6. Set up the unit (via provided PC software)Page 27
7. Transmit the set up files to the unitPage 27
Brief Operating Instructions
Your new unit has the Operating Instructions built-in. The unit's simple control system enables you
to commission for many applications, practically without any paper. Your unit displays instructions
at the push of a button directly on screen. This description is nevertheless delivered with the unit it is a supplement to the Operating Instructions built into the unit. Anything that is not described
directly at the unit by plain text or menus is explained here.
Fig. 1: Variable softkey (e.g. calling up internal Help function in the Setup menu)
Index
A very extensive index can be found at the end of these Operating Instructions. It acts as a
complement to the table of contents and helps you find special terms and functions.
This unit is designed for the electronic acquisition, display, recording, analysis, remote transmission
and archiving of analog and digital input signals in non-hazardous areas.
• The unit is designed for installation in a panel or a cabinet and may only be operated in an installed
state.
• The manufacturer does not accept liability for damage caused by improper or non-designated use.
The unit can cause danger if used improperly or other than intended.
1.2Installation, commissioning and operation
• The unit may only be installed, connected, commissioned and serviced by qualified and
authorized expert staff (e.g. electrical technicians) strictly adhering to the instructions contained
in this manual, the applicable norms, legal regulations and certificates (depending on the
application).
• These experts must have read and understood this manual and follow the instructions it contains.
• The unit may only be modified or repaired if expressly permitted in the Operating Instructions.
• Damaged units which could pose a source of danger may not be put into operation and must be
marked as defective.
• Primarily observe local regulations regarding opening and repairing electrical units.
#
1.3Operational safety
• The unit is safely built and tested according to state-of-the-art technology and has left the factory
in perfect condition as regards technical safety. The applicable regulations and European standards
have been taken into account.
• Please observe the technical data on the nameplate! The nameplate is on the left-hand side of the
housing.
Desk top version
Warning!
• The mains plug must only be inserted into a socket with grounding contact.
• The protective effect must not be removed by an extension lead without ground wire.
• Relay outputs: U(max) = 30 V eff (AC) / 60 V (DC)
Repairs
Repairs that are not described in these Operating Instructions must only be carried out directly by
the manufacturer or by the service department.
Electromagnetic compatibility
The measuring system meets the general safety requirements of IEC 61010 and the EMC
requirements of IEC 61326.
Technical improvement
The manufacturer reserves the right to adapt technical data to the most up-to-date technical
developments without any special announcement. Ask your supplier for information about activities
and possible extensions to these Operating Instructions.
1.4Return
The following measures must be taken before you return a measuring unit, e.g. for repair or
calibration:
• The unit must be packed in protective packaging. The original packaging offers the best
protection.
5
Page 6
Safety instructions
#
"
!
1.5Notes on safety conventions and icons
Always refer to the safety instructions in these Operating Instructions labeled with the following
symbols:
Warning!
This symbol draws attention to activities or procedures that can lead to injuries to persons, safety
risks or the destruction of the unit if not carried out properly.
Caution!
This symbol draws attention to activities or procedures that can lead to defective operation or to
destruction of the unit if not carried out properly.
Note!
This symbol draws attention to activities or procedures that have an indirect effect on operation, or
can trigger an unforeseen unit reaction if not carried out properly.
ESD - Electrostatic discharge
Protect the terminals against electrostatic discharge. Failure to comply with this instruction can
result in the destruction of parts of the electronics.
6
Page 7
Identification
2Identification
2.1Device designation
2.1.1Nameplate
Compare the nameplate on the left-hand side of the unit with the delivery note and with the
following diagram:
Fig. 2: 1. Order code
2. Serial number
3. Software version
4. Fields for indicating the installed software updates
5. Supply voltage, power frequency, power consumption
6. Ambient temperature range
7. Unit approvals
2.2Scope of delivery
• Unit (with terminals, as per your order)
• 4 fastening clips
• USB cable
• Optional CompactFlash CF card (CF card is enclosed separately.)
• PC operating and configuration software on CD-ROM
• Delivery note
• Multilanguage Brief Operating Instructions as hard copy
• Operating Instructions on CD-ROM
• locking plate
Anything missing? Then please inform your supplier.
2.3Certificates and approvals
An overview of all certificates and approvals can be found in the Technical Data, Section 10.
7
Page 8
Installation
3Installation
3.1Incoming acceptance, transport, storage
3.1.1Incoming acceptance
After receiving the goods, check the following points:
• Is the packaging or the contents damaged?
• Is the delivery complete? Compare the goods delivered with what you ordered.
3.1.2Transport and storage
Observe the following points:
• The unit must be packed in shockproof packaging for storage (and transport). The original
packaging offers the best protection for this.
• The permitted storage temperature is -20 to +60 °C (-4 to 140 °F)
3.2Installation conditions
Working temperature range:
0 to 50 °C (32 to 122 °F), max. 75% rel. humidity without condensation.
Caution!
"
• To avoid heat accumulation, please always ensure that the unit is sufficiently cooled.
• Maintain distance from strong magnetic fields (see Section 10 "Technical data", interference
immunity )
• Environment at front in accordance with unit ingress protection IP 54
3.3Installation instructions
3.3.1Mounting tool
To install the control panel, all you need is a screwdriver.
8
Page 9
3.3.2Panel mounting, installation dimensions
Y
X
137.9 mm
5.43”
21 mm
0.83”
150 mm
5.9”
36.1 mm
1.42”
138 mm
5.43“
+1
+0.04
138 mm
5.43“
+1
+0.04
86.5 mm
3.4”
144 mm
5.67”
144 mm
5.67”
Installation
!
Fig. 3: Panel mounting and installation dimensions
• Installation depth: approx. 171 mm (6.73 inch) (incl. terminals and fastening clips)
• Panel cutout: 138
+1
x 138+1 mm (5.43
+0.04
x 5.43
+0.04
inch)
• Panel thickness: 2 to 40 mm (0.08 to 1.57 inch)
• Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30°
downward.
• Securing to DIN 43 834
1.Push the unit through the panel cutout from the front. To avoid heat accumulation, we
recommend keeping a distance of > 15 mm (> 0.59 in) from the walls and other units.
2.Hold the unit level and then hang jack screws in the openings (2 x top, 2 x bottom).
3.Tighten the screws on the jack screws equally with a screwdriver, such that a secure seal to
the control panel is guaranteed.
Note!
A distance of min. 15 mm (0.59 in) between the units has to be observed if aligning the units in the
Y-direction (vertically above one another).
The units can be arranged horizontally beside one another in the X direction without any spacing
between the units.
9
Page 10
Installation
3.4Mechanical locking
The CompactFlash card can be secured against unauthorized removal using the locking plate
supplied. For this purpose, insert the locking plate into the slit below the handle of the cover plate
(see Fig. 4). Now you can lead-seal or seal the cover plate with a suitable lock.
Fig. 4: Inserting the locking plate
3.5Post-installation check
After installing the control panel, please check the following points:
• Is the unit fixed firmly in the center of the control panel cutout?
• Does the seal run all around the housing collar?
10
Page 11
4Wiring
4.1Quick wiring guide
Wiring
#
"
!
Warning!
Please note that the entire electrical connection may only take place when the unit is de-energized.
Caution!
• The ground connection must be made before all other connections. Any interruption in the
ground can cause danger.
• Before commissioning, compare the supply voltage with the information specified on the
nameplate (left-hand side of the housing).
• The mixed connection of safety extra-low voltage and dangerous contact voltage to the relay is
not permitted.
• Provide a suitable switch or circuit breaker when installing in a building. This switch must be
installed near to the unit (easily accessible) and be labeled as a separator.
• An overcurrent protective unit (nominal current 10 A) is required for the power cable.
Note!
Please also refer to the terminal diagram on the rear of the unit.
4.1.1Channel color table
When wiring the analog channels, please ensure that the color display on the display for the
individual channels is specified as follows:
3-channel version
Analog 1:BlueAnalog 2:Red
Analog 3:GreenDigital 1:Cyan
Digital 2:RedDigital 3:Green
6-channel version
Analog 1:MagentaAnalog 2:Red
Analog 3:BlackAnalog 4:Green
Analog 5:BlueAnalog 6:Brown
Digital 1:CyanDigital 3:Red
Digital 2:Green
11
Page 12
Wiring
4.1.2Wiring diagram
12
Fig. 5: Circuit diagram
Page 13
4.1.3Auxiliary voltage output for 2-wire sensors
5
6
9
1
DI3
93
92
91
GND
RxD/TxD +
RxD/TxD -
Ethernet
RS232
Rel2
41
42
31
32
21
22
111312
L+N-PE
Rel4 Rel3
Rel1
RS485
CH 4CH 5CH 6
611
612
613
614
615
616
411
412
413
414
415
416
CH 1
CH 2
CH 3
111
112
113
114
115
116
211
212
213
214
215
216
311
312
313
314
315
316
511
512
513
514
515
516
_
+
-
Y
+
-
Y
+
+
_
Out: max. 250 mA
On connecting channels 1-4 see
terminal connections CH 5-6
Sensor 1
e.g. TR10 from E+H
Sensor 2
External display
(optional) e.g.
RIA261 from E+H
Wiring
Fig. 6: Using the auxiliary voltage output as power supply for 2-wire sensors (at current measurement range)
13
Page 14
Wiring
5
6
9
1
GND
RxD/TxD +
RxD/TxD -
Ethernet
RS232
Rel2
41
42
31
32
21
22
111312
L+N-PE
Rel4 Rel3
Rel1
RS485
CH 4CH 5CH 6
611
612
613
614
615
616
411
412
413
414
415
416
CH 1
CH 2
CH 3
111
112
113
114
115
116
211
212
213
214
215
216
311
312
313
314
315
316
511
512
513
514
515
516
DI3
93
92
91
_
+
-
Y
+
+
_
+
-
Y
Out: max.250 mA
On connecting channels 1-4 see
terminal connections CH 5-6
Sensor 1 e.g. TR13 from E+H
Sensor 2
Ext. display
(optional)
e.g. RIA261 from E+H
4.1.4Auxiliary voltage output for 4-wire sensors
"
!
Fig. 7: Using the auxiliary voltage output as power supply for 4-wire sensors (at current measurement range)
4.2Terminal assignment
Caution!
If high-energy transients occur when using long signal cables, we recommend connecting a suitable
overvoltage protection (e.g. E+H HAW560/562).
Use shielded signal lines for serial interfaces!
4.2.1Cable specification, spring terminals
All connections on the rear of the unit are designed as screw or spring terminal blocks with reverse
polarity protection. This makes the connection very quick and easy. The spring terminals are
unlocked with a slotted screwdriver (size 0).
Please note the following when connecting:
• Digital I/O wire cross-section, RS485 and analog inputs: max. 1.5 mm
terminals)
2
• Power wire cross-section: max. 2.5 mm
• Relay wire cross-section: max. 2.5 mm
(13 AWG) (screw terminals)
2
(13 AWG) (spring terminals)
• Stripping length: 10 mm (0.39 in)
Note!
No ferrules have to be used when connecting flexible wires to spring terminals.
2
(14 AWG) (spring
14
Page 15
Wiring
L+N-PE
CH x
x11
x12
x13
x14
x15
x16
4.2.2Supply voltage
Power supply typeTerminal
100-230 VACL+N-GND
Phase LZero conductor NGround
24 V AC/DCL+N-GND
Phase L or +Zero conductor N or -Ground
4.2.3Analog inputs
The first digit (x) of the three-digit terminal number corresponds to the associated channel (1.. to
6..: channels 1 to 6):
TypeTerminal
x11x12x13x14x15x16
Current(+)(-)
Voltage > 1 V(+)(-)
Voltage 1 V(+)(-)
Resistance
thermometer
RTD (2-wire)
Resistance
thermometer
RTD (3-wire)
Resistance
thermometer
RTD (4-wire)
Thermocouples
TC
(A)(B)
(A)b (sense)(B)
(A)a (sense)b (sense)(B)
(+)(-)
15
Page 16
Wiring
DI3
93
92
91
41
42
31
32
21
22
111312
Rel4 Rel3
Rel2
Rel1
4.2.4Digital I/O
TypeTerminal
(-)(+)919293
Digital inputDigital input 1Digital input 2Digital input 3
Auxiliary voltage
output, not stabilized,
max. 250 mA
GroundApprox. + 24 V
4.2.5Relay
TypeTerminal
414231322122111312
Alarm
relay 1
Relay 2Switching
Relay 3Switching
contact
Normally
open
contact
2)
(NO)
contact
Normally
open
contact
2)
(NO)
Normally
open
contact
2)
(NO)
Changeover
contact
Normally
closed
contact
1)
(NC)
Relay 4Switching
contact
1) NC = normally closed (breaker)
2) NO = normally open (maker)
16
!
Normally
open
contact
2)
(NO)
Note!
The opening and closing function (= activation or deactivation of the relay coil) in case of a limit
value can be defined in the setup "Setup - Relay"
Page 17
Wiring
4.2.6"Ethernet" option
Ethernet connection
An IEEE 802.3 compatible connector on a shielded RJ45 plug on the rear side of the unit is available
as a network connection. Through this connection, the unit can be connected with a hub or switch
to units in an office environment. For safe spacing distances, the office equipment standard EN
60950 must be observed. The pin assignment corresponds to a standard MDI interface (AT&T258),
so that a shielded 1:1 cable with a maximum length of 100 meters (328 ft) can be used here. The
Ethernet interface is designed as 10BASE-T. Direct connection to a PC is possible with a crossover
cable. Half duplex and full-duplex data communication is supported.
!
Fig. 8: RJ45 socket (assignment AT&T256)
LED description
Beneath the Ethernet connection (see rear of unit) there are two light emitting diodes which
indicate the status of the Ethernet interface.
• Yellow LED: link signal; is on when the unit is connected to a network. If this LED is not
illuminated then communication is impossible.
• Green LED: Tx/Rx; when the unit is receiving or sending data it flashes irregularly, otherwise is
continuously on.
4.2.7USB connection
USB connection
A compatible USB connection (V1.1, lowspeed 1.5 Mbit/s) is available on a shielded USB-B socket
at the front of the unit. The unit can be connected to a laptop via this connection. The pin
assignment corresponds to a standard USB interface, so that a shielded standard cable with a
maximum length of 3 meters (9.8 ft) can be used here.
Note!
USB2.0 is compatible to USB1.1, i.e. communication is possible.
17
Page 18
Wiring
4.2.8Option "RS232/RS485 interface"
RS232 connection
A compatible RS232 connection is available on a shielded SUB-D9 socket at the rear of the unit.
This can be used to transmit data or programs or as a modem connection. The pin assignment
corresponds to a standard RS232 interface, so that a shielded 1:1 cable can be used here.
Pin of the SUB-D9 socket
123456789
RS232
assignmen
t
ShieldTxD (data
output)
Fig. 9: RS232 assignment
RS485 connection
A compatible RS485 connection is available on the rear of the unit. This can be used to transmit
data or programs or as a modem connection. Use a shielded cable.
Caution!
"
Only one interface can be used at any one time (RS232 or RS485).
TerminalRS485 assignment:
GND
RxD/TxD +
RxD/TxD -
RxD (data
input)
GND
RxD/TxD +
RxD/TxD -
GND
Caution!
"
Unoccupied connections should be left empty. The RS232/RS485 interfaces
cannot be used simultaneously. Choose the interface to be used under “Extras
- Serial Interface”.
18
4.3Degree of protection
At the front, the unit meets all the requirements of ingress protection IP54.
4.4Post-connection check
After completing the unit's electrical connections, carry out the following checks:
Unit status and specificationsNotes
Is the unit or cable damaged (visual inspection)?-
Electrical connectionNotes
Does the supply voltage match the information on the nameplate?Compare nameplate on
the unit
Are the mounted cables relieved of tension?-
Are all the terminals firmly seated at the contacts?-
Page 19
Operation
E
5Operation
5.1Quick operating guide
Your new unit has the Operating Instructions built-in. The unit's simple control system enables you
to commission for many applications, practically without any operating instructions. Your unit
displays instructions at the push of a button directly on screen. This description is a supplement to
the Operating Instructions built into the unit. Anything that is not described directly in plain text or
menus is explained here. We reserve the right to make alterations that contribute to technical
progress.
Fig. 10: Variable softkey (e.g. calling up internal Help function in the Setup menu)
19
Page 20
Operation
5.2Display and operating elements
Fig. 11: Unit display / control units
Operating element (Item No.)Operating function
(Display mode = Signal display)
(Setup menu = Operation in the Setup menu)
1
Z
UT
V
W
F
1aFunction indicator of the softkey
2Slot for CF card
2aKey to eject the CF card
2bLED at CF slot
2cUSB socket
At display mode: Quick return to current time
At Setup menu: ESC key to abort the input and/or quick return to the preceding display.
At display mode: Changes between the various display modes (e.g. bargraph,...)
At Setup menu: Moves the cursor to left or right
At display mode: Rewinds recording (history display - "remove paper")
At Setup menu: Moves the cursor bar upwards, changes parameter / signs
At display mode: Forwards recording to current time ("wind on paper")
At Setup menu: Moves the cursor bar downwards, changes parameter / signs
At display mode: Displays main menu
At Setup menu: ENTER key = Selection of the marked function, start the parameter change
Variable softkey (e.g. calling up internal Help function in the Setup menu)
Caution!
"
Do not actuate if LED (2b) is lit! Risk of data loss!
LED lights up if the unit is reading or writing to the CF card.
20
Page 21
Operating element (Item No.)Operating function
(Display mode = Signal display)
(Setup menu = Operation in the Setup menu)
3At display mode: Window for measured value display
Displays the current measured values depending on the signal display selected.
Note!
!
If a measuring point has limit value status, the corresponding channel identifier is displayed in red (quick detection of limit
values). When you are operating the unit, measured value acquisition continues to run without interruption.
4At display mode: Displays the current date/time
At Setup menu: Displays the operating item
5At display mode: Indicates what portion of the CF card is already written to (in %)
6At display mode: Functions of the LED displays on the display (as per NAMUR NE44:)
At Setup menu: Displays the operating code
• Green LED lights up: power supply OK, unit working without faults
• Red LED flashes: need for maintenance if unit-external problem occurs (e.g. cable open circuit etc.) or a message /
note to be acknowledged is pending, calibration in progress.
5.3Entering text and numbers
A virtual keyboard is available for entering text and numbers. This is opened automatically if
needed. Here, use the arrow keys to select the letters you need and confirm with the "E" key.
Operation
Fig. 12: Virtual keyboard
5.4Overview of the symbols used
SymbolExplanation
Intermediate statistics
Daily analysis
Monthly analysis
Annual analysis
21
Page 22
Operation
SymbolExplanation
Total analysis
Measured value
5.5Confirming error messages
Error messages on the display are acknowledged by pressing the "E" key.
5.6Communication; PC software installation
!
!
!
!
Note!
The current PC operating software (CD-ROM supplied) must be installed to be able to establish
communication between the unit and the PC (minimum V1.23.0.0).
5.6.1Installing the provided PC software
Note!
The "Arial Unicode MS™" font must be installed on your PC to operate the provided PC software.
Otherwise certain characters might be displayed incorrectly or not at all. Check this on your PC
under "Control Panel - Fonts". If this font is not installed, please refer to your Microsoft Office
Microsoft Windows
Note!
The provided PC software is only supported by Windows
rights are required!
1.Install the supplied PC software on your computer. The program's Operating Instructions can
be printed out after installation, if required.
2.After the successful installation you can call up the program under "Start - Programs".
®
manual.
®
2000 and Windows® XP. Administrator
®
or
5.6.2Communication via USB / USB driver installation
Once the provided PC operating software has been installed successfully, the unit can be connected
to the PC with a USB cable. The operating system automatically recognizes the new USB unit.
Note!
Proceed as follows to then install the USB driver (depends on operating system):
1.The Windows prompt "Should a connection be established with Windows Update to look for
software?" appears. Click "No, not this time" and then "Next".
22
!
2.The "What do you want the wizard to do?" window appears. Select "Install the software
automatically (Recommended)" and then click "Next".
You can now start the provided PC software to establish communication with the unit.
Note!
In the provided PC software, the USB interface is addressed like a COM port (serial interface). In
the Windows device manager, you can determine the COM port via which the unit can be
addressed. The unit is displayed in the device manager under "Connections (COM and LPT)" as
"ETU00xA (Com x)". The provided PC software supports the COM-ports 1 to 20 (from version
V1.21.2.0), if necessary reduce the allocation accordingly in the Windows equipment manager.
Page 23
!
2
3
5
2
3
4
5
6
7
8
2
3
5
2
3
4
5
6
7
20
Unit SUB-D 9-pin
modem SUB-D 9-pin
Unit SUB-D 9-pin
modem SUB-D 25-pin
"
Operation
5.6.3Communication via serial interfaces RS232 / RS485
The RS232 serial interface can be accessed from the rear (9-pin Sub-D socket).
Note!
It is not possible to use the RS232 and RS485 interface simultaneously. The desired interface type
must be selected in the setup under "Communication - Serial Interface".
Alternatively to the RS232 interface, the RS485 interface can be accessed from the rear of the unit.
Caution!
When using an RS232/RS485 converter, ensure that it supports automatic changeover between
"sending" and "receiving" (e.g. W+T type 86000).
5.6.4Communication via modem
In principle, any modem with a complete AT command set can be used for data transfer between
your unit with RS232 interface and the supplied PC software.
!
!
Note!
An industrial modem with a watch dog is recommended (e.g. WESTERMO).
Modem at unit
The modem, which is later connected to the unit, must be initialized once with the provided PC
software (Extras - Preparing modem for unit). The modem is, therefore, connected to the PC with
its original cable (1:1 modem calble - normally enclosed with every modem).
Initialization must be carried out with the same data format (baudrate, data bits, parity) with which
the measuring unit works.
After successful initialization, the modem is connected to the unit with a special modem cable.
Only three cables (TxD, RxD, GND), and 2 bridges on modem side are required.
Cable assignment:
Note!
The modem's original cable cannot be used for this because the unit and the modem have the same
pin assignments at the interface plug.
Fig. 13: Modem cable assignment
Modem at PC
The modem, which works from the PC, does not have to be initialized. Connection to the PC is
made with the original modem cable (normally included with the modem).
The first connection to the receiver is made as follows:
• In the provided PC software, select "Display/change unit setup - Add new device"
• Select unit, set interface parameters manually (COM, baudrate, number of data bits, parity)
• Activate modem operation - set up modem
23
Page 24
Operation
!
• Enter receiver's telephone number.
• OK
• Now enter the telephone number under which the unit connected by modem can be reached and
start the connection with "OK".
Fig. 14: Modem connection at unit and PC
5.6.5Communication via Ethernet (TCP/IP)
In principle, all units equipped with an internal Ethernet interface can be integrated into a PC
network (TCP/IP Ethernet).
The unit(s) can be accessed by any of the PCs in the network using the provided PC software. There
is no need to install driver software ("COM redirection") on the PC because the provided PC
software has direct access to the Ethernet.
The system parameters "IP address", "Subnetmask" and "Gateway" are input directly at the unit.
Changes to the system parameters are not activated until the SETUP menu is closed and the settings
accepted. Only then will the unit work with the new settings.
Note!
It is not possible for several clients (PC) to communicate with a server (unit) at the same time. If a
second client (PC) tries to establish a connection, he receives an error message.
Ethernet commissioning
Before a connection can be established via the PC network, the system parameters in the unit must
be set via "Setup - Communication - Ethernet".
!
!
Note!
You can obtain the system parameters from your relevant network administrator.
The following system parameters must be set:
1.IP address
2.Subnetmask
3.Gateway
Note!
This menu does not appear unless the unit is equipped with an internal Ethernet interface.
24
Page 25
Operation
5.6.6Communication in the network via the provided PC software
After the unit has been configured and connected to the PC network, a connection to one of the
PCs in the network can be established.
The following steps are required for this:
1.Install the supplied PC software on the PC via which communication is to take place.
(see Section 5.6.1)
2.A new unit now has to be registered in the database. After the unit description has been input,
select how the unit settings are to be transferred. In this case, select Ethernet (TCP/IP).
Fig. 15: Registering a new unit in the PC database
Now enter the IP address. The port address is 8000.
The unit address set at the unit and the release code must also be set correctly here.
Fig. 16: Entering the IP address of the new unit
Confirm the entry with "Continue" and start the transfer with OK.
The connection is now established and the unit is saved in the unit database.
25
Page 26
Commissioning
6Commissioning
6.1Function check
Make sure that all post-connection checks have been carried out before you put your unit into
operation:
• See Section 3.5 'Post-installation check'
• Checklist in Section 4.4 'Post-connection check'
6.2Switching on the unit
Once the operating voltage is applied, the display lights up and the unit is ready for operation.
• When you first commission the unit, program the set up in accordance with the description in the
Operating Instructions.
• If you are commissioning a unit that is already configured, measuring is immediately started in
accordance with the settings. The values of the display group currently configured appear on the
display.
6.2.1Setting the operating language
The default setting for the operating language is English (GB). A different operating language can be
configured in the set up (see Section 6.4.1).
-> Set up ->Basic settings -> Language
F
Fig. 17: Change the operating language
6.3Unit Set up
6.3.1General
Access to the set up is released when the unit leaves the factory and can be locked in various ways,
e.g. entering a 4-digit release code ( Chap. 6.4.1 "Basic settings").
When locked, basic settings can be checked but not changed.
26
You can also put your unit into service and/or configure it via PC. The following are available for
this:
1.CompactFlash card slot for reading in parameters saved on CompactFlash card.
2.Rear RS232/RS485/Ethernet system interface
3.Front-panel USB system port
Advantages of configuration via PC
• The unit data is saved in a database and can be accessed again at any time.
• Text entries can be carried out more quickly and efficiently by keyboard.
Page 27
Commissioning
• Measured values can also be read out, archived and displayed on the PC with the same program.
!
!
Note!
The interfaces cannot be used at the same time for configuration. Select the interface used under
"Set up - Communication".
Note!
To delete the temporary set up files you should delete the CompactFlash CF card and the internal
memory after the commissioning (unit set up).
Delete CF:
Delete internal memory:
memory
Main menu -> CompactFlash (CF) functions -> Delete CF
F
Main menu -> Diagnostic/unit information -> Delete internal
F
6.3.2Set up via interface and provided PC software
Fig. 18: Example: Set up via the provided PC software
Procedure for set up via interface and the provided PC software:
Start
Install the provided PC software on the PC or laptop (see chapter 5.5)
Connect the unit interface (RS232 / RS485, USB or Ethernet) to the PC
Check selected communication settings in the unit (see Section 6.4.4 communication)
Create the new unit in the provided PC software and make interface settings
Once the PC software has identified the unit, the current unit settings are displayed. Now all the parameters can be
Save the settings in the unit database and send to the unit
configured (see the next chapter)
End
27
Page 28
Commissioning
Procedure set up via interface and the provided PC software:
!
!
Note!
In order to be able to use this function, the unit must already be registered in the PC database, and/
or register in the PC database at first.
1.Connect the unit interface (RS232 / RS485, USB or Ethernet) to the PC.
2.Start the provided PC software and add new unit in the PC database:
- Select "Unit -> Display/change unit set-up/add new unit"
- Select "Unit -> Add new unit" in the new window.
- Assign general informations for the new unit. Select the interface for the unit set up. Select
"Continue". Select the appropriate interface parameters (must agree with the attitudes to
communication on the unit). Select "Continue". A summary of the data to the new unit is
indicated. With "OK" a connection to the unit is made and the new unit will be registered in
the PC data base.
3.Adjust the unit settings and select "Finished -> Transmit set-up to unit". The new set up
parameters are automatically transferred to the unit.
4.Finally, the unit settings should be saved in the unit database. Select "Finished -> Store set-up
into unit database".
6.3.3Set up via CompactFlash card
Save the unit settings on the PC onto the CompactFlash card using the provided PC software. This
set up file can be adopted into the unit if released under "Main menu -> CompactFlash (CF)
functions -> Load set-up from CF".
Note!
In order to be able to use this function, the unit must already be registered in the PC database, and/
or register in the PC database at first. In addition a CompactFlash card slot must be present at the
PC.
Procedure set up via CompactFlash card:
1.Copy set up to CompactFlash card:
- Insert a formatted CompactFlash card into the unit.
- In the main menu, select "CompactFlash (CF) functions -> Copy set-up to CF".
- In the main menu, select "CompactFlash (CF) functions -> Safely remove CF".
- Remove the CompactFlash card from the unit and insert it into the CompactFlash card slot
in the PC.
2.Start the provided PC software and add new unit in the PC database:
- Select "Unit -> Display/change unit set-up/add new unit"
- Select "Unit -> Add new unit" in the new window.
- Assign general informations for the new unit. Select "Parameter file from a data source (e.g.
diskette, ATA flash card)". Select "Continue". Select the appropriate parameter file (*.rpd) from
the CompactFlash card. Select "Continue". A summary of the data to the new unit is indicated.
With "OK" the new unit will be registered in the PC data base.
3.Adjust set up in the provided PC software and save in the associated database:
- Adjust the unit settings.
- Select "Finished -> Store set-up into unit data base". The new set up parameters are saved in
the PC database. Transfer the new set up file to the CompactFlash card in your PC: select
"Finished -> Create set-up data carrier (diskette/ATA flash card)" and select the suitable
CompactFlash card slot.
- Remove the CompactFlash card from the slot in the PC and insert it into the unit.
4.Read the new set up into one (or more) unit(s):
- In the main menu, select "CompactFlash (CF) functions -> Load set-up from CF". Repeat this
procedure, to set up further units with this parametrization.
28
Page 29
"
"
!
Commissioning
Caution!
If the set up CompactFlash card is not removed, the measurement data will begin to be saved after
approx. 5 minutes. The set up data is still kept. Please change the CompactFlash card if the
measurement data is not meant to be saved onto this card.
Caution!
Correct and safe functioning is only guaranteed with genuine CompactFlash cards of the
manufacturer (see "Accessories", Section 8).
6.3.4Set up direct at the unit (via unit keyboard)
•Press F. The main menu appears.
•With
• Confirm with
• Use the softkey to call up the Help on the entry selected.
Key function in set up
Cancel entries or return to previous screen.
Z
UT
VW
: Enter key = selects the highlighted function, starts parameter change.
F
Note!
• Every parameter is modified via a dialog box.
• The altered settings only take effect once you return to normal operation by pressing
times (confirm you accept changes with
data.
Procedure for unit configuration/set up:
or W select the desired chapter
V
F
Moves cursor left or right.
Moves bar up or down, changes parameter/sign.
). Until this time, the unit still works with the previous
F
several
Z
Start
Basic settings (language, date/time, save cycle, CompactFlash, etc.)
Signal settings for the analog inputs (signal type, input range, etc.)
Signal settings for the digital inputs (function, designation, etc.)
Signal settings of the set points and alarm relays (if necessary)
Signal settings for the relays (operating mode, description, etc.)
Communication settings (USB/RS232/RS485/Ethernet)
End
29
Page 30
Commissioning
6.4The set up window (at main menu)
Fig. 19: The main menu
Fig. 20: The set up window
The individual parameters are summarized in the set up menu in the following sections:
Basic settings
see Section 6.4.1
Signal settings
see Section 6.4.2
Signal analysis
see Section 6.4.3
Communication
see Section 6.4.4
Service
see Section 6.4.5
Settings that are not channel specific, this means date, time etc.
Settings of the connected analog inputs (incl. set point settings), relays and the digital
input.
Set up, in order to obtain signal analysis for presettable time ranges/cycles as well as a
manual reset of the signal analysis. Function only visible if a digital input has been
activated as a counter!
Set up only required if you are using the USB, RS232, RS485 or Ethernet interface of the
unit (PC operation, serial data read-out, modem operation, etc.).
Settings such as calibration etc.
Caution!
"
Changes must only be made by skilled personnel. The unit will operate incorrectly if
incorrect settings are made!
Input principle:
1.Begin changing parameters each time with
2.Use
3.If the parameter is set correctly, press
or W to scroll through the values, symbols and picklists.
V
F
.
F
.
30
Page 31
Commissioning
!
Note!
• Any settings that are displayed in gray cannot be selected/cannot be changed (only notes, or
option not available/not activated).
• With the factory setting "0000" (delivery status), configuration is possible at any time. It can be
protected against unauthorized manipulation by entering a 4-digit release code. This has to be
entered when the settings are later changed, if the unit settings are to be changed by keyboard.
Tip: Make a note of your release code. Store it somewhere where unauthorized persons do not
have access to it.
• The altered settings only take effect once you return to normal operation by pressing
times and confirming with
. Until this time, the unit still works with the previous data.
F
several
Z
6.4.1Set up - Basic settings
Settings that are not channel specific, this means date, time etc.
Procedure for basic settings:
Start
Assign unit identifier
Select the operating language from the list
Select decimal separator (comma or point)
Select temperature unit (°C, °F, K)
Select the save cycle for saving measured values
Select alarm cycle (= measured value save cycle in event of alarm limit violation)
Set the release code. Factory setting: "0000", i.e. unit setting is possible any time without code.
Make date/time settings (e.g. select region for summer time changeover).
Make settings for external memory (CompactFlash)
Set rear illumination. The "screen saver" increases the operating life of the rear illumination.
End
31
Page 32
Commissioning
Fig. 21: Set up, Basic settings
"Basic settings"
menu items
Unit identifierIndividual unit identifier (max. 22 characters).
Note!
!
Is also saved on the CompactFlash card.
LanguageSelect unit operating language. Factory setting: English (GB)
Decimal separatorSelect in which form the decimal separator character is to be displayed. Picklist: comma, point
Temp. unitsSelection of temperature units. All directly connected thermocouples or resistance thermometers (RTD) are displayed in the preset
engineering units. Picklist: °C, °F, K
Save cycleSelects the cycle for normal operation (= no set point alarm) in which data is stored and displayed
Alarm cycleSelects the cycle for alarm condition (e.g. alarm set point violation) in which data is stored and displayed.
Release codeUsing this code set up access can be protected from unauthorized persons. In order to change any parameter the correct code must
Picklist: off, 1s to 1h, (1min)
Note!
!
Depending upon adjusted save cycle the available recording length changes. Tables to the typical recording length you will find in
the technical data, chapter 10.8.3.
Picklist: off, 1s to 1h, (1min)
be entered. Factory setting: "0", i.e. changes are possible any time.
Tip: Make a note of the code and store in a safe place.
Note!
!
This release code must be also entered in the provided PC software.
Configurable parameters
(Factory settings bold marked)
Set point codeThe unit is protected by a release code. If a set point code has been set up then the user can change the alarm set points after entering
this code or the unit release code (all other operating positions cannot be changed).
Factory default: "0" means that alarm set points can only be changed by entering the release code.
Note!
!
Alarm set point code and release code should not be identical!
32
Page 33
Commissioning
"Basic settings"
menu items
Submenu:
Date/time set-up
Configurable parameters
(Factory settings bold marked)
Here you can find various date and time settings.
Fig. 22: Set up, Basic settings, "Date/time set-up" submenu
Date formatSelect in which format the date is to be set and displayed. (DD.MM.YYY)
Time formatSelect in which format the time is to be set and displayed. Picklist: 12 hours AM/PM or
24 hours
Actual dateSet up the actual date for the unit.
Actual timeSet up the actual time for the unit.
NT/ST changeoverFunction for summer time/normal time changeover.
NT/ST region
only at "NT/ST changeover automatic"
Date NT -> ST
only at "NT/ST changeover manual"
Time NT -> ST
only at "NT/ST changeover manual"
Date ST -> NT
only at "NT/ST changeover manual"
Time ST -> NT
only at "NT/ST changeover manual"
“Automatic”: changes as per the local regional regulations
“Manual”: changeover times can be set in the following addresses
“Off”: no changeover times required
Selects the regional settings for summer/normal time changeover. Picklist: Europe,
USA
Day, when in the spring a change from normal to summer time occurs.
Time when the time is moved forward by 1 hour on the day of the changeover from
normal time to summer time. (Format: hh:mm)
Day, when in the autumn a change from summer to normal time occurs.
Time when the time is moved back by 1 hour on the day of the changeover from
summer time to normal time. (Format: hh:mm)
33
Page 34
Commissioning
E
"Basic settings"
menu items
Submenu:
Display
Configurable parameters
(Factory settings bold marked)
Various general settings for the measured value display, e.g. grid etc.
Fig. 23: Set up, Basic settings, "Display" submenu
Channel ident."Standard, 10 digit"
"With add. channel info.": enables entry of additional 13-character information text per
channel. This means that the channel identifier can be supplemented with, for example
individual tag numbers (e.g.: power station tag systems).
Note!
!
In normal operation, the additional information can be listed along with the 10-digit
channel identifier at "Main Menu -> Signal display -> Measurement point identifier".
Group identifierGroup identifier which is used by the provided PC software. A 10-digit text can be
Grid divisionsIndicates the number of lines ("amplitude grid") that should be displayed on the screen
Soft-keyPlease select the function for the softkey in the measured value display mode. Factory
entered here. Factory setting: Group 1
in the display mode "Curve". Example: display of 0 ... 100%: select 10 divisions, display
0 ... 14pH: select 14 divisions. Picklist: 1 to 20 (10)
Fig. 24: Grid divisions setting: example on left, 10 divisions, example on right, 14
setting: Event list
!
In the set up mode the softkey is always occupied with the integrated Help function!
divisions
Note!
34
Abb. 25: Variable "Soft-key"
Page 35
Commissioning
"Basic settings"
menu items
Submenu:
External memory
(CompactFlash CF)
Configurable parameters
(Factory settings bold marked)
Settings for the external data carrier (CompactFlash CF), amongst other things which data is to be stored in which format on the
external data carrier.
Save as"Protected format": all data is stored in a manipulation protected encrypted format.
This data can only be visualized by using our software package.
"Open format (*.csv)": data is stored in a CSV format, this can be opened by a number
of different programs (e.g. MS Excel). (Attention: no manipulation security). MS Excel
limits the open format on max. 65535 lines.
Memory build-up"Stack memory": no more data can be stored once the data carrier is full.
"Ring memory (FIFO)": once the data carrier is full the oldest data is deleted so that new
data can be stored (first in first out (FIFO). Option only possible for "Protected format".
Separator for CSV
only at "Open format (*.csv)"
Operating time
only at "Open format (*.csv)"
Date/time
only at "Open format (*.csv)"
Warning at
only at "Stack memory"
Switches output
only at "Stack memory"
Specify which separator is used by your application (e.g. in Excel = semicolon). Picklist:
comma, semicolon
Specify the format for which operating times should be saved/displayed. (0000:00:00)
Specify whether the date and the time should be saved in a joint column or in two separate columns when saving the data in CSV format.
Gives warning before the data carrier is x% full. A warning is indicated on the unit and
this is also stored in the event list. A relay can also be switched on. (90%)
When the warning "Data carrier full" is displayed a relay can also be switched on.
Picklist: not used, relay 1 to 4 (Cl. xd-xd)
35
Page 36
Commissioning
"Basic settings"
menu items
Submenu:
Screen saver
Configurable parameters
(Factory settings bold marked)
Note!
!
To increase the life span of the LCDs the rear illumination can be switched off (= screen saver).
If the unit is in an alarm condition (e.g. open circuit or alarm point violation), the screen saver is not switched on or is automatically
switched off. In this way, alarms can be read even if the screen saver is activated.
Fig. 27: Set up, Basic settings, "Screen saver" submenu
Screen saver“Switched off”: LCD is always switched on
“Switch on for x min.”: display goes dark after x minutes. All other functions remain in
operation. Press an operating key: Illumination is switched back on. (x = 10, 30, 60
min.)
“Switched daily”: enter time span. With this setting, the display turns dark 1 minute
after the last key was pressed.
ON daily from
only at "Switched daily"
OFF daily from
only at "Switched daily"
Set time (hh:mm) from which the rear illumination is to be switched off (e.g. shift end
time). (20:00)
Set time (hh:mm) from which the rear illumination is to be switched on (e.g. shift start
time). (07:00)
36
Page 37
Commissioning
6.4.2Setup - Signal Settings
Setup of the analog and digital inputs, mathematics function, set points, relays and display.
Procedure for the signal settings of the analog inputs:
Start
Set signal for analog input (current, voltage, resistance therm., thermocouple)
Set range for analog input (e.g. 0-20 mA for current)
Enter channel identifier
Select plot type
Enter unit/dimension
Enter number of digits after decimal point
Enter measuring range and zoom range
Enter damping/filter (if necessary)
Enter offset for start and end of measuring range
Set fault mode (e.g. in event of cable open circuit)
Do set points have to be defined? Yes
->
No
Select channel display for curve display, bar graph and digital display
End
See Signal Settings -> Set Points
(see Page 46)
37
Page 38
Commissioning
Fig. 28: Setup, Signal Settings
"Signal Settings"
menu items
Submenu: Analog
Inputs, Analog Input x
Configurable parameters
(factory settings are highlighted in bold)
Setup of the connected analog measurement point
View or change settings for the selected channel.
Fig. 29: Setup, Signal Settings,
Analog Inputs submenu, Analog Input x
SignalSelect the type of signal connected (current, voltage, etc.). The channel is switched off
if no signal type is selected (factory default).
Picklist: Switched Off, Current, Voltage, Resistance Therm., Thermocouple or
Mathematics.
38
Setting the mathematics functions:
Channels can be calculated with one another. The mathematics function can be selected
here instead of an analog signal. Here, the user can specify whether an analog signal is
attached or whether a calculation should be performed. Mathematics channels are
treated like "real" analog inputs, e.g. set points, totalizing. If mathematics is selected, an
analog signal can no longer be recorded there. If the device is a 3-channel device, analog
input 4 - 6 can be used as a mathematics channel.
Note!
!
Analog input 1 cannot be selected as a mathematics channel.
RangeSelect the input range or which resistance thermometer/thermocouple is connected.
Connection
Only for "Resistance thermometer"
Channel Ident.Identifier for the measurement point connected to this input (e.g. "Pressure",
The respective terminal layout can be found in the operating manual or on the rear of
the unit.
Specify whether RTDs are connected as 2-, 3- or 4-wire systems. Factory setting: 3-
wire
"Temperature", "Heater", ...). 10-character entry. Factory setting: Analog x
Page 39
Commissioning
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)
Additional Info.
Note!
!
Only available if switched on in the basic
settings.
Plot TypeThe analog inputs are scanned in a 100ms cycle. Depending on the save cycle, the
Engineering UnitInput of the engineering (physical) unit for the measuring point connected to this input
Decimal PointNumber of places after decimal point for the display. Picklist: 0 to 5 number of places
Formula
Only for "Mathematics"
Additional information on channel identifier, e.g. the respective measurement point tag
number (example: tag numbers in power stations). In normal operation, the additional
information can be listed along with the 10-digit channel identifier at "Main Menu ->
Signal display -> Measurement point identifier". 13-character entry.
selected data are determined from the scanned values and saved (e.g. with a save cycle
of 1 min., the average of 600 values (10x60) is calculated and saved).
"Instantaneous Value": the value pending for the save cycle is saved.
"Average": the average value during the save cycle is calculated and saved.
"Minimum Value": the minimum value is calculated and saved.
"Maximum Value": the maximum value is calculated and saved.
"Envelope Curve": both minimum and maximum values are saved (requires higher
memory capacity)
(e.g. %, bar, °C, m/h, etc.). 6–digit entry.
Note!
!
Note: cannot be changed for resistance thermometers and thermocouples!
after the decimal point
f = (y1*a) ? (y2*b) +c: linking two channels;
f = g(y1...y2) * b + c: calculates the average or sum total of two or more channels.
Mathematics channels are treated like "real" analog inputs, (set points etc.).
Function 'g'
Only for "Mathematics"
Signal 'y1'
Only for "Mathematics"
Factor 'a'
Only for "Mathematics"
Math Operator '?'
Only for "Mathematics"
Signal 'y2'
Only for "Mathematics"
Factor 'b'
Only for "Mathematics"
Constant 'c'
Only for "Mathematics"
Range StartTransmitters convert the physical measurement into a standard signal. Example: 0-14
"Sum" or "Average" of channels 'y1' to 'y2'.
Picklist: Not Used, Sum, Average
'y1' signal that should be linked to another signal.
Picklist: Analog Input x
Note!
!
Other mathematics channels can be used for the calculation if their channel number is
smaller than the number of the mathematics channel that is computed.
Factor 'a' by which the value of the 'y1' signal is multiplied.
Factory setting: 1.0
Mathematical operator for combining the channels. To deactivate the second part of the
formula (y2*b), select "Not Used" for the operator.
Picklist: Not Used, - (Subtraction), + (Addition), * (Multiplication), / (Division)
Second signal, "y2", which is to be linked with the first one, "y1".
Picklist: Analog Input x
Factor 'b' by which the 'y2' signal or the function g(y1...y2) is multiplied.
Factory setting: 1.0
'c' constant is added to the result of linking the two signals y1 and y2. Factory setting:
0.0
Entry in the (technical or physical) unit of the mathematics channel.
pH from the sensor is converted to 4-20 mA. Enter the starting point of the
measurement range. A "0" for 0-14 pH.
Note!
!
Note: cannot be changed for resistance thermometers and thermocouples!
39
Page 40
Commissioning
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)
Meas. Range EndThe same as "Range Start". Enter the end value for the measurement range, e.g. "14" for
a 0-14 pH transmitter.
Note!
!
Note: cannot be changed for resistance thermometers and thermocouples!
Zoom StartIf the total transmitter range is not being used then the lower value of the required range
Zoom EndAs in "Zoom Start". Enter the upper value of the required range here. Example:
Damping/ FilterThe more unwanted interference there is on the measurement signal the higher the
Comparison Point
Only for "Thermocouples"
Comparison Temp.
Only for "Comparison Point - External"
Submenu: Meas. Value Correct.
(Offset)
can be entered here (higher resolution). Example: transmitter 0-14 pH, required range:
5-9 pH. Set "5" here. The zoom has no influence on the storage.
transmitter 0-14 pH, required range: 5-9 pH. Enter "9" here.
value that should be entered here. Result: fast changes will be damped/suppressed.
Only used when directly connecting thermocouples.
"Internal": compensation of the voltage errors by measuring the terminal temperature.
"External": compensation of error voltage by using thermostated comparison points.
Settings for the external comparison temperature (only when connecting thermocouples
directly).
Correction value, this can be entered before further evaluation takes place (e.g. in order
to smooth out measurement chain tolerances).
Follow these instructions:
1. Measure the current value at the lower measurement range.
2. Measure the current value at the upper measurement range.
3. Enter the respective target and actual values in the submenu for the lower and
upper correction values.
Lower Correction Value:
Correction value for the lower measurement range. Example of measuring range 0°C to
100°C:
Target Value: enter the target value here (e.g.: 0°C).
Actual Value: enter the value actually measured here (e.g. 0.5°C).
Upper Correction Value:
Correction value for the upper measurement range. Example of measuring range 0°C to
100°C:
Target Value: enter the target value here (e.g.: 100°C).
Actual Value: enter the value actually measured here (e.g. 100.5°C).
40
Page 41
Commissioning
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)
Submenu: Totalization (option)Settings only required if this analog measuring point is to be totalized for calculating the
volume for example. For analysis periods, see "Signal analysis".
Totalization: using the totalization function, the volume in m3 can be calculated from
an analog signal (e.g. flow in m
Totalization Base: select the corresponding time base. Example: ml/s -> time base
seconds (s); m
Total. Eng. Unit: here, enter the unit for the volume determined by totalization (e.g.
3
").
"m
Scroll Display: select the counter which should be displayed alternately with the
instantaneous value. Factory setting: No, Only Instant Value
Low flow cut off: specify how the device should perform low flow cut off:
Area Around Zero Point: all values in the zero point range that are smaller than the
(absolute) "Low flow cut off" are not totalized (e.g. Low flow cut off = 0.1m/h: all values
<= -0.1m/h and >= 0.1m/h are totalized; all other values are discarded).
Absolute Value: all values that are smaller than the configured "Low flow cut off" are not
totalized (e.g. Low flow cut off = 0.1m/h: all values < 0.1 m/h are not totalized).
Low flow cut off: specify the threshold value for the low flow cut off here. Factory
setting: 0 %
3
/h -> time base hours (h).
3
/h). Picklist: no, yes
Calc. Factor: factor for calculating the totalized value (e.g. the transmitter returns l/s
-> totalization base = second -> desired unit is m
setting: 1
Submenu: Fault ModeSettings that lay down how this channel is to react under fault conditions (e.g. cable
open circuit, over range).
Fault Switches: switches the selected relay under fault conditions. The terminal
numbers are shown in brackets. Picklist: Not Used, Relay x (Term. xx-xx)
Save Event: stores an event in the event memory when a fault condition occurs.
Picklist: No, Yes
Cable Open Circ.: The cable open circuit detection function can be switched on and
off here.
In the case of thermocouples: When thermocouples are switched in parallel, enabled
cable open circuit detection causes false alarms. Picklist: no, yes
In the 1 to 5 V range: Values < 0.8 V or > 5.2 V are assessed as cable open circuits.
There is no underrange/overrange. Picklist: no, yes
NAMUR NE43: Switch monitoring of the 4 to 20 mA range as per NAMUR
Recommendation NE43 on and off. The following error ranges apply when NE43 is
switched on:
3.8 mA: underrange (display shows: vvvvvv)
20.5 mA: overrange (display shows: ^^^^^^)
3.6 mA or 21.0 mA: open circuit (display shows: – – – –)
Picklist: On, Off
-> enter 0.001 as the factor). Factory
On Error: Specify the value the unit should continue to use (for calculations) if the
measured value is not valid (e.g. cable open circuit).
Picklist: Last Valid Value, Range Start, Meas. Range End, Value is Invalid, Free
Configuration
Error Value: only if "Free Configuration" is selected for the error.
The unit continues calculating with this value if a fault occurs. Factory setting: 0 %
(See the following table)
Copy SettingsCopies settings from actual channel to selected channel. Picklist: No, in Analog Input x
41
Page 42
Commissioning
Fault mode
Failsafe mode if an
input signal/variable is invalid
(e.g. cable open circuit, invalid result of mathematics calculation; e.g. dividing by zero).
Set failsafe
"Invalid" channelDependent channels
mode
Value is Invalid• "– – – – –" or "******" are
displayed
• Channel name is highlighted in red
• Status "F" is displayed
• Limit value monitoring is suspended
• Totalization is suspended
• A relay is switched if set.
• Analysis: if the error is pending during the entire analysis
period, the value in the analysis is invalid. If there was at least
1 valid value, the result of the analysis is valid.
All other settings• "– – – – –" or "******" are
displayed
• Channel name is highlighted in red
• Status "F" is displayed
• Value is totalized
• A relay is switched if set.
• Analysis: if the error is pending during the entire analysis
period, the value in the analysis is invalid. If there was at least
1 valid value, the result of the analysis is valid.
• "– – – – –" or "******" are
displayed
• Channel name is highlighted in red
• Status "F" is displayed
• Limit value monitoring/totalization:
depends on the set failsafe mode of this channel
• A relay is switched if set.
• Analysis: if the error is pending during the entire analysis
period, the value in the analysis is invalid. If there was at least
1 valid value, the result of the analysis is valid.
• Calculated value is displayed
• Channel name is highlighted in red
• Status "F" is displayed
The channel is treated as "valid", i.e.:
• Value is totalized
• Limit value monitoring remains active
• If the result of the calculation for this channel is invalid, the set
failsafe mode for this channel applies
• Analyses: the channel is analyzed as normal
42
Page 43
Commissioning
Setup - Signal Settings, submenu: Digital Inputs
Procedure for the signal settings of the digital inputs:
1. Start
2. Select the function of the digital channel
3. Control input3. On/off event3. Pulse counter3. Operational time3. Event + operation
time
4. Enter channel
identifier
4. Enter channel
identifier
4. Enter channel
identifier
4. Enter channel
identifier
4. Enter channel
identifier
5. Select action5. Enter event text
for status change
from L->H
5. Enter unit/
dimension
5. Where necessary,
enter current
counter reading to
continue a total/
yearly counter
5. Enter event text
for status change
from L->H
6. End6. Enter event text
for status change
from H->L
6. Select the number
of decimal places
6. Select display for
counter type (e.g.
daily counter)
6. Enter event text
for status change
from H->L
7. End7. Enter pulse factor7. End7. Where necessary,
enter current
counter reading to
continue a total/
yearly counter
8. Where necessary,
enter current
counter reading to
continue a total/
yearly counter
8. Select display for
counter type (e.g.
daily counter)
9. Select display for
counter type (e.g.
daily counter)
9. End
10. End
43
Page 44
Commissioning
"Signal Settings"
menu items
Submenu:
Digital Inputs
Configurable parameters
(factory settings are highlighted in bold)
Setting up only required if the digital inputs (e.g. events) are to be used.
View or change the settings for the selected digital channel.
Fig. 30: Setup, Signal Settings,
"Digital Input 1" submenu
FunctionSelect the required function. Digital inputs are High active; this means the described
effect is achieved by a high input.
Low = -3 to +5 V, High = +12 to +30 V
Note!
!
Depending on the selected function, the unit's user interface adapts itself, so that each
time only parameters that are required for safe unit functioning have to be checked/set.
The following functions are available:
"Switched Off": digital input is not active.
"Control Input": various control functions can be activated using the digital input.
"On/Off Event": switch conditions of connected units (e.g. pump on/off) are displayed
and stored.
"Pulse Counter": pulses are added up and stored as numeric counter values.
"Operational Time": running times of external units are recorded e.g. for maintenance
purposes.
Example: if the d ai ly r unni ng ti me of a pump is to b e save d, ac ti vat e "Op er ati onal T im e"
here and "Daily Analysis" under "Signal Analysis".
"Event+Operation Time":
both the on/off events and the operating time of an external unit are recorded and
stored.
Channel Ident.Measurement point name (e.g. "Pump") or description of the function of this input (e.g.
"Fault message"). 10-character entry.
Factory setting: digital 1
Additional Info.
Note!
!
Only available if switched on in the basic
settings.
Action
Only for "Control Input"
Additional information on channel identifier, e.g. the respective measurement point tag
number (example: tag numbers in power stations). In normal operation, the additional
information can be listed along with the 10-digit channel identifier at "Main Menu ->
Signal display -> Measurement point identifier". 13-character entry.
Set up the function of the control input.
"Start Recording": data are displayed/stored only if the input is active.
"Screensaver On": display is switched off so long as the input is active.
"Ext. Inter. Analysis": starts and ends the external intermediate analysis (the analysis
progresses as long as the input is active).
"Set Up Lock": setup cannot be changed as long as the input is active.
"Time Synchronization": rounds off the current time to a full minute, rounding off to the
higher minute if >= 30s and to the lower minute if <30s.
44
Page 45
Commissioning
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)
Engineering UnitTechnical unit of the count input, e.g. liters, m, etc. Only active for the functions "Pulse
Counter", "Operational Time" and "Event+Operation Time". This value can only be
changed for the "Pulse Counter" function. 6-character entry.
Decimal PointNumber of places after decimal point for the display. Picklist: 0 to 5
number of places after the decimal point. Only active for "Impulse Counter" function.
Factory setting: one (XXXX.X)
1 impulse =Pulse factor = factor which, when multiplied by the input pulse, results in the required
physical value. Example: 1 pulse equals 5 m –> enter "5". Only active for "Pulse
Counter" function. Factory setting: 1.0
Description 'H'Description of the status if the digital input is activated. This text is both shown in the
display and saved to memory. Only active for "On/Off Event" and "Event+Operation
Time" functions. Factory setting: on
Description 'L'Description of the status if the digital input is not activated. This text is both shown in
the display and saved to memory. Only active for "On/Off Event" and "Event+Operation
Time" functions. Factory setting: off
Message Window"Do Not Display": no message is output when the digital input switches.
"Display+Acknowledge": a message window is displayed that has to be acknowledged
by pressing a key.
Only active for "On/Off Event" and "Event+Operation Time" functions.
Save EventDetermines whether the condition change from low to high or high to low is stored in
the event list. Note: increased memory capacity needed.
Only active for "On/Off Event" and "Event+Operation Time" functions.
Picklist: Yes, No
Event Text L->HDescription of condition change from low to high. Event text is stored (e.g. start filling).
22-character entry. Only active for "Event+Operation Time" and "On/Off Event"
functions.
Event Text H->LDescription of condition change from high to low. Event text is stored (e.g. stop filling).
22-character entry. Only active for "Event+Operation Time" and "On/Off Event"
functions.
Total/Year Count.Preset for the totalizer/yearly counter. Useful when continuing a measurement
performed to date with an electromechanical counter. 13-character entry. Only active
for "Pulse Counter", "Operational Time" and "Event+Operation Time" functions.
Factory setting: 0
DisplayCounter values are saved in specific time cycles (e.g. daily, monthly, ... - see "Signal
Copy SettingsCopies settings from actual channel to selected channel.
analysis"). Here you can select the counter type that is to be constantly displayed.
Picklist: Intermediate Counter:, Daily Counter, Monthly Counter, Total/Yearly
Counter. Only available for "Impulse Counter", "Operating Time" and "Events +
Operating Time" functions.
Picklist: No, in Digital Input x
45
Page 46
Commissioning
"Signal Settings"
menu items
Submenu:
Set Points,
Set Point x
Configurable parameters
(factory settings are highlighted in bold)
The measured values can be monitored for alarm set point violation. A relay can be switched or an event message displayed on
violation. Channels can be individually assigned to the set points.
View or change the setup for the selected alarm set point.
Fig. 31: Setup, Signal Settings,
"Set Point, Set Point x" submenu
ChannelSelect the input the alarm set point refers to.
Picklist: Switched Off, Analog Input x, Digital Input x
TypeType of alarm set point (dependent on the input signal):
"Lower Set Point": analog signal drops below the set point.
"Upper Set Point": analog signal exceeds the set point.
"Intermed. Analysis", "Daily Counter", "Monthly Counter", "Total/Yearly Counter":
counter exceeds the set point. Note: the counters are regularly reset to zero. Always
take note of the "Signal Analysis" setup.
Range Start
Only for "Analog Input x" with "Upper
or Lower Set Point"
Meas. Range End
Only for "Analog Input x" with "Upper
or Lower Set Point"
Set PointAnalog set point in the preset engineering unit, e.g. in °C, bar, etc.
Hysteresis Type
Only for "Analog Input x" with "Upper
or Lower Set Point"
Hysteresis (%)
Only for "Percentual" hysteresis type
Hysteresis (abs.)
Only for "Absolute" hysteresis type
Time DelayIn order to be interpreted as an alarm the signal must exceed or undercut the preset
Switches OutputSwitches the respective relay in alarm condition. The terminal numbers are shown in
The lower value of the set measuring range is displayed here.
The upper value of the set measuring range is displayed here.
Counter alarm set point in the engineering units set up, e.g. m, piece, ... .
"Percentual": set hysteresis in %.
"Absolute": enter hysteresis in the preset engineering units (e.g. in °C, bar, etc.)
The alarm condition is only canceled when the signal has changed into the normal
operation range by the preset value. Factory setting: 0 %
The alarm condition is only canceled when the signal has changed into the normal
operation range by the preset value. Factory setting: 0
value by at least the time set up. Factory setting: 0 s
brackets. Please take note of the connection notes found in the operating manual.
Picklist: Not Used, Relay x (Term. xd–xd)
46
Page 47
Commissioning
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)
LV Messages"Display+Acknowledge": message - with date, time, measurement point with alarm set
point or event text LV on/off - must be acknowledged.
Note!
!
The screensaver is
automatically disabled in the event of a limit value message!
"Do Not Display": alarm condition is displayed by measurement point ident. with red
background.
Save EventStores a message in the event memory on limit value violation. Picklist: No, Yes
Event Text LV OnIf the event of a limit value, this text (including date and time) is shown on the display
or stored in the event list. Only available when "LV Messages" is set to "Display +
Acknowledge" or "Save Event" is set to "Yes". 22-character entry.
Event Text LV Off
Only for "Analog Input x" with "Upper
or Lower Set Point"
Save CycleNormal: save in normal save cycle.
When returning from the limit value to normal operation, this text (including date and
time) is shown on the display or stored in the event list. Only available when "LV
Messages" is set to "Display + Acknowledge" or "Save Event" is set to "Yes". 22-character
entry.
"Alarm Cycle":
fast storage during an alarm violation, e.g. every second. Attention: requires higher
memory capacity!
Save cycles are set up in the menu "Basic Settings".
Submenu:
Relay
Copy SettingsCopies the setup of the actual alarm set point into the selected alarm set points.
Picklist: No, In Set Point x
Various relay settings (e.g. operation mode)
Fig. 32: Setup, Signal Settings,
Submenu:
Relay x,
"Relay" submenu
Setup for the selected relay:
"Terminals": shows the relay terminal number
"Operating Mode": relay function in alarm condition:
"Opening": the relay is closed in the rest condition. In the event of a violation it opens.
"Closing": the relay is open in the rest condition. In the event of a violation it closes.
Note!
!
Relay 1 has changeover contacts.
47
Page 48
Commissioning
"Signal Settings"
menu items
Submenu: DisplaySpecify the channels which should be displayed as the instantaneous value (Tip: the fewer the channels assigned, the larger the
device can display the channels). If no channels are assigned, the device assigns the channels automatically.
Note!
!
Note: these settings do not affect measured value storage.
Fig. 33: Setup, Signal Settings,
"Display" submenu
Submenu: Curve displayIf no channels are assigned, the device assigns the channels automatically. Caution: All
Configurable parameters
(factory settings are highlighted in bold)
the channels are always displayed in the curve.
Picklist: channel x: Switched Off, Analog Input x, Digital Input x
Submenu: BargraphSpecify the channels that should be displayed in the bar graph. If no channels are
Submenu: Digital displaySpecify the channels which should be displayed in the digital display. If no channels are
assigned, the device assigns the channels automatically.
Picklist: channel x: Switched Off, Analog Input x, Digital Input x
assigned the device assigns the channels automatically.
Picklist: channel x: Switched Off, Analog Input x, Digital Input x
48
Page 49
!
Commissioning
6.4.3Set up - Signal analysis
Function only visible if a digital input has been activated as a counter, or the option "Integration +
Analysis + Mathematic" is activated!
Set up in order to get signal analysis for a preset time range/cycle as well as the function to manually
reset the signal analysis.
The analyses can be displayed in normal operation at the touch of a button ("Main menu - Analysis").
Note!
Signal analysis means a quantity analysis or an operational time analysis (built-in function) and a
min/max/average value analysis (with option "integration + analysis + mathematic") within the
adjusted period.
This information is also saved (reduces the memory available for the graphics), transferred to a PC
and can be used there for further analyses.
Fig. 34: Set up, Signal analysis
"Signal analysis"
menu items
Intermed analysisCalculates quantities and operating times for the time cycles preset here. Picklist: No, External, 1min,...12h
DayCalculates daily quantities and operation times. Picklist: no (off), yes (on)
MonthCalculates monthly quantities and operation times. Picklist: no (off), yes (on)
Total/year count.Calculates quantities and operation times.
Synchron. timeTime for ending the signal analysis. If, for example, 07:00 is set up then the daily analysis will run from 07:00 of the actual day until
Reset to zeroThe analyzed values can be reset to zero. Example: Reset after commissioning plant. All (installation) signals are deleted. The graphics
"Yes": analysis time cycle is one year.
"No(=Total)": the analysis is continuous from the time of the last reset (useful as a totalizer).
07:00 of the following day. (00:00)
or memory storage are not influenced (traceability)!
Picklist: no, intermed analysis, daily counter, monthly counter, total/yearly counter, all counters.
Note!
!
• All previous (commissioning) signals are discarded.
• If the previous signals are still required, save them on the CompactFlash card before resetting (see Section "Commissioning Accessible functions - CompactFlash card").
• The reset takes effect immediately if you confirm here with "E= Accept".
Configurable parameters
(Factory settings bold marked)
49
Page 50
Commissioning
6.4.4Set up - Communication
Information on the interface used
Set up required if you are using the USB, RS232, RS485 or Ethernet interface of the unit (PC
operation, serial data read-out, modem operation, etc.).
Caution!
"
The various interfaces can be operated in parallel.
Only one of the RS232/RS485 interfaces can be used at any one time.
Fig. 35: Set up, Communication
"Communication"
menu items
Unit addressEach unit using the USB, RS232, RS485 or Ethernet interfaces must have its individual address (0 - 99). Factory setting: 1.
Submenu: Serial
interface
Set up required if you are using the RS232 or RS485 unit interface.
Fig. 36: Set up, Communication, Serial interface
Configurable parameters
(Factory settings bold marked)
50
TypeSelection as to which interface is being used (RS232 or RS485).
BaudrateTransmission speed ("Baudrate") - must be the same as the settings for the provided PC
software. Picklist: 1200 to 115200
Data bitsPlease check that settings are compatible with the PC settings! Fixed settings - cannot
be changed. Default value "8".
ParityPlease check that settings are compatible with the PC settings! Fixed settings - cannot
be changed. Default value "none".
Stop bitsPlease check that settings are compatible with the PC settings! Fixed settings - cannot
be changed. Default value "1".
Page 51
Commissioning
"Communication"
menu items
Submenu: EthernetSet up required if you are using the Ethernet interface of the unit.
Note!
!
Several user cannot access at the same time via provided PC software and Ethernet to the unit.
Fig. 37: Set up, Communication, Ethernet
MAC-AddressMAC address (Fixed settings - cannot be changed). The MAC address (Media Access
IPPlease input the IP-address (given by your network administrator). This IP address is
Configurable parameters
(Factory settings bold marked)
Control) is the hardware address, which identificates the unit in the network.
assigned by your network administrator. Please talk to your network administrator
about this.
The unit is delivered with a preset IP address which must, however, be changed in the
set up procedure. Before you can make the input in the un it, an IP a ddres s valid for your
network must be defined.
Note!
!
The IP address must be unique within the network!
Please be aware that this number is not arbitrary, rather it must be defined dependent
on the network address of the TCP/IP network. The input form corresponds to syntax
(e.g. 192.168.100.002).
PortPlease check that settings are compatible with the PC settings! Fixed settings - cannot
be changed. Port preset at the factory to "8000".
Note!
!
The port "8000" must be opened on the Firewall of the accessing PC, with Web server
function open the port "80" too. Call your system administrator!
SubnetmaskPlease input the subnetmask (given by your network administrator).
The subnetmask must be input if the unit is to establish connections in another subnetwork. Specify the subnetmask of the sub-network in which the unit is located (e.g.
255.255.255.000). Please note: the IP address determines the network class. The result
of this is a default subnetmask (e.g. 255.255.000.000 for a Class B network).
GatewayPlease input the Gateway (given by your network administrator).
Enter the IP address of the gateway here, if connections are to be established in other
networks. Factory setting: 000.000.000.000
Note!
!
Changes to the system parameters are not activated until the set up menu is closed and
the settings accepted. Only then will the unit work with the new settings.
51
Page 52
Commissioning
"Communication"
menu items
Submenu: Web serverSet up for operation of the unit as a web server. Instantaneous values can be read off using an Internet Browser, e.g. MS Internet
Do not enter any leading zeros in the IP address!
With device software version V01.01.00 or higher, it is possible to call up the web server without the "web" parameter in the address
(e.g. http://192.168.100.2). The "http://<IP-Adresse>/web?refresh=x" call-up can be used to specify automatic updating of the
page. (Note: x is the update interval in seconds, e.g. http://10.55.81.109/web?refresh=20)
Fig. 38: Set up, Communication, Web server
Using a web server to remotely monitor process values
The unit is equipped with an integrated web server. This makes it possible for the user to display the instantaneous values in a
standard web browser, such as Internet Explorer or Firefox, on a PC. Maximally 4 user can have access to the unit via Web server
at the same time.
Note!
!
The port "80" must be opened on the Firewall of the accessing PC. Call your system administrator!
A physical web link must be established via LAN or Internet to display the values on the web browser of a PC:
Configurable parameters
(Factory settings bold marked)
Ethernet
Internet PC
Telephone Network
Ethernet
Router
Fig. 39: Remote monitoring with web browser
The desired IP address of the unit must be entered in the address line of the web browser. You find the IP address of the unit under
"Main menu -> Set up -> Communication -> Ethernet". It is necessary to have a fixed IP address!
This function makes it possible to remotely monitor process variables. Access is password-protected. The following parameters must
be configured in the unit:
ActiveSwitch the web server function on or off (= factory default). The instantaneous values
can be displayed by means of the web server using an Internet browser.
Note!
!
Only possible using the Ethernet interface!
Picklist: no (off), yes (on)
Router
52
Page 53
6.4.5Setup - Service
Service setup.
Caution!
"
Changes must only be made by skilled personnel. The unit will operate incorrectly if incorrect
settings are made!
Fig. 40: Setup, Service, Preset
Commissioning
"Service" menu
items
Operating Mode"Normal Operation": unit plots the signals from the connected measuring points.
"Simulation": instead of operating with the real measuring points connected, the signals are simulated (using the actual settings).
Note!
!
If required, use the "Signal Analysis- Reset to Zero" function, so that the values of the simulated signals do not corrupt your true
minima/maxima/quantities after switching back to normal operation. If the previous signals are still required, save them on the
CompactFlash card beforehand (see Section 7 "Commissioning - Accessible functions - CompactFlash card functions").
PRESET
Screen Saver"Off on Alarm": the screensaver is automatically deactivated in an alarm condition (e.g. limit value, cable open circuit, etc.).
Submenu: Reset to
Zero
Caution!
"
Returns all parameters to the factory default setup! The internal memory contents is deleted!
Picklist: No, Yes
Note!
!
Can only be changed using the service code.
"Always On": the screensaver remains switched on even in the event of an alarm.
Note!
!
Active messages that have to be acknowledged always deactivate the screensaver.
Service setup.
Caution!
"
Changes must only be made by skilled personnel. The unit will operate incorrectly if incorrect settings are made!
Note!
!
Can only be changed using the service code.
Configurable parameters
(factory settings are highlighted in bold)
Submenu:
Analog Input x
"Unit Running Time:"Resets the unit operating time to 0 hours. Picklist: No, Yes
"LCD Running Time:"Resets the LCD operating time to 0 hours. Picklist: No, Yes
"Correction RWT": rear wall temperature correction value for this analog input (only required for thermocouples).
Factory setting: -1.0 °C
Note!
!
Can only be changed using the service code.
53
Page 54
Commissioning
!
6.5The main menu
Press the F key to call up the main menu:
Abb. 41: Main menu
6.5.1Main menu - Signal display
Changes the display mode, e.g. curve display, bar graph, digital display or event list. The various
display modes have no influence on the signal recording.
Note!
You can change between the various display modes using
and T .
U
54
Fig. 42: Main menu, Signal display
Page 55
Commissioning
"Signal display" menu
Description
items
Using total screenAll channels are displayed over the total width. Maximum resolution in upscale direction.
Fig. 43: "Using total screen" signal display
Split zonesEach channel is displayed in its own chart zone. Accuracy of the plot is not influenced in this display mode.
Fig. 44: "Split zones" signal display
Bar graphDisplay of the active analog measured values as bar graphs including values. The digital input is displayed as a status or
counter/operating time counter.
Fig. 45: "Bar graph" signal display
55
Page 56
Commissioning
"Signal display" menu
Description
items
Digital displayDisplay of the active analog measured values as digital values. The digital input is displayed as a status or counter/
operating time counter.
Fig. 46: "Digital display" signal display
EventsEvents such as alarm set point infringement and power failure are listed in the correct time sequence.
Fig. 47: "Events" signal display
Measurement point identifierListing of the 10-character channel identifier together with additional 13-character information text (e.g. additional
measurement tag numbers, identification system in power stations etc.).
Note!
!
Only visible if "With add. channel info" is selected under "Set up - Basic settings - Display - Channel ident.".
Fig. 48: "Measurement point identifier" signal display
56
Page 57
Commissioning
6.5.2Main menu - Signal analysis
Function only visible if a digital input was activated as a counter or the option "Integration +
Analysis" is activated and signal analysis is activated in the set up!
As an option, it is also possible to perform signal analysis for analog inputs (option "Integration +
Analysis" with activated integration for analog inputs).
Display of the last 7 intermediate, daily, monthly, yearly analyses (so long as they are available).
The digital input is displayed as the respective counter or operating time counter.
When using analog inputs, the min. value, max. value, average value and, if applicable, the
integrated meter reading are output ("Integration + Analysis" option).
Fig. 49: Main menu, "Signal analysis"
Once an analysis is selected, it appears on the display.
6.5.3Main menu - Search in trace
Search for events or times in the internal memory.
Fig. 50: Main menu, "Search in trace"
"Search in trace" menu
items
Search criteriaYou can search for a specific time or event in the memory.
When searching for a "time" the graphic display shows from this time.
When searching for an "event" the ones found are displayed as a list.
Date
only at search criteria "time"
Time
only at search criteria "time"
Enter the required date. Factory setting: actual date
Enter the required time. Factory setting: actual time
Description
(Factory setting bold marked)
57
Page 58
Commissioning
"Search in trace" menu
items
Search filterFor a better overview a search can be conducted looking for specific events (e.g. only set up changes). In the standard
all events are shown. Function only possible for search criterion "Search for events".
Picklist: All events, Alarm limit violation, On/off events, Setup change, Power on/off, Service, CompactFlash card
Time spanSelect the times where the events are to be searched for. Function only possible for search criterion "Search for events".
Picklist: the last 12 hours, the last 24 hours, this week, this month, 3 month back, total memory
Start searchStart search with set up parameters
Description
(Factory setting bold marked)
The search results appear on the display shortly after the search is started. You can use the arrow
keys
display
to scroll through the search results. Press the ESC key to return to the current value
V W
.
Z
Fig. 51: Main menu, "Search in trace" - search results
Fig. 52: Main menu, "Search in trace" - event list
6.5.4Main menu - CompactFlash (CF) functions
Functions for measured data storage and unit set up onto the CompactFlash card. The following
functions are possible:
58
Page 59
Commissioning
"CompactFlash (CF)
functions" menu items
Safely remove CFIn order to ensure safe removal of the CompactFlash card all internal access is ended. You will receive a message when
the card can be safely removed.
Note!
!
Remove the card within 5 minutes otherwise the unit will start to automatically store data onto the card again. Only
remove the card using this function otherwise data can be lost!
Update CFData that has not been transferred to the CompactFlash card is now stored.
Complete memory to CFThe content of the internal memory is completely copied to the CompactFlash card. Please be patient! Measured value
recording continues in parallel and has the highest priority.
Copy set up to CFAll unit parameters (set up) are copied to the CompactFlash card. They can be archived and used for other units. The
file has the extension .rpd.
Load set up from CFLoads unit parameters (set up) from the Compact Flash card into the internal nonvolatile memory of the unit. The file
Delete CFDeletes all data on the CompactFlash card.
!
has the extension .rpd.
Note!
!
If a release code has been set up then the CompactFlash card can only be deleted after this code has been entered.
Without affecting the internal memory, data packages are copied block-by-block to the CF card.
Tests are also made to determine whether the data has been written onto the data carrier without
any errors. The same happens when storing the data on the PC with the associated PC software.
Note!
• Before removing the CompactFlash card, select "CompactFlash card functions/Update CF". The
current data block is closed and saved to CompactFlash. This ensures that all current data (until
the last save) is included on the CF card.
• You are informed before the CF card is 100 % full. This is achieved by an acknowledgeable
message in the display, which indicates that the CF card described needs changing (only for "Stack
memory" ext. save mode, not for "Ring memory FIFO". ) In addition, a relay can be switched.
• Your unit knows which data has already been copied onto the CF card. Should you ever forget to
change it in time (or if there is no CF card inserted), the new CF card is filled with the missing
data from the internal memory - in as far as it is still available there.
• Since measured value acquisition/registration has highest priority, it can take some minutes until
the contents of the internal memory is copied onto the CF card.
• If the CF card is being accessed, the LED lights up. During this process, the CF card must not be
removed.
Description
6.5.5Main menu - Set up
Here you can trim your new unit to optimum operation, all possible operating parameters are
accessible (see see Section 6.4).
6.5.6Main menu - Set contrast
You can set the viewing angle upwards or downwards to an optimum contrast depending on the
installation height.
6.5.7Main menu - Diagnostic/unit information
Unit information and service functions for a swift unit check. The following functions are possible:
59
Page 60
Commissioning
Fig. 53: Main menu, "Diagnostic/unit information"
"Diagnostic/unit
Description
information" menu items
Unit informationDisplay of important unit and memory information, such as program name and software version. In addition, the
memory time available is also displayed.
This time is reduced if
CalibrationCalibration must only be carried out by skilled and trained personnel.
Caution!
"
Malfunctions possible if not performed correctly!
Normal trending is interrupted for the complete time that this function is operational. This is also identified in the event
list.
Note!
!
Protection via a service code to prevent unintentional release.
ProtocolsBoot log: Only for service purposes
Error log: Only for service purposes
Note!
!
Protection via a service code to prevent unintentional release.
Delete internal memory
Caution!
"
Completely deletes the measured values with all analyses recorded in the internal memory. The total counter remains.
Note!
!
The CompactFlash card is not deleted. When the release code (password) is set in the unit, then you will need to enter it.
60
Page 61
6.6Saving measured values
Fig. 55: Schematic display of measured value saving
Commissioning
!
6.6.1Internal memory
Measured value saving shows signal changes and provides access to processes which took place long
ago. They are stored (nonvolatile) in a Flash memory which is secure on power failure. This large
internal memory works as a ring memory. If it is full, the oldest data is overwritten (FIFO - first in/
first out principle). As a result, the current data is always available.
6.6.2Scrolling through measured values
In running operation, you can scroll through the saved measured values in curve display. Use the
arrow keys ( V W ) to move backwards or forwards. Press the ESC key
value display.
to return to the current
Z
6.6.3How the CompactFlash card works
Without affecting the internal memory, data packages are copied block-by-block to the
CompactFlash card. Tests are also made to determine whether the data has been written onto the
CompactFlash without any errors. The same happens when storing the data on the PC with the PC
software contained in the scope of delivery. The data, monitored against manipulation, is available
here. If you wish, you can export this data into other programs, such as MS Excel
the protected data basis.
Note!
• Only use new, formatted CompactFlash cards recommended by the manufacturer (see
"Accessories", Section 8). Any data on the CompactFlash card is overwritten once the card is
inserted into the slot.
• The CompactFlash memory being written to is shown in normal operation at the top right of the
display ("CF: xx %")
• Dashes "-" on this display mean that no CompactFlash is inserted.
• Before removing the CompactFlash card, select "CompactFlash card functions/Update CF". The
current data block is closed and saved to CompactFlash. This ensures that all current data (until
the last save) is included on it.
®
, without losing
61
Page 62
Commissioning
• Depending on the configuration of your unit (see "Set up/Basic settings/External memory/
Warning at"), an acknowledgeable message on the display informs you that the CompactFlash
being written to needs to be changed before the CompactFlash is 100 % full.
• Your unit knows which data has already been copied onto the CompactFlash. Should you ever
forget to change the CompactFlash in time (or if there is no CompactFlash inserted), the new
CompactFlash is filled with the missing data from the internal memory - in as far as it is still
available there. Since measured value acquisition/registration has highest priority, it can take
several minutes until the data is copied from the internal memory to CompactFlash.
6.7Important functions of the provided PC software
!
Note!
The current PC software must be installed on a PC (for installation instructions, see description on
CD-ROM or chapter 5.5 in this manual).
6.7.1Data transfer to the provided PC software
CompactFlash
*.csv
Fig. 56: Data transfer to the provided PC software
Data can be transferred to the installed PC software in one of the following ways:
• Using USB, RS232/485 or Ethernet. Communication and download of data to PC using the
function "Read out -> Read measured values using interface/Modem".
• Save the data to CompactFlash in the unit using the function "Main menu -> CompactFlash (CF)
functions -> Update CF".
Now insert the CF card into the PC and read the data using the function "Read out -> Read out
measured values using PC card drive".
62
• Read out the CompactFlash CF card with the provided PC software:
In principle the values can be read out directly from the CompactFlash CF card. The connection
to the unit is made by RS232/RS485, Ethernet or USB. Start the provided PC software. Select
"Read out -> Read out memory card by interface/modem". Select the appropriate unit from the
PC data base. Select "Unit -> open unit(s)". The connection is developed. Select the appropriate
file on the CompactFlash CF card and confirm with "OK". The measured values are read out. The
measured values remain on the CompactFlash CF card.
Page 63
Commissioning
6.7.2Offline data check, analysis and printout
The data saved offline or downloaded to the PC (using one of the methods described above), can be
viewed in the provided PC software using the function "Display -> Display measured values from
data base".
All data received can be viewed as trend graphics and in tabular form and printed out (see
corresponding print function in the main menu of the provided PC software). A detailed description
of the functions can be found on the CD-ROM of the provided PC software.
Fig. 57: Data analysis at PC
!
6.7.3Viewing data in a spreadsheet (e.g. MS-Excel®)
Fig. 58: Data analysis in spreadsheet
Select "open format (*.csv)" (comma separated values) as the save mode in the unit under "Set up > Basic settings -> External memory -> Save as", to be able to open saved data directly in the
spreadsheet for analysis and printout.
Note!
To open the data directly in MS-Excel
"Set up -> Basic settings -> External memoy -> Separator for CSV". MS-Excel limits the open format
(*.csv) to max. 65535 lines.
Alternatively, the data can be exported to *.xls, *.csv or *.txt format in the provided PC software
under "Extras -> Export measured values".
®
, select the semicolon ";" as the separator in the unit under
63
Page 64
Maintenance
7Maintenance
The unit is maintenance-free.
7.1Software update via the provided PC software
Caution!
"
When the program is updated, all measurement data in the memory is deleted. If the measured
values saved in the unit are still required, they should first be read out or the CompactFlash card
should be updated and removed from the unit. After the program transfer, all unit settings are reset
to the factory settings.
Procedure:
1.Start the supplied PC software
2.Connect the unit via USB to the PC (update only possible via USB connection!)
3.Select "Extras -> Special unit functions -> (select the unit) -> Transmit program"
4.Select interface parameters (Com-Port)
5.Select desired program file (*.prg) and confirm with OK.
!
7.2Instruction for releasing a software option e.g.
"Integration + Analysis + Maths"
Note!
• You need the provided PC software (at least version 1.23.0 or higher) for releasing a software
option.
• The firmware of the unit must be at least version 2.00.00 or higher. Is this not the case, please
contact the manufacturer.
• Please hold the release code, which you have received from the manufacturer, ready (see delivery
order).
• It is necessary to read out the unit parameters before beginning. The unit's settings must be stored
in the PC software database.
• Please make sure, that the unit is connected with a communication cable. The communication
port must be the same as used for the settings´ readout before (e.g. USB).
Procedure:
1.Start the supplied PC software
2.Select menu item "Extras -> Service -> Release options"
3.You will see a list of units stored in the PC database. Select the relevant unit.
4.Please enter the release code, which you have received from the manufacturer (see delivery
order), into the appearing pop-up window. Start the transmission of the release code with a
click on the button "OK".
5.If the transmission was successful a message on the provided PC software will appear. The unit
will reboot. A relevant message will be saved in the event list, indicating the successful option
release.
64
6.A new read out of the unit parameters is necessary.
The released option is now useable.
Page 65
8Accessories
320 mm (12.6“)
320 mm (12.6“)
254 mm (10“)
Accessories
!
Note!
If ordering accessories, please specify the serial number of the unit!
8.1Accessory parts
The following accessories are available:
Order codeAccessory
50078843Terminal, pluggable, 3-pole, for power supply
51009211Terminal, pluggable, 6-pole, for analog input
51009214Terminal, pluggable, 3-pole, for relay
51009215Terminal, pluggable, 6-pole, for relay
71062537Terminal, pluggable, 5-pole, for digital I/O
71043991CompactFlash (CF) memory card 128 MB
51009640CompactFlash (CF) memory card 256 MB
71007465Cable USB-A - USB-B, 2 m (6.56 ft)
RXU10-A1Cable set for connection PC or modem
RSG30A-H1Field housing IP65
65
Page 66
Troubleshooting
9Troubleshooting
9.1Diagnostic/unit information
Unit information and service functions for a swift unit check. The following functions are possible:
Fig. 59: Main menu, "Diagnostic/unit information"
"Diagnostic/unit
Description
information" menu items
Unit informationDisplay of important unit and memory information, such as program name and software version. In addition, the
memory time available is also displayed.
This time is reduced if
CalibrationCalibration must only be carried out by skilled and trained personnel.
Caution!
"
Malfunctions possible if not performed correctly!
Normal trending is interrupted for the complete time that this function is operational. This is also identified in the event
list.
Note!
!
Protection via a service code to prevent unintentional release.
ProtocolsBoot log: Only for service purposes
Error log: Only for service purposes
Note!
!
Protection via a service code to prevent unintentional release.
66
Page 67
Troubleshooting
"Diagnostic/unit
Description
information" menu items
Delete internal memory
Caution!
"
Completely deletes the measured values with all analyses recorded in the internal memory. The total counter remains.
Note!
!
The CompactFlash card is not deleted. When the release code (password) is set in the unit, then you will need to enter it.
9.2Troubleshooting instructions
Problem:Cause:Remedy:
Display does not functionScreen saver is activePress a key. Check settings for screen saver in the setup.
No LED lights up on CF drive or rear of unit (Ethernet)
=> no power supply
No LED lights up on CF drive or rear of unit (Ethernet)
=> power supply faulty
LED lights up on CF drive or rear of unit (Ethernet) =>
display faulty
LED lights up on rear of unit (Ethernet) => CPU faulty
Please check the power supply and the power supply.
Please replace the power supply or call the service
department of the supplier!
Please replace the display or call the service department of
the supplier!
Please replace the CPU or call the service department of the
supplier!
CompactFlash slot or LED not
working
No data on the CompactFlash
card
Setup is lockedSetup lock active, i.e. the setup is only released with a
Relay does not functionIncorrect connection
RS232/RS485, Ethernet interface
not working
CPU defectivePlease replace the CPU or call the service department of the
Setup change
Software update / upgrade
CF card defective
CPU defective
digital signal
Incorrect configuration
Power supply defective
Cable defective
Incorrect connection assignment
Incorrect unit address
Incorrect interface parameters
Communication card defective
supplier!
Save the data onto a data carrier before any changes to the
setup.
Save measured values onto a data carrier before any changes
to the software.
Replace the CF card, use genuine cards from the
manufacturer! (Accessories, see Section 8)
Please replace the CPU or call the service department of the
supplier!
Create a digital signal to remove setup lock.
Please check the connection and the relay circuit.
Please check the relay configuration.
Replace the power supply card or call the service
department of the supplier!
Replace cable (Accessories, see Section 8)
Please use original cable
Check and set correctly.
Check and set correctly.
Replace communication card
Modem connection not workingModem not installed on unit
Incorrect or faulty connecting cable
Initialize modem via provided PC software
Replace cable (Accessories, see Section 8)
67
Page 68
Troubleshooting
Problem:Cause:Remedy:
Digital input does not functionIncorrect connection
Incorrect configuration
Power supply defective
Analog input shows "- - - -"
This means cable open circuit
Analog input shows "*******"
This means the measured value is
invalid
Analog input shows "^^^^^^^"
This means overranging
Analog input shows "vvvvvv"
This means underranging
The signal lines are incorrectly connected or not
connected.
The input signal does not correspond to the configured
signal.
The sensor is defective.
9.3System error messages
Your unit informs you of faults or incorrect entries using plain text on the screen.
Please check the connection and the digital input circuit.
Please check the digital input configuration.
Replace the power supply card or call the service
department of the supplier!
Please check the connections.
Please check the input signal and the configuration.
Please check the input signal and replace the sensor.
!
9.4Spare parts
Note!
If ordering spare parts, please specify the serial number of the unit!
Installation instructions are included with the spare part.
9.4.3Spare parts structure for the CPU with software
Pos.Order No.Description
HRSG30X1-...CPU board with software, USB interface and CompactFlash socket
Operating language package
A
B
C
D
E
F
G
Standard (German, English)
Central/western Europe (German, English, French, Spanish, Italian, Dutch)
Northern Europe (German, English, Danish, Swedish)
Eastern Europe (German, English, Polish, Russian, Czech, Slovak)
America (German, English, French, Spanish, American, Portuguese)
Japan (German, English, Japanese)
China (German, English, Chinese)
A
A
C
A
B
Internal memory
2 MB
Software
Standard
Integration (totalizer) + analysis + mathematic
Model
Standard
Standard North American Region
9.4.4Spare parts structure for unit software options
Pos.Order No.Description
RSG30A1-0CASoftware options
0Release code on delivery note + PC operating software on CD-ROM
Software
C
A
Option integration (totalizer) + analysis + mathematic; needed information: serial number! (Option possible from
unit software version 2.00.00)
Operation language
All languages (possible for all languages)
70
!
!
Note!
Installation instructions see chapter 7 "Maintenance".
9.5Return
The unit must be packed in protective packaging for later reuse or in case of repair. The original
packaging offers the best protection. Repairs must only by carried out by your supplier's service
organization or by skilled personnel.
Note!
When sending for repair, please enclose a note with a description of the error and the application.
01.00.00 / 06.2005Original softwareV1.18.0.0 and higherBA194R/09/06.05
01.00.08 / 08.2005Software revisionV1.18.2.0 and higherBA194R/09/08.05
01.00.13 / 10.2005Software revisionV1.19.0.0 and higherBA194R/09/10.05
01.01.00 / 02.2006Software revisionV1.20.0.0 and higherBA194R/09/02.06
01.02.00 / 10.2006Software revisionV1.21.2.0 and higherBA194R/09/11.06
02.00.00 / 11.2007Software revision: Mathematic function
included; 3 digital inputs
02.01.00 / 03.2008Software revision: 1...5 V analog inputV1.23.2.0 and higherBA194R/09/03.08
02.02.01 / 05.2008New RTD inputs Pt46 and Cu53V1.24.0.0 and higherBA194R/09/06.08
02.02.08 / 04.2010Texts modified; Bug fixingV1.27.0.0 and higherBA194R/09/13.10
V1.23.0.0 and higherBA194R/09/10.07
71
Page 72
Technical data
10Technical data
10.1Input
10.1.1Analog multi-function input channel 1-6
Measured variable, measuring
range
Measured
variable
Current0...20 mA
0...5 mA
4...20 mA
Overrange: up to 22 mA
Voltage > 1 V0...10 V
0...5 V
1...5 V
± 10 V
± 30 V
Voltage 1 V0...1 V
± 1 V
± 150 mV
Resistance
thermometer
(RTD)
Pt100: -200 to 850 °C (-328 to 1562 °F) (IEC751, JIS1604, GOST)
Pt500: -200 to 850 °C (-328 to 1562 °F) (IEC751, JIS1604)
Pt1000: -200 to 600 °C (-328 to 1112 °F) (IEC751, JIS1604)
Cu100: -200 to 200 °C (-328 to 392 °F) (GOST)
Cu50: -200 to 200 °C (-328 to 392 °F) (GOST)
Pt50: -200 to 850 °C (-328 to 1562 °F) (GOST)
To IEC 60873-1:
An additional display error of -/+ 1 digit is permitted for every measured value.
Measuring ranges which can be selected per channel:
Cu53: -50 to 180 °C (-58 to 356 °F) (GOST)
Pt46: -200 to 650 °C (-328 to 1202 °F) (GOST)
Type J (Fe-CuNi): -210 to 999.9 °C (-346 to 1832 °F) (IEC581-1)
Type K (NiCr-Ni): -200 to 1372 °C (-328 to 2501.6 °F) (IEC581-1)
Type T (Cu-CuNi): -270 to 400 °C (-454 to 752 °F) (IEC581-1)
Type N (NiCrSi-NiSi): -270 to 1300 °C (-454 to 2372 °F) (IEC581-1)
Type L (Fe-CuNi): -200 to 900 °C (-328 to 1652 °F) (DIN43710,
GOST)
Type D (W3Re-W25Re): 0 to 2315 °C (32 to 4199 °F) (ASTME998)
Type C (W5Re-W26Re): 0 to 2315 °C (32 to 4199 °F) (ASTME998)
Type B (Pt30Rh-Pt6Rh): 0 to 1820 °C (32 to 3308 °F) (IEC581-1)
Type S (Pt10Rh-Pt): 0 to 1768 °C (32 to 3214 °F) (IEC581-1)
Type R (Pt13Rh-Pt): -50 to 1768 °C (-58 to 3214 °F) (IEC581-1)
± 0.10 % oMR from -100 °C (-148 °F)
± 0.10 % oMR from -130 °C (-202 °F)
± 0.10 % oMR from -200 °C (-328 °F)
± 0.10 % oMR from -100 °C (-148 °F)
± 0.10 % oMR from -100 °C (-148 °F)
± 0.15 % oMR from 500 °C (932 °F)
± 0.15 % oMR from 500 °C (932 °F)
± 0.15 % oMR from 600 °C (1112 °F)
± 0.15 % oMR from 100 °C (212 °F)
± 0.15 % oMR from 100 °C (212 °F)
( 2.7 MOhm
( 2.7 MOhm
Limit valuesLimit values for input voltage and current as well as cable open circuit detection/line influence/
temperature compensation
72
Page 73
Technical data
Measured
variable
CurrentMaximum permitted input voltage: 2.5 V
Voltage > 1 VMaximum permitted input voltage: 35 V1...5 V range with cable open circuit monitoring:
Voltage 1 VMaximum permitted input voltage: 12 V
Resistance
thermometer
(RTD)
Thermocouples
(TC)
Limit values (steady-state,
without destroying input)
Maximum permitted input current: 50 mA
Measuring current: 1 mADisengageable cable open circuit detection
Maximum permitted input voltage: 12 VDisengageable cable open circuit detection from 50 kOhm
Cable open circuit detection/line influence/temperature
compensation
4...20 mA range with cable open circuit monitoring to NAMUR NE43.
Activate/deactivate the 4...20 mA loop monitoring as per NAMUR recomendation NE43.
On activation:
3.8 mA: Under range (indicate: vvvvvv)
20.5 mA: Over range (indicate: ^^^^^^)
3.6 mA or 21.0 mA: Open Circuit (indicate: - - - -)
< 0.8 V or > 5.2 V: Open Circuit (indicate: - - - -)
Maximum barrier resistance (or line resistance):
Max. 200 Ohm (4-wire)
Max. 40 Ohm (3-wire)
Maximum influence of barrier resistance (or line resistance) for Pt100, Pt500 and
Pt1000: 4-wire: ±0.0002%/Ohm, 3-wire: ±0.002%/Ohm
Maximum influence of barrier resistance (or line resistance) for Pt46, Pt50, Cu100, Cu50
and Cu53: 4-wire: ±0.0006%/Ohm, 3-wire: ±0.006%/Ohm
Error, internal temperature compensation: 2 K
Channel isolationAll analog inputs are galvanically isolated from one another. The testing voltage between the
Integration (Quantity calculation of analog channels): It is possible to calculate an intermediate,
daily, monthly, yearly or total value (13-digit, 64 bit).
Analysis: Quantity-/operating time recording (standard function), additionally a min/max/
average value evaluation within the preset period.
Mathematic: Up to 5 mathematics channels. Mathematic calculation of analog channels using
basic arithmetic operands (+, -, *,/), constants. In addition either the sum or the average value of
several channels can be calculated. If the mathematics channel is used then 1 analog channel is lost.
10.1.2Digital inputs
Number3 digital inputs
Input levelTo IEC 61131-2:
Logical "0" (corresponds to -3 to +5 V), activation with logical "1" (corresponds to +12 to +30 V)
Input frequencyMax. 25 Hz
73
Page 74
Technical data
Pulse lengthMin. 20 ms
Input currentMax. 2 mA
Input voltageMax. 32 V (steady-state, without destroying input)
message+operating time.
Functions of the control input: start recording, rear illumination OFF, setup lock, time
synchronization.
10.2Output
10.2.1Auxiliary voltage output
The auxiliary voltage is provided to activate the digital input (or sensors) with floating contacts and
is galvanically isolated from the system and the inputs (testing voltage 500 V). The ground of the
auxiliary voltage and the ground of the digital input are electrically interconnected.
!
Output voltage:
Approx. 24 V, max. 28 V
Output current:
Maximum 250 mA, short-circuit proof, not stabilised
10.2.2Relay outputs
Alarm relay:
1 Alarm relay with changeover contact
Standard relay:
3 relays with NO contact for limit value messages (can be configured as NC contact).
Note!
It is not permitted to mix low voltage and safety extra low voltage (do not mix SELV circuits and
low voltage).
Response time:
1 s
74
Maximum DC contact load:
50 V / 300 mA (steady-state, without destroying input)
Maximum AC contact load:
230 V / 3 A (steady-state, without destroying input)
Page 75
10.3Power supply/terminal diagram
10.3.1Electrical connection (wiring diagram)
(Wiring diagram, see Section 4 "Wiring")
10.3.2Supply voltage
Low voltage power supply: 100...230 VAC (±10%)
Extra-low voltage power supply: 24 V
10.3.3Frequency
Nominal frequency: 50 / 60 Hz
10.3.4Cable specification
(-10%, +15%)
AC/DC
Technical data
Screw or spring terminal blocks with reverse polarity protection:
Digital I/O wire cross-section, RS485 and analog inputs: max. 1.5 mm
terminals)
Power wire cross-section: max. 2.5 mm
Relay wire cross-section: max. 2.5 mm
(13 AWG) (screw terminals)
(13 AWG) (spring terminals)
(14 AWG) (spring
10.3.5Power consumption
100...230 V: max. 30 VA
24 V: max. 24 VA
10.3.6Connection data interface, communication
USB port (standard):
Front-mounted USB-B socket (V1.1) for connecting a laptop or computer using a shielded USB
cable. The USB port can be used for program transmission and unit configuration (printers or
modems cannot be connected here).
Ethernet interface (option):
Rear-mounted Ethernet interface 10BaseT, plug type RJ45, connection via shielded cable, allocation
of IP address via setup menu in unit. The unit can be connected to units in an office environment
with this interface. For safe spacing distances, observe the office equipment standard IEC 60950-1.
Direct connection to a PC is possible with a "crossover" cable. The unit can be used in the network
as a "Web server". Two Ethernet function LEDs on the rear of the unit.
Serial RS232/RS485 interface (option):
Rear-mounted RS232 SUB-D9 socket or RS485 interface (terminal connection) for data/program
transmission or as modem connection.
The following baudrates are supported: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Max. line length with shielded cable: 2 m (6.6 ft) (RS232), or 1000 m (3281 ft) (RS485)
Both interfaces are galvanically isolated from the system.
The RS232/RS485 interfaces cannot be used simultaneously.
75
Page 76
Technical data
10.4Performance characteristics
10.4.1Reference operating conditions
Ambient temperature: 25 °C ± 5 K (77 °F ± 9 °F)
Air humidity: 55 % ± 10 % r.h.
10.4.2Maximum measured error
See Inputsee Section 10.1.1
10.4.3Temperature drift
Cu100, Cu50, Cu53, Pt46 and Pt50: max. ± 0.02 %/K (of measuring range)
All other ranges: max. ± 0.01 %/K (of measuring range)
10.4.4Long-term drift
To IEC 61298-2: max. ± 0.01 %/month (of measuring range)
10.5Installation conditions
10.5.1Orientation
Position of use as per DIN 16 257, NL 90 ± 30°
10.5.2Installation instructions
(Panel mounting, see Section 3)
• Installation depth: approx. 171 mm (6.73 inch) (incl. terminals and fastening clips)
• Panel cutout: 138
• Panel thickness: 2 to 40 mm (0.08 to 1.57 inch)
• Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30°
downward.
• Securing to DIN 43 834
+1
x 138+1 mm (5.43
+0.04
x 5.43
+0.04
inch)
10.6Environment
10.6.1Ambient temperature range
0 to 50 °C (32 to 122 °F)
76
10.6.2Storage temperature
-20 to +60 °C (-4 to 140 °F)
10.6.3Relative air humidity
0 to 50 °C (32 to 122 °F), max. 75% humidity without condensation.
10.6.4Climate class
To IEC 60654-1: B1
Page 77
Technical data
10.6.5Degree of protection
Front-panel IP 54 (IEC 60529, Cat. 2) NEMA 2
rear-panel IP 20 (IEC 60529, Cat. 2)
10.6.6Electrical safety
IEC 61010-1, protection class I
Low voltage: overvoltage category II
Environment < 3000 m (< 9843 ft) above MSL (mean sea level)
10.6.7Electromagnetic compatibility (EMC)
Interference immunity:
To IEC 61326: Class B (industrial environment) and NAMUR NE21:
• Surge on power line: IEC 61000-4-5: 2 kV asymmetrical, 1 kV symmetrical
• Surge on signal line: IEC 61000-4-5: 1 kV asymmetrical (with external protection element)
• Conducted HF: IEC 61000-4-6: 150 kHz to 80 MHz, 10 V
• Power failure: IEC 61000-4-11 (> 20 ms/0%)
• Voltage variation: IEC 61000-4-11 (40% / 0%)
Emission:
To IEC 61326: Class A (operation in industrial environment)
Interference voltage:
Power line: To CISPR 16-1/-2: Class A
Interference current:
Ethernet line: To EN 50022: Class A
Interference field intensity:
Housing/all connections: to CISPR 16: Class A
Interference voltage suppression:
• Common mode interference voltage suppression: IEC 61298-3:
Analog inputs: 80 dB at 60 V and 50 Hz / 60 Hz
• Push-pull interference voltage suppression: IEC 61298-3:
Analog inputs: 40 dB at 50 Hz / 60 Hz, for measuring range/10
77
Page 78
Technical data
Y
X
137.9 mm
5.43”
21 mm
0.83”
150 mm
5.9”
36.1 mm
1.42”
138 mm
5.43“
+1
+0.04
138 mm
5.43“
+1
+0.04
86.5 mm
3.4”
144 mm
5.67”
144 mm
5.67”
10.7Mechanical construction
10.7.1Design, dimensions
Panel-mounted instrument:
10.7.2Weight
• Panel-mounted instrument: approx. 700 g (1.54 lb)
10.7.3Materials
Front frame/removable media door: plastic (ABS)
Housing: fiberglass reinforced plastic (PC)
Protective cover in front of display: plastic (PC)
10.8Human interface
10.8.1Display elements
Type:
LC color graphic display
Size (screen size, measured diagonally):
120 mm (4.7")
Resolution:
76,800 pixels (320 x 240 pixels)
78
Page 79
Technical data
Rear illumination:
50,000 h half value time (= half brightness)
Number of colors:
64 colors
Point of view:
Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30°
downward.
Display modes:
Curves/load curves, curves in ranges, digital display, bar graph, events list (set points/power
failure), status display, history display in curve form with display of digital measured values, date
and time
10.8.2Operating elements
Keyboard:
Option of operation and configuration via 7 push buttons on the front side in interactive dialog with
the screen or using the provided PC software. Display of integrated operating instructions at the
push of a button.
• Setup data memory, measured data memory: permanent back-up of setup data and measured data
in internal Flash memory (nonvolatile)
• Main memory: 2 MB SRAM
Data buffering and RTC buffering with lithium cell (replace after 10 years)
External memory:
• Cyclic copying of the measured data for archiving on CompactFlash card
(CompactFlash base: type I)
• Supported CF memory cards : 32 MB, 64 MB, 128 MB, 256 MB and 512 MB. Please use the CF
memory cards recommended by the manufacturer (see "Accessories").
• A green LED beside the CF slot indicates data access. During this process, the CF card must not
be removed. Risk of losing data!
Typical recording lengths:
Requirements for the following tables:
• No alarm point violation/event storage
• Digital input not used
• Signal analysis deactivated
Note!
!
Frequent entries in the events list reduce the memory availability!
Calculation of recording duration using "storage calculator" (can be found under "tools" on the CDROM of the PC software supplied).
Save cycle 1
min.
Save cycle 30 s.Save cycle 10 s.Save cycle 1 s.
10.8.4Real time clock (RTC)
Switchable summer time/normal time automated system
Power reserve: buffering via lithium battery
Deviation: < 10 min./year
Time synchronization possible
10.8.5Remote operation
Configuring and archiving the unit settings with CompactFlash or with supplied PC software via
rear-mounted serial interface RS232/RS485 (e.g. modem), Ethernet, or front-mounted USB port.
10.9Certificates and approvals
10.9.1CE mark
The measuring system meets the legal requirements of the EC directives. The manufacturer
confirms successful testing of the device by affixing the CE mark.
10.9.2UL listed for Canada and USA
The device was examined by Underwriters Laboratories Inc. (UL) in accordance with the standards
UL 61010-1 and CSA C22.2 No. 61010-1 and listed under the number E225237 UL.
10.9.3Other standards and guidelines
CSA approval
CAN/CSA-C22.2 No. 61010-1-04 Safety requirements for electrical equipment for measurement,
control, and laboratory use - General requirements, Second Edition.
10.10Accessories
Accessories available, see Section 8
10.11Documentation
Brochure on recording technology (FA014R/09/en)
Technical Information (TI115R/09/en)
Brief Operating Instructions (KA199R/09/c5)