 0 to 1200 mbar (0 to 18 psi)
• Max. pressure, measured with Deltapilot 2: 300 mbar (4.5 psi) measuring cell to be selected:
0 to 400 mbar (6 psi)
Possibility of probe 2 flooding during differential pressure measurement.
Measured errors can occur.
‣ When installing, make sure that probe 2 cannot be flooded.
Endress+Hauser11
Deltapilot M FMB50/51/52/53
p
2
Δh
p
1
1
2
3
Δh
1
2
3
Density measurementYou can measure the density in tanks with pressure overlay using two Deltapilot M and a signal
processing unit or a PLC. The signal processing unit or the PLC calculates the density from the known
distance between the two Deltapilot M devices h and the two measured values p
Level measurement in a closed tank with pressure overlay
1Deltapilot 1 determines pressure measured value p
2Deltapilot 2 determines pressure measured value p
3Signal processing unit determines the density from the two measured values p1 and p2 and the distance h
1
2
and p2.
1
A0023544
Level measurement with
automatic density correction
(with media changing in the
tank)
Level measurement with automatic density correction is possible in conjunction with a limit switch
such as Liquiphant and a PLC. The limit switch always switches at the same level. In the switch point,
the signal processing unit determines the corrected density from the pressure of the Deltapilot M
currently measured and the known distance between Deltapilot M and the limit switch. The signal
processing unit then calculates the level from the new density and the measured pressure of the
Deltapilot M.
A0023546
Level measurement with automatic density correction
1Deltapilot M
2Liquiphant
3PLC
12Endress+Hauser
Deltapilot M FMB50/51/52/53
WARNING
!
Fieldgate
FXA520
FXN 520
FXN 520
Multidrop-Connector
FXN520
Deltapilot M
Á
11
2
Electrical differential
pressure measurement with
gauge pressure sensors
A0023549
1Shut-off valves
2e.g. filter
In the example given, two Deltapilot M devices (each with a gauge pressure sensor) are interconnected.
The pressure difference can thus be measured using two independent Deltapilot M devices.
Communication and data
processing
Risk of explosion!
‣ If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.
• 4 to 20 mA with HART communication protocol
•PROFIBUS PA
– The Endress+Hauser devices meet the requirements of the FISCO model.
– Due to the low current consumption of 11 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
– up to 8 Deltapilot M for Ex ia, CSA IS and FM IS applications
– up to 31 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS
DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
– The Endress+Hauser devices meet the requirements of the FISCO model.
– Due to the low current consumption of 16 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
– up to 6 Deltapilot M for Ex ia, CSA IS and FM IS applications
– up to 22 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components
can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
4) By default, the device is set to a lower range limit of 0 bar. Please specify in the order if the lower range limit is to be set to a different default value.
Smallest calibratable
measuring span
(preset at the factory)
MWP OPL Vacuum
1)
resistance
Inert oil
(0.145/0.6)
abs
(psi
2)
)]
abs
Option
1C
3)
14Endress+Hauser
Deltapilot M FMB50/51/52/53
U – 11.5 V
23 mA
[]W
30
20
11.5
40 45
1239
1456
804
369
£
U
[V]
1
2
R
L
max
3
R
L
max
Output
Output signal• 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.02)
• Digital communication signal FOUNDATION Fieldbus
• 4 to 20 mA HART
Options:
– Max. alarm: can be set from 21 to 23 mA (Factory setting: 22 mA)
– Hold measured value: last measured value is held
– Min. alarm: 3.6 mA
• PROFIBUS PA: can be set in the Analog Input block,
Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
• FOUNDATION Fieldbus: can be set in the Analog Input block,
Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
Load - 4 to 20 mA HART
Load diagram
1Power supply 11.5 to 30 V DC for intrinsically safe device versions
2Power supply 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and for uncertified device
versions
Maximum load resistance
R
Lmax
USupply voltage
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 must be taken into account.
Endress+Hauser15
A0023090
Dead time, time constant
I
63 %
100 %
t
t1t
2
90 %
t
3
Deltapilot M FMB50/51/52/53
A0019786
Presentation of the dead time and the time constant
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (Burst): max. 3/s, typical 2/s
The Deltapilot M commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (Burst): min. 300 ms
Response time
• Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles)
• Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)
16Endress+Hauser
Deltapilot M FMB50/51/52/53
Dynamic behavior:
PROFIBUS PA
Dynamic behavior:
FOUNDATION Fieldbus
TypeDead time (t1)
[ms]
min.
max.119512851345
min.FMB51
max.
FMB50
FMB52
FMB53
95185245
535785-
16351885-
Dead time (t1) [ms] +
Time constant T63 (= t
) [ms]
2
Dead time (t1) [ms] +
Time constant T90 (= t
) [ms]
3
Reading cycle
• Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control
loop)
• Acyclic: typical 25/s
Cycle time (update time)
min. 100 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on
the segment coupler used and on the internal PLC cycle time.
Response time
• Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval)
• Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval)
TypeDead time (t1)
[ms]
min.
max.110511951255
min.FMB51
max.
FMB50
FMB52
FMB53
105195255
545795-
1545
Dead time (t1) [ms] +
Time constant T63 (= t
1795
) [ms]
2
Dead time (t1) [ms] +
Time constant T90 (= t
-
) [ms]
3
Reading cycle
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
• Acyclic: typical 5/s
Cycle time (update time)
Cyclic: min. 100 ms
Response time
• Cyclic: max. 20 ms (for standard bus parameter settings)
• Acyclic: typical 70 ms (for standard bus parameter settings)
DampingA damping affects all outputs (output signal, display).
• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Via DIP-switch on the electronic insert, switch position
"on" (= set value) and "off" (= damping switched off)
Galvanic isolationThe following devices have a galvanic isolation between electronic and probe:
• FMB51, FMB52, FMB53
• FMB50 with separate housing
Protocol-specific dataHART
Manufacturer ID17 (11 hex)
Device Type Code35 (23 hex)
Device Revision01 (01 hex) - SW version 01.00.zz
HART specification6
DD Revision• 01 (Dutch)
• 02 (Russian)
Device description files
(DTM, DD)
HART loadMin. 250
HART device variablesThe measured values can be freely assigned to the device variables:
Supported functions• Burst mode
Information and files can be found:
• www.endress.com
• www.hartcomm.org
Measured values for PV (primary variable)
• Pressure
• Level
•Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth variable)
•Temperature
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
PROFIBUS PA
Manufacturer ID17 (11 hex)
Ident number1554 hex
Profile Version3.02
• SW Version 01.00.zz
GSD Revision5
DD Revision1
GSD FileInformation and files can be found:
DD Files
Output valuesMeasured values for PV (via Analog Input Function Block)
• www.endress.com
• www.profibus.org
• Pressure
•Flow
• Level
•Tank content
Measured values for SV
• Pressure
•Temperature
18Endress+Hauser
Deltapilot M FMB50/51/52/53
Input valuesInput value sent from PLC, can be shown on display
Supported functions• Identification & Maintenance
1) Only with Profile Version 3.02
Simple device identification via control system and nameplate
•Condensed status
• Automatic ident number adaptation and switchable to following ident
• Device locking: The device can be locked by hardware or software.
)
numbers
– 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status".
– 1503: Compatibility mode for the old Deltapilot M (DB50, DB50L,
DB51, DB52, DB53).
– 1555: Identification number for the new Deltapilot M (FMB50,
FMB51, FMB52, FMB53).
1)
:
Data of the FOUNDATION Fieldbus interface
Basic data
Device Type0x1023
Device Revision01 (hex)
DD Revision0x01021
CFF Revision0x000102
ITK Version5.2.0
ITK Certification Driver No.IT067500
Link-Master (LAS) capableYes
Link Master / Basic Device
selectable
Number of VCRs44
Number of Link Objects in VFD50
Number of FB-Schedule Objects40
Yes; Factory setting: Basic Device
Virtual communication references (VCRs)
Permanent Entries44
Client VCRs0
Server VCRs5
Source VCRs8
Sink VCRs0
Subscriber VCRs12
Publisher VCRs19
Link settings
Slot time4
Min. inter PDU delay12
Max. response delay40
Endress+Hauser19
Deltapilot M FMB50/51/52/53
Transducer Blocks
BlockContentOutput values
TRD1 BlockContains all parameters related to the measurement• Pressure or level (channel 1)
• Process temperature (channel 2)
• Measured pressure value
(channel 3)
•Max. pressure (channel4)
• Level before linearization
(channel 5)
Diagnostic
Block
Display BlockContains parameters to configure the onsite displayNo output values
Contains diagnostic information• Error code via DI channels
(channel 10 to 15)
Function blocks
BlockContentNumber
of
blocks
Resource
Block
Analog Input
Block 1
Analog Input
Block 2
Digital Input
Block
Digital Output
Block
PID BlockThe PID Block serves as a proportional-integral-
Arithmetic
Block
Input Selector
Block
The Resource Block contains all the data that
uniquely identify the device. It is an electronic
version of a nameplate of the device.
The AI Block receives the measuring data from
the Sensor Block, (selectable via a channel
number) and makes the data available to other
function blocks at its output. Enhancement:
digital outputs for process alarms, fail safe mode.
This block contains the discrete data of the
Diagnose Block (selectable via a channel number
10 to 15) and provides them for other blocks at
the output.
This block converts the discrete input and thus
initiates an action (selectable via a channel
number) in the DP Flow Block or in the TRD1
Block. Channel 20 resets the counter for max.
pressure transgressions value and Channel 21
resets the Totalizer.
derivative controller and is used almost
universally for closed-loop-control in the field
including cascade and feedforward. Input IN can
be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
This block is designed to permit simple use of
popular measurement math functions. The user
does not have to know how to write equations.
The math algorithm is selected by name, chosen
by the user for the function to be performed.
The Input Selector Block facilitates the selection
of up to four inputs and generates an output
based on the configured action. This block
normally receives its inputs from AI Blocks. The
block performs maximum, minimum, average
and ‘first good’ signal selection. Inputs IN1 to IN4
can be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_1_CONTENT).
1enhanced
225 msenhanced
120 msStandard
120 msStandard
140 msStandard
135 msStandard
130 msStandard
Execution timeFunctionality
20Endress+Hauser
Deltapilot M FMB50/51/52/53
BlockContentNumber
of
blocks
Signal
Characterizer
Block
Integrator
Block
Additional function block information:
Instantiate Function BlockYES
Number of instantiate blocks20
The Signal Characterizer Block has two sections,
each with an output that is a non-linear function
of the respective input. The non-linear function is
generated by a single look-up table with
21 arbitrary x-y pairs.
The Integrator Block integrates a variable as a
function of the time or accumulates the counts
from a Pulse Input Block. The block may be used
as a totalizer that counts up until reset or as a
batch totalizer that has a setpoint, where the
integrated or accumulated value is compared to
pre-trip and trip settings, generating a binary
signal when the setpoint is reached.
140 msStandard
135 msStandard
Execution timeFunctionality
Endress+Hauser21
WARNING
!
Terminal assignment
- +
1
2
3
4
5
6
7
Deltapilot M FMB50/51/52/53
Power supply
Incorrect connection can limit electrical safety!
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings ä 71 ff, "Safety instructions" and "Installation/Control Drawings" ordering
features.
‣ All explosion protection data are given in separate documentation which is available upon request.
The Ex documentation is provided with all Ex-systems as standard ä 71 ff, "Safety instructions"
and "Installation/Control Drawings" ordering features.
‣ According to IEC/EN61010 a suitable disconnector has to be installed for the device
‣ HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia IIC
and IEC Ex ia can be ordered as an option (see "Ordering information" ordering feature).
‣ Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
‣ The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply.
Electrical connection
1External grounding terminal
2Internal grounding terminal
3Supply voltage
44...20 mA for HART devices
5For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be configured anywhere
along the bus line via menu operation.
6Terminals
7For HART devices: test terminals, see section "Taking 4 to 20 mA test signal"
ä
22
Supply voltage4 to 20 mA HART
Type of protectionSupply voltage
• Intrinsically safe11.5 ... 30 V DC
• Other types of protection
• Devices without certificate
11.5 to 45 V DC (versions with plug-in connection 35 V DC)
Taking 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the
measurement.
22Endress+Hauser
A0023505
Deltapilot M FMB50/51/52/53
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption• PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
IP66/68 NEMA4X/6P + pressure compensation via cable S
1)
PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding, and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the
PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Terminals• Supply voltage and internal ground terminal: 0.5 ... 2.5 mm² (20...14 AWG)