Emerson Fisher DLC3010 Data Sheet

Product Bulletin
DLC3010 Digital Level Controller
D102727X012
11.2:DLC3010
Fisherr FIELDVUEt DLC3010 Digital Level Controller
The FIELDVUE DLC3010 digital level controller is used with level sensors to measure liquid level, the level of the interface between two liquids, or liquid specific gravity (density). Changes in level or specific gravity exert a buoyant force on a displacer, which rotates a torque tube shaft. The digital level controller converts this rotational motion to an electronic signal.
The DLC3010 is a communicating, microprocessor-based instrument that can be configured to sense the level, interface level, or density of liquids. In addition to the normal function of providing a 4 to 20 milliampere current signal, the DLC3010, using HART gives easy access to information critical to process operation. You can obtain information about the process, instrument, or sensor using the 475 or 375 Field Communicator. The DLC3010 can be used in analog or HART digital signaling mode with the Emerson Process Management DeltaVt system.
The connection for HART communication may be made at any point in the field wiring that meets the HART impedance requirements. Configuration, calibration, diagnostics, parameter review, signal monitoring and alert monitoring are all available
R
communications protocol,
W7977-1
through the HART protocol. Information from the field can be integrated into control systems or be received on a single loop basis.
The DLC3010 digital level controller is designed to directly replace standard pneumatic and electronic level transmitters. It mounts on a wide variety of Fisher 249 caged and cageless level sensors.
August 2014
www.Fisher.com
Product Bulletin
11.2:DLC3010 August 2014
DLC3010 Digital Level Controller Specifications
DLC3010 Digital Level Controller
D102727X012
Available Configurations
DLC3010 Digital Level Controller:
Mounts on caged and cageless 249 sensors. See tables 4 and 5 and sensor description.
Function: Transmitter
Communications Protocol: HART
Input Signal
Level, Interface, or Density: Rotary motion of torque tube shaft proportional to changes in liquid level, interface level, or density that change the buoyancy of a displacer.
Process Temperature: Interface for 2- or 3-wire 100 ohm platinum RTD for sensing process temperature, or optional user-entered target temperature to permit compensating for changes in specific gravity
Output Signal
Analog: 4 to 20 milliamperes DC (
J direct
action—increasing level, interface, or density increases output; or
J reverse action—increasing
level, interface, or density decreases output)
High saturation: 20.5 mA Low saturation: 3.8 mA High alarm: 22.5 mA Low Alarm: 3.7 mA
Only one of the above high/low alarm definitions is available in a given configuration. NAMUR NE 43 compliant when high alarm level is selected.
Digital: HART 1200 Baud FSK (frequency shift keyed)
HART impedance requirements must be met to enable communication. Total shunt impedance across the master device connections (excluding the master and transmitter impedance) must be between
230 and 1100 ohms. The transmitter HART receive impedance is defined as:
Rx: 42K ohms and Cx: 14 nF
In point-to-point configuration, analog and digital signalling are available. The instrument may be queried digitally for information, or placed in Burst mode to regularly transmit unsolicited process information digitally. In multi-drop mode, the output current is fixed at 4 mA, and only digital communication is available.
Performance
(1)
w/ 3-Inch
249W, Using
a 14-inch
Displacer
$0.8% of
output span
- - - - - -
$0.5% of
output span
- - - - - -
<1.0% of
output span
w/ All Other 249 Sensors
$0.5% of
output span
$0.3% of
output span
<1.0% of
output span
Performance
Criteria
Independent
Linearity
Hysteresis
Repeatability
Dead Band
Hysteresis plus
Deadband
NOTE: At full design span, reference conditions.
1. To lever assembly rotation inputs.
DLC3010 Digital Level Controller
$0.25% of
output span
<0.2% of
output span
$0.1% of full
scale output
<0.05% of
input span
- - -
Note: At effective proportional band (PB)<100%, linearity, dead band, repeatability, power supply effect, and ambient temperature influence are potentially derated by the factor (100%/PB)
Operating Influences
Power Supply Effect: Output changes <±0.2% of full scale when supply varies between minimum and maximum voltage specifications.
Table of Contents
DLC3010 Specifications 2........................
Features 7.....................................
Principle of Operation 9.........................
249 Level Sensor Specifications 10................
249 Level Sensors 10............................
2
-continued-
Installation 12.................................
Ordering Information 12.........................
Construction 13...............................
Heat Insulator 13..............................
DLC3010 Digital Level Controller 13..........
DLC3010 Digital Level Controller
D102727X012
DLC3010 Digital Level Controller Specifications (continued)
Product Bulletin
11.2:DLC3010 August 2014
Transient Voltage Protection: The loop terminals are protected by a transient voltage suppressor. The specifications are as follows:
Pulse Waveform
Rise Time
(ms)
10 1000 93.6 16
8 20 121 83
Note: μs = microsecond
Decay to 50% (ms)
Max V
CL
(Clamping
Voltage) (V)
Max I
PP
(Pulse Peak
@ Current) (A)
Ambient Temperature: The combined temperature effect on zero and span without the 249 sensor is less than 0.03% of full scale per degree Kelvin over the operating range -40 to 80_C (-40 to 176_F)
Process Temperature: The torque rate is affected by the process temperature (see figure 1). The process density may also be affected by the process temperature.
Process Density: The sensitivity to error in knowledge of process density is proportional to the differential density of the calibration. If the differential specific gravity is 0.2, an error of 0.02 specific gravity units in knowledge of a process fluid density represents 10% of span.
Electromagnetic Compatibility
Meets EN 61326‐1 and EN 61326‐2‐3  Immunity—Industrial locations per Table 2 of   EN 61326‐1 and Table AA.2 of EN 61326‐2‐3.   Performance is shown in table 1 below.  Emissions—Class A   ISM equipment rating: Group 1, Class A
signal reasonableness monitor User-configurable alarms: Hi-Hi and Lo-Lo Limit process alarms
HART-readable only:
RTD signal reasonableness monitor: When RTD installed
Processor free-time monitor. Writes-remaining in Non Volatile Memory monitor. User-configurable alarms: Hi and Lo limit process
alarms, Hi and Lo limit temperature alarms, Hi and Lo limit electronics temperature alarms
Diagnostics
Output loop current diagnostic. LCD meter diagnostic. Spot specific gravity measurement in level mode: used
to update specific gravity parameter to improve process measurement Digital signal-tracing capability: by review of “troubleshooting variables”, and
Basic trending capability for PV, TV and SV.
LCD Meter Indications
LCD meter indicates analog output on a percent scale bar graph. The meter also can be configured to display:
Process variable in engineering units only. Percent range only. Percent range alternating with process variable or Process variable, alternating with process temperature (and degrees of pilot shaft rotation).
Supply Requirements (See figure 3)
12 to 30 volts DC; instrument has reverse polarity protection.
A minimum compliance voltage of 17.75 is required to guarantee HART communication.
Compensation
Transducer compensation: for ambient temperature. Density parameter compensation: for process
temperature (requires user-supplied tables). Manual compensation: for torque tube rate at target process temperature is possible.
Digital Monitors
Linked to jumper-selected Hi (factory default) or Lo analog alarm signal:
Torque tube position transducer: Drive monitor and
Electrical Classification
Hazardous Area:
CSA Intrinsically Safe, Explosion‐proof, Division 2,
Dust Ignition‐proof
FM— Intrinsically Safe, Explosion‐proof, Non‐incendive, Dust Ignition‐proof
ATEX— Intrinsically Safe, Type n, Flameproof
IECEx— Intrinsically Safe, Type n, Flameproof
Refer to tables 8, 9, 10, and 11 for additional approval information.
Electrical Housing:
CSA Type 4X FM— NEMA 4X ATEX— IP66 IECEx— IP66
-continued-
3
Product Bulletin
11.2:DLC3010 August 2014
DLC3010 Digital Level Controller Specifications (continued)
DLC3010 Digital Level Controller
D102727X012
Other Classifications/Certifications
FSETAN—Russian - Federal Service of Technological, Ecological and Nuclear Inspectorate
GOST‐R—Russian GOST‐R INMETRO— National Institute of Metrology,
Standardization, and Industrial Quality (Brazil) NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety Organisation - Chief Controller of Explosives (India)
TIIS— Technology Institution of Industrial Safety (Japan)
Contact your Emerson Process Management sales office for classification/certification specific information
Minimum Differential Specific Gravity
With a nominal 4.4 degrees torque tube shaft rotation for a 0 to 100 percent change in liquid level (specific gravity=1), the digital level controller can be adjusted to provide full output for an input range of 5% of nominal input span. This equates to a minimum differential specific gravity of 0.05 with standard volume displacers.
See 249 sensor specifications for standard displacer volumes and standard wall torque tubes. Standard volume for 249C and 249CP is 980 cm most others have standard volume of 1640 cm
3
(60 in3),
3
(100 in3).
Operating at 5% proportional band will degrade accuracy by a factor of 20. Using a thin wall torque tube, or doubling the displacer volume will each roughly double the effective proportional band. When proportional band of the system drops below 50%, changing displacer or torque tube should be considered if high accuracy is a requirement.
Mounting Positions
Digital level controller can be mounted right- or left-of-displacer, as shown in figure 8.
Instrument orientation is normally with the coupling access door at the bottom, to provide proper drainage of lever chamber and terminal compartment, and to limit gravitational effect on the lever assembly. If alternate drainage is provided by
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
user, and a small performance loss is acceptable, the instrument could be mounted in 90 degree rotational increments around the pilot shaft axis. The LCD meter may be rotated in 90 degree increments to accommodate this.
Construction Materials
Case and Cover: Low-copper aluminum alloy Internal: Plated steel, aluminum, and stainless steel;
encapsulated printed wiring boards; Neodymium Iron Boron Magnets
Electrical Connections
Two 1/2-14 NPT internal conduit connections; one on bottom and one on back of terminal box. M20 adapters available.
Options
J Heat insulator. See description under Ordering
Information. and Foxboro/Eckhardt displacers available.
J Mountings for Masoneilan, Yamatake
J Level
Signature Series Test (Performance Validation Report) available (EMA only) for instruments factory-mounted on 249 sensor.
J Factory
Calibration: available for instruments factory-mounted on 249 sensor, when application, process temperature and density(s) are supplied.
J Device is compatible with user-specified remote
indicator.
Operating Limits
Process Temperature: See table 3 and figure 2. Ambient Temperature and Humidity: See below
Conditions
Ambient
Temperature
Ambient
Relative
Humidity
1. LCD meter may not be readable below -20_C (-4_F)
2. Contact your Emerson Process Management sales office or application engineer if temperatures exceeding these limits are required.
Normal
(1)(2)
Limits
-40 to 80_C
(-40 to 176_F)
0 to 95%,
(non-condensing)
Transport and
Storage
(1)
Limits
-40 to 85_C
(-40 to 185_F)
0 to 95%,
(non-condensing)
Nominal
Reference
25_C
(77_F)
40%
Weight
Less than 2.7 Kg (6 lbs)
(1)
4
DLC3010 Digital Level Controller
D102727X012
Table 1. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level
Electrostatic discharge (ESD) IEC 61000‐4‐2
Enclosure
I/O signal/control
Note: RTD wiring must be shorter than 3 meters (9.8 feet)
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering. Specification limit = +/- 1% of span.
2. HART communication was considered as “not relevant to the process” and is used primarily for configuration, calibration, and diagnostic purposes.
Radiated EM field IEC 61000‐4‐3
Rated power frequency magnetic field
Burst IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV (line to ground only, each) B Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms A
IEC 61000‐4‐8 60 A/m at 50 Hz A
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Product Bulletin
11.2:DLC3010 August 2014
Performance
(1)(2)
Criteria
A
A
5
Product Bulletin
11.2:DLC3010 August 2014
Figure 1. Theoretical Reversible Temperature Effect on Common Torque Tube Materials
TORQUE RATE REDUCTION
(NORMALIZED MODULUS OF RIGIDITY)
1.00
DLC3010 Digital Level Controller
D102727X012
0.98
0.96
0.94
0.92
0.90
Gnorm
0.88
0.86
0.84
0.82
0.80 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420
1
TEMPERATURE (_C)
TORQUE RATE REDUCTION
(NORMALIZED MODULUS OF RIGIDITY)
1.00
0.98
0.96
1
N05500
N06600
N10276
S31600
0.94
0.92
0.90
Gnorm
0.88
0.86
0.84
0.82
0.80 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800
TEMPERATURE (_F)
Note:
1 Due to the permanent drift that occurs near and above 260_C (500_F), N05500 is not recommended
for temperatures above 232_C (450_F).
6
N05500 N06600
N10276
S31600
DLC3010 Digital Level Controller
D102727X012
Product Bulletin
11.2:DLC3010 August 2014
Features
n Simplified Setup and Calibration—For quick analog
transmitter replacement (4-20mA out only), the instrument may be configured with default sensor data, zero Level Offset, differential process SG, and zero/span procedure only. For full compensation and diagnostic capabilities, complete sensor data entry and calibration is recommended.
Using Guided Setup, digital level controller start-up is straightforward and fast. Level and temperature alarms, specific gravity tables, calibration trim and trending are readily configurable. The DLC3010 also supports re-ranging without a fluid reference.
n Responsive to Small Process Changes—Accurate,
high-gain analog-to-digital conversion enables measurement of small changes in the process variable. This allows the DLC3010 to be used in difficult liquid level, interface, or density applications. In addition, an adjustable input filter and output damping help to attenuate displacer-induced ripple in the output signal due to liquid turbulence.
n Reduced Temperature Effects—An internal
temperature sensor enables consistent performance of the digital level controller despite ambient temperature changes. With a temperature input signal, either via HART protocol or an RTD connected to the instrument, the digital level controller can also automatically compensate for specific gravity changes due to temperature. A user-supplied table of up to ten linear segments may be entered to implement this feature. (A sample water/steam table is provided in the DLC3010 instruction manual (D102748X012). The measured torque tube rate may be manually pre-compensated for a target process temperature using the data available in the DLC3010 Device Description (DD).
nAdditional Compensation—The instrument
measurement algorithm corrects for the small motion of the displacer as buoyancy changes, allowing it to calculate the true cage or vessel level. This provides additional accuracy on the shorter displacers.
n Rugged Construction—Mechanical safeguards
designed into the digital level controller help it to withstand physical abuse often incurred during installation or in transport, without compromising performance. The fully encapsulated printed wiring boards resist the effects of vibration, temperature, and corrosive atmospheres. The lever assembly is pinned at the neutral position when the coupling access door is open, providing shipping stabilization for a separate transmitter purchase. Locking set screws are provided for covers and the access door handle.
n Easy Maintenance—Field wiring connections are in a
compartment separated from the electronics. This protects the electronics from any moisture brought into the housing by the field wiring. This also eases installation and maintenance. The digital level controller does not have to be removed to facilitate troubleshooting or service. Modular construction (figure 4) allows servicing in the field. However, if it is necessary to remove the digital level controller for in-shop maintenance and calibration, field wiring does not need to be disconnected.
n Alarm Jumper—The DLC3010 digital level controller
includes self-diagnostics that detect an error (e.g. electronics failure) that would render the process variable measurement inaccurate. The instrument can also be configured to indicate a process variable high or low alarm. When a process variable alarm or an error is detected the analog output signal is driven either above or below the normal 4 to 20 mA range, depending on the user-selectable position of the alarm jumper. The unit ships from the factory with the jumper in the high position.
7
Product Bulletin
11.2:DLC3010 August 2014
DLC3010 Digital Level Controller
D102727X012
Figure 2. Guidelines for Use of Optional Heat Insulator Assembly
AMBIENT TEMPERATURE (_C)
0
PROCESS TEMPERATURE (_F)
800
400
-325
-40 -30
0
1
TOO COLD
-10
10 20-20
HEAT INSULATOR REQUIRED
NO HEAT INSULATOR NECESSARY
HEAT INSULATOR REQUIRED
020406080 100 120 140 160
-20-40
AMBIENT TEMPERATURE (_F)
30 40 50 60
TOO HOT
70
176
80
425 400
300
200
100
0
-100
-200
PROCESS TEMPERATURE (_C)
STANDARD TRANSMITTER
Notes: 1 For process temperature below -29_ (C-20_F) and above 204_C (400_F) sensor materials must be appropriate for the process (refer to bulletin
34.2:2500).
2. If ambient dew point is above process temperature, ice formation might cause instrument malfunction and reduce insulator effectiveness.
39A4070-B A5494-1
Figure 4. FIELDVUE DLC3010 Digital Level Controller Assembly
Figure 3. Power Supply Requirements and Load Resistance
Maximum Load = 43.5 X (Supply Voltage - 12.0)
783
Load (Ohms)
250
0
10 20 2515
E0284
12 30
SUPPLY VOLTAGE (VDC)
Operating
Region
E1472
ADAPTER RING
LEVER ASSEMBLY
TRANSDUCER ASSEMBLY
ELECTRONICS MODULE
TERMINAL BOX
TERMINAL BOX COVER
LCD METER ASSEMBLY
COVER
8
DLC3010 Digital Level Controller
D102727X012
Product Bulletin
11.2:DLC3010 August 2014
Principle of Operation
The DLC3010 digital level controller is a loop-powered instrument that measure changes in liquid level, level of an interface between two liquids, or density of a liquid. A level, density, or interface level change in the measured fluid causes a change in the displacer buoyancy (figure 5). This change is transferred to the torque tube assembly. As the measured fluid changes, the torque tube assembly rotates.
The rotary motion of the torque tube is transferred to the digital level controller lever assembly (figure 5). The rotary motion moves a magnet attached to the lever assembly, changing the magnetic field that is sensed by the Hall-effect sensor. The sensor converts the magnetic field signal to a varying electronic signal, which is processed digitally to provide linearity corrections, sensitivity adjustment, and temperature compensation.
The signal is interpreted as a buoyancy change by reference to the stored torque rate, coupling point, and moment arm data. The buoyancy change in turn is interpreted as a level, interface, or density change by reference to stored displacer volume, specific gravity, and displacer length data. In level or interface modes, the correction for displacer motion is then added, as well as user-supplied offset to change the PV reference from the bottom of the displacer or correct for a coupling point error.
The resultant primary variable (PV) is then compared to PV alarm thresholds (if enabled) and used to set status bits and/or trigger the analog alarm current. If the alarm is not triggered, the PV is used to generate 4-20 mA analog and 0-100% range digital signals by reference to the stored upper and lower range values. The resultant analog command is limited at the saturation values to allow discrimination between saturated and alarm signals.
Figure 5. Cutaway View of Fisher 249 Displacer Sensor with FIELDVUE DLC3010 Digital Level Controller
W1389-1
TORQUE TUBE
E1471
DISPLACER
9
Product Bulletin
11.2:DLC3010 August 2014
249 Level Sensors Specifications
DLC3010 Digital Level Controller
D102727X012
Input Signal
Liquid Level or Liquid-to-Liquid Interface Level:From 0 to 100 percent of displacer length Liquid Density: From 0 to 100 percent of displacement force change obtained with given displacer volume—standard volumes are (60 inches3) for 249C and 249CP sensors or
J 1640 cm
3
(100 inches3) for most other sensors;
J 980 cm
other volumes available depending upon sensor construction
Sensor Displacer Lengths
See tables 4 and 5 footnotes
Sensor Working Pressures
Consistent with applicable ASME pressure/temperature ratings for the specific sensor constructions shown in tables 4 and 5
Caged Sensor Connection Styles
Cages can be furnished in a variety of end connection styles to facilitate mounting on vessels; the
equalizing connection styles are numbered and are shown in figure 7.
Mounting Positions
Most level sensors with cage displacers have a
3
rotatable head. The head may be rotated through 360 degrees to any of eight different positions, as shown in figure 8.
Construction Materials
See tables 2, 4, and 5
Operative Ambient Temperature
See table 3. For ambient temperature ranges, guidelines, and use of optional heat insulator, see figure 2.
Options
J Heat insulator, see description under Ordering
Information 232_C (420 psig at 450_F), and
J Gauge glass for pressures to 29 bar at
J Reflex gauges for
high temperature and pressure applications
249 Level Sensors
249 level sensors used with the DLC3010 digital level controller are available in both caged and cageless configurations. Figure 6 shows a DLC3010 mounted on a caged 249 sensor. Caged sensors provide more stable operation than do cageless sensors for vessels with internal obstructions or considerable internal turbulence. Cageless sensors are generally used on specific gravity and interface control applications requiring large displacers that are more easily accommodated by flange connections up to 8 inches. The availability of many different displacer stem lengths permits lowering the displacer down to the most advantageous depth in the vessel.
Figure 6. FIELDVUE DLC3010 Digital Level Controller and Fisher 249B Level Sensor
W7926
10
DLC3010 Digital Level Controller
D102727X012
Product Bulletin
11.2:DLC3010 August 2014
Table 2. Displacer and Torque Tube Materials
Part Standard Material Other Materials
316 Stainless Steel,
Displacer 304 Stainless Steel
Displacer Stem, Driver Bearing, Displacer Rod and
316 Stainless Steel
Driver
Torque Tube N05500
1. N05500 is not recommended for spring applications above 232_C (450_F). Contact your Emerson Process Management sales office or application engineer if temperatures exceeding this limit are required.
(1)
Table 4. Caged Displacer Sensors
TORQUE TUBE ORIENTATION
249
SENSOR
(3)
N10276, N04400, Plastic, and Special Alloys
N10276, N04400, other Austenitic Stainless Steels, and Special Alloys
316 Stainless Steel, N06600, N10276
(1)
STANDARD CAGE, HEAD, AND TORQUE TUBE ARM
MATERIAL
Cast Iron
Screwed 1-1/2 or 2 Flanged 2
Table 3. Allowable Process Temperatures for Common Fisher 249 Sensor Pressure Boundary Materials
MATERIAL
Cast Iron -29_C (-20_F) 232_C (450_F)
Steel -29_C (-20_F) 427_C (800_F)
Stainless Steel -198_C (-325_F) 427_C (800_F)
N04400 -198_C (-325_F) 427_C (800_F)
Graphite Laminate/SST Gaskets
N04400/PTFE Gaskets -73_C (-100_F) 204_C (400_F)
EQUALIZING CONNECTION
Style Size (NPS)
PROCESS TEMPERATURE
Min. Max.
-198_C (-325_F) 427_C (800_F)
Screwed or optional socket weld 1-1/2 or 2 CL600
Torque tube arm rotatable with respect to equalizing connections
249B, 249BF
249C
249K Steel
(4)
Steel
Raised face or optional ring type joint flanged
Screwed 1-1/2 or 2 CL600
(3)
316 Stainless Steel
Raised face flanged
Raised face or optional ring type joint flanged
249L Steel Ring type joint flanged 2
1. Standard displacer lengths for all styles (except 249) are 14, 32, 48, 60, 72, 84, 96, 108 and 120 inches. The 249 uses a displacer with a length of either 14 or 32 inches.
2. DIN flange connections available in EMA (Europe, Middle East and Africa).
3. Not available in EMA.
4. 249BF available in EMA only. Also available in DIN size DN40 with PN10 to PN100 flanges and size DN50 with PN10 to PN63 flanges.
5. Top connection is 1-inch ring-type joint flanged for connection styles F1 and F2.
1-1/2 CL150, 300, or 600 2 CL150, 300, or 600
1-1/2 CL150, 300, or 600 2 CL150, 300, or 600
1-1/2 or 2 CL900 or 1500
(5)
PRESSURE RATING
CL125 or 250
CL2500
(2)
Table 5. Cageless Displacer Sensors
Mounting Sensor
(1)
Standard Head
(6)
Body
, and Torque Tube
(2)
Arm Material
(4)
Mounts on
249BP
249CP 316 Stainless Steel NPS 3 raised face CL150, 300, or 600
Steel
top of vessel
(5)
249P
Mounts on side of vessel
249VS
Mounts on top of vessel or on customer supplied
249W
cage
1. Standard displacer lengths are 14, 32, 48, 60, 72, 84, 96, 108, and 120 inches.
2. Not used with side-mounted sensors.
3. DIN flange connections available in EMA (Europe, Middle East and Africa).
4. Not available in EMA.
5. 249P available in EMA only.
6. Wafer Body only applicable to 249W.
Steel or Stainless Steel
Cast Iron, Cast Steel or CF8M (316 Stainless Steel)
WCC (steel) or CF8M
LCC (steel) or CF8M For NPS 4 raised face CL150, 300, or 600
, Wafer
Flange Connection Pressure Rating
NPS 4 raised face or optional ring type joint CL150, 300, or 600 NPS 6 or 8 raised face CL150 or 300
NPS 4 raised face or optional ring type joint
NPS 6 or 8 raised face
For NPS 4 raised face or flat face
CL900 or 1500 (EN PN 10 to DIN PN 250)
CL150, 300, 600, 900, 1500, or 2500
CL125, 150, 250, 300, 900, or 1500 (EN PN 10 to DIN PN 160
For NPS 4 butt weld end, XXS CL2500
For NPS 3 raised face CL150, 300, or 600
(3)
11
Product Bulletin
11.2:DLC3010 August 2014
Figure 7. Style Number of Equalizing Connections
DLC3010 Digital Level Controller
D102727X012
TOP AND BOTTOM CONNECTIONS,
SCREWED (S-1) OR FLANGED (F-1)
28B5536-1 B1820-2
STYLE 1
STYLE 2
TOP AND LOWER SIDE CONNECTIONS,
SCREWED (S-2) OR FLANGED (F-2)
Installation
A 249 sensor may be shipped with the DLC3010 digital level controller installed or they may be shipped separately.
When shipping a skid mounted system, where the displacer cannot be restrained, it is recommended that the transmitter be uncoupled and the lever assembly locked to prevent damage. The transmitter must be re-coupled at commissioning, and a zero-trim will be required.
Dimensions for the DLC3010 and 249 sensor product construction are shown in figure 9 and tables 6 and 7. Dimensions of other combinations are available upon request.
UPPER AND LOWER SIDE CONNECTIONS,
STYLE 3
SCREWED (S-3) OR FLANGED (F-3)
STYLE 4
UPPER SIDE AND BOTTOM CONNECTIONS,
SCREWED (S-4) OR FLANGED (F-4)
Ordering Information
When ordering, specify:
n Process temperature and pressure and ambient air
temperature
n Application
n Liquid level service (specific gravity)
n Interface level service (specific gravity of both
liquids and minimum differential gap or span required)
n Density service (minimum and maximum specific
gravity required)
12
Product Bulletin
DLC3010 Digital Level Controller
D102727X012
Figure 8. Typical Mounting Positions for FIELDVUE DLC3010 Digital Level Controller on Fisher 249 Sensors
11.2:DLC3010 August 2014
SENSOR
CAGED
CAGELESS
LEFT-OF-DISPLACER
7
1
5
1
3
6
4
8
2
3
1
7
RIGHT-OF-DISPLACER
1
5
2
8
4
6
1 Not available for NPS 2 CL300 and 600 249C.
Construction
Refer to the specifications tables. Review the descriptions below each specification and in the referenced tables and figures; specify the desired choice whenever there is a selection to be made.
Heat Insulator
DLC3010 Digital Level Controller
If the DLC3010 and the 249 sensor are ordered as an assembly, and a heat insulator is required for the application, order the heat insulator as a 249 sensor option. If the DLC3010 is ordered separately, the heat insulator is available as a kit. Order part number 28B5741X012 for the heat insulator kit.
13
Product Bulletin
11.2:DLC3010 August 2014
Figure 9. Dimensions for FIELDVUE DLC3010 Digital Level Controller Mounted on a Fisher 249B Sensor (also see tables 6 and 7)
1-1/2 11-1/2 NPT
103
(4.06)
DLC3010 Digital Level Controller
D102727X012
421
(16.56)
G
F
W
M
106
(4.19)
A
A
S-3 AND F-3 UPPER AND
MATCH LINE (B)
202.4 (7.97)
3/4-14 NPT
244
(9.62)
203
(8.00)
TOP VIEW
503.4
(19.83)
1/2-14 NPT CONDUIT CONN
102.1 (4.02)
125.7 (4.95)
102.6
(4.04)
73.7
(2.90)
DETAILED FRONT VIEW OF
DLC3010 DIGITAL LEVEL CONTROLLER
LOWER SIDE CONNECTIONS
25.F83 19A3071 19A8853-D 17B0219-A 18B5524-1 B1822-5
Table 6. Dimension A for FIELDVUE DLC3010 Digital Level Controller Mounted on a Fisher 249B Sensor
148 148
DIN
A
5.81
5.81
(1)
154 155
6.06
6.12
153 153
154 157
6.06
6.19
SIZE
(NPS)
1-1/22121
SIZE
DN40 DN50
1. Dimension A for 249BF with din flanges.
Screwed NPT CL150 RF CL150 RTJ CL300 RF CL300 RTJ CL600 RF CL600 RTJ
mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches mm Inches
121
4.75
4.75
PN10/PN16 PN25/PN40 PN63 PN100
mm mm mm mm
143 145
145 145
5.69
5.69
152 151
6.00
5.94
145 147
1/2-14 NPT CONDUIT CONN
mm
(INCH)
159 159
153
- - -
6.25
6.25
Table 7. Dimensions F, G, M, and W for FIELDVUE DLC3010 Digital Level Controller Mounted on a Fisher 249B Sensor
DISPLACER LENGTH F G M W
mm Inches mm Inches mm Inches mm Inches mm Inches
356 14 356 14.00 197 7.75 284 11.19 394 15.50
813 32 813 32.00 425 16.75 513 20.19 851 33.50
14
Product Bulletin
DLC3010 Digital Level Controller
D102727X012
Table 8. Hazardous Area Classifications for Canada—CSA
Certification Body Certification Obtained Entity Rating Temperature Code
Intrinsically Safe Class I,II,III Division 1 GP A,B,C,D,E,F,G per drawing 28B5744 T6
CSA
Explosion-proof Class I, Division 1 GP B,C,D T6
Class I Division 2 GP A,B,C,D T6 Class II Division 1, 2 GP E,F,G T6 Class III
Table 9. Hazardous Area Classifications for United States—FM
Certification Body Certification Obtained Entity Rating Temperature Code
Intrinsically Safe Class I,II,III Division 1 GP A,B,C,D,E,F,G per drawing 28B5745 T5
FM
Explosion-proof Class I, Division 1 GP A,B,C,D
Class I Division 2 GP A,B,C,D Class II Division 1 GP E,F,G Class II Division 2 GP F,G
Vmax = 30 VDC Imax = 226 mA Ci = 5.5 nF Li = 0.4 mH
- - - T6 (Tamb ≤ 80_C)
- - - T6 (Tamb ≤ 80°C)
Vmax = 30 VDC Imax = 226 mA Pi = 1.4 W Ci = 5.5 nF Li = 0.4 mH
- - - T5 (Tamb ≤ 80_C)
- - - T5 (Tamb ≤ 80°C)
11.2:DLC3010 August 2014
T6 (Tamb ≤ 80°C)
T5 (Tamb ≤ 80°C)
Table 10. Hazardous Area Classifications—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
Intrinsically Safe II 1 G D Gas Ex ia IIC T5 Ga Dust Ex ia IIIC T83_C Da IP66
Flameproof II 2 G D
ATEX
Gas Ex d IIC T5 Gb Dust Ex tb IIIC T83_C Db IP66
Type n II 3 G D Gas Ex nA IIC T5 Gc Dust Ex t IIIC T83_C Dc IP66
Ui = 30 VDC Ii = 226 mA Pi = 1.4 W Ci = 5.5 nF Li = 0.4 mH
T5 (Tamb ≤ 80_C)
- - - T5 (Tamb ≤ 80_C)
- - - T5 (Tamb ≤ 80_C)
15
Product Bulletin
11.2:DLC3010 August 2014
Table 11. Hazardous Area Classifications—IECEx
Certificate Certification Obtained Entity Rating Temperature Code
Intrinsically Safe Gas Ex ia IIC T5 Ga Dust Ex ia IIIC T83_C Da IP66
Flameproof Gas
IECEx
Exd IIC T6 Gb Dust Ex t IIIC T83_C Db IP66
Type n Gas Ex nA IIC T5 Gc Dust Ex t IIIC T83_C Dc IP66
DLC3010 Digital Level Controller
Ui = 30 VDC Ii = 226 mA Pi = 1.4 W Ci = 5.5 nF Li = 0.4 mH
- - - T5 (Tamb ≤ 80°C)
- - - T5 (Tamb ≤ 80°C)
T5 (Tamb ≤ 80°C)
D102727X012
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and DeltaV are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the HART Communication Foundation. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
E 2000, 2014 Fisher Controls International LLC. All rights reserved.
16
Loading...