Endress+Hauser Ecograph T Technical Information

Technical Information
Ecograph T
Multi Channel Recorder RSG30 Display, record, communicate

Applications

The instrument can be used in many processes and industries:
• Quality and quantity monitoring in the water/ wastewater industry
• Monitoring of processes in power stations
• Food and dairy industry processes
• Displaying and recording critical parameters in production cycles
• Tank and level monitoring
• Temperature monitoring in metal working
• Cold storage and transportation monitoring
4 1 â

Your benefits

• Informative: interim, daily, monthly and yearly analysis; counters, operation time and quantities; min-, max- and average value recording
• Versatile: up to 6 universal inputs record all measuring signals
• Clear layout: multi-coloured display, digital, bargraph and curve display
• Compact: low installation depth, saves space and money
• Safe: reliable data archiving with internal memory and separate CompactFlash card (mechanically locked). No data loss even in event of power failure!
• System-enabled: network integration and remote data transmission via Ethernet, RS232/RS485 (modem) and USB
• Available worldwide: integrated Web server function for remote monitoring e.g. with E+H Fieldgate
®
Viewer
• Reliable: inputs are galvanically isolated from the system
• Complete: ReadWin® 2000 PC software package contained in scope of supply for professional, tamper­proof data processing
• Flexible: direct access to archived data also with MS Excel or in ReadWin
®
2000 for example
®
TI115R/09/en No. 51009568
Ecograph T

Function and system design

Measuring principle Electronic acquisition, display, recording, analysis, remote transmission and archiving of analog and digital

input signals.

Measuring system Multi-channel data recording system with multi-coloured LCD display (120 mm / 4.7" screen size),

galvanically isolated universal inputs (U, I, TC, RTD), digital input, transmitter power supply, limit relay, communication interfaces (USB, Ethernet, RS232/485), internal Flash memory and CompactFlash card. 100 ms scan rate for all channels. ReadWin data analysis.
®
2000 PC software for comprehensive offline device configuration and

Block diagram

Communication
PSTN-/GSM-Modem
Serial connection RS232, RS485 (option)
ReadWin®2000
PC software
Ethernet 10Base T (Option)
USB
Web-Browser function
Display modes:
- Bargraph
- Trend
- Digital
1x24V,250mA Transmitter power supply output
Memory
Slot for external
Compact Flash CF-card
*.csv *.dat
Lockable cover for CF-card
2MB Internal memory
LCD 4,7” Display
E
3/6 universal inputs:
-TC
- RTD
-mA
- mV, V
Optional:
- Integration
- Mathematic
- Analysis
Mathematic functions: Addition, subtraction, division, multiplication
V
4 Relays:
- 1 change-over contact
- 3 normally open contacts
M
16 limit values (variable channel mapping)
Inputs
mA
3 digital I/O:
- Event
- Time
- Counter
- Control function
115/230 V AC 24 V AC/DC
Outputs
Power
This block diagram is only indicative of the functionality.

Input

Analog multi-function input channel 1-6

2 Endress+Hauser

Measured variable, measuring range

To IEC 60873-1: An additional display error of -/+ 1 digit is permitted for every measured value. Measuring ranges which can be selected per channel:
Ecograph T
Measured
variable
Current 0...20 mA
Voltage > 1 V 0...10 V
Voltage 1 V 0...1 V
Resistance thermometer (RTD)
Thermocouples (TC)
0...5 mA
4...20 mA Overrange: up to 22 mA
0...5 V ± 10 V ± 30 V
± 1 V ± 150 mV
Pt100: -200 to 850 °C (-328 to 1562 °F) (IEC751, JIS1604, GOST) Pt500: -200 to 850 °C (-328 to 1562 °F) (IEC751, JIS1604) Pt1000: -200 to 600 °C (-328 to 1112 °F) (IEC751, JIS1604)
Cu100: -200 to 200 °C (-328 to 392 °F) (GOST) Cu50: -200 to 200 °C (-328 to 392 °F) (GOST) Pt50: -200 to 850 °C (-328 to 1562 °F) (GOST)
Type J (Fe-CuNi): -210 to 999.9 °C (-346 to 1832 °F) (IEC581-1) Type K (NiCr-Ni): -200 to 1372 °C (-328 to 2501.6 °F) (IEC581-1) Type T (Cu-CuNi): -270 to 400 °C (-454 to 752 °F) (IEC581-1) Type N (NiCrSi-NiSi): -270 to 1300 °C (-454 to 2372 °F) (IEC581-1) Type L (Fe-CuNi): -200 to 900 °C (-328 to 1652 °F) (DIN43710, GOST)
Measuring range Maximum measured error
of measuring range (oMR)
± 0.10 % Load: = 50 Ohm
± 0.10 % ( 980 kOhm
± 0.10 % ( 2.7 MOhm
4-wire: ± 0.10 % oMR 3-wire: ± (0.10 % oMR + 0.8 K) 2-wire: ± (0.10 % oMR + 1.5 K)
4-wire: ± 0.20 % oMR 3-wire: ± (0.20 % oMR + 0.8 K) 2-wire: ± (0.20 % oMR + 1.5 K)
± 0.10 % oMR from -100 °C (-148 °F) ± 0.10 % oMR from -130 °C (-202 °F) ± 0.10 % oMR from -200 °C (-328 °F) ± 0.10 % oMR from -100 °C (-148 °F) ± 0.10 % oMR from -100 °C (-148 °F)
Input
impedance
( 2.7 MOhm
Type D (W3Re-W25Re): 0 to 2315 °C (32 to 4199 °F) (ASTME998) Type C (W5Re-W26Re): 0 to 2315 °C (32 to 4199 °F) (ASTME998) Type B (Pt30Rh-Pt6Rh): 0 to 1820 °C (32 to 3308 °F) (IEC581-1) Type S (Pt10Rh-Pt): 0 to 1768 °C (32 to 3214 °F) (IEC581-1) Type R (Pt13Rh-Pt): -50 to 1768 °C (-58 to 3214 °F) (IEC581-1)

Limit values

Limit values for input voltage and current as well as cable open circuit detection/line influence/temperature compensation
Measured
variable
Current Maximum permitted input voltage: 2.5 V
Voltage > 1 V Maximum permitted input voltage: 35 V
Voltage 1 V Maximum permitted input voltage: 12 V
Limit values (steady-state,
without destroying input)
Maximum permitted input current: 50 mA
± 0.15 % oMR from 500 °C (932 °F) ± 0.15 % oMR from 500 °C (932 °F) ± 0.15 % oMR from 600 °C (1112 °F) ± 0.15 % oMR from 100 °C (212 °F) ± 0.15 % oMR from 100 °C (212 °F)
( 2.7 MOhm
Cable open circuit detection/line influence/temperature
compensation
4...20 mA range with cable open circuit monitoring to NAMUR NE43. Activate/deactivate the 4...20 mA loop monitoring as per NAMUR recomendation NE43. On activation:
3.8 mA: Under range (indicate: vvvvvv) 20.5 mA: Over range (indicate: ^^^^^^) 3.6 mA or 21.0 mA: Open Circuit (indicate: - - - -)
Endress+Hauser 3
Ecograph T
Measured
variable
Resistance thermometer (RTD)
Thermocouples (TC)
Limit values (steady-state,
without destroying input)
Measuring current: 1 mA Disengageable cable open circuit detection
Maximum permitted input voltage: 12 V Disengageable cable open circuit detection from 50 kOhm
Cable open circuit detection/line influence/temperature
compensation
Maximum barrier resistance (or line resistance): Max. 200 Ohm (4-wire) Max. 40 Ohm (3-wire)
Maximum influence of barrier resistance (or line resistance) for Pt100, Pt500 and Pt1000: 4-wire: ±0.0002%/Ohm, 3-wire: ±0.002%/Ohm
Maximum influence of barrier resistance (or line resistance) for Pt50, Cu100 and Cu50: 4-wire: ±0.0006%/Ohm, 3-wire: ±0.006%/Ohm
Error, internal temperature compensation: 2 K

Channel isolation

All analog inputs are galvanically isolated from one another. The testing voltage between the channels is 500 V (no safety isolation)

Scan rate

All channels are scanned within 100 ms.

Resolution

For all ranges: 18 bit

Integration, analysis, mathematic (option package)

Integration (Quantity calculation of analog channels): It is possible to calculate an intermediate, daily,
monthly, yearly or total value (13-digit, 64 bit).
Analysis: Quantity-/operating time recording (standard function), additionally a min/max/average value evaluation within the preset period.
Mathematic: Up to 5 mathematics channels. Mathematic calculation of analog channels using basic arithmetic operands (+, -, *,/), constants. In addition either the sum or the average value of several channels can be calculated. If the mathematics channel is used then 1 analog channel is lost.

Digital inputs Number

3 digital inputs

Input level

To IEC 61131-2: Logical "0" (corresponds to -3 to +5 V), activation with logical "1" (corresponds to +12 to +30 V)

Input frequency

Max. 25 Hz

Pulse length

Min. 20 ms

Input current

Max. 2 mA

Input voltage

Max. 32 V (steady-state, without destroying input)
4 Endress+Hauser
Ecograph T

Selectable functions

Control input, ON/OFF message, pulse counter (13-digit, 64 bit), operating time, message+operating time. Functions of the control input: start recording, rear illumination OFF, setup lock, time synchronization.

Output

Auxiliary voltage output The auxiliary voltage is provided to activate the digital input (or sensors) with floating contacts and is

galvanically isolated from the system and the inputs (testing voltage 500 V). The ground of the auxiliary voltage and the ground of the digital input are electrically interconnected.

Output voltage:

Approx. 24 V, max. 28 V

Output current:

Maximum 250 mA, short-circuit proof, not stabilised

Relay outputs Alarm relay:

1 Alarm relay with changeover contact

Standard relay:

3 relays with NO contact for limit value messages (can be configured as NC contact).
!
Note! It is not permitted to mix low voltage and safety extra low voltage (do not mix SELV circuits and low voltage).

Response time:

1 s

Maximum DC contact load:

50 V / 300 mA (steady-state, without destroying input)

Maximum AC contact load:

230 V / 3 A (steady-state, without destroying input)
Endress+Hauser 5
Electrical connection (wiring
_
_
_
_
diagram)
Ecograph T

Power supply / terminal diagram

To modem: Cable with 25 pol. Sub-D socket
To modem: Cable with 9 pol. Sub-D socket
To PC: Cable with 25 pol. Sub-D plug
To PC: Cable with 9 pol. Sub-D plug RxD-3 GND-5 TxD-2
RS 232
14
1
2
6
1
2
14
1
2
6
1
2
611
612
CH 3
311
312
R=
L
RxD/TxD(-) RxD/TxD(+)
9X
L+N-PE
613
614
615
313
314
315
Cable resistance
616
316
_
12V-24VDC
+
L+ N-
115 / 230 VAC
PE
Power
50/60Hz
RS 485
24 V AC/DC
50/60Hz
R
L
Further units
Digital in (DI)
>20 ms
12V-24VDC
>5 mA
_
9X
+
+
9X
10 k
Out: max. 250 mA
413
414
113
114
Rel4 Rel3
41
415
416
115
116
42
max. 250 V/3A
Rel2
31
32
21
22
U>1V
+
511
512
513
514
CH 2
211
212
213
214
+
515
215
Rel1
111312
+
x11x12 x13 x14 x15 x16
516
216
25
7
3
5
9 5
3
5
7
3
5
9
5
3
5
13
DI3
91
92
93
Ethernet
25
13
LED yellow LED green
6
9
-
TC
+
GND RxD/TxD + RxD/TxD -
CH 4 CH 5 CH 6
RS485
411
412
5
CH 1
RS232
111
112
1
Analog inputs
x12x11 x13 x14 x15 x16
x12x11 x13 x14 x15 x16
x12x11 x13 x14 x15 x16
x12x11 x13 x14 x15 x16
x12x11 x13 x14 x15 x16
0...20 mA, 4...20 mA, 0...5 mA
(Volt drop 1 V, Ri50 Ohm)≤≤
a) 0...5 V, 0...10 V, +/- 10 V, +/- 30 V b) 0...1 V, +/- 150 mV, +/- 1 V
Typ: J, K, T, N, L, D, C, B, S, R
Typ: Pt50, Pt100, Pt500, PT1000, CU50, CU100
RTD
I
U
TC
+
-
a)>1V
x12x11 x13 x14 x15 x16
x12x11 x13 x14 x15 x16
+
-
+
-
b) 1 V
+
-
6 Endress+Hauser
Ecograph T

Supply voltage Low voltage power supply: 115 / 230 V

Extra-low voltage power supply: 24 V
AC
AC/DC

Frequency Nominal frequency: 50 / 60 Hz

Cable specification Screw or spring terminal blocks with reverse polarity protection:

Digital I/O wire cross-section, RS485 and analog inputs: max. 1.5 mm2 (14 AWG) (spring terminals) Power wire cross-section: max. 2.5 mm
2
(13 AWG) (screw terminals)
Relay wire cross-section: max. 2.5 mm2 (13 AWG) (spring terminals)

Power consumption 115/230 V: max. 30 VA

24 V: max. 24 VA

Connection data interface, communication

USB port (standard):
Front-mounted USB-B socket (V1.1) for connecting a laptop or computer using a shielded USB cable. The USB port can be used for program transmission and unit configuration (printers or modems cannot be connected here).
Ethernet interface (option):
Rear-mounted Ethernet interface 10BaseT, plug type RJ45, connection via shielded cable, allocation of IP address via setup menu in unit. The unit can be connected to units in an office environment with this interface. For safe spacing distances, observe the office equipment standard IEC 60950-1. Direct connection to a PC is possible with a "crossover" cable. The unit can be used in the network as a "Web server". Two Ethernet function LEDs on the rear of the unit.
Serial RS232/RS485 interface (option):
Rear-mounted RS232 SUB-D9 socket or RS485 interface (terminal connection) for data/program transmission or as modem connection. The following baudrates are supported: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Max. line length with shielded cable: 2 m (6.6 ft) (RS232), or 1000 m (3281 ft) (RS485) Both interfaces are galvanically isolated from the system. The RS232/RS485 interfaces cannot be used simultaneously.

Performance characteristics

Reference operating conditions

Maximum measured error (See Input)

Temperature drift Cu100, Cu50 and Pt50: max. ± 0.02 %/K (of measuring range)

Long-term drift To IEC 61298-2: max. ± 0.01 %/month (of measuring range)

Ambient temperature: 25 °C ± 5 K (77 °F ± 9 °F) Air humidity: 55 % ± 10 % r.h.
All other ranges: max. ± 0.01 %/K (of measuring range)
Endress+Hauser 7

Installation conditions

Orientation Position of use as per DIN 16 257, NL 90 ± 30°

Installation instructions Panel cutout and installation / design, dimensions:

144 mm
5.67”
144 mm
5.67”
86.5 mm
3.4”
Ecograph T
!
21 mm
150 mm
0.83”
5.9”
137.9 mm
5.43”
36.1 mm
X
1.42”
+1
138 mm
+0.04
5.43
138 mm
5.43
+1
+0.04
Y
• Installation depth: approx. 171 mm (6.73 inch) (incl. terminals and fastening clips)
• Panel cutout: 138+1 x 138+1 mm (5.43
• Panel thickness: 2 to 40 mm (0.08 to 1.57 inch)
• Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30° downward.
• Securing to DIN 43 834
Note! A distance of min. 15 mm (0.59 in) between the units has to be observed if aligning the units in the Y-direction (vertically above one another). The units can be arranged horizontally beside one another in the X direction without any spacing between the units.
+0.04
x 5.43
+0.04
inch)

Environment

Ambient temperature range 0 to 50 °C (32 to 122 °F)

Storage temperature -20 to +60 °C (-4 to 140 °F)

Relative air humidity 0 to 50 °C (32 to 122 °F), max. 75% humidity without condensation.

Climate class To IEC 60654-1: B1

8 Endress+Hauser
Ecograph T

Degree of protection Front-panel IP 54 (IEC 60529, Cat. 2) NEMA 2

rear-panel IP 20 (IEC 60529, Cat. 2)

Electrical safety IEC 61010-1, protection class I

Low voltage: overvoltage category II Environment < 3000 m (< 9843 ft) above MSL (mean sea level)

Electromagnetic compatibility (EMC)

Interference immunity:
To IEC 61326: Class B (industrial environment) and NAMUR NE21:
• ESD (electrostatic discharge): IEC 61000-4-2 severity 3 (6/8 kV)
• HF field (electromagnetic interference fields): IEC 61000-4-3: severity 3 (10 V/m)
• Burst (quick transient disturbance variables): IEC 61000-4-4 severity 3 (1 kV signal, 2 kV power supply)
• Surge on power line: IEC 61000-4-5: 2 kV asymmetrical, 1 kV symmetrical
• Surge on signal line: IEC 61000-4-5: 1 kV asymmetrical (with external protection element)
• Conducted HF: IEC 61000-4-6: 150 kHz to 80 MHz, 10 V
• Power failure: IEC 61000-4-11 (> 20 ms/0%)
• Voltage variation: IEC 61000-4-11 (40% / 0%)
Emission:
To IEC 61326: Class A (operation in industrial environment)
Interference voltage:
Power line: To CISPR 16-1/-2: Class A
Interference current:
Ethernet line: To EN 50022: Class A
Interference field intensity:
Housing/all connections: to CISPR 16: Class A
Interference voltage suppression:
• Common mode interference voltage suppression: IEC 61298-3: Analog inputs: 80 dB at 60 V and 50 Hz / 60 Hz
• Push-pull interference voltage suppression: IEC 61298-3: Analog inputs: 40 dB at 50 Hz / 60 Hz, for measuring range/10

Mechanical construction

Design, dimensions See Installation conditions

Weight Panel-mounted instrument: approx. 700 g (1.54 lb)

Materials Front frame / removable media door: plastic (ABS)

Housing: fibre-glass reinforced plastic (PC) Protective cover in front of display: plastic (PC)

Human interface

Display elements Type:

LC color graphic display
Size (screen size, measured diagonally):
120 mm (4.7")
Endress+Hauser 9
Resolution:
76,800 pixels (320 x 240 pixels)
Rear illumination:
50,000 h half value time (= half brightness)

Number of colors:

64 colors

Point of view:

Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30° downward.

Display modes:

Curves/load curves, curves in ranges, digital display, bar graph, events list (set points/power failure), status display, history display in curve form with display of digital measured values, date and time

Operating elements Keyboard:

Option of operation and configuration via 7 push buttons on the front side in interactive dialog with the screen or using the provided PC software. Display of integrated operating instructions at the push of a button.
Ecograph T

Data storage Save cycle:

• Selectable save cycle: 1s / 2s / 3s / 4s / 5s / 10s / 15s / 20s / 30s / 1min / 2min / 3min / 4min / 5min / 10min / 30min / 1h
Selected save cycle Equal to a feed rate in mm/h Equal to a feed rate in inch/h
1s 1000 40
2s 600 24
3s 300 12
4s 240 10
10s 120 4.8
20s 60 2.4
30s 30 1.2
1min (60s) 20 0.8
2min (120s) 10 0.4
4min (240s) 5 0.2
Internal memory:
• Program memory: 2 MB Flash (nonvolatile)
• Setup data memory, measured data memory: permanent back-up of setup data and measured data in internal Flash memory (nonvolatile)
• Main memory: 2 MB SRAM Data buffering and RTC buffering with lithium cell (replace after 10 years)
External memory:
• Cyclic copying of the measured data for archiving on CompactFlash card (CompactFlash base: type I)
• Supported CF memory cards : 32 MB, 64 MB, 128 MB, 256 MB and 512 MB. Please use the CF memory cards recommended by the manufacturer (see "Accessories").
10 Endress+Hauser
Ecograph T
• A green LED beside the CF slot indicates data access. During this process, the CF card must not be removed. Risk of losing data!
Typical recording lengths:
Requirements for the following tables:
• No alarm point violation/event storage
• Digital input not used
• Signal analysis deactivated
Note!
!
Frequent entries in the events list reduce the memory availability!
Internal memory (weeks = w, days = d, hours = h):
Analog inputs Save cycle 5
min.
1 68 w, 5 d, 0 h 15 w, 1 d, 23 h 7 w, 4 d, 11 h 2 w, 3 d, 19 h 1 d, 18 h
3 34 w, 2 d, 12 h 7 w, 1 d, 20 h 3 w, 4 d, 10 h 1 w, 1 d, 11 h 20 h
6 19 w, 4 d, 10 h 4 w, 0 d, 11 h 2 w, 0 d, 5 h 4 d, 17 h 11 h
CompactFlash 128 MB (weeks = w, days = d, hours = h):
Analog inputs Save cycle 5
min.
1 5738 w, 6 d, 14 h 1276 w, 4 d, 7 h 638 w, 2 d, 3 h 212 w, 5 d, 9 h 21 w, 1 d, 22 h
3 2869 w, 4 d, 2 h 606 w, 4 d, 10 h 303 w, 2 d, 5 h 101 w, 0 d, 17 h 10 w, 0 d, 18 h
6 1639 w, 6 d, 0 h 339 w, 4 d, 18 h 169 w, 5 d, 21 h 56 w, 4 d, 7 h 5 w, 4 d, 15 h
CompactFlash 256 MB (weeks = w, days = d, hours = h):
Analog inputs Save cycle 5
min.
Save cycle 1
min.
Save cycle 1
min.
Save cycle 1
min.
Save cycle 30 s. Save cycle 10 s. Save cycle 1 s.
Save cycle 30 s. Save cycle 10 s. Save cycle 1 s.
Save cycle 30 s. Save cycle 10 s. Save cycle 1 s.
1 11526 w 3 d, 0 h 2564 w, 0 d, 5 h 1282 w, 0 d, 2 h 427 w, 2 d, 8 h 42 w, 5 d, 3 h
3 5763 w, 3 d, 2 h 1218 w, 2 d, 20 h 609 w, 1 d, 10 h 203 w, 0 d, 11 h 20 w, 2 d, 3 h
6 3293 w, 4 d, 3 h 682 w, 1 d, 16 h 341 w, 0 d, 20 h 113 w, 4 d, 22 h 11 w, 2 d, 14 h
Calculation of recording duration:
Calculation of recording duration using "storage calculator" (can be found under "tools" on the CD-ROM of the PC software supplied).

Real time clock (RTC) Switchable summer time/normal time automated system

Power reserve: buffering via lithium battery Deviation: < 10 min./year Time synchronization possible

Remote operation Configuring and archiving the unit settings with CompactFlash or with supplied PC software via rear-mounted

serial interface RS232/RS485 (e.g. modem), Ethernet, or front-mounted USB port.
Endress+Hauser 11
Ecograph T

Certificates and approvals

CE mark The measuring system meets the legal requirements of the EC directives. The manufacturer confirms successful

testing of the device by affixing the CE mark.

UL listed for Canada and USA The device was examined by Underwriters Laboratories Inc. (UL) in accordance with the standards UL 61010-

1 and CSA C22.2 No. 61010-1 and listed under the number E225237 UL.
Other standards and guideli­nes

Product structure

CSA approval CAN/CSA-C22.2 No. 61010-1-04 Safety requirements for electrical equipment for measurement, control, and laboratory use - General requirements, Second Edition.

Ordering information

Basic features:
4.7" LC colour graphic display (320 x 240 pixels) Analog inputs, 3 digital inputs, 4 relays Interactive dialogue operation with 7 push buttons 24 V auxiliary output voltage USB connection incl. connecting cable 16 limit values, can be freely defined PC software package CompactFlash (CF) slot
Input signal
A 3 universal (U, I, TC, RTD)
B 6 universal (U, I, TC, RTD)
Power supply
1 115/230 V AC, 50/60 Hz
2 24 V AC/DC, 50/60 Hz
Interface
A USB
B USB + RS232/485 + Ethernet
Memory medium
1 without CF card
3 CF card industrial grade, 256 MB
4 CF card industrial grade, 128 MB
Housing
A Panel 144x144 mm (5.67 x 5.67"), IP54, NEMA 2
C Desk top, cable plug earth. type
D Desk top, cable plug US
E Desk top, cable plug Suisse
F Field housing, IP65, NEMA 4x
Operation language
A Standard (German, English)
B Central/western Europe (German, English, French, Spanish, Italian, Dutch)
C Northern Europe (German, English, Danish, Swedish)
D Eastern Europe (German, English, Polish, Russian, Czech, Slovak)
E America (German, English, French, Spanish, American, Portuguese)
F Japan (German, English, Japanese)
G China (German, English, Chinese)
Additional option
A Standard
C Integration + Analysis + Maths
Approval
1 Non-hazardous area, standard with logo
2 Non-hazardous area, neutral without label
RSG30- Order code
12 Endress+Hauser
Ecograph T

Accessories

Scope of delivery • Unit (with terminals, as per your order)

• 4 fastening clips
• USB cable
• Optional CompactFlash CF card (CF card is enclosed separately.)
• PC operating and configuration software on CD-ROM
• Delivery note
• Multilanguage Brief Operating Instructions as hard copy
• Operating Instructions on CD-ROM
• locking plate
Anything missing? Then please inform your supplier.

Accessory parts The following accessories are available:

Order code Accessory
50078843 Terminal, pluggable, 3-pole, for power supply
51009211 Terminal, pluggable, 6-pole, for analog input
51009214 Terminal, pluggable, 3-pole, for relay
51009215 Terminal, pluggable, 6-pole, for relay
71062537 Terminal, pluggable, 5-pole, for digital I/O
71043991 CompactFlash (CF) memory card 128 MB
51009640 CompactFlash (CF) memory card 256 MB
71007465 Cable USB-A - USB-B, 2 m (6.56 ft)
RXU10-A1 Cable set for connection PC or modem
RSG30A-S3 Adapter set RS232/RS485 230 VAC in compact housing, without galvanic isolation
RSG30A-S5 Adapter set RS232/RS485 115 VAC in compact housing, without galvanic isolation
RSG30A-S6 Adapter set RS232/RS485 for DIN rail 230 VAC with galvanic isolation and interface cable for
RSG30A-S7 Adapter set RS232/RS485 for DIN rail 115 VAC with galvanic isolation and interface cable for
RSG30A-H1 Field housing IP65
PC/modem
PC/modem
320 mm (12.6“)
320 mm (12.6“)
254 mm (10“)

Documentation

Brochure on recording technology (FA014R/09/en)Operating Instructions (BA194R/09/en)Brief Operating Instructions (KA199R/09/c5)