6. Set up the unit (via provided PC software)Page 27
7. Transmit the set up files to the unitPage 27
Brief Operating Instructions
Your new unit has the Operating Instructions built-in. The unit's simple control system enables you
to commission for many applications, practically without any paper. Your unit displays instructions
at the push of a button directly on screen. This description is nevertheless delivered with the unit it is a supplement to the Operating Instructions built into the unit. Anything that is not described
directly at the unit by plain text or menus is explained here.
Fig. 1: Variable softkey (e.g. calling up internal Help function in the Setup menu)
Index
A very extensive index can be found at the end of these Operating Instructions. It acts as a
complement to the table of contents and helps you find special terms and functions.
This unit is designed for the electronic acquisition, display, recording, analysis, remote transmission
and archiving of analog and digital input signals in non-hazardous areas.
• The unit is designed for installation in a panel or a cabinet and may only be operated in an installed
state.
• The manufacturer does not accept liability for damage caused by improper or non-designated use.
The unit can cause danger if used improperly or other than intended.
1.2Installation, commissioning and operation
• The unit may only be installed, connected, commissioned and serviced by qualified and
authorized expert staff (e.g. electrical technicians) strictly adhering to the instructions contained
in this manual, the applicable norms, legal regulations and certificates (depending on the
application).
• These experts must have read and understood this manual and follow the instructions it contains.
• The unit may only be modified or repaired if expressly permitted in the Operating Instructions.
• Damaged units which could pose a source of danger may not be put into operation and must be
marked as defective.
• Primarily observe local regulations regarding opening and repairing electrical units.
#
1.3Operational safety
• The unit is safely built and tested according to state-of-the-art technology and has left the factory
in perfect condition as regards technical safety. The applicable regulations and European standards
have been taken into account.
• Please observe the technical data on the nameplate! The nameplate is on the left-hand side of the
housing.
Desk top version
Warning!
• The mains plug must only be inserted into a socket with grounding contact.
• The protective effect must not be removed by an extension lead without ground wire.
• Relay outputs: U(max) = 30 V eff (AC) / 60 V (DC)
Repairs
Repairs that are not described in these Operating Instructions must only be carried out directly by
the manufacturer or by the service department.
Electromagnetic compatibility
The measuring system meets the general safety requirements of IEC 61010 and the EMC
requirements of IEC 61326.
Technical improvement
The manufacturer reserves the right to adapt technical data to the most up-to-date technical
developments without any special announcement. Ask your supplier for information about activities
and possible extensions to these Operating Instructions.
1.4Return
The following measures must be taken before you return a measuring unit, e.g. for repair or
calibration:
• The unit must be packed in protective packaging. The original packaging offers the best
protection.
5
Safety instructions
#
"
!
1.5Notes on safety conventions and icons
Always refer to the safety instructions in these Operating Instructions labeled with the following
symbols:
Warning!
This symbol draws attention to activities or procedures that can lead to injuries to persons, safety
risks or the destruction of the unit if not carried out properly.
Caution!
This symbol draws attention to activities or procedures that can lead to defective operation or to
destruction of the unit if not carried out properly.
Note!
This symbol draws attention to activities or procedures that have an indirect effect on operation, or
can trigger an unforeseen unit reaction if not carried out properly.
ESD - Electrostatic discharge
Protect the terminals against electrostatic discharge. Failure to comply with this instruction can
result in the destruction of parts of the electronics.
6
Identification
2Identification
2.1Device designation
2.1.1Nameplate
Compare the nameplate on the left-hand side of the unit with the delivery note and with the
following diagram:
Fig. 2: 1. Order code
2. Serial number
3. Software version
4. Fields for indicating the installed software updates
5. Supply voltage, power frequency, power consumption
6. Ambient temperature range
7. Unit approvals
2.2Scope of delivery
• Unit (with terminals, as per your order)
• 4 fastening clips
• USB cable
• Optional CompactFlash CF card (CF card is enclosed separately.)
• PC operating and configuration software on CD-ROM
• Delivery note
• Multilanguage Brief Operating Instructions as hard copy
• Operating Instructions on CD-ROM
• locking plate
Anything missing? Then please inform your supplier.
2.3Certificates and approvals
An overview of all certificates and approvals can be found in the Technical Data, Section 10.
7
Installation
3Installation
3.1Incoming acceptance, transport, storage
3.1.1Incoming acceptance
After receiving the goods, check the following points:
• Is the packaging or the contents damaged?
• Is the delivery complete? Compare the goods delivered with what you ordered.
3.1.2Transport and storage
Observe the following points:
• The unit must be packed in shockproof packaging for storage (and transport). The original
packaging offers the best protection for this.
• The permitted storage temperature is -20 to +60 °C (-4 to 140 °F)
3.2Installation conditions
Working temperature range:
0 to 50 °C (32 to 122 °F), max. 75% rel. humidity without condensation.
Caution!
"
• To avoid heat accumulation, please always ensure that the unit is sufficiently cooled.
• Maintain distance from strong magnetic fields (see Section 10 "Technical data", interference
immunity )
• Environment at front in accordance with unit ingress protection IP 54
3.3Installation instructions
3.3.1Mounting tool
To install the control panel, all you need is a screwdriver.
8
3.3.2Panel mounting, installation dimensions
Y
X
137.9 mm
5.43”
21 mm
0.83”
150 mm
5.9”
36.1 mm
1.42”
138 mm
5.43“
+1
+0.04
138 mm
5.43“
+1
+0.04
86.5 mm
3.4”
144 mm
5.67”
144 mm
5.67”
Installation
!
Fig. 3: Panel mounting and installation dimensions
• Installation depth: approx. 171 mm (6.73 inch) (incl. terminals and fastening clips)
• Panel cutout: 138
+1
x 138+1 mm (5.43
+0.04
x 5.43
+0.04
inch)
• Panel thickness: 2 to 40 mm (0.08 to 1.57 inch)
• Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30°
downward.
• Securing to DIN 43 834
1.Push the unit through the panel cutout from the front. To avoid heat accumulation, we
recommend keeping a distance of > 15 mm (> 0.59 in) from the walls and other units.
2.Hold the unit level and then hang jack screws in the openings (2 x top, 2 x bottom).
3.Tighten the screws on the jack screws equally with a screwdriver, such that a secure seal to
the control panel is guaranteed.
Note!
A distance of min. 15 mm (0.59 in) between the units has to be observed if aligning the units in the
Y-direction (vertically above one another).
The units can be arranged horizontally beside one another in the X direction without any spacing
between the units.
9
Installation
3.4Mechanical locking
The CompactFlash card can be secured against unauthorized removal using the locking plate
supplied. For this purpose, insert the locking plate into the slit below the handle of the cover plate
(see Fig. 4). Now you can lead-seal or seal the cover plate with a suitable lock.
Fig. 4: Inserting the locking plate
3.5Post-installation check
After installing the control panel, please check the following points:
• Is the unit fixed firmly in the center of the control panel cutout?
• Does the seal run all around the housing collar?
10
4Wiring
4.1Quick wiring guide
Wiring
#
"
!
Warning!
Please note that the entire electrical connection may only take place when the unit is de-energized.
Caution!
• The ground connection must be made before all other connections. Any interruption in the
ground can cause danger.
• Before commissioning, compare the supply voltage with the information specified on the
nameplate (left-hand side of the housing).
• The mixed connection of safety extra-low voltage and dangerous contact voltage to the relay is
not permitted.
• Provide a suitable switch or circuit breaker when installing in a building. This switch must be
installed near to the unit (easily accessible) and be labeled as a separator.
• An overcurrent protective unit (nominal current 10 A) is required for the power cable.
Note!
Please also refer to the terminal diagram on the rear of the unit.
4.1.1Channel color table
When wiring the analog channels, please ensure that the color display on the display for the
individual channels is specified as follows:
3-channel version
Analog 1:BlueAnalog 2:Red
Analog 3:GreenDigital 1:Cyan
Digital 2:RedDigital 3:Green
6-channel version
Analog 1:MagentaAnalog 2:Red
Analog 3:BlackAnalog 4:Green
Analog 5:BlueAnalog 6:Brown
Digital 1:CyanDigital 3:Red
Digital 2:Green
11
Wiring
4.1.2Wiring diagram
12
Fig. 5: Circuit diagram
4.1.3Auxiliary voltage output for 2-wire sensors
5
6
9
1
DI3
93
92
91
GND
RxD/TxD +
RxD/TxD -
Ethernet
RS232
Rel2
41
42
31
32
21
22
111312
L+N-PE
Rel4 Rel3
Rel1
RS485
CH 4CH 5CH 6
611
612
613
614
615
616
411
412
413
414
415
416
CH 1
CH 2
CH 3
111
112
113
114
115
116
211
212
213
214
215
216
311
312
313
314
315
316
511
512
513
514
515
516
_
+
-
Y
+
-
Y
+
+
_
Out: max. 250 mA
On connecting channels 1-4 see
terminal connections CH 5-6
Sensor 1
e.g. TR10 from E+H
Sensor 2
External display
(optional) e.g.
RIA261 from E+H
Wiring
Fig. 6: Using the auxiliary voltage output as power supply for 2-wire sensors (at current measurement range)
13
Wiring
5
6
9
1
GND
RxD/TxD +
RxD/TxD -
Ethernet
RS232
Rel2
41
42
31
32
21
22
111312
L+N-PE
Rel4 Rel3
Rel1
RS485
CH 4CH 5CH 6
611
612
613
614
615
616
411
412
413
414
415
416
CH 1
CH 2
CH 3
111
112
113
114
115
116
211
212
213
214
215
216
311
312
313
314
315
316
511
512
513
514
515
516
DI3
93
92
91
_
+
-
Y
+
+
_
+
-
Y
Out: max.250 mA
On connecting channels 1-4 see
terminal connections CH 5-6
Sensor 1 e.g. TR13 from E+H
Sensor 2
Ext. display
(optional)
e.g. RIA261 from E+H
4.1.4Auxiliary voltage output for 4-wire sensors
"
!
Fig. 7: Using the auxiliary voltage output as power supply for 4-wire sensors (at current measurement range)
4.2Terminal assignment
Caution!
If high-energy transients occur when using long signal cables, we recommend connecting a suitable
overvoltage protection (e.g. E+H HAW560/562).
Use shielded signal lines for serial interfaces!
4.2.1Cable specification, spring terminals
All connections on the rear of the unit are designed as screw or spring terminal blocks with reverse
polarity protection. This makes the connection very quick and easy. The spring terminals are
unlocked with a slotted screwdriver (size 0).
Please note the following when connecting:
• Digital I/O wire cross-section, RS485 and analog inputs: max. 1.5 mm
terminals)
2
• Power wire cross-section: max. 2.5 mm
• Relay wire cross-section: max. 2.5 mm
(13 AWG) (screw terminals)
2
(13 AWG) (spring terminals)
• Stripping length: 10 mm (0.39 in)
Note!
No ferrules have to be used when connecting flexible wires to spring terminals.
2
(14 AWG) (spring
14
Wiring
L+N-PE
CH x
x11
x12
x13
x14
x15
x16
4.2.2Supply voltage
Power supply typeTerminal
100-230 VACL+N-GND
Phase LZero conductor NGround
24 V AC/DCL+N-GND
Phase L or +Zero conductor N or -Ground
4.2.3Analog inputs
The first digit (x) of the three-digit terminal number corresponds to the associated channel (1.. to
6..: channels 1 to 6):
TypeTerminal
x11x12x13x14x15x16
Current(+)(-)
Voltage > 1 V(+)(-)
Voltage 1 V(+)(-)
Resistance
thermometer
RTD (2-wire)
Resistance
thermometer
RTD (3-wire)
Resistance
thermometer
RTD (4-wire)
Thermocouples
TC
(A)(B)
(A)b (sense)(B)
(A)a (sense)b (sense)(B)
(+)(-)
15
Wiring
DI3
93
92
91
41
42
31
32
21
22
111312
Rel4 Rel3
Rel2
Rel1
4.2.4Digital I/O
TypeTerminal
(-)(+)919293
Digital inputDigital input 1Digital input 2Digital input 3
Auxiliary voltage
output, not stabilized,
max. 250 mA
GroundApprox. + 24 V
4.2.5Relay
TypeTerminal
414231322122111312
Alarm
relay 1
Relay 2Switching
Relay 3Switching
contact
Normally
open
contact
2)
(NO)
contact
Normally
open
contact
2)
(NO)
Normally
open
contact
2)
(NO)
Changeover
contact
Normally
closed
contact
1)
(NC)
Relay 4Switching
contact
1) NC = normally closed (breaker)
2) NO = normally open (maker)
16
!
Normally
open
contact
2)
(NO)
Note!
The opening and closing function (= activation or deactivation of the relay coil) in case of a limit
value can be defined in the setup "Setup - Relay"
Wiring
4.2.6"Ethernet" option
Ethernet connection
An IEEE 802.3 compatible connector on a shielded RJ45 plug on the rear side of the unit is available
as a network connection. Through this connection, the unit can be connected with a hub or switch
to units in an office environment. For safe spacing distances, the office equipment standard EN
60950 must be observed. The pin assignment corresponds to a standard MDI interface (AT&T258),
so that a shielded 1:1 cable with a maximum length of 100 meters (328 ft) can be used here. The
Ethernet interface is designed as 10BASE-T. Direct connection to a PC is possible with a crossover
cable. Half duplex and full-duplex data communication is supported.
!
Fig. 8: RJ45 socket (assignment AT&T256)
LED description
Beneath the Ethernet connection (see rear of unit) there are two light emitting diodes which
indicate the status of the Ethernet interface.
• Yellow LED: link signal; is on when the unit is connected to a network. If this LED is not
illuminated then communication is impossible.
• Green LED: Tx/Rx; when the unit is receiving or sending data it flashes irregularly, otherwise is
continuously on.
4.2.7USB connection
USB connection
A compatible USB connection (V1.1, lowspeed 1.5 Mbit/s) is available on a shielded USB-B socket
at the front of the unit. The unit can be connected to a laptop via this connection. The pin
assignment corresponds to a standard USB interface, so that a shielded standard cable with a
maximum length of 3 meters (9.8 ft) can be used here.
Note!
USB2.0 is compatible to USB1.1, i.e. communication is possible.
17
Wiring
4.2.8Option "RS232/RS485 interface"
RS232 connection
A compatible RS232 connection is available on a shielded SUB-D9 socket at the rear of the unit.
This can be used to transmit data or programs or as a modem connection. The pin assignment
corresponds to a standard RS232 interface, so that a shielded 1:1 cable can be used here.
Pin of the SUB-D9 socket
123456789
RS232
assignmen
t
ShieldTxD (data
output)
Fig. 9: RS232 assignment
RS485 connection
A compatible RS485 connection is available on the rear of the unit. This can be used to transmit
data or programs or as a modem connection. Use a shielded cable.
Caution!
"
Only one interface can be used at any one time (RS232 or RS485).
TerminalRS485 assignment:
GND
RxD/TxD +
RxD/TxD -
RxD (data
input)
GND
RxD/TxD +
RxD/TxD -
GND
Caution!
"
Unoccupied connections should be left empty. The RS232/RS485 interfaces
cannot be used simultaneously. Choose the interface to be used under “Extras
- Serial Interface”.
18
4.3Degree of protection
At the front, the unit meets all the requirements of ingress protection IP54.
4.4Post-connection check
After completing the unit's electrical connections, carry out the following checks:
Unit status and specificationsNotes
Is the unit or cable damaged (visual inspection)?-
Electrical connectionNotes
Does the supply voltage match the information on the nameplate?Compare nameplate on
the unit
Are the mounted cables relieved of tension?-
Are all the terminals firmly seated at the contacts?-
Operation
E
5Operation
5.1Quick operating guide
Your new unit has the Operating Instructions built-in. The unit's simple control system enables you
to commission for many applications, practically without any operating instructions. Your unit
displays instructions at the push of a button directly on screen. This description is a supplement to
the Operating Instructions built into the unit. Anything that is not described directly in plain text or
menus is explained here. We reserve the right to make alterations that contribute to technical
progress.
Fig. 10: Variable softkey (e.g. calling up internal Help function in the Setup menu)
19
Operation
5.2Display and operating elements
Fig. 11: Unit display / control units
Operating element (Item No.)Operating function
(Display mode = Signal display)
(Setup menu = Operation in the Setup menu)
1
Z
UT
V
W
F
1aFunction indicator of the softkey
2Slot for CF card
2aKey to eject the CF card
2bLED at CF slot
2cUSB socket
At display mode: Quick return to current time
At Setup menu: ESC key to abort the input and/or quick return to the preceding display.
At display mode: Changes between the various display modes (e.g. bargraph,...)
At Setup menu: Moves the cursor to left or right
At display mode: Rewinds recording (history display - "remove paper")
At Setup menu: Moves the cursor bar upwards, changes parameter / signs
At display mode: Forwards recording to current time ("wind on paper")
At Setup menu: Moves the cursor bar downwards, changes parameter / signs
At display mode: Displays main menu
At Setup menu: ENTER key = Selection of the marked function, start the parameter change
Variable softkey (e.g. calling up internal Help function in the Setup menu)
Caution!
"
Do not actuate if LED (2b) is lit! Risk of data loss!
LED lights up if the unit is reading or writing to the CF card.
20
Operating element (Item No.)Operating function
(Display mode = Signal display)
(Setup menu = Operation in the Setup menu)
3At display mode: Window for measured value display
Displays the current measured values depending on the signal display selected.
Note!
!
If a measuring point has limit value status, the corresponding channel identifier is displayed in red (quick detection of limit
values). When you are operating the unit, measured value acquisition continues to run without interruption.
4At display mode: Displays the current date/time
At Setup menu: Displays the operating item
5At display mode: Indicates what portion of the CF card is already written to (in %)
6At display mode: Functions of the LED displays on the display (as per NAMUR NE44:)
At Setup menu: Displays the operating code
• Green LED lights up: power supply OK, unit working without faults
• Red LED flashes: need for maintenance if unit-external problem occurs (e.g. cable open circuit etc.) or a message /
note to be acknowledged is pending, calibration in progress.
5.3Entering text and numbers
A virtual keyboard is available for entering text and numbers. This is opened automatically if
needed. Here, use the arrow keys to select the letters you need and confirm with the "E" key.
Operation
Fig. 12: Virtual keyboard
5.4Overview of the symbols used
SymbolExplanation
Intermediate statistics
Daily analysis
Monthly analysis
Annual analysis
21
Operation
SymbolExplanation
Total analysis
Measured value
5.5Confirming error messages
Error messages on the display are acknowledged by pressing the "E" key.
5.6Communication; PC software installation
!
!
!
!
Note!
The current PC operating software (CD-ROM supplied) must be installed to be able to establish
communication between the unit and the PC (minimum V1.23.0.0).
5.6.1Installing the provided PC software
Note!
The "Arial Unicode MS™" font must be installed on your PC to operate the provided PC software.
Otherwise certain characters might be displayed incorrectly or not at all. Check this on your PC
under "Control Panel - Fonts". If this font is not installed, please refer to your Microsoft Office
Microsoft Windows
Note!
The provided PC software is only supported by Windows
rights are required!
1.Install the supplied PC software on your computer. The program's Operating Instructions can
be printed out after installation, if required.
2.After the successful installation you can call up the program under "Start - Programs".
®
manual.
®
2000 and Windows® XP. Administrator
®
or
5.6.2Communication via USB / USB driver installation
Once the provided PC operating software has been installed successfully, the unit can be connected
to the PC with a USB cable. The operating system automatically recognizes the new USB unit.
Note!
Proceed as follows to then install the USB driver (depends on operating system):
1.The Windows prompt "Should a connection be established with Windows Update to look for
software?" appears. Click "No, not this time" and then "Next".
22
!
2.The "What do you want the wizard to do?" window appears. Select "Install the software
automatically (Recommended)" and then click "Next".
You can now start the provided PC software to establish communication with the unit.
Note!
In the provided PC software, the USB interface is addressed like a COM port (serial interface). In
the Windows device manager, you can determine the COM port via which the unit can be
addressed. The unit is displayed in the device manager under "Connections (COM and LPT)" as
"ETU00xA (Com x)". The provided PC software supports the COM-ports 1 to 20 (from version
V1.21.2.0), if necessary reduce the allocation accordingly in the Windows equipment manager.
!
2
3
5
2
3
4
5
6
7
8
2
3
5
2
3
4
5
6
7
20
Unit SUB-D 9-pin
modem SUB-D 9-pin
Unit SUB-D 9-pin
modem SUB-D 25-pin
"
Operation
5.6.3Communication via serial interfaces RS232 / RS485
The RS232 serial interface can be accessed from the rear (9-pin Sub-D socket).
Note!
It is not possible to use the RS232 and RS485 interface simultaneously. The desired interface type
must be selected in the setup under "Communication - Serial Interface".
Alternatively to the RS232 interface, the RS485 interface can be accessed from the rear of the unit.
Caution!
When using an RS232/RS485 converter, ensure that it supports automatic changeover between
"sending" and "receiving" (e.g. W+T type 86000).
5.6.4Communication via modem
In principle, any modem with a complete AT command set can be used for data transfer between
your unit with RS232 interface and the supplied PC software.
!
!
Note!
An industrial modem with a watch dog is recommended (e.g. WESTERMO).
Modem at unit
The modem, which is later connected to the unit, must be initialized once with the provided PC
software (Extras - Preparing modem for unit). The modem is, therefore, connected to the PC with
its original cable (1:1 modem calble - normally enclosed with every modem).
Initialization must be carried out with the same data format (baudrate, data bits, parity) with which
the measuring unit works.
After successful initialization, the modem is connected to the unit with a special modem cable.
Only three cables (TxD, RxD, GND), and 2 bridges on modem side are required.
Cable assignment:
Note!
The modem's original cable cannot be used for this because the unit and the modem have the same
pin assignments at the interface plug.
Fig. 13: Modem cable assignment
Modem at PC
The modem, which works from the PC, does not have to be initialized. Connection to the PC is
made with the original modem cable (normally included with the modem).
The first connection to the receiver is made as follows:
• In the provided PC software, select "Display/change unit setup - Add new device"
• Select unit, set interface parameters manually (COM, baudrate, number of data bits, parity)
• Activate modem operation - set up modem
23
Operation
!
• Enter receiver's telephone number.
• OK
• Now enter the telephone number under which the unit connected by modem can be reached and
start the connection with "OK".
Fig. 14: Modem connection at unit and PC
5.6.5Communication via Ethernet (TCP/IP)
In principle, all units equipped with an internal Ethernet interface can be integrated into a PC
network (TCP/IP Ethernet).
The unit(s) can be accessed by any of the PCs in the network using the provided PC software. There
is no need to install driver software ("COM redirection") on the PC because the provided PC
software has direct access to the Ethernet.
The system parameters "IP address", "Subnetmask" and "Gateway" are input directly at the unit.
Changes to the system parameters are not activated until the SETUP menu is closed and the settings
accepted. Only then will the unit work with the new settings.
Note!
It is not possible for several clients (PC) to communicate with a server (unit) at the same time. If a
second client (PC) tries to establish a connection, he receives an error message.
Ethernet commissioning
Before a connection can be established via the PC network, the system parameters in the unit must
be set via "Setup - Communication - Ethernet".
!
!
Note!
You can obtain the system parameters from your relevant network administrator.
The following system parameters must be set:
1.IP address
2.Subnetmask
3.Gateway
Note!
This menu does not appear unless the unit is equipped with an internal Ethernet interface.
24
Operation
5.6.6Communication in the network via the provided PC software
After the unit has been configured and connected to the PC network, a connection to one of the
PCs in the network can be established.
The following steps are required for this:
1.Install the supplied PC software on the PC via which communication is to take place.
(see Section 5.6.1)
2.A new unit now has to be registered in the database. After the unit description has been input,
select how the unit settings are to be transferred. In this case, select Ethernet (TCP/IP).
Fig. 15: Registering a new unit in the PC database
Now enter the IP address. The port address is 8000.
The unit address set at the unit and the release code must also be set correctly here.
Fig. 16: Entering the IP address of the new unit
Confirm the entry with "Continue" and start the transfer with OK.
The connection is now established and the unit is saved in the unit database.
25
Commissioning
6Commissioning
6.1Function check
Make sure that all post-connection checks have been carried out before you put your unit into
operation:
• See Section 3.5 'Post-installation check'
• Checklist in Section 4.4 'Post-connection check'
6.2Switching on the unit
Once the operating voltage is applied, the display lights up and the unit is ready for operation.
• When you first commission the unit, program the set up in accordance with the description in the
Operating Instructions.
• If you are commissioning a unit that is already configured, measuring is immediately started in
accordance with the settings. The values of the display group currently configured appear on the
display.
6.2.1Setting the operating language
The default setting for the operating language is English (GB). A different operating language can be
configured in the set up (see Section 6.4.1).
-> Set up ->Basic settings -> Language
F
Fig. 17: Change the operating language
6.3Unit Set up
6.3.1General
Access to the set up is released when the unit leaves the factory and can be locked in various ways,
e.g. entering a 4-digit release code ( Chap. 6.4.1 "Basic settings").
When locked, basic settings can be checked but not changed.
26
You can also put your unit into service and/or configure it via PC. The following are available for
this:
1.CompactFlash card slot for reading in parameters saved on CompactFlash card.
2.Rear RS232/RS485/Ethernet system interface
3.Front-panel USB system port
Advantages of configuration via PC
• The unit data is saved in a database and can be accessed again at any time.
• Text entries can be carried out more quickly and efficiently by keyboard.
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.