Pressure sensor with the CONTITETM measuring cell
Condensate-resistant
Application
The device is used for the following measuring tasks:
• Hydrostatic pressure measurement in liquids and paste-like media in all areas of
process engineering, process measuring technology, pharmaceuticals and the food
industry
• Level, volume or mass measurements in liquids
Your benefits
• Very good reproducibility and long-term stability
• Maximum plant safety provided by one-of-a-kind, condensate-proofed CONTITE
measuring cell
• High reference accuracy: ±0.2 %
optionally ±0.1 %
• Turn down 100:1
• Standardized platform for differential pressure, hydrostatics, and pressure
(Deltabar M – Deltapilot M – Cerabar M)
• Simple, fast commissioning through a user interface designed for real-world
applications
• Used for process pressure monitoring up to SIL2, certified to IEC 61508 Edition 2.0
and IEC 61511 by TÜV NORD
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol Meaning
Direct current
A terminal at which DC voltage is present or through which direct current flows.
A0018335
Alternating current
A terminal at which alternating voltage is present or through which alternating current
A0018336
flows.
Direct current and alternating current
• A terminal at which alternating voltage or DC voltage is present.
A0018337
• A terminal through which alternating current or direct current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
A0018338
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0018339
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
A0011201
potential equalization line or a star grounding system depending on national or company
codes of practice.
Tool symbols
SymbolMeaning
Phillips head screwdriver
A0011219
Flat-blade screwdriver
A0011220
Torx screwdriver
A0013442
Hexagon wrench
A0011222
Allen screw
A0011221
4Endress+Hauser
Page 5
Deltapilot M FMB50/51/52/53
1.
2.
1.
2.
-
.
Symbols for certain types of information
Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0015483
Reference to page
Refers to the corresponding page number.
A0015484
Reference to graphics
Refers to the corresponding graphic number and page number.
A0015486
, , ...Series of steps
Help in the event of a problem
A0015488
Symbols in graphics
SymbolMeaning
1, 2, 3, 4 etc.Numbering for main items
, , ...Series of steps
A, B, C, D etc.Views
A-A, B-B, etc.Sections
Hazardous area
Indicates the hazardous area.
A0011187
Safe area (non-hazardous area)
Indicates the non-hazardous area.
A0011188
Endress+Hauser5
Page 6
Terms and abbreviations
URLOPLMWP
LRL
0
p
LRV
URV
1
2
3
4
Deltapilot M FMB50/51/52/53
Position Term/AbbreviationExplanation
1OPLThe OPL (over pressure limit = sensor overload limit) for the sensors
depends on the lowest-rated element, with regard to pressure, of the
selected components, i.e. the process connection must be taken into
consideration in addition to the measuring cell. Also observe pressuretemperature dependency. For the relevant standards and additional notes,
see the " ä 35" section.
The OPL may be applied for a limited time period.
2MWPThe MWP (maximum working pressure) for the sensors depends on the
lowest-rated element, with regard to pressure, of the selected components,
i.e. the process connection has to be taken into consideration in addition to
the measuring cell. Also observe pressure-temperature dependency. For the
relevant standards and additional notes, see the " ä 35" section.
The MWP may be applied for an unlimited time.
3Maximum sensor
4Calibrated/Adjusted
p-Pressure
-LRLLower range limit
-URLUpper range limit
-LRVLower range value
-URVUpper range value
-TDTurn down
measuring range
measuring span
Range between LRL and URL
This span is the maximum calibratable/adjustable measuring span.
Range between LRV and URV
Factory setting: 0...URL
Other calibrated spans can be ordered with customised settings.
A0029505
6Endress+Hauser
Page 7
Deltapilot M FMB50/51/52/53
LRV
URLURV
LRL
1 = 2
3
Turn down calculation
1Calibrated/Adjusted measuring span
2Zero-based span
3Upper range limit
Example
• Sensor: 10 bar (150 psi)
• Upper range limit (URL) = 10 bar (150 psi)
Turn down (TD):
TD =
|URV-LRV|
URL
A0029545
• Calibrated/Adjusted measuring span: 0...5 bar
(0...75 psi)
• Lower range value (LRV) = 0 bar
• Upper range value (URV) = 5 bar (75 psi)
TD =
In this example, the TD is thus 2:1.
This span is based on the zero point.
|5 bar (75 psi)-0 bar (0 psi)|
10 bar (150 psi)
=2
Endress+Hauser7
Page 8
Device selection
Deltapilot M FMB50/51/52/53
Function and system design
Deltapilot M –
FMB50
FMB51
FMB52
FMB53
Product family
Compact version
A0023537
Rod version
A0023538
Cable version
A0023539
Cable version with
A0023540
Mounting bracket
Field of application– Level measurement
– Pressure measurement
IndustriesFood, pharmaceuticals, chemicals, power plants, automotive, etc.Environment (freshwater
and wastewater)
Process connections– Thread
–Flanges
–Thread
–Flanges
–Thread
–Flanges
Suspension clamp
– Flush-mounted hygienic
connections
Measuring rangesFrom –0.1 to +0.1 (-1.5 to +1.5 psi) bar to –1 bar to +10 bar (-15 to 150 psi)
OPLMax. 40 bar (600 psi)
Process temperature range–10 to +100 °C (+14 to
+212°F) (+135 °C (275°F) for
30 minutes maximum)
–10 to +85 °C
(+14 to +185°F)
With PE cable (unmoved): –10 to +70 °C (+14 to +158°F)
With FEP cable (unmoved):
–10 to +80 °C (+14 to +176°F)
Ambient temperature range• Without LCD display: -40 to +85 °C (-40 to +185°F)
• With LCD display: -20 to +70 °C (-4 to +158°F) (extended temperature application range -40 to 85 °C
(-40 to +158°F) with restrictions in optical properties such as display speed and contrast)
• Separate housing: -20 to +60 °C (-4 to +140°F)
Reference accuracy0.2 % (option 0.1 %) depends on the measuring range ä 27
Supply voltage– 11.5 to 45 V DC (versions with plug-in connection 35 V DC)
– For intrinsically safe device versions: 11.5 to 30 V DC
Output4 to 20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options– Gold/rhodium-coated process isolating diaphragm
– 3.1 inspection certificate
– 3A approval and EHEDG approval for FMB50
– Specific firmware versions
– Initial device settings can be ordered
– Separate housing
Specialties– Absolute resistance to condensate thanks to hermetically sealed CONTITE
TM
cell
– Maximum flexibility thanks to modular design
– Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops
8Endress+Hauser
Page 9
Deltapilot M FMB50/51/52/53
TYPE EL
February 2010
74 -
FMB50, FMB51, FMB52 universal application
• Modular probe program to ensure optimum process adaptation
• FMB50 compact version: installation in the tank from below or from the side
• FMB51, FMB52 rod and cable extension: installation from above, i.e. easy to retrofit ground tanks,
no additional opening in the vessel floor
FMB50 optimized for hygienic applications
• All typical flush-mounted process connections can be supplied
• Welding flanges
• Stainless steel housing
• All the sanitary process connections are gap-free and can be cleaned so that the unit is free of
residue, e.g. CIP cleaning
• USDA/H1-approved transfer liquid as per FDA Directive
• 3A approval or EHEDG approvals
A0023536
A0020029
FMB53 for level measurement in water and wastewater
• The housing with the electronic insert is mounted outside shafts and vessels in such a way that it is
protected from flooding. The extension cable is secured with a suspension clamp.
• The measuring cell tube made of stainless steel (AISI 316L) and the Alloy process isolating
diaphragm allow use in aggressive media such as wastewater for example.
• Extension cable up to 400 m (1312 ft) in length (up to 100 m (328 ft) in Ex-areas) without strain
relief.
• Special measuring cell with gold/rhodium coating for applications in which severe hydrogen
formation can occur (e.g. digested sludge); ä 32.
• Special measuring cell with gold/platinum coating for acids, alkalis or sea water; ä 32.
Endress+Hauser9
Page 10
Measuring principle
h
h =
p
r · g
p= p - p
messgesatm
p= (p+ p
messatmhydr.
) - p
atm
3
2
1
p
atm
p
atm
p
ges
p
hydr.
h ~ p
p
atm
p= p+ p
atmhydr.
p = p+ p
gesatmhydr.
Deltapilot M FMB50/51/52/53
A0023541
Deltapilot M hydrostatic level measurement and measuring principle
1Rear isolating membrane of the CONTITE™ measuring cell
2Measuring element
3Process isolating diaphragm
gGravitational acceleration
hLevel height
Total pressure = hydrostatic pressure + atmospheric pressure
p
ges
Atmospheric pressure
p
atm
Hydrostatic pressure
p
hydr.
Measured pressure in the measuring cell = hydrostatic pressure
p
mess
Density of the medium
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the
hydrostatic pressure depends solely on the height h of the liquid column.
The CONTITE™ measuring cell, which works on the principle of the gauge pressure sensor, constitutes
the core of Deltapilot M. In contrast to conventional gauge pressure sensors, the precision measuring
element (2) in the CONTITE™ measuring cell is absolutely protected, situated between the process
isolating diaphragm (3) and the rear isolating membrane (1). Thanks to this hermetic sealing of the
measuring element, the CONTITE™ measuring cell is absolutely insensitive to condensate/
condensation and aggressive gases. The pressure applied is transferred from the process isolating
diaphragm to the measuring element by means of an oil without any loss in pressure.
Any measured errors due to fluctuations in temperature are compensated for in the electronics unit by
means of the sensor temperature.
A linearization function with max. 32 points, based on a table entered either manually or
semi-automatically, can be activated locally or remotely. This function facilitates measurement in
engineering units, and provides a linear output signal for spherical and horizontal cylindrical vessels,
and vessels with a conical outlet.
10Endress+Hauser
Page 11
Deltapilot M FMB50/51/52/53
NOTICE
NOTICE
1
2
3
Level measurement in closed
tanks with pressure overlay
You can determine the differential pressure in tanks with pressure overlay using two Deltapilot M. The
pressure measured values of the two probes are sent to a signal processing unit such as
Endress+Hauser RMA or a PLC. The signal processing unit or PLC determines the difference in pressure
and uses this to calculate the level and the density where necessary.
A0023542
Level measurement in a closed tank with pressure overlay
1Deltapilot 1 measures the total pressure (hydrostatic pressure and top pressure)
2Deltapilot 2 measures the top pressure
3Signal processing unit determines the difference in pressure and uses this to calculate the level
Measured errors can occur.
Large measured errors can occur if the ratio of the level to the top pressure is >1:6. This does not affect
reproducibility.
‣ When selecting the measuring cell, make sure you select measuring ranges that are sufficiently
• Max. total pressure, measured with Deltapilot 1 = 300 mbar (4.5 psi) + 600 mbar (9 psi) = 900 mbar
(13.5 psi) measuring cell to be selected: 0 to 1200 mbar (0 to 18 psi)
• Max. pressure, measured with Deltapilot 2: 300 mbar (4.5 psi) measuring cell to be selected:
0 to 400 mbar (6 psi)
Possibility of probe 2 flooding during differential pressure measurement.
Measured errors can occur.
‣ When installing, make sure that probe 2 cannot be flooded.
Endress+Hauser11
Page 12
Deltapilot M FMB50/51/52/53
p
2
Δh
p
1
1
2
3
Δh
1
2
3
Density measurementYou can measure the density in tanks with pressure overlay using two Deltapilot M and a signal
processing unit or a PLC. The signal processing unit or the PLC calculates the density from the known
distance between the two Deltapilot M devices h and the two measured values p
Level measurement in a closed tank with pressure overlay
1Deltapilot 1 determines pressure measured value p
2Deltapilot 2 determines pressure measured value p
3Signal processing unit determines the density from the two measured values p1 and p2 and the distance h
1
2
and p2.
1
A0023544
Level measurement with
automatic density correction
(with media changing in the
tank)
Level measurement with automatic density correction is possible in conjunction with a limit switch
such as Liquiphant and a PLC. The limit switch always switches at the same level. In the switch point,
the signal processing unit determines the corrected density from the pressure of the Deltapilot M
currently measured and the known distance between Deltapilot M and the limit switch. The signal
processing unit then calculates the level from the new density and the measured pressure of the
Deltapilot M.
A0023546
Level measurement with automatic density correction
1Deltapilot M
2Liquiphant
3PLC
12Endress+Hauser
Page 13
Deltapilot M FMB50/51/52/53
WARNING
!
Fieldgate
FXA520
FXN 520
FXN 520
Multidrop-Connector
FXN520
Deltapilot M
Á
11
2
Electrical differential
pressure measurement with
gauge pressure sensors
A0023549
1Shut-off valves
2e.g. filter
In the example given, two Deltapilot M devices (each with a gauge pressure sensor) are interconnected.
The pressure difference can thus be measured using two independent Deltapilot M devices.
Communication and data
processing
Risk of explosion!
‣ If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.
• 4 to 20 mA with HART communication protocol
•PROFIBUS PA
– The Endress+Hauser devices meet the requirements of the FISCO model.
– Due to the low current consumption of 11 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
– up to 8 Deltapilot M for Ex ia, CSA IS and FM IS applications
– up to 31 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS
DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
• FOUNDATION Fieldbus
– The Endress+Hauser devices meet the requirements of the FISCO model.
– Due to the low current consumption of 16 mA ± 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
– up to 6 Deltapilot M for Ex ia, CSA IS and FM IS applications
– up to 22 Deltapilot M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components
can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
4) By default, the device is set to a lower range limit of 0 bar. Please specify in the order if the lower range limit is to be set to a different default value.
Smallest calibratable
measuring span
(preset at the factory)
MWP OPL Vacuum
1)
resistance
Inert oil
(0.145/0.6)
abs
(psi
2)
)]
abs
Option
1C
3)
14Endress+Hauser
Page 15
Deltapilot M FMB50/51/52/53
U – 11.5 V
23 mA
[]W
30
20
11.5
40 45
1239
1456
804
369
£
U
[V]
1
2
R
L
max
3
R
L
max
Output
Output signal• 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.02)
• Digital communication signal FOUNDATION Fieldbus
• 4 to 20 mA HART
Options:
– Max. alarm: can be set from 21 to 23 mA (Factory setting: 22 mA)
– Hold measured value: last measured value is held
– Min. alarm: 3.6 mA
• PROFIBUS PA: can be set in the Analog Input block,
Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
• FOUNDATION Fieldbus: can be set in the Analog Input block,
Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
Load - 4 to 20 mA HART
Load diagram
1Power supply 11.5 to 30 V DC for intrinsically safe device versions
2Power supply 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and for uncertified device
versions
Maximum load resistance
R
Lmax
USupply voltage
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 must be taken into account.
Endress+Hauser15
A0023090
Page 16
Dead time, time constant
I
63 %
100 %
t
t1t
2
90 %
t
3
Deltapilot M FMB50/51/52/53
A0019786
Presentation of the dead time and the time constant
• Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
• Cyclic (Burst): max. 3/s, typical 2/s
The Deltapilot M commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (Burst): min. 300 ms
Response time
• Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles)
• Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)
16Endress+Hauser
Page 17
Deltapilot M FMB50/51/52/53
Dynamic behavior:
PROFIBUS PA
Dynamic behavior:
FOUNDATION Fieldbus
TypeDead time (t1)
[ms]
min.
max.119512851345
min.FMB51
max.
FMB50
FMB52
FMB53
95185245
535785-
16351885-
Dead time (t1) [ms] +
Time constant T63 (= t
) [ms]
2
Dead time (t1) [ms] +
Time constant T90 (= t
) [ms]
3
Reading cycle
• Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control
loop)
• Acyclic: typical 25/s
Cycle time (update time)
min. 100 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on
the segment coupler used and on the internal PLC cycle time.
Response time
• Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval)
• Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval)
TypeDead time (t1)
[ms]
min.
max.110511951255
min.FMB51
max.
FMB50
FMB52
FMB53
105195255
545795-
1545
Dead time (t1) [ms] +
Time constant T63 (= t
1795
) [ms]
2
Dead time (t1) [ms] +
Time constant T90 (= t
-
) [ms]
3
Reading cycle
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
• Acyclic: typical 5/s
Cycle time (update time)
Cyclic: min. 100 ms
Response time
• Cyclic: max. 20 ms (for standard bus parameter settings)
• Acyclic: typical 70 ms (for standard bus parameter settings)
DampingA damping affects all outputs (output signal, display).
• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Via DIP-switch on the electronic insert, switch position
"on" (= set value) and "off" (= damping switched off)
Galvanic isolationThe following devices have a galvanic isolation between electronic and probe:
• FMB51, FMB52, FMB53
• FMB50 with separate housing
Protocol-specific dataHART
Manufacturer ID17 (11 hex)
Device Type Code35 (23 hex)
Device Revision01 (01 hex) - SW version 01.00.zz
HART specification6
DD Revision• 01 (Dutch)
• 02 (Russian)
Device description files
(DTM, DD)
HART loadMin. 250
HART device variablesThe measured values can be freely assigned to the device variables:
Supported functions• Burst mode
Information and files can be found:
• www.endress.com
• www.hartcomm.org
Measured values for PV (primary variable)
• Pressure
• Level
•Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth variable)
•Temperature
• Additional Transmitter Status
• Device Locking
• Alternative operating modes
PROFIBUS PA
Manufacturer ID17 (11 hex)
Ident number1554 hex
Profile Version3.02
• SW Version 01.00.zz
GSD Revision5
DD Revision1
GSD FileInformation and files can be found:
DD Files
Output valuesMeasured values for PV (via Analog Input Function Block)
• www.endress.com
• www.profibus.org
• Pressure
•Flow
• Level
•Tank content
Measured values for SV
• Pressure
•Temperature
18Endress+Hauser
Page 19
Deltapilot M FMB50/51/52/53
Input valuesInput value sent from PLC, can be shown on display
Supported functions• Identification & Maintenance
1) Only with Profile Version 3.02
Simple device identification via control system and nameplate
•Condensed status
• Automatic ident number adaptation and switchable to following ident
• Device locking: The device can be locked by hardware or software.
)
numbers
– 9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status".
– 1503: Compatibility mode for the old Deltapilot M (DB50, DB50L,
DB51, DB52, DB53).
– 1555: Identification number for the new Deltapilot M (FMB50,
FMB51, FMB52, FMB53).
1)
:
Data of the FOUNDATION Fieldbus interface
Basic data
Device Type0x1023
Device Revision01 (hex)
DD Revision0x01021
CFF Revision0x000102
ITK Version5.2.0
ITK Certification Driver No.IT067500
Link-Master (LAS) capableYes
Link Master / Basic Device
selectable
Number of VCRs44
Number of Link Objects in VFD50
Number of FB-Schedule Objects40
Yes; Factory setting: Basic Device
Virtual communication references (VCRs)
Permanent Entries44
Client VCRs0
Server VCRs5
Source VCRs8
Sink VCRs0
Subscriber VCRs12
Publisher VCRs19
Link settings
Slot time4
Min. inter PDU delay12
Max. response delay40
Endress+Hauser19
Page 20
Deltapilot M FMB50/51/52/53
Transducer Blocks
BlockContentOutput values
TRD1 BlockContains all parameters related to the measurement• Pressure or level (channel 1)
• Process temperature (channel 2)
• Measured pressure value
(channel 3)
•Max. pressure (channel4)
• Level before linearization
(channel 5)
Diagnostic
Block
Display BlockContains parameters to configure the onsite displayNo output values
Contains diagnostic information• Error code via DI channels
(channel 10 to 15)
Function blocks
BlockContentNumber
of
blocks
Resource
Block
Analog Input
Block 1
Analog Input
Block 2
Digital Input
Block
Digital Output
Block
PID BlockThe PID Block serves as a proportional-integral-
Arithmetic
Block
Input Selector
Block
The Resource Block contains all the data that
uniquely identify the device. It is an electronic
version of a nameplate of the device.
The AI Block receives the measuring data from
the Sensor Block, (selectable via a channel
number) and makes the data available to other
function blocks at its output. Enhancement:
digital outputs for process alarms, fail safe mode.
This block contains the discrete data of the
Diagnose Block (selectable via a channel number
10 to 15) and provides them for other blocks at
the output.
This block converts the discrete input and thus
initiates an action (selectable via a channel
number) in the DP Flow Block or in the TRD1
Block. Channel 20 resets the counter for max.
pressure transgressions value and Channel 21
resets the Totalizer.
derivative controller and is used almost
universally for closed-loop-control in the field
including cascade and feedforward. Input IN can
be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
This block is designed to permit simple use of
popular measurement math functions. The user
does not have to know how to write equations.
The math algorithm is selected by name, chosen
by the user for the function to be performed.
The Input Selector Block facilitates the selection
of up to four inputs and generates an output
based on the configured action. This block
normally receives its inputs from AI Blocks. The
block performs maximum, minimum, average
and ‘first good’ signal selection. Inputs IN1 to IN4
can be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_1_CONTENT).
1enhanced
225 msenhanced
120 msStandard
120 msStandard
140 msStandard
135 msStandard
130 msStandard
Execution timeFunctionality
20Endress+Hauser
Page 21
Deltapilot M FMB50/51/52/53
BlockContentNumber
of
blocks
Signal
Characterizer
Block
Integrator
Block
Additional function block information:
Instantiate Function BlockYES
Number of instantiate blocks20
The Signal Characterizer Block has two sections,
each with an output that is a non-linear function
of the respective input. The non-linear function is
generated by a single look-up table with
21 arbitrary x-y pairs.
The Integrator Block integrates a variable as a
function of the time or accumulates the counts
from a Pulse Input Block. The block may be used
as a totalizer that counts up until reset or as a
batch totalizer that has a setpoint, where the
integrated or accumulated value is compared to
pre-trip and trip settings, generating a binary
signal when the setpoint is reached.
140 msStandard
135 msStandard
Execution timeFunctionality
Endress+Hauser21
Page 22
WARNING
!
Terminal assignment
- +
1
2
3
4
5
6
7
Deltapilot M FMB50/51/52/53
Power supply
Incorrect connection can limit electrical safety!
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings ä 71 ff, "Safety instructions" and "Installation/Control Drawings" ordering
features.
‣ All explosion protection data are given in separate documentation which is available upon request.
The Ex documentation is provided with all Ex-systems as standard ä 71 ff, "Safety instructions"
and "Installation/Control Drawings" ordering features.
‣ According to IEC/EN61010 a suitable disconnector has to be installed for the device
‣ HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia IIC
and IEC Ex ia can be ordered as an option (see "Ordering information" ordering feature).
‣ Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
‣ The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply.
Electrical connection
1External grounding terminal
2Internal grounding terminal
3Supply voltage
44...20 mA for HART devices
5For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be configured anywhere
along the bus line via menu operation.
6Terminals
7For HART devices: test terminals, see section "Taking 4 to 20 mA test signal"
ä
22
Supply voltage4 to 20 mA HART
Type of protectionSupply voltage
• Intrinsically safe11.5 ... 30 V DC
• Other types of protection
• Devices without certificate
11.5 to 45 V DC (versions with plug-in connection 35 V DC)
Taking 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the
measurement.
22Endress+Hauser
A0023505
Page 23
Deltapilot M FMB50/51/52/53
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption• PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
IP66/68 NEMA4X/6P + pressure compensation via cable S
1)
PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding, and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the
PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Terminals• Supply voltage and internal ground terminal: 0.5 ... 2.5 mm² (20...14 AWG)
Standard, CSA GP
ATEX II1/2G or II2G Ex ia,
IEC Ex ia Ga/Gb or Ex ia Gb,
FM/ CSA IS
ATEX II1/2D Ex t, II1/2GD Ex ia,
II3G Ex nA,
IEC Ex t Da/Db
Plastic M20x1.55 to 10 mm (0.2 to 0.39 in)
Metal M20x1.5 (Ex e)7 to 10.5 mm (0.28 to 0.41 in)
For other technical data, see the housing section ä 36 ff".
Endress+Hauser23
Page 24
ConnectorDevices with valve connector
+
21
–
+
AB
BU BN GNYE
2
1
3
+
–
–
Han7D
–
+
+–
–
+
1
5
4
6
7
8
2
3
AB
21
3
4
BN = brown, BU = blue, GNYE = green/yellow
AElectrical connection for devices with valve connector
BView of the connection on the device
Material: PA 6.6
Deltapilot M FMB50/51/52/53
A0023097
Devices with Harting plug Han7D
AElectrical connection for devices with Harting plug Han7D
BView of the connection on the device
Material: CuZn, gold-plated contacts of plug-in jack and connector
Devices with M12 plug
PIN assignment for M12 connector
PIN assignment for M12 connectorPINMeaning
1Signal +
2Not assigned
3Signal –
4Earth
A0019990
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
• Material: body PA; coupling nut CuZn, nickel-plated
24Endress+Hauser
A0011175
Page 25
Deltapilot M FMB50/51/52/53
2
1
4
3
• Degree of protection (fully locked): IP66/67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 71114212
Cable 4x0.34 mm² (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
• Material: body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP66/67
• Order number: 52010285
Devices with 7/8" plug
PIN assignment for 7/8" connector
PIN assignment for 7/8" connectorPINMeaning
1Signal –
2Signal +
3Not assigned
4Shield
External thread: 7/8 - 16 UNC
• Material: 316L (1.4401)
• Protection: IP66/68
Cable specificationHART
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• The cable outer diameter depends on the cable entry used.
PROFIBUS PA
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded two-wire cable, preferably cable type A
A0011176
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Start-up current HART12 mA or 22 mA (selectable)
Residual rippleNo influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply0.001 % of URL/V
Endress+Hauser25
Page 26
Deltapilot M FMB50/51/52/53
1
2
3
4
+
-
+
-
rt
sw
+
-
A
B
Overvoltage protection
(optional)
The device can be fitted with overvoltage protection. The overvoltage protection is mounted at the
factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in length
(take additional length into account when installing). The device is connected as illustrated in the
following graphic.
For details refer to TI001013KEN, XA01003KA3 and BA00304KA2.
Ordering information:
Product Configurator, "Mounted accessories" ordering feature, option NA
A0023111
AWithout direct shield grounding
BWith direct shield grounding
1Incoming connection cable
2HAW569-DA2B
3Unit to be protected
4Connection cable
26Endress+Hauser
Page 27
Deltapilot M FMB50/51/52/53
12
Performance characteristics
Reference operating
conditions
• As per IEC 60770
• Ambient temperature T
= constant, in the range of: +21 to +33 °C (+70 to 91°F)
A
• Humidity = constant, in the range of: 5 to 80 % RH
• Ambient pressure pA = constant, in the range of: 860 to 1060 mbar (12.47 to 15.37 psi)
• Position of the measuring cell: constant, in range: FMB50: horizontally 1°
FMB51/FMB52/FMB53: vertically 1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Span based on zero point
• Material of the process isolating diaphragm: Alloy C276 (2.4819) and Alloy C276 (2.4819) with
coating (AuRh or AuPt)
Thermal change in the zero
output and the output span
VersionMeasuring cell-10 to +60 °C
(+14 to +140°F)
FMB50
FMB51/52/53 snap-on
FMB51/52/53 welded
FMB50/51/52/53
0.1 bar (1.5 psi)
0.1 bar (1.5 psi)
0.4 bar (6 psi)
1.2 bar (18 psi),
4 bar (60 psi),
10 bar (150 psi)
< (0.32 + 0.30 x
TD)
< (0.32 + 0.50 x
TD)
< (0.31 + 0.25 x
TD)
< (0.31 + 0.10 x
TD)
60 to 85 °C
(140 to 185°F)
% of the calibrated span
< (0.34 + 0.40 x
TD)
< (0.34 + 0.60 x
TD)
< (0.32 + 0.30 x
TD)
< (0.32 + 0.15 x
TD)
Only FMB50:
85 to 100 °C
(185 to 212°F)
< (0.34 + 0.55 x
TD)
-
-
< (0.33 + 0.20 x
TD)
Total performanceThe "Total performance" specification comprises the non-linearity including hysteresis, non-
reproducibility as well as the thermal change in the zero point.
Total performance in % of the URL
VersionMeasuring cell-10 to +60 °C
(+14 to +140°F)
FMB50
FMB51/52/53 snap-on
FMB51/52/53 welded0.1 bar (1.5 psi)< 0.8< 1< 1.4
FMB50/51/52/53
0.1 bar (1.5 psi)< 0.35< 0.45< 0.6
0.4 bar (6 psi)< 0.35< 0.45< 0.6
1.2 bar (18 psi), 4 bar (60 psi),
10 bar (150 psi)
< 0.15< 0.2< 0.25
60 to 85 °C
(140 to 185°F)
85 to 100 °C
(185 to 212°F)
Long-term stability
Measuring cellLong-term stability [%]
0.1 bar (1.4 psi)
0.4 bar (6 psi)
1.2 bar (18 psi)
4 bar (60 psi)
10 bar (150 psi)
• < 0.18 of the upper range limit (URL) / year
• < 0.45 of the upper range limit (URL) / 5 years
• < 0.1 of the upper range limit (URL) / year
• < 0.25 of the upper range limit (URL) / 5 years
• < 0.05 of the upper range limit (URL) / year
• < 0.125 of the upper range limit (URL) / 5 years
Total error The total error comprises the long-term stability and the total performance:
Measuring cell% of the URL/year (in the permitted temperature range)
0.1 bar (1.5 psi)
0.4 bar (6 psi)0.61
1.2 bar (18 psi)0.27
4 bar (60 psi), 10 bar (150 psi)0.25
•Snap-on: 0.63
• Welded: 1.0
Warm-up period• 4 to 20 mA HART:
– FMB50 = 5 s
– FMB51/FMB52/FMB53 = 8 s
•PROFIBUS PA: 8 s
• FOUNDATION Fieldbus: 20 s (after a TOTAL-reset 45 s)
28Endress+Hauser
Page 29
Deltapilot M FMB50/51/52/53
WARNING
!
L
E
17 (0.67)
Installation
General installation
instructions
FMB50Level measurement
• The position-dependent zero point shift can be corrected:
– directly at the device via an operating key
– directly at the device via operating keys on the display
– via digital communication if the cover is not open
Risk of explosion!
In hazardous areas, comply strictly with the safety instructions when the housing cover is closed and
open.
• The local display can be rotated in 90° stages.
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– in the filling curtain
– in the tank outflow
– or at a point in the tank that can be affected by pressure pulses from the agitator
• The calibration and functional test can be carried out more easily if you mount the device
downstream of a shutoff device.
• Deltapilot M must be included in the insulation for media that can harden when cold.
Pressure measurement in gases
Mount Deltapilot M with shutoff device above the tapping point so that any condensate can flow into
the process.
Pressure measurement in steams
• Mount Deltapilot M with siphon above the tapping point.
• Fill the siphon with liquid before commissioning.
The siphon reduces the temperature to almost the ambient temperature.
Pressure measurement in liquids
Mount Deltapilot M with the shutoff device below or at the same level as the tapping point.
FMB51/FMB52/FMB53• When mounting rod and cable versions, make sure that the probe head is located at a point as free
as possible from flow. To protect the probe from impact resulting from lateral movement, mount the
probe in a guide tube (preferably made of plastic) or secure it with a clamping fixture.
• In the case of devices for hazardous areas, comply strictly with the safety instructions when the
housing cover is open.
• The length of the extension cable or the probe rod is based on the planned level zero point.
The height of the protective cap must be taken into consideration when designing the layout of the
measuring point. The level zero point (E) corresponds to the position of the process isolating
diaphragm.
Level zero point = E; top of the probe = L.
• Do not clean or touch process isolating diaphragms with hard or pointed objects.
• The process isolating diaphragm in the rod and cable version is protected against mechanical
damage by a plastic cap.
Seal
• Deltapilot M devices with a G 1 ½ thread:
When screwing the device into the tank, the flat seal has to be positioned on the sealing surface of
the process connection. To avoid additional strain on the process isolating diaphragm, the thread
should never be sealed with hemp or similar materials.
• Deltapilot M devices with NPT threads:
– Wrap Teflon tape around the thread to seal it.
– Tighten the device at the hexagonal bolt only. Do not turn the device at the housing.
– Do not overtighten the thread when screwing in the screw. Max. torque: 20 to 30 Nm
(14.75 to 22.13 lbf ft)
Sealing the probe housing
Moisture must not penetrate the housing when mounting the device, establishing the electrical
connection and during operation.
• Always firmly tighten the housing cover and the cable entries.
• Lubricant is provided on the O-ring seal in the housing cover and on the thread of the aluminum
cover. To ensure that the cover seals tight, any lubricant which has been removed must be replaced.
Use silicone grease or graphite paste as the lubricant. Mineral oil-based grease can destroy the
O-ring.
PE cable length > 300 m (984 ft)
• Two suspension clamps must be used for PE cables longer than 300 meters (984 ft).
Cable length tolerances
•FMB52
– Cable length < 5 m (16 ft): up to -35 mm (-1.38 in)
– Cable length 5...10 m (16...33 ft): up to -75 mm (-2.95 in)
– Cable length 10...100 m (33...328 ft): up to -100 mm (-3.94 in)
•FMB53
– Cable length < 5 m (16 ft): up to ±17.5 mm (±0.69 in)
– Cable length 5...10 m (16...33 ft): up to ±37.5 mm (±1.48 in)
– Cable length 10...100 m (33...328 ft): up to ±50 mm (±1.97 in)
Rod length tolerances
•FMB51
– Rod length < 4000 mm (157 in): up to -4 mm (-0.16 in)
Wall and pipe mountingEndress+Hauser offers a mounting bracket for installing the device on pipes or walls. The mounting
bracket is
• included in the delivery for the FMB50/51/52 with a separate housing (available for order via
feature 600) and for the FMB53
• available for order as a separate accessory (Part No.: 71102216).
For the dimensions, see ä 50.
30Endress+Hauser
Page 31
Deltapilot M FMB50/51/52/53
r ³120 (4.72)
4
5
231
"Separate housing" version With the "separate housing" version, you are able to mount the housing with the electronics insert at a
distance from the measuring point. This allows for trouble-free measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or
difficult to access)
• If rapid cleaning of the measuring point is required
In the case of the "separate housing" version, the sensor is delivered with th e process connection and cable ready mounted. The housing
and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both ends. These sockets are simply
connected to the housing and the sensor.
1Process connection with sensor - see the following section for the degrees of protection
2Process connection adapter (weight 0.93 kg (2.05 lbs))
3Cable (weight 0.05 kg/Meter (0.11 lbs/meter)), both ends are fitted with a socket
4Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
5Housing with electronic insert - degrees of protection
ä
33 ff
Degree of protection for the process connection and sensor with the use of
•FEP cable:
–IP69
1)
– IP66 NEMA 4/6P
– IP68 (1.83 mH
O for 24 h) NEMA 4/6P
2
•PE cable:
– IP66 NEMA 4/6P
– IP68 (1.83 mH
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 in)
O for 24 h) NEMA 4/6P
2
• Cable extraction force: max. 450 N (101 lbf)
• Resistance to UV light
Use in hazardous area:
• Intrinsically safe installations (Ex ia/IS)
• FM/CSA IS: for Div.1 installation only
A0023567
1) Identification of IP protection category according to DIN EN 60529. The earlier designation “IP69K” according to DIN 40050 Part 9 is no longer
valid (the standard was withdrawn on November 1, 2012). The tests required for both standards are identical.
Endress+Hauser31
Page 32
Deltapilot M FMB50/51/52/53
NOTICE
Oxygen applicationsOxygen and other gases can react explosively to oils, grease and plastics. As a result, the following are
some of the precautions that must be taken:
– All components of the system, such as measuring devices, must be cleaned in accordance with the
BAM (DIN 19247) requirements.
– Depending on the materials used, a certain maximum temperature and maximum pressure must not
be exceeded for oxygen applications. The maximum temperature T
for oxygen applications is
max
60 °C (140°F).
The devices suitable for gaseous oxygen applications are listed in the following table with the
specification p
max
.
Order code for devices1) cleaned for
oxygen applications
2)
FMB50
FMB51
1) Only device, not accessory or enclosed accessory
4) Oxygen applications possible with FKM seal and inert oil.
)
p
for oxygen applications
max
• Depends on the lowest-rated element, with regard to pressure, of
the selected components: over pressure limit (OPL) of the sensor or
process connection (1.5 x PN)
• Depends on filling oil
• Depends on the lowest-rated element, with regard to pressure, of
the selected components: over pressure limit (OPL) of the sensor or
process connection (1.5 x PN)
• Depends on filling oil
• Depends on seal material
3)
4)
)
)
PWIS cleaningSpecial cleaning of the transmitter to remove paint-wetting substances, for use in paint shops, for
instance.
Ordering information: Product Configurator, "Service" ordering feature, option HC
The stability of the materials used must be checked before using them in the medium.
The protective cap of the process isolating diaphragm must be removed if necessary (FMB51/FMB52/
FMB53).
Applications with hydrogenA gold-plated metal process isolating diaphragm offers universal protection against hydrogen
diffusion, both in gas applications and in applications with aqueous solutions.
Applications with hydrogen in aqueous solutions
A gold/rhodium-plated metal process isolating diaphragm (AU/Rh) offers effective protection
against hydrogen diffusion.
Special measuring cells for
acids, alkalis or sea water
For acids, alkalis or sea water, Endress+Hauser offers process isolating diaphragms with a gold/
platinum coating.
(not FMB50)
With temperature exposure (up to 85°C(185°F)) there is an additional zero point deviation of 1.1
mbar (0.0165 psi).
1) Extended temperature application range (-40 °C to +85 °C (–40°F to +185°F)) with restrictions in optical
properties such as display speed and contrast
VersionFMB50FMB51FMB52FMB53
Without LCD display–40 °C to +90 °C
With LCD display –40 °C to +85 °C
With M12 plug , elbowed-25 °C to +90 °C
With separate housing and
FEP cable
1)
(-13°F to +185°F)
(-40°F to +194°F)
(-40°F to +185°F)
(-13°F to +194°F)
With PE cable: -40 °C to +70 °C (-40°F to +158°F)
With FEP cable: –40 °C to +80 °C (-40°F to +176°F)
–20 °C to +70 °C (-4°F to +158°F)
With PE cable: -25 °C to +70 °C (-13°F to +158°F)
With FEP cable: -25 °C to +80 °C (-13°F to +176°F)
-20 °C to +60 °C (-4°F to +140°F)
With PE cable: -40 °C to +70 °C (-40°F to +158°F)
With FEP cable: –40 °C to +80 °C (-40°F to +176°F)
With PE cable: -25 °C to +70 °C (-13°F to +158°F)
With FEP cable: -25 °C to +80 °C (-13°F to +176°F)
-20 °C to +60 °C (-4°F to +140°F)
Climate classClass 4K4H (air temperature: –20 to 55 °C (–4 to +131°F), relative humidity: 4 to 100%) satisfied as per
• Part 7: Guidelines for the Performance of
Type Approvals
• Chapter 2: Test Requirements for Electrical /
Electronic Equipment and Systems
FMB50, FMB52, FMB53
with mounting bracket
FMB51IEC 60068-2-6 Guaranteed for:
IEC 61298-3
Guaranteed for:
5 to 25 Hz: ±1.6 mm (0.06 in);
25 to 100 Hz: 4 g
in all 3 planes
Guaranteed for:
10 to 60 Hz: ±0.15 mm (0.01 in);
60 to 500 Hz: 2 g
in all 3 planes
10 to 60 Hz: ±0.075 mm (0.003 in)
60 to 150 Hz 1g in all 3 planes
Endress+Hauser33
Page 34
Deltapilot M FMB50/51/52/53
Electromagnetic
compatibility
• Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and
NAMUR Recommendation EMC (NE21).
• Max. deviation during EMC-tests < 0.5% of the span
• All tests were performed with full measurement range (TD 1:1).
Further details can be found in the manufacturer declaration.
34Endress+Hauser
Page 35
Deltapilot M FMB50/51/52/53
WARNING
!
Process
Process temperature range
–10 °C to +100 °C (+14°F to 212°F)
135 °C (275°F) for 30 min. maximum
Lateral load FMB51 (static) 30 Nm
Pressure specifications
The maximum pressure for the measuring device depends on the lowest-rated element with
regard to pressure ä 14 ff, "Measuring range" ordering feature and ä 36 ff "Mechanical
construction" ordering feature
‣ Only operate the measuring device within the prescribed limits!
‣ The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring device.
‣ The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of +20 °C (68°F), (100°F (38 °C) for ANSI flanges), and may be applied to the
device for an unlimited time. Pay attention to pressure-temperature dependencies. Please refer to
the following standards for pressure values permitted at higher temperatures
EN 1092-1: 2001 Tab. 18
ASME B 16.5a – 1998 Tab. 2-2.2 F316
ASME B 16.5a – 1998 Tab. 2.3.8 N10276
JIS B 2220.
The test pressure corresponds to the over pressure limit of the sensor and may only be applied for
a limited time period to ensure measurement within specification and in order to avoid permanent
damage. In the case of sensor range and process connections where the over pressure limit (OPL)
of the process connection is smaller than the nominal value of the sensor, the device is set at the
factory, at the very maximum, to the OPL value of the process connection. If you want to use the
entire sensor range, select a process connection with a higher OPL value.
‣ Oxygen applications:
The values for "p
be exceeded.
‣ Avoid steam hammering!
Steam hammering can cause zero point drift.
Recommendation: Residue (such as condensation or drops of water) can remain at the process
isolating diaphragm after CIP cleaning and lead to local steam hammering if immediately steam is
introduced. In practice, drying the process isolating diaphragm (e.g. by blowing off excess
moisture) has proven to be a successful way of avoiding steam hammering.
FMB50FMB51FMB52FMB53
max
and T
–10 °C to +85 °C
(+14°F to +185°F)
Min. process temperature when using the KALREZ seal:
-3 °C (27°F)
2)
for oxygen applications" as per ä 32, "Oxygen applications" may not
max
With PE cable: -10 °C to +70 °C (-14°F to 158°F)
With FEP cable: –10 °C to +80 °C (-14°F to 176°F)
2) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The
chemical composition of the two materials can be identical.
Endress+Hauser35
Page 36
Mechanical construction
115 (4.53)
103 (4.06)
112 (4.41)
127 (5)
94 (3.7)
1
2
Device heightThe device height is calculated from
• the height of the housing and
• the height of the individual process connection.
The individual heights of the components are listed in the following sections. To calculate the device
height simply add up the individual heights of the components. Where applicable also take into
consideration the installation distance (space that is used to install the device).
You can use the following table for this purpose:
Section PageHeight
Housing height ä 36 ff
Process connections ä 37 ff
Installation distance
Device height
F31 housing, aluminum
Deltapilot M FMB50/51/52/53
Engineering unit mm (in)
1Cover with viewing window
2Cover without viewing window
3) Endress+Hauser supplies DIN/EN stainless steel flanges as per AISI 316L (DIN/ EN material number 1.4404 or 14435). With regard to their
stability-temperature property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN 1092-1: 2001 Tab.18. The chemical
composition of the two materials can be identical.
4) Designation as per DIN 2526 in brackets
38Endress+Hauser
0.8 μm (31.5 μin). Lower surface
a
Page 39
Deltapilot M FMB50/51/52/53
D
k
f
g
2
g
b
1.61
d=Mø1.41
Process connections FMB50,
ASME flanges, connection dimensions as per ANSI B 16.5, raised face RF
3) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
Endress+Hauser39
Page 40
Deltapilot M FMB50/51/52/53
D
k
f
g
2
g
b
41
d=Mø35.8
Process connections FMB50,
FMB51, FMB52 - continued
1)
Flange
Material Nominal
diameter
40 A10 K140168124191052.55 (5.62)KEJ
AISI 316L
(1.4435)
50 A10 K155169624191202.95 (6.50)KFJ
80 A10 K1851812628191504.25 (9.37)KGJ
100 A10 K2101815128191755.35 (11.79)KHJ
Nominal
pressure
JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF
Engineering unit mm
BoltholesWeight Option
DThickness Diameter of
raised face
bgfg
[mm] [mm][mm][mm][mm][mm][kg (lbs)]
Height of
raised
face
Quantity Diameter Hole circle
2
k
A0020004
2)
1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), is < R
Lower surface roughness available on request.
Universal process adapter incl. silicone molded seal
(spare part no.: 52023572) FDA 21CFR177.2600/USP Class VI-70C
Universal process adapter incl. EPDM molded seal
(order no.: 71100719) EPDM-70, FDA, USP Class VI; (5 pieces)
Universal process adapter, 6 inch extension incl. silicone molded seal
(spare part no.: 52023572) FDA 21CFR177.2600/USP Class VI-70C
Universal process adapter, 6 inch extension incl. EPDM molded seal
(order no.: 71100719) EPDM-70, FDA, USP Class VI; (5 pieces)
Universal adapter
A0026355
B
A0020014
2)
•1: top section
AISI 316L
(1.4404)
EHEDG, 3A
0.8 (1.76)
EHEDG, 3AUNJ
UPJ
3)
)
•2: bottom
section
AISI 316L
(1.4435)
EHEDG, 3A
EHEDG, 3AUOJ
1.7 (3.75)
UQJ
)
)
1) Surface roughness of the surfaces in contact with the medium Ra 0.76μm (30 μin) as standard. Surface roughness Ra<0.38 μm electropolished
(wetted) Ordering information: Product Configurator, "Service" ordering feature, option "HK".
3) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material
number 1.4307).
A0020009
2)
42Endress+Hauser
Page 43
Deltapilot M FMB50/51/52/53
ø84 (3.31)
ø68 (2.68)
20.5 (0.81)
59.5 (2.34)
Rd 70 x 1/6
ø65 (2.56)
ø84 (3.31)
59.5 (2.34)
ø9 (0.35)
27 (1.06)
ø90 (3.54)
ø70 (2.76)
ø49.9 (1.96)
59.5 (2.34)
F
Engineering unit mm (in)
1)
Item
DesignationMaterialApprovalWeight
A0020010
G
Engineering unit mm (in)
H
A0020011
Engineering unit mm (in)
Option
kg (lbs)
FVarivent Type N for pipes 40 – 162, PN 40
GSMS 2", PN 25EHEDG, 3A0.7 (1.54)TXJ
AISI 316L (1.4435)
EHEDG, 3A1 (2.21)TRJ
HNEUMO, D50, PN 16, 316L3A0.8 (1.76)S4J
A0020012
2)
3)
1) Surface roughness of the surfaces in contact with the medium R
0.76μm (30 μin) as standard. Lower surface roughness available on request.
3) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L
(DIN/EN material number 1.4307).
Endress+Hauser43
Page 44
Deltapilot M FMB50/51/52/53
ø21,3 (0.84)
ø42,4 (1.67)
ø43,5 (1.71)
208 (8.19)
L
H
Process connections FMB51
(rod version)
Threaded connection ISO 228 and NPT
HFor dimensions of process connections
LProbe length L = 0.4 m to 4 m (1.3 ft to 13 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
ä
36 ff
A0023592
Process connection incl. sensorWeight
Housing weight ä 36 ff
Process connection weight ä 37 ff
Pipe incl. cable0.77 kg/m (1.70 lbs/3.3 ft)
Threaded connection incl. measuring cell tube and sensor1.65 kg (3.64 lbs)
Flange connection incl. measuring cell tube and sensor, without a flange-
Total weight of device
44Endress+Hauser
Page 45
Deltapilot M FMB50/51/52/53
ø21,3 (0.84)
ø42,4 (1.67)
ø43,5 (1.71)
208 (8.19)
L
H
EN/DIN, ANSI and JIS flanges
A0023593
HFor dimensions of process connections
LProbe length L = 0.4 m to 4 m (1.3 ft to 13 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
Process connection incl. sensorWeight
Housing weight ä 36 ff
Process connection weight ä 37 ff
Pipe incl. cable0.77 kg/m (1.70 lbs/3.3 ft)
Threaded connection incl. measuring cell tube and sensor-
Flange connection incl. measuring cell tube and sensor, without a flange1.3 kg (2.87 lbs)
Total weight of device
ä
36 ff
Endress+Hauser45
Page 46
Deltapilot M FMB50/51/52/53
ø10,4 (0.41)
ø42,4 (1.67)
ø43,5 (1.71)
236 (9.29)
L
H
Process connections FMB52
(cable version)
Threaded connection ISO 228 and NPT
HFor dimensions of process connections
LProbe length L = 0.5 to 400 m (1.6 to 1312 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
ä
36 ff
A0023594
Process connection incl. sensorWeight
Housing weight ä 36 ff
Process connection weight ä 37 ff
PE cable0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable0.18 kg/m (0.40 lbs/3.3 ft)
Threaded connection incl. measuring cell tube and sensor1.65 kg (3.64 lbs)
Flange connection incl. measuring cell tube and sensor, without a flange-
Total weight of device
46Endress+Hauser
Page 47
Deltapilot M FMB50/51/52/53
H
ø10,4 (0.41)
ø42,4 (1.67)
ø43,5 (1.71)
236 (9.29)
L
EN/DIN, ANSI and JIS flanges
A0023597
HFor dimensions of process connections
LProbe length L = 0.5 to 400 m (1.6 to 1312 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
Process connection incl. sensorWeight
Housing weight ä 36 ff
Process connection weight ä 37 ff
PE cable0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable0.18 kg/m (0.40 lbs/3.3 ft)
Flange connection incl. measuring cell tube and sensor, without a flange1.3 kg (2.87 lbs)
Total weight of device
ä
36 ff
Endress+Hauser47
Page 48
Dimensions of FMB53 with
ø10,4 (0.41)
ø42,4 (1.67)
ø43,5 (1.71)
236 (9.29)
L
238 (9.37)
169 (6.65)
137 (5.39)
156 (6.14)
194 (7.64)
222 (8.74)
235 (9.25)
5
33
4
ø61 (2.4)
11
22
181 (7.13)
R 200 (7.87)
³
F31 housing, suspension
clamp and mounting bracket
Deltapilot M FMB50/51/52/53
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
1Dimensions for housing covers with a viewing window.
2Housing covers without a viewing window are approx. 15 mm (0.59 in) lower.
3Mounting bracket for pipe and wall mounting (for pipes from 1 ¼" up to 2" diameter)
4Suspension clamp
5Measuring cell tube
LProbe length = 0.5 to 400 m (1.6 to 1312 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
Process connection incl. sensorWeight
Housing weight ä 36 ff
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel)0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel)0.18 kg/m (0.40 lbs/3.3 ft)
Mounting bracket0.2 kg (0.44 lbs)
Pipe bend incl. cable entry0.65 kg (1.43 lbs)
Suspension clamp0.4 kg (0.88 lbs)
Measuring cell tube incl. sensor 1.0 kg (2.21 lbs)
Total weight of device
A0023598
48Endress+Hauser
Page 49
Deltapilot M FMB50/51/52/53
ø10,4 (0.41)
ø42,4 (1.67)
ø43,5 (1.71)
236 (9.29)
L
238 (9.37)
159 (6.26)
127 (5)
146 (5.75)
187 (7.36)
211 (8.31)
224 (8.82)
5
33
4
ø61 (2.4)
174 (6.85)
1
2
1
2
R 200 (7.87)
³
Dimensions of FMB53 with
F15 housing, suspension
clamp and mounting bracket
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
1Dimensions for housing covers with a viewing window.
2Housing covers without a viewing window are approx. 15 mm (0.59 in) lower.
3Mounting bracket for pipe and wall mounting (for pipes from 1 ¼" up to 2" diameter)
4Suspension clamp
5Measuring cell tube
LProbe length = 0.5 to 400 m (1.6 to 1312 ft) - see Product Configurator, “Probe connection” section
Engineering unit mm (in)
Process connection incl. sensorWeight
Housing weight ä 36 ff
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel)0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel)0.18 kg/m (0.40 lbs/3.3 ft)
Mounting bracket0.2 kg (0.44 lbs)
Pipe bend incl. cable entry0.65 kg (1.43 lbs)
Suspension clamp0.4 kg (0.88 lbs)
Measuring cell tube incl. sensor 1.0 kg (2.21 lbs)
Total weight of device
A0023600
Endress+Hauser49
Page 50
Wall and pipe mounting with
63 (2.48)
L1
50 (1.97)
L
122 (4.8)
52 (2.05)
86 (3.39)
70 (2.76)
140 (5.51)
158 (6.22)
175 (6.89)
A
B
ø52 (2.05)ø20 (0.79)
6 (0.24)
ø6 (0.24)
ø42...60 (1.65...2.36)
1
2
95 (3.74)
114 (4.49)
112 (4.4)
127 (5)
69 (2.72)
1
2
"Separate housing" version
Deltapilot M FMB50/51/52/53
1Housing cover with viewing window.
2Housing cover without viewing window
LPE cable 2 m (6.6 ft), 5 m (16 ft) or 10 m (33 ft). FEP cable 5 m (16 ft)
L1FMB50 = 91 mm (3.58 in); FMB51 and FMB52 = 81 mm (3.19 in)
Also available for order as a separate accessory: part number 71102216
Housing (F31 or F15)Mounting
ä 36 ff 0.5 kg (1.10) U
bracket
A0025834
1)
50Endress+Hauser
Page 51
Deltapilot M FMB50/51/52/53
91 (3.58)
F31
F15
1
ø54.1 (2.13)
r ³120 (4.72)r³ 120 (4.72)
1
1
2
2
19 (0.75)
34 (1.34)
7 (0.28)
26 (1.02)
1
81 (3.19)
F31
F15
1
ø54.1 (2.13)
r ³120 (4.72)r³ 120 (4.72)
1
1
2
2
29 (1.14)
44 (1.73)
17 (0.67)
36 (1.42)
1
FMB50: Reduction in installation height
If the separate housing is used, the mounting height of the process connection is reduced compared to
the dimensions of the standard version.
A0025833
1 Process connection adapter
Engineering unit mm (in)
FMB51, FMB52: Reduction in installation height
If the separate housing is used, the mounting height of the process connection is reduced compared to
the dimensions of the standard version.
A0025827
1 Process connection adapter
Engineering unit mm (in)
Endress+Hauser51
Page 52
Example for a "Separate housing" version
121,7 (4.79)
L1
R20 (4.72)
³1
L
ø54.1 (2.13)
3
1
2
Deltapilot M FMB50/51/52/53
A0023603
Connecting cable with process connection adapter and mounting bracket, here shown with an FMB52
1Mounting bracket for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
2Process connection adapter
3Measuring cell tube
L1PE cable = 2 m (6.6 ft), 5m (16 ft) or 10 m (33 ft)
FEP cable = 5 m (16 ft)
LProbe length = 0.5 to 400 m (1.6 to 1312 ft)
Engineering unit mm (in)
Process connection incl. sensorWeight
Separate housing for FMB50Weight of housing ( ä 36 ff) + 0.5 kg (1.10 lbs)
Separate housing for FMB51 and FMB52Weight of housing ( ä 36 ff) + 0.65 kg (1.43 lbs)
Process connection adapter0.4 kg (0.88 lbs)
Mounting bracket0.2 kg (0.44 lbs)
Pipe bend incl. cable entry0.65 kg (1.43 lbs)
PE cable 2 m (6.6 ft)0.16 kg (0.35 lbs)
PE cable 5 m (16 ft)0.32 kg (0.71 lbs)
Total weight of device
Ordering information for FMB50, FMB51, FMB52: Product Configurator, "Separate housing" ordering
feature
52Endress+Hauser
Page 53
Deltapilot M FMB50/51/52/53
1141516
4
10
711
12
5
3
2
6
9
8
13
Materials not in contact with
process
F31 housing
Front view, left-hand side view, top view
Item
number
1
2
3Cover sealEPDM
4Sight glassMineral glass
5Sight glass sealSilicone (VMQ)
6External ground terminalAISI 304 (1.4301)
7NameplatesPlastic film
8Attachment for tie-on labelAISI 304 (1.4301)/ AISI 316 (1.4401)
9Pressure compensation filterAISI 316L (1.4404) and PBT-FR
10Pressure compensation filter, O-ringVMQ or EPDM
11Sealing ringEPDM
12Snap ringPC Plastic
13Seal of cable gland and blind plugEPDM/NBR
14
15Blind plugPBT-GF30 FR
16Cover clampClamp AISI 316L (1.4435), screw A4
Component partMaterial
F31 housing, RAL 5012 (blue)Die-cast aluminum with protective powder-coating
on polyester base
Cover, RAL 7035 (gray)Die-cast aluminum with protective powder-coating
on polyester base
Cable glandPolyamide (PA), for dust ignition-proof: CuZn nickel-
plated
for dust ignition-proof, Ex d, FM XP and CSA XP:
AISI 316L (1.4435)
A0023615
Endress+Hauser53
Page 54
F15 housing
114
9101213
4
5
8
3
6
11
7
2
Front view, left-hand side view, top view
Deltapilot M FMB50/51/52/53
A0023616
Item
number
1F15 housing
2Cover
3Cover sealSilicone with PTFE coating
4Sight glass for non-hazardous area, ATEX Ex
4Sight glass for ATEX 1/2 D, ATEX 1/3 D,
5Sight glass sealSilicone (VMQ)
6External ground terminalAISI 304 (1.4301)
7Attachment for tie-on labelAISI 304 (1.4301)/ AISI 316 (1.4401)
8Pressure compensation filterAISI 316L (1.4404) and PBT-FR
9Pressure compensation filter, O-ringVMQ or EPDM
10Nameplateslasered
11Cable glandPolyamide (PA), for dust ignition-proof: CuZn
12Seal of cable gland and blind plugNBR/Silicone/EPDM
13Sealing ringEPDM
14ScrewA4-50
Component partMaterial
AISI 316L (1.4404)
ia, NEPSI Zone 0/1 Ex ia, IECEx Zone 0/1 Ex
ia, FM NI, FM IS, CSA IS
1) Product Configurator, "Material of process isolating diaphragm" ordering feature
2)
B
1)
1)
Endress+Hauser57
Page 58
Deltapilot M FMB50/51/52/53
Seals
DesignationOption
FKM VitonA
EPDMJ
Kalrez 6375L
None, welded cellU
1) Product Configurator, "Seal" ordering feature
2) Not FMB50
1)
2)
)
)
TSE Certificate of Suitability (Transmissible Spongiform Encephalopathy)
The following applies to all process wetted device components:
• They do not contain any materials derived from animals.
• No auxiliaries or operating materials derived from animals are used in production or processing.
58Endress+Hauser
Page 59
Deltapilot M FMB50/51/52/53
1
3
2
4
5
E
+
–
Operability
Operating conceptOperator-oriented menu structure for user-specific tasks
• Commissioning
•Operation
•Diagnostics
•Expert level
Quick and safe commissioning
Guided menus for applications
Reliable operation
• Onsite operation possible in several languages
• Standardized operation at the device and in the operating tools
• Parameters relating to measured values can be locked/unlocked using the device's write protection
switch, using the device software or via remote control.
A 4-line liquid crystal display (LCD) is used for display and operation. The local display shows measured
values, dialog texts as well as fault and notice messages in plain text, thereby supporting the user at
every stage of operation. The liquid crystal display of the device can be turned in 90° stages. Depending
on the orientation of the device, this makes it easy to operate the device and read the measured values.
Functions:
• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as
current display; or for PROFIBUS PA as graphic display of the standardized value of the AI Block; for
FOUNDATION Fieldbus as graphic display of the transducer output in relation to the set pressure
range.
• Simple and complete menu guidance as parameters are split into several levels and groups
• Each parameter is given a 3-digit ID number for easy navigation
• Possibility of configuring the display to suit individual requirements and preferences, such as
language, alternating display, contrast setting, display of other measured values such as sensor
temperature etc.
• Comprehensive diagnostic functions (fault and warning message etc.)
1Operating keys
2Bar graph
3Symbol
4Header
5Parameter ID number
Setting lower range value and upper range value - reference pressure present
at the device
Device reset
Locking and unlocking parameters relevant to the measured value
Value acceptance indicated by the green LED―――
Switching damping on and off
Operating keys and elements located on the electronic insert
A0023125
HART electronic insert
1Operating keys for lower range value (zero) and
upper range value (span)
2Green LED to indicate successful operation
3Slot for optional local display
4DIP switch only for Deltabar M
5DIP switch only for Deltabar M
6DIP switch for alarm current SW / Alarm Min
(3.6 mA)
7DIP switch for switching damping on/off
8DIP switch for locking/unlocking parameters
relevant to the measured value
FunctionOperation with operating keys and elements on the
Position adjustment (zero point correction)
Setting lower range value and upper range value - reference pressure present
at the device
Device reset
Locking and unlocking parameters relevant to the measured value
Value acceptance indicated by the green LED
Switching damping on and off
PROFIBUS PA electronic insert
1Green LED to indicate successful operation
2Operating key for position zero adjustment or
reset (Zero)
3Slot for optional local display
4DIP switch for bus address SW / HW
5DIP switch for hardware address
6DIP switch only for Deltabar M
7DIP switch only for Deltabar M
8Not used
9DIP switch for switching damping on/off
10DIP switch for locking/unlocking parameters
relevant to the measured value
A0023126
FOUNDATION Fieldbus electronic insert
1Operating key for position zero adjustment or
reset (Zero)
2Green LED to indicate successful operation
3Slot for optional local display
4DIP switch only for Deltabar M
5DIP switch only for Deltabar M
6DIP switch for simulation mode
7DIP switch for switching damping on/off
8DIP switch for locking/unlocking parameters
Remote operation All software parameters are accessible depending on the position of the write protection switch on the
device.
Hardware and software for remote
operation
FieldCare ä 61 ff
FieldXpert SFX100 ä 61 ff―
NI-FBUS Configurator ä 62 ff――
1) Commubox FXA195 required ä 62 ff
2) Profiboard or Proficard required ä 62 ff
HARTPROFIBUS PAFOUNDATION Fieldbus
1)
2)
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you
can configure all Endress+Hauser devices as well as devices from other manufacturers that support the
FDT standard.
FieldCare supports the following functions:
• Configuration of transmitters in offline and online mode
• Loading and saving device data (upload/download)
•HistoROM
®
/M-DAT analysis
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
• Service interface with Commubox FXA291 and ToF adapter FXA291 (USB).
For further information please contact your local Endress+Hauser Sales Center.
Field Xpert SFX100
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on
Windows Mobile. It offers wireless communication via the optional VIATOR Bluetooth modem. Field
Xpert also works as a stand-alone device for asset management applications. For details refer to
BA00060S/04/EN.
Endress+Hauser61
Page 62
Deltapilot M FMB50/51/52/53
Commubox FXA195
For intrinsically safe HART communication with FieldCare via the USB interface. For details refer to
TI00404F/00/EN.
Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface
(= Endress+Hauser Common Data Interface) and the USB port of a computer or laptop.
For details, see TI00405C/07/EN.
For the following Endress+Hauser devices, you also need the "ToF adapter FXA291" accessory:
• Cerabar S PMC71, PMP7x
•Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70
ToF adapter FXA291
The ToF adapter FXA291 connects the Commubox FXA291 to devices in the ToF platform, pressure
devices and Gammapilot via the USB port of a computer or laptop. For details, see KA00271F.
Profiboard
For connecting a PC to PROFIBUS.
Proficard
For connecting a laptop to PROFIBUS.
FF configuration program
FF configuration program, such as NI-FBUS Configurator, to
• connect devices with "FOUNDATION Fieldbus signal" into an FF-network
• set FF-specific parameters
Remote operation via:
• Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and
a schedule based on the fieldbus concepts.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
– Set block and device tags
– Set device addresses
– Create and edit function block control strategies (function block applications)
– Configure vendor-defined function and transducer blocks
– Create and edit schedules
– Read and write to function block control strategies (function block applications)
– Invoke Device Description (DD) methods
– Display DD menus
– Download a configuration
– Verify a configuration and compare it to a saved configuration
– Monitor a downloaded configuration
– Replace a virtual device by a real device
– Save and print a configuration
System integrationThe device can be given a tag name (max. 8 alphanumeric characters).
DesignationOption
Measuring point (TAG), see additional specificationsZ1
CE markThe device meets the legal requirements of the relevant EC directives.
Endress+Hauser confirms that the device has been successfully tested by applying the CE mark.
RCM-Tick markingThe supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well as
health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0027319-DE
Ex approvals•ATEX
•FM
•CSA
• Also combinations of different approvals
All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous
areas.
ä 71 ff, "Safety Instructions" and "Installation/Control Drawings" ordering features.
EAC conformityThe measuring system meets the legal requirements of the applicable EAC guidelines. These are listed
in the corresponding EAC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark.
Suitability for hygienic
processes
All materials in contact with foodstuffs comply with framework Regulation (EC) 1935/2004.
The Deltapilot is available with hygienic process connections (overview: see order code).
Contamination in the process!
Risk of contamination if incorrect seals and parts are used!
‣ To avoid the risk of contamination, when installing the device comply with the design principles of
EHEDG, Guideline 37 "Hygienic Design and Application of Sensors" and Guideline 16 "Hygienic Pipe
Couplings".
‣ Suitable assemblies and seals must be used to ensure hygienic design in accordance with 3-A SSI
and EHEDG specifications.
‣ The leak-proof connections can be cleaned with the cleaning methods typical of this industry (CIP
and SIP). Attention must be paid to the pressure and temperature specifications of the sensor and
process connections for CIP and SIP processes (clean in place/sterilize in place).
A0024005A0020029
Gap-free connections can be cleaned without residue using the usual cleaning methods.
Functional safety SILThe Deltapilot M with 4 to 20 mA output signal has been developed to assessed and certified by
TÜV NORD CERT as per IEC 61508 Edition 2.0 and IEC 61511. These devices can be used to monitor
the process level and pressure up to SIL 2. For a detailed description of the safety functions with
Deltapilot M, settings and functional safety data, see the "Functional safety manual - Deltapilot M"
SD00347P.
Ordering information:
Product Configurator, "Additional approval:" ordering feature, option "LA".
Overfill protectionWHG (FMB50, FMB51, FMB52): see document ZE00275P
AD2000The pressure retaining material 316L (1.4435/1.4404) corresponds to AD2000 - W2/W10.
Pressure Equipment Directive
(PED)
The Deltapilot M device corresponds to Article 3 (3) of the EC directive 97/23/EC (Pressure Equipment
Directive) and has been designed and manufactured according to good engineering practice.
Manufacturer declaration•FDA conformity
• TSE-free, materials free from animal origin
• Regulation EC 2023/ 2006 (GMP)
• Regulation (EC) No. 1935/2004 on materials intended to come into contact with food
Classification of process
sealing between electrical
systems and (flammable or
combustible) process fluids in
accordance with ANSI/
ISA 12.27.01
Endress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or
dual seal devices with annunciation, allowing the user to waive the use and save the cost of installing
external secondary process seals in the conduit as required by the process sealing sections of ANSI/
NFPA 70 (NEC) and CSA 22.1 (CEC). These instruments comply with the North-American installation
practice and provide a very safe and cost-saving installation for pressurized applications with
hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
Inspection certificate
DesignationFMB50FMB51FMB52FMB53 Option
3.1 Material certificate, wetted metallic parts, EN10204-3.1 inspection certificateJA
Conformity to NACE MR0175, wetted metallic partsJB
Conformity to NACE MR0103, wetted metallic partsJE
Conformity to AD2000, wetted metallic parts, excepting process membrane― ― ―JF
2) Only device, not accessory or enclosed accessory
1)
66Endress+Hauser
Page 67
Deltapilot M FMB50/51/52/53
Ordering information
Detailed ordering information is available as follows:
• In the Product Configurator on the Endress+Hauser website: www.endress.com→ Click "Corporate" → Select your country → Click "Products" → Select the product using the filters and search field → Open
product page → The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: direct input of information specific to measuring point, such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Configuration data sheetPressure
The following configuration data sheet has to be filled in and included with the order if the option J Customized pressure has been selected in feature 90 "Calibration; unit" in the ordering information.
Pressure Engineering Unit
mbar mmHO mmHg Pa
bar mH
psi inH
Calibration Range / Output
Low range value (LRV):_______________ [pressure engineering unit]
Upper range value (URV): _______________ [pressure engineering unit]
Display Information
1st Value Display
Main Value none (Default)
O
O kgf/cm2 kPa
ftH
O MPa
1)
2nd Value Display
Main Value [%]
Pressure
Current [mA] (HART only)
Temperature
1)
1)
Depending on sensor and communication variant
Damping
Damping:__________ sec (Default 2 sec)
Endress+Hauser67
Page 68
Deltapilot M FMB50/51/52/53
A
B
Level
The following configuration data sheet has to be filled in and included with the order if the option K Customized level has been selected in feature 90 "Calibration; unit" in the ordering information.
Pressure Engineering UnitOutput Unit (Scaled unit)
Empty pressure [a]:
Low pressure value (empty) ______________
O kPa
O kgf/cm2 MPa kg m l gal %
ftH
O t dm hl Igal
lb cm
mm m
ft in
ft
3
3
3
inch
Example
Empty calibration [a]:
Low level value (empty) ______________
[pressure
[Scaled Unit]
engineering unit]
Full pressure [b]:
High pressure value (full)______________
Full calibration [b]:
High level value (full)______________
[pressure
engineering unit]
Display Information
1st Value Display
1)
2nd Value Display
Main Value none (Default)
Main Value [%]
Pressure
Current [mA] (HART only)
Temperature
1)
Depending on sensor and communication variant
Damping
[Scaled Unit]
A0023621
A0 mbar / 0m
B300 mbar (4.5psi) / 3 m (9.8 ft).
1)
Damping:__________ sec (Default 2 sec)
Smallest calibratable measuring span (preset at the factory) ä 14.
68Endress+Hauser
Page 69
Deltapilot M FMB50/51/52/53
Accessories
Suspension clamp
(FMB53 only)
Extension cable shortening
kit (FMB53 only)
M12 connector ä 24 ff
Welding necks and Weld-in
tool flanges
ä 30 ff
See Product Configurator, "Accessory enclosed" ordering feature, option "PW"
or can be ordered as a separate accessory (part no. 71125862). For details refer to SD00553P/00/A2.